Measurement
Measurement
3.1. INTRODUCTION
Electric power is the rate of doing work. It is expressed in Watts. The higher units of power
PWatts VI cos
used in practice include kilowatts, megawatts, etc. , i.e., a power of one watt is
said to be expended when a source of one volt passes a current of one ampere through a load
resistance/ impedance of one ohm at unity power factor.
The power measurements are made with the help of a wattmeter. Wattmeter is an indicating
deflecting type of instrument used in laboratories for measurement of power in various ranges.
A wattmeter consists of two coils as shown in the schematic representative Figure 3.1
Current coil (CC): connected in series with circuit and carries the load current. It is designed
such that it is wound with 2 to 3 turns of thick wire and hence it has a very low resistance.
Voltage or Pressure or Potential coil (PC): connected across the load circuit and hence carries
a current proportional to the load current. The total load voltage appears across the PC. It is
designed such that it is wound with several turns of thin wire and hence it has a very high
resistance.
The wattmeter can be a HPF meter or LPF meter depending on the type of the load connected
in the measuring circuit. For power measurements in AC circuits, the wattmeter is widely
adopted. In principle and construction, it is a combination of those applicable for an ammeter
and a voltmeter.
The electrical power can be of three forms:
Real power or simply, the power is the power consumed by the resistive loads on the system.
It is expressed in watts (W). This is also referred as true power, absolute power, average power,
or wattage.
Reactive power is the power consumed by the reactive loads on the system. It is expressed in
reactive volt-amperes (VAr).
Apparent power is the vector sum of the above two power components. It is expressed in volt-
amperes (VA).
V
ip 2 sin t 2I p
sin t
R p
ic 2 I sin t
dM
T i ic i p
d
2 I sin t 2I p
dM
sin t
d 3.3
Average deflecting torque,
T
1
Td T i
d t
T 0
T
1 dM
T
I I cos
P
cos 2 t d t
d
0
V dM
I cos
IP d
3.4
Tc K
Since the controlling torque,
We have at balance of the moving point,
Td Tc
VI cos dM
KR p d
So that
dM
K P
d
3.5
K KR
Where p
and P is the power consumption. Thus the deflection of the wattmeter is found
to be the direct indication of the power being consumed in the load circuit.
If an ordinary electrodynamometer wattmeter is used for measurement of power in low power fac-
tor circuits, (PF<0.5), then the measurements would be difficult and inaccurate since:
• The deflecting torque exerted on the moving system will be very small and
• Errors are introduced due to pressure coil inductance (which is large at LPF) Thus, in a LPF
wattmeter, special features are incorporated in a general electro-dynamometer wattmeter circuit to
make it suitable for use in LPF circuits as under:
The pressure coil circuit is designed to have a low value of resistance so that the current through
the pressure coil is increased to provide an increased operating torque.
Figure 3.4
Thus it is necessary to compensate for the pressure coil current in a low power factor wattmeter.
For this, a compensating coil is used in the instrument to compensate for the power loss in the
pressure coil circuit as shown in figure 3.5.
(c) Compensation for pressure coil inductance:
At low power factor, the error caused by the pressure coil inductance is very large. Hence, this
has to be compensated, by connecting a capacitor C across a portion of the series resistance in the
pressure coil circuit as shown in Figure 3.5.
Low power factor wattmeters are designed to have a very small control torque so that they can
provide full scale deflection (f.s.d) for power factor values as low as 10%. Thus, the complete
circuit of a low power factor wattmeter is as shown in Figure 3.5.
Figure 3.5
A single wattmeter can also be used for three phase reactive power measurements. For example,
the connection of a single wattmeter for 3-phase reactive power measurement in a balanced three
phase circuit is as shown in figure 3.6.
The current coil of the wattmeter is inserted in one line and the potential coil is connected across
V RB V R V B
the other two lines. Thus, the voltage applied to the voltage coil is where, VR and VB
are the phase voltage values of lines R and B respectively, as illustrated y the phasor diagram of
figure 3.7.
I y V L cos 90
3 V ph I ph
sin
3W ph
/ 3
3 Wattmeter reading 3.7
3.4 THREE PHASE REAL POWER MEASUREMENTS
The three phase real power is given by,
P3 ph 3 V ph
I ph
cos
P3 ph 3 V L I L cos
Or 3.8
The three phase power can be measured by using either one wattmeter, two wattmeters or three
wattmeters in the measuring circuit. Of these, the two wattmeter method is widely used for the
obvious advantages of measurements involved in it as discussed below.
The circuit diagram for two wattmeter method of measurement of three phase real power is as
shown in the figure 3.7. The current coil of the wattmeters W1 and W2 are inserted respectively in
R and Y phases. The potential coils of the two wattmeters are joined together to phase B, the third
V RB V R V B
phase. Thus, the voltage applied to the voltage coil of the meter, W1 is , while the
VY V B
voltage applied to the voltage coil of the meter, W2 is V YB , where, VR, VB and VC are the
phase voltage values of lines R, Y and B respectively, as illustrated by the phasor diagram of Figure
3.8. Thus, the reading of the two wattmeters can be obtained based on the phasor diagram of Figure
3.8, as follows:
W 1 I R V RB
I L V L cos 30 3.9
W 2 I Y V YB
I L V L cos 30 3.10
W1 W 2 3 V L I L cos P3 ph
Hence, 3.11
W 1 W 2 V L I L sin
And, 3.12
3 W 1 W 2
Tan
So that, W 1 W 2 3.13
1
3 W 1 W 2
Tan
W 1 W 2
3.14
IR
VR
W1
IB
VB
W2
IY
VY
(lag) cos V L I L cos 30 V L I L cos 30 3 V L I L cos W1 W 2
Gen. Case (always )
00 UPF 3 3 2 W 1 or 2 W 2 W1 W 2
VLIL VLIL
2 2
600 0.5 3 W1 W2
VLIL
alone reads zero
2 Zero
>600 <0.5 W1 W2 W 1 W 2 For taking readings, the PC or
reads
W2
negative CC connection of should be
reversed (LPF case)
Example 3.1
The power input to a 2000 V, 50 Hz, 3-phase motor running on full-load at an efficiency of 90 %
is measured by two measured by two wattmeters which indicate 300 kW and 100 kW respectively.
Calculate:
i. the input power ii. Power factor.
Solution
W 1 300 kW and W 2 100 kW
W1 W 2 300 100
Phase angle
Example 3.2
A 3-phase balanced load connected across a 3- , 400 V ac supply draws a line current of 10 A.
Two wattmeters are used to measure input power. The ratio of two wattmeter readings is 2: 1. Find
the readings of the two wattmeters.
Solution
W2
r
W1
Let the ratio of wattmeter readings be r,
W2
1
W1 W 2 W1 1 r
tan 3 3 3
W2
W1 W 2 1 r
1
W1
And
1 1 1
cos
sec 1 tan
2
2
1 r
1 3
And power factor, 1 r
W2 1
r 0 .5
W1 2
Substituting
1
cos 0 . 866
2
1 0 .5
1 3
Power factor of the load, 1 0 .5
1
cos 0 . 866 30
0
Or phase angle,
Assignment 3
1a Draw a schematic diagram of an electrodynamometer type wattmeter and explain its
principle of operation.
2a Show that in two-wattmeter method of a 3-phase power measurement the sum of the
readings of the two wattmeters gives the total power consumed in 3-phase circuit.
2b. Hence prove that
W1 W
Tan
2
3
W1 W 2
3. A 3-phase 400 V load has Power Factor (pf) of 0.6 lagging. The wo wattmeters read a total
input of 20 kW. Find the reading on each wattmeter.
4. Power is measured in a 3-phase balanced load with the help of two wattmeters. What will
be the power factors:
(i) When the readings of the two wattmeters are equal.
(ii) When the reading of one of the wattmeters is zero.
(iii) When the readings of the two wattmeters are equal and opposite.