LOAD CALCULATIONS

OHT DATA :
GROUND LEVEL (N.G.L) (ASSUMED) 192.235 m
STAGING OF TANK AS PER HYDRAULICS 15.000 m
LOW WATER LEVEL OF TANK 192.235+15 = 207.235 m
EFFECTIVE WATER HEIGHT (ASSUMED) 3.550 m
MAXIMUM WATER LEVEL OF TANK 207.235+3.55 = 210.785 m
FREEBOARD (ASSUMED) 0.500 m
DEAD STORAGE (ASSUMED) 0.150 m

MATERIAL DATA :
DENSITY OF CONCRETE 25 kN / m3
DENSITY OF WATER 10.00 kN / m3
DENSITY OF SOIL 20 kN / m3
GRADE OF CONCRETE (M) 30 N / mm2
GRADE OF STEEL (Fe) 500 N / mm2
DENSITY OF STEEL (Dst) 78.5 kN / m3
LOAD CALCULATIONS : -
1.2.3.4 EARTH QUAKE LOAD:
LOAD CASE-1,2,3 & 4 ARE 100 % EARTH QUAKE LOADS IN X AND Z DIRECTIONS
Impulsive Load to be applied on wall nodes= 0.46 kN at a height of 18.794m from top of footing
Impulsive Load to be applied on wall nodes= 0.4 kN at a height of 16.5925981313102m from top of footing
Convective load to be applied on wall nodes= 0.15 kN at a height of 19.275m from top of footing
THE FRAME IS ANALYSED FOR EARTH QUAKE LOADS IN X & Z DIRECTIONS
AS PER IS :1893-2016 BY SRSS METHOD
THE NODAL LUMPED MASSES ARE EVALUATED FOR A LOAD 100% DEAD LOAD + 25% LIVE LOAD, AS PER TABLE -10 of
IS:1893 -Part-1:2016
LUMPED MASSES ARE EVALUATED LISTED IN STAAD PRO ANALYSIS.
SESMIC ZONE III *ZONE FROM ANNEX E OF IS : 1893 (PART -I) :2016

SESMIC INTENSITY (Z) 0.16 *ZONE FACTOR FROM TABLE 3 OF IS : 1893 (PART -I) :2016

*FROM TABLE 2 OF IS : 1893 (PART -II) :2014 AMENDMENT


REDUCTION FACTOR (RF) 3.0
NO.1

IMPORTANCE FACTOR (I) 1.5 *FROM TABLE 1 OF IS : 1893 (PART -II) :2014

DAMPING PERCENT (DM) 5 % *FROM CLAUSE 7.2.4 OF IS : 1893 (PART -I) :2016

5. DEAD LOAD:
SELF WEIGHT OF tank upto FRB -1 ALONG Y DIRECTION

FLOOR FINISHING ON BOTTOM SLAB 1.0 Kn/m2

DEAD LOAD OF LANDING SLAB ON TO BEAM 2.1875 KN/M


DEAD LOAD OF MS LADDER ON TO BEAM 1 KN/M
6. LIVE LOAD:
LOADS ON THE SLAB :
*FROM TABLE 2 OF IS : 875 (PART -2)
LIVE LOAD on Gallery Projection 5.00 Kn/m^2
:1987
LL on landing beams 17.23 KN/M
7. WATER LOAD:
HEIGHT OF WATER INCLUDING FREEBOARD = 4.200 M
HEIGHT OF WATER = 3.700 M
WATER LOAD ON BOTTOM SLAB = 37.00 KN/m2 LC-07-Seismic &wind case
WATER LOAD ON WALLS = 37.00 KN/m2
WATER LOAD ON BOTTOM SLAB = 42.00 KN/m2 LC-14-Normal case
WATER LOAD ON WALLS = 42.00 KN/m2
Floor beam design:
BOTTOM SLAB 42 = 42.0 Kn/sqm
8.9.10.11. WIND LOAD:
FROM ANNEX -A - AS PER IS :875 (PART
BASIC WIND SPEED (Vb) 47 m / sec
3) - 2015
CALCULATION OF DESIGN WIND SPEED (VZ)
K1 = 1.06 FROM TABLE -1 - AS PER IS :875 (PART 3) - 2015
FOR 0-10M ,FROM TABLE -2 - AS PER IS :875 (PART 3) - 2015 FOR TERRAIN
K2 = 1.05
CATEGORY 1
FOR 10-15M ,FROM TABLE -2 - AS PER IS :875 (PART 3) - 2015 FOR TERRAIN
K2 = 1.09
CATEGORY 1
FOR 15-20M ,FROM TABLE -2 - AS PER IS :875 (PART 3) - 2015 FOR TERRAIN
K2 = 1.12
CATEGORY 1
FOR 20-30M ,FROM TABLE -2 - AS PER IS :875 (PART 3) - 2015 FOR TERRAIN
K2 = 1.15
CATEGORY 1
FOR 30-50M ,FROM TABLE -2 - AS PER IS :875 (PART 3) - 2015 FOR TERRAIN
K2 = 1.20
CATEGORY 1
K3 = 1.00 FROM CLAUSE - 6.3.3.1 AS PER IS:875(PART 3) -2015
K4= 1.00 FROM CLAUSE 6.3.4 AS PER IS :875 (PART 3) - 2015
*VZ = Vb*K1*K2*K3*K4,FROM CLAUSE - 6.3 AS PER IS:875(PART 3) - 2015
WIND SPEED (VZ) = 52.3 m/sec ( 0-10m)
54.3 m/sec ( 10-15m)
55.8 m/sec ( 15-20m)
57.3 m/sec ( 20-30m)
59.8 m/sec ( 30-50m)
*PZ = 0.6*VZ2, FROM CLAUSE - 7.2 AS PER IS:875(PART 3) - 2015
WIND PRESSURE (PZ) = 1.640 kn / m2 (0-10m)
1.770 kn / m2 (10-15m)
1.870 kn / m2 (15-20m)
1.970 kn / m2 (20-30m)
2.140 kn / m2 (30-50m)
Area of container exposed to wind = (4.33)x4.2
sq
= 18.190
m
*Pd = Kd*Ka*Kc*Pz, FROM CLAUSE - 7.2 AS PER IS:875(PART 3) - 2015
Wind directionality factor Kd = 1.00 FROM CLAUSE - 7.2.1 AS PER IS:875(PART 3) -2015

Area averaging factor Ka = 0.91 FROM CLAUSE - 7.2.2 AS PER IS:875(PART 3) -2015

Combination factor Kc = 0.90 FROM CLAUSE - 7.2.3.13 AS PER IS:875(PART 3) -2015


DESIGN WIND PRESSURE (Pd) = 1.34 kn / m2 (0-10m)
DESIGN WIND PRESSURE (Pd) = 1.45 kn / m2 (10-15m)
DESIGN WIND PRESSURE (Pd) = 1.53 kn / m2 (15-20m)
DESIGN WIND PRESSURE (Pd) = 1.61 kn / m2 (20-30m)
DESIGN WIND PRESSURE (Pd) = 1.75 kn / m2 (30-50m)
TOTAL FORCE ACTING ON THE ROOF OF THE STRUCTURE, P = 0.785 D 2 (Cpi - Cpe) Pd
As per IS 875(III)-2015-7.3.3.7
Cpi = 0.2 From clause 7.3.2.1 of IS 875 (Part-3): 2015
At top Cpe = -0.750
At base Cpe = -0.600
Design wind pressure Pd = 1.45 kn / m2 (15-20m)
Design wind pressure Pd = 1.53 kn / m2 (15-20m)
Ht. of structure Z 19.200 m
Ht. of tank upto top roof H 4.200 m
(Z/H)-1 = 3.57
As per SP-64 2001, example 20
Uplift pressure = (Cpe - Cpi) A Pd at top -1.45 kn/sqm
Uplift pressure = (Cpe - Cpi) A Pd at bottom -1.16 kn/sqm
ON TANK WALL:
SHAPE FACTOR = 0.7
*PZ = 0.7*Pd From Table-25 of IS 875 (Part-3): 2015
WIND PRESSURE (PZ) = 1.07 kn / m2 (15-20m)