Note 5 - SyncGenerator
Note 5 - SyncGenerator
Synchronous
Generators
Figure 4-3
Brushless exciter circuit.
nm P
fe
120
Where
fe = electrical frequency, in Hz
P = number of poles
2
• The induced voltage is proportional to the rotor flux for a
given rotor angular frequency in electrical Radians per
second.
• Since the rotor flux depends on the field current IF, the
induced voltage EA is related to the field current as
shown below. This is generator magnetization curve or
the open-circuit characteristics of the machine.
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Figure 4-7
(a) Plot of flux versus field current for a synchronous generator. (b) The magnetization
curve for the synchronous generator.
Bnet BR BS
+ EAR - + IA
+
EA Enet V
-
-
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
• The two reactances may be combined into a single
reactance called the synchronous reactance of the
machine:
XS X AR X
Figure 4-12
The per phase equivalent circuit of a synchronous generator.
Figure 4-15
The power-flow diagram of a synchronous generator
Figure 4-16
3V E ASin( )
ind
m X S
V· , E ; B
· ,B
A net R
Figure 4-19
A sketch of the approximate synchronous reactance of a synchronous generator as a
function of the field current. Notes 6_SynGenerator_Dr. Irneza
The Effect of Load Changes on a Synchronous
Generator Operating Alone
• At constant field current and rotor speed
Figure 4-22
The effect of an increase in generator load upon its terminal voltage. At a fixed power
factor (a) Lagging; (b) unity; (c) leading.
Notes 6_SynGenerator_Dr. Irneza
Parallel Operation of Synchronous Generators
Requirements:
1. Must have the same voltage magnitude.
2. The phase angles of the two a phases must be the same.
3. The generators must have the same phase sequences.
4. The frequency of the oncoming generator must be slightly
higher than the frequency of the running generator.
Figure 4-27
(a) The two possible phase sequences of a three phase system
(b) The three-light-bulb method for checking phase sequence.
Copyright © The McGraw-Hill Companies, Inc. Permission required
Notes 6_SynGenerator_Dr. Irneza for reproduction or display.
Frequency-Power Characteristics of a Synchronous
Generator
P SP (fnl fsys )
Figure 4-29
(a) The speed-power curve for a typical prime mover. (b) The resulting frequency-power
curve for the generator.
Copyright © The McGraw-Hill Companies, Inc. PermissionIrneza
Notes 6_SynGenerator_Dr. required for reproduction or display.
Voltage-Reactive Power Characteristics of a
Synchronous Generator
Figure 4-30
Terminal voltage versus reactive power characteristics, assuming generator’s voltage
regulator produces an output that is linear with changes in reactive power
Figure 4-33
(a) A synchronous generator operating in parallel with an infinite bus.(b) The f-P diagram
(or house diagram) for a synchronous generator in parallel with an infinite bus.
Notes 6_SynGenerator_Dr. Irneza
Figure 4-36
The effect of increasing the governor’s set point on at constant excitation (a) the house
diagram; (b) the phasor diagram.
Figure 4-38
(a) A generator connected in parallel with another machine of the same size. (b) The
corresponding house diagrams at the moment generator 2 is paralleled with the system.
(c) The effect of increasing generator 2’s governor set point on the operation of the
system. (d) The effect of increasing generator 2’s field current on the operation of the
system
Notes 6_SynGenerator_Dr. Irneza
Operation of Synchronous Generators in Parallel with
Other Generators of the Same Size
Figure 4-40
(a) Shifting power sharing without affecting system frequency. (b) Shifting system
frequency without affecting power sharing. (c) Shifting reactive power sharing without
affecting terminal voltage. (d) Shifting terminal voltage without affecting reactive power
sharing.
Notes 6_SynGenerator_Dr. Irneza
Synchronous Generator Transients
3V E A
Pmax
XS
Figure 4-45
The Symmetric ac component of the fault current.
EA
ISS
XS
EA
I'
X'
EA
I"
X"
PSCL 3I A2RA
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Figure 4-47
The effect of the rotor field current limit on setting the rated power factor of the generator
Figure 4-48
Derivation of a synchronous generator capability curve. (a) The generator phasor
diagram; (b) the corresponding power limits.