BTech 2 Lecture Notes 4&5
BTech 2 Lecture Notes 4&5
Example One
A domestic installation consists of the following circuits in conduit:
8 lights, each to be controlled by l-way switch; 2 lights, each to be controlled by 2-
way switch and rated 100W;
10, 13A socket outlets wired in ring main circuits;
An electric cooker with a total rating of l2kW, plus a socket on the cooker unit.
Instantaneous water heater rated at 3kW and the supply voltage is 240 V. Floor area
is 30m x 20m
Determine:
Current per circuit.
Number of sub-circuits.
Protection/fuse rating.
Size of cable for each circuit.
Lighting Circuit
Power, P = I x V,
= (8 + 2) x 100 W = I x 240, ie l,000 W = 240 x I
Current, I =P/V, =1,000/240 = 4.2 A.
5/6A protection and 1.5sqmm cable is chosen.
Cooker Circuit
I= P/V= l2, 000 /240 =50 A.
Because not all 4 hot plates, the grill and the oven will be used at the same time
(application of diversity) 30A/32A circuit breaker/fuse is used for protection. The
cable used is 6sqmm².
Example two
In a four-bedroom apartment, the following lamps are to be used
15-40W fluorescent lamp
10-60W CFL
The supply voltage is 240V. Determine the rating of an appropriate protective device
for the lighting system.
Solution
Total power for fluorescent lamp = 15 × 40
= 600𝑊
𝑃 600×1.8
Current I = = = 4.5𝐴
𝑉 240
Example One
The future estimated load of an installation is 260KW. The growth factor is taken as
1.3.
Determine the present load.
Solution
𝑒𝑠𝑡𝑖𝑚𝑎𝑡𝑒𝑑 𝑓𝑢𝑡𝑢𝑟𝑒 𝑙𝑜𝑎𝑑
Growth factor =
𝑝𝑟𝑒𝑠𝑒𝑛𝑡 𝑙𝑜𝑎𝑑
260𝐾𝑊
1.3 = 𝑃𝑟𝑒𝑠𝑒𝑛𝑡 𝑙𝑜𝑎𝑑
260𝐾𝑊
Present load = 1.3
= 200𝐾𝑊
Example Two
A load of 200KW is estimated to be added to an existing load of 500KW in future.
Determine the growth factor in future.
Solution
𝐸𝑠𝑡𝑖𝑚𝑎𝑡𝑒𝑑 𝑓𝑢𝑡𝑢𝑟𝑒 𝑙𝑜𝑎𝑑
Growth factor =
𝑃𝑟𝑒𝑠𝑒𝑛𝑡 𝑙𝑜𝑎𝑑
200
=
500
2
=
5
= 2.5
TRANSMISSION AND DISTRIBUTION SYSTEMS
Electric-power transmission
This is the bulk transfer of electrical energy from generating power plants or station to
electrical substations located near demand centers. Transmission lines, when
interconnected with each other, become transmission networks. In Ghana, these are
typically referred to as the "National Grid". Most transmission lines use high-voltage
three-phase alternating current (AC), although single phase AC is sometimes used in
railway electrification systems.
Transmission system
The act of transferring bulk power from a generating station to primary substations.
Electric power distribution
This is the local wiring between high-voltage substations and customers. It is the final
stage in the delivery of electricity to end users. Electricity is transmitted at high
voltages 161 kV to reduce the energy lost in long-distance transmission. The reason
for these high voltage is simply that the higher the voltage the less current is required
to flow for the transmission of given amount of power. Reduced currents also effect a
reduction in conductor losses, cable size and switchgear capacities.
The transmission voltages are reduced to the distribution voltages of 33KV and 11KV,
then by large consumers and then further reduced for domestic consumers to
415V/240V, three-phase, 4-wire, 50Hz. A single-phase supply at 240V, 50Hz is the
most common supply for domestic premises. Power is usually transmitted through
overhead power lines. Underground power transmission has a significantly higher cost
and greater operational limitations but is sometimes used in urban areas or sensitive
locations.
Distribution system
The act of sending power from a substation to the consumers.
The above figure shows a simple radial AC power distribution system. The figure
does not show other equipment like circuit breakers, measuring instruments etc. for
simplicity purpose.
Functions of substation
1. A substation reduces the incoming voltage to the required level for distribution
to consumers.
2. It also reroutes power to other transmission lines that serve local markets.
3. The distribution substations transform power from transmission voltage to the
low voltage used for local distribution to homes and businesses.
Methods of power distribution
Basically there are four methods of power distribution. These are;
1. Single phase two-wire system
2. Single phase three-wire system
3. Three phase four-wire system
4. Three phase three-wire system
1. Single phase two-wire system
This system of distribution comes with only two wires, live and neutral which are
normally taken form the secondary of a transformer at the distribution substation. One
side of the secondary is taken as the live while the other side is earthed and taken as
the neutral.
In this system, the supply is taken form the secondary of a distribution transformer.
Notice that the neutral is obtained by tapping and earthing the centre of the transformer.
TERMINOLOGIES IN ILLUMINATION
BRIGHTNESS
This is the luminous intensity of light source. It is measured in candela per unit area.
(cd/m)
GLARE
This is the excessive brightness in the field of vision.
EFFECTS OF GLARE
Disability
Discomfort
LAWS OF ILLUMINATION/LUMINACE
1. Inverse square law
2. Cosine law
Where E = illumination
I= luminous intensity
d= distance
QUESTION 1: A light emits 100candela in all directions. Determine the illumination
produced at a point on a horizontal surface 2m vertically below it.
SOLUTION
Luminous Intensity (i) =100cd distance= 2m
𝐼 100 𝟏𝟎𝟎
a) E = 𝑑2 = = = 25 lux
22 𝟒
COSINE LAW
This law states that the illumination is directly proportional to the cosine of angle made
by the normal to the illuminated surface with the direction of the incident flux.
Icos3 ᴓ
E=
d2
Where E= Illumination in lux
I= Luminous Intensity in candela in the direction
d = distance in metres.
QUESTION 1 A 250W sodium vapour lamp emits a light of 22500 candela and is
situated 5m above the road. Calculate the illumination a) directly below the lamp b) at
a horizontal distance along the road of 6m.
SOLUTION
Power=250W Luminous Intensity=22500cd distance=5m
I 22500 22500
a) Illumination directly below the lamp E = d2 = = = 900lx
52 25
Icos3 ᴓ
b) Illumination at a horizontal distance along the road of 6m = E = d2
6
Tanᴓ = 5 = 1.2 ᴓ = tan−1 ( 1.2) ᴓ = 50.194 cos 50.194 = 0.64
Icos3 ᴓ 22500×0.643 22500×0.262
E= = = = 235.9lx
d2 52 25
QUESTION 2
Light
500 cd
4m
B 3m C
SOLUTION
𝐼 500 500
i) Illumination at point B E = 𝑑2 = 16 = 31.25 lux
42
Icos3 ᴓ 3
ii) Illumination at point C E= tanᴓ 4 = 0.75 ᴓ = tan−1 0.75 = 36.8 Cos
d2
=36.86=0.8
Icos3 ᴓ 500×0.83 500×0.512
E= = = E = 16lux
d2 42 16
QUESTION 3: If a light source of intensity of 450cd is 3m directly above a point on
a horizontal bench, calculate
a) the illumination on that point
b) illumination on the second point on the bench which is 4m from the first point
SOLUTION
Luminous Intensity (I) = 450cd distance=3m
𝐼 450 450
a) Illumination on that point E = 𝑑2 = = 50lux
32 9
This consists of a photoelectric cell made up of a layer of selenium coated onto a steel
base plate. A film of gold is formed over the selenium and is so thin that any light
which falls on the cell will penetrate the gold layer to release electrons inside the
selenium. These electrons then flow to the gold layer giving it a negative charge. The
cell is coupled to a sensitive micro-ammeter whose scale is marked off in lm/m2. The
greater the amount of light falling on the cell the greater will be the voltage (lm/m 2)
recorded.
COEFFICIENT OF UTILIZATION
This is the proportion of light that emitted by the lamp that actually reaches the working
plane. All of the luminous flux emitted from a light source does not reach the working
plane, some of it is absorbed by the walls, ceiling and adjacent objects. The value of
coefficient of utilization is about 0.6
MAINTENANCE FACTOR
This is the ratio of illumination on a given area after a period of time to the initial
illumination on the same area. That is, immediately a lighting installation is put into
service, it begins to deteriorate. A film of dust or dirt begins to reduce the transparency
or reflecting power of all the exposed surfaces of the lamps, fittings and the walls and
ceiling of a room. This process if unchecked may results in the level of illumination
falling very low in a comparatively short time. Maintenance factor is used in lighting
calculation to account for the depreciation of lamp of reflection. Maintenance factor
can also involve the replacement of lamps which have either failed or have suffered
reduction in their light output. The value of maintenance factor is 0.8.
MOUNTING HEIGHT
This is the distance from the bottom of the fixtures to either the floor or the working
plane. The ceiling may be very low or very high. If the fittings is fixed at the lower
levels care must be taken to diffuse the light and cut down glare.
ABSORPTION FACTOR
Absorption factor is a measure of the ability of an object to absorb radiation, equal to
the ratio of the absorbed radiant flux to the incident flux. In situations where the
atmosphere is smoke or dust laden, the illumination level on working plane is reduced
by the fact that absorption occurs, which is the scattering of light by the foreign
particles.
Power 625
Number of lamps = Wattage of lamp = = 7.35
85
Lamps = 8 lamps
Solution
Area=15m by 20m E=70lx Efficacy=12lm/w Spacing-height ratio=1.2
Distance=4m
UF=0.5 MF=0.8
E×A 70×15×20 21,000
Total Lumen (F) = CU×MF = = = 52,500 lm
0.5×0.8 0.4
S S
Spacing – Height ratio=H 1.2=4 Spacing(S) =1.2× 4m = 5m
width of room 15
Number of rows of fittings = = = 3m
Spacing 5
Lengh of room 20
Number of length of fittings = = = 4m
Spacing 5
52,500
Total number of fittings= 4 × 3=12 Lumen per fitting = = 4375 lm
12
ELECTRICAL SAFETY
Over current protection
Compared to other energy sources, electricity has many advantages, but also many
risks. It is used daily by the general public and many accidents still occurs, resulting
in burns, fires, and electrocution. Dependable protective devices have been designed
by carefully analyzing the risks and consequences of equipment failures or incorrect
use, The IEE Regulation is to help protect lives, properties, Equipment’s and
sometimes leakages. With the guidelines to know and use circuit protective devices
appropriately.
Semi-enclosed fuse
This fuse consists of an element which is made up of a piece of tin-lead or tinned-
copper wire. The usual form of fuse called the Home Office Type. It consists of a
porcelain or Bakelite fuse carrier with contacts capable of being plugged into sockets
in the fuse base. The element is connected between terminals on the carrier.
ADVANTAGES
1. Very cheap
2. Rewirable
Disadvantages
1. Wrong size of fuse wire can be used when rewiring,
2. Even when correct wire is used for the element, the current rating and fusing
factor may not be exactly as intended.
3. Unsuitable for protection against very large fault currents
4. Deterioration of fuse wire over a period
5. Slow action so fire and damage can occur before it melts.
Cartridge fuse
The fuse consists of a sealed tube with metal caps. The fuse wire passes through the
tube from cap to cap and is welded or soldered to the inside of the cap. The cartridge
fuse is an advance on semi-enclosed fuse, as the rating of the replacement fuse element
is determined by the manufacturer. Cartridge fuses only are used in fused plugs, such
as in the 13A plug for the common ring circuit.
Advantages
1. Quick and easy replacement
2. Colour coding of fuse sizes
3. Lack of deterioration
4. The rating is accurately known
Disadvantages
1. Fuse element is more expensive to replace.
2. Unsuitable for use where extremely high values of fault current may occur.
Advantages
1. Its characteristic can be designed to suit the nature of the load.
2. Ability to clear heavy fault currents safety.
3. Fast action, they are designed to rupture dangerous faults of 35 kilo ampers in
1 milli second.
4. No deterioration of fuse because fuse element is hermetically sealed.
Disadvantages
1. Very expensive
Prospective current
Prospective current is the value which would be reached by a short circuit current if
the fuse were replaced by a solid link. A graph which includes the actual or cut-off
current value when protection is by means of a high breaking capacity fuse is shown
below.
It could be seen from the graph that while the current is rising in value, it is quickly
cut-off by the H.B.C. fuse thereby preventing it from reaching such a high value as
indicated by the arrow labeled prospective current.
Current Operated Earth Leakage Circuit Breaker/ Residual current device (RCD)
Connection of RCD in a Circuit
Reasons of earthing
i. It ensures that a neutral conductor is obtained for single-phase loads
ii. It prevents the potential of live conductors from rising above the declared value.
iii. To cut off the supply automatically when an appreciable leakage current flows,
during fault conditions.
iv. It minimizes the danger of electric shock from exposed metals, which may be
live.
v. To prevent danger of fire outbreak due to overheating from leakage current
flow.
Earthing terminologies
Earth: The conductive mass of the earth, whose electric potential at any point is taken
as zero.
Earthing: The act of connecting the exposed conductive parts of an installation to the
main earthing terminal of an installation.
Earthing conductor: A protective conductor connecting the main earthing terminal of
an installation to an earth electrode or to other means of earthing.
Earth electrode: A conductor or group of conductors in intimate contact with and
providing an electrical connection to Earth.
Earth electrode resistance: The resistance of an electrode to Earth.
Electric shock: A dangerous physiological effect resulting from the passing of an
electric current through a human body or livestock.
Earth fault current: A fault current which flows to Earth
Earth fault loop impedance: The impedance of the earth fault current loop starting
and ending at the point of earth fault. This impedance is denoted by the symbol
Earth leakage current: A current which flows to earth or to extraneous conductive –
parts in a circuit which is electrically sound.
Earth fault loop path: Earth fault loop is the path which the leakage current will take
back to the supply transformer when there is an earth leakage in an installation.
Earthing resistance area: This is the surface area of ground on which a significant
voltage gradient may exist.
TYPES OF SYSTEM EARTHING
1. TN-S systems
Single-source systems
TN-S systems have one point directly earthed at the source, the exposed-conductive
parts of the installation(s) being connected to that point by protective conductors. Two
types of TN system are considered according to the arrangement of neutral and
protective conductors.
TN-S
3. TT system
Single-source system
A TT system has only one point directly earthed at the source, the exposed-conductive-
parts of the installation(s) being connected to earth electrodes electrically independent
of the earth electrode of the supply system (the source earth).
All exposed-conductive-parts of an installation are connected to an earth electrode
which is electrically independent of the source earth.
Separate neutral and protective conductors throughout the system.
TT-S
IT System
To conduct the test it is necessary to disconnect electrode under test from the earthing
system. As the basis concept is shown in the diagram, an electrode C is driven as the
earth at a distance of 50m from electrode A and B is placed approximately half way
between them. This ensures that B is outside the resistance area of A. An alternating
current from a low voltage A is applied to the electrode as shown in the diagram. The
resistance being calculated form the readings of the ammeter and the voltmeter.
Electrode B is first moved to position B1 then to B2 either side of position B and
reading latter provided the three readings are similar, the value will be taken as the
earth electrode resistance, the value will depend upon the soil and moisture content.
If a fault occurs between the phase conductor and the earthed metal case, the leakage
current flows from the faulty circuit into the circuit protective conductor. The leakage
current then flows along the circuit protective conductor to the earthing lead. The
earthing lead carries the current to the earth electrode. The leakage current now takes
the shortest path back to the earthed neutral of the supply transformer.
Effects of high loop impedance
1. Earth leakage current relaying is difficult
2. Produces high transient voltage
3. Ground fault current is increased
4. Causes persistent arcing grounds.
Lightning conductors
Lightning conductors are installed to connect and interconnect to earth. The air
terminals and others metal parts of the object to be protected. They are made of
copper or aluminium. In general lightning conductors should
1. Not be bent to a radius of less than 20cm.
2. Not be bent to an angle of more than 900.
3. Maintain a horizontal or doward course.
4. Provide at least two paths for current flow from an air terminal to earth.
5. Provide and earth path for every 30.5m of perimeter.
6. Connect all metallic bodies, such as exhaust fans and roof vents, to the
protection system.
7. Be securely fastened to the protection to the terminals, the ground and the
structure.
8. Not be concealed in metallic conduit, unless the conductor is securely bonded
to the conduit at both end.
Ground connections
The grounds are usually copper clad steel rods at least 3m long and 1.2cm in
diameter.
However, where the top soil is very shallow, ground plates may be use. In general,
grounding connections should be;
1. Made with rod driven into the earth, at least 0.6m from the protected object so that
the rod top is 3m under the earth.
2. Made to underground metallic pipes of metal casing.
3. Interconnected with driven ground electrodes.