Hilti PROFIS Engineering 3.1.

www.hilti.com.qa
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

Specifier's comments: Tota weight on each Leg = 2.5tons

1 Anchor Design
1.1 Input data

Anchor type and diameter: HIT-HY 200-R V3 + HAS-U 5.8 M16


Return period (service life in years): 50
Item number: 2223828 HAS-U 5.8 M16x150 (element) / 2262131
HIT-HY 200-R V3 (adhesive)
Specification text: Hilti HAS-U 5.8 threaded rod with HIT-HY
200-R V3 injection mortar with 80 mm
embedment hef, M16, Steel galvanized,
SAFEset - automatic cleaning installation per
ETA 19/0601
Effective embedment depth: hef,opti = 80.0 mm (hef,limit = 114.0 mm)
Material: 5.8
Evaluation Service Report: ETA 19/0601
Issued I Valid: 29/01/2024 | -
Proof: Design Method EN 1992-4, Chemical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 8.0 mm

Anchor plate
CBFEM
: lx x ly x t = 250.0 mm x 610.0 mm x 8.0 mm;

Profile: Square hollow, 80 x 80 x 5,0; (L x W x T) = 80.0 mm x 80.0 mm x 5.0 mm


Base material: 2
cracked concrete, C25/30, fc,cyl = 25.00 N/mm ; h =150.0 mm, Temp. short/long: 30/40 °C,
User-defined partial material safety factor gc = 1.500
Installation: automatic cleaned drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
with longitudinal edge reinforcement d >= 12.0 [mm]
Reinforcement to control splitting acc. to EN 1992-4, 7.2.1.7 (2) b) 2) present

CBFEM
- The anchor calculation is based on a component-based Finite Element Method (CBFEM)

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

1.1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = -25.000; Vx = 0.000; Vy = 0.000; no no 1
Mx = 0.000; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

1.2 Load case/Resulting anchor forces 2y

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.165 0.000 -0.000 0.000 Tension
2 0.165 0.000 -0.000 -0.000 x
Compression

Resulting tension force in (x/y)=(0.0/0.0): 0.330 [kN]


Resulting compression force in (x/y)=(0.0/0.0): 27.747 [kN]

1
Anchor forces are calculated based on a component-based Finite Element Method (CBFEM)

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

1.3 Tension load (EN 1992-4, Section 7.2.1)

Load [kN] Capacity [kN] Utilization bN [%] Status


Steel Strength* 0.165 52.333 1 OK
Combined pullout-concrete cone failure** 0.165 21.931 1 OK
Concrete Breakout Failure** 0.165 36.726 1 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

1.3.1 Steel Strength

N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gMs

NRk,s [kN] gMs NRd,s [kN] NEd [kN]


78.500 1.500 52.333 0.165

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

1.3.2 Combined pullout-concrete cone failure

N
NEd £ NRd,p = Rk,p EN 1992-4, Table 7.1
gMp
0 Ap,N
NRk,p = NRk,p · 0
· y g,Np · y s,Np · y re,Np · y ec1,Np · y ec2,Np EN 1992-4, Eq. (7.13)
Ap,N
0
NRk,p = y sus · t Rk · p · d · hef EN 1992-4, Eq. (7.14)
y sus =1 EN 1992-4, Eq. (7.14a)

scr,Np = 7.3 · d · √y sus · t Rk £ 3 · hef EN 1992-4, Eq. (7.15)


0,5
y g,Np
0
= y g,Np -
s
s
( ) · (y g,Np - 1) ³ 1.00
cr,Np
0
EN 1992-4, Eq. (7.17)
1,5
0
y g,Np = √n - (√n - 1) · (tt )
Rk

Rk,c
³ 1.00 EN 1992-4, Eq. (7.18)
k3
t Rk,c = · √hef · fck EN 1992-4, Eq. (7.19)
p·d
c
y s,Np = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.20)
ccr,Np £
1
y ec1,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec1,N £
1+ (
scr,Np )
1
y ec2,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec2,N £
1+ (
scr,Np )
2 0 2 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,20 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm] fc,cyl [N/mm ]
57,600 57,600 15.00 240.0 120.0 ∞ 25.00
0
yc t Rk,cr [N/mm ]
2
k3 t Rk,c [N/mm ]
2
y g,Np y g,Np
1.023 8.18 7.700 6.85 1.000 1.000

ec1,N [mm] y ec1,Np ec2,N [mm] y ec2,Np y s,Np y re,Np


0.0 1.000 0.0 1.000 1.000 1.000
0
y sus asus y sus
0.890 0.000 1.000
0
NRk,p [kN] NRk,p [kN] gMp NRd,p [kN] NEd [kN]
32.896 32.896 1.500 21.931 0.165

Group anchor ID
2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

1.3.3 Concrete Breakout Failure

N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gMc
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eN,1 £
1+ (
scr,N )
1
y ec2,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eN,2 £
1+ (
scr,N )
z
y M,N = 2.0 - 1.00 EN 1992-4, Eq. (7.7)
1.5 · hef ³

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
57,600 57,600 120.0 240.0 25.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N z [mm]


0.0 1.000 0.0 1.000 1.000 1.000 0.0
0
y M,N k1 NRk,c [kN] gMc NRd,c [kN] NEd [kN]
2.000 7.700 27.548 1.500 36.726 0.165

Group anchor ID
2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

1.4 Shear load (EN 1992-4, Section 7.2.2)

Load [kN] Capacity [kN] Utilization bV [%] Status


Steel Strength (without lever arm)* 0.000 37.680 1 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 0.000 36.731 1 OK
Concrete edge failure in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)


When the input edge distance is set to "infinity", edge breakout verification is not performed in that direction

1.4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gMs
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gMs VRd,s [kN] VEd [kN]
47.100 1.000 47.100 1.250 37.680 0.000
1.4.2 Pryout Strength (Concrete Breakout Strength controls)

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gMc,p
VRk,cp = k8 · min {NRk,c; NRk,p} EN 1992-4, Eq. (7.39c)
0 A
NRk,c = NRk,c · 0c,N · y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
57,600 57,600 120.0 240.0 2.000 25.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 1.000 1.000 1.000
0
k1 NRk,c [kN] gMc,p VRd,cp [kN] VEd [kN]
7.700 27.548 1.500 36.731 0.000

Group anchor ID
2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

1.5 Combined tension and shear loads (EN 1992-4, Section 7.2.3)
Steel failure

bN bV a Utilization bN,V [%] Status


0.003 0.000 2.000 1 OK

a a
bN + bV £ 1.0

Concrete failure

bN bV a Utilization bN,V [%] Status


0.008 0.000 1.500 1 OK

a a
bN + bV £ 1.0

1.6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates as per current regulations (ETAG 001/Annex C, EOTA
TR029, etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor
plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above.
The proof if the rigid base plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• Please note that this design utilizes user defined material safety factor values that differ from the default values recommended in EN1992-4.
Partial Safety factor value: gc = 1.500
• Characteristic bond resistances depend on short- and long-term temperatures.
• Edge reinforcement is not required to avoid splitting failure
• Load transfer from supplementary reinforcement to the structural member shall be verified by the responsible structural engineer.
• With supplementary reinforcement and post-installed anchors, please ensure that in the jobsite the rebars are not drilled through.
• The anchor design methods in PROFIS Engineering require rigid anchor plates, as per current regulations (AS 5216:2021, ETAG 001/Annex
C, EOTA TR029 etc.). This means that the anchor plate should be sufficiently rigid to prevent load re-distribution to the anchors due to
elastic/plastic displacements. The user accepts that the anchor plate is considered close to rigid by engineering judgment."
• The characteristic bond resistances depend on the return period (service life in years): 50

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

1.7 Installation data


2
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm
2 Anchor type and diameter: HIT-HY 200-R V3 + HAS-U 5.8
M16
Profile: Square hollow, 80 x 80 x 5,0; (L x W x T) = 80.0 mm x 80.0 mm x 5.0 Item number: 2223828 HAS-U 5.8 M16x150 (element) /
mm 2262131 HIT-HY 200-R V3 (adhesive)
Hole diameter in the fixture: df = 18.0 mm Maximum installation torque: 80 Nm
Plate thickness (input): 8.0 mm Hole diameter in the base material: 18.0 mm
Hole depth in the base material: 80.0 mm
Drilling method: SafeSet - automatic cleaning Minimum thickness of the base material: 116.0 mm
Cleaning: Automatically performed while drilling

Hilti HAS-U 5.8 threaded rod with HIT-HY 200-R V3 injection mortar with 80 mm embedment hef, M16, Steel galvanized, SAFEset - automatic
cleaning installation per ETA 19/0601

1.7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Dispenser including cassette and mixer
• Properly sized drill bit for SAFEset - • For deep installations, a piston plug is
automatic cleaning (TE-CD / TE-YD) necessary
• Vacuum cleaner • Torque wrench

y
125.0 125.0
25.0

2
305.0
560.0

x
305.0

1
25.0

125.0 125.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0.0 -280.0 - - - -
2 0.0 280.0 - - - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

2 Anchor plate design

2.1 Input data


Anchor plate: Shape: Rectangular
lx x ly x t = 250.0 mm x 610.0 mm x 8.0 mm
Calculation: CBFEM
Material: S 275; Fy = 275.00 N/mm²; εlim = 5.00%
Anchor type and size: HIT-HY 200-R V3 + HAS-U 5.8 M16, hef = 80.0 mm
Anchor stiffness: The anchor is modeled considering stiffness values determined from load displacement curves tested in an
independent laboratory. Please note that no simple replacement of the anchor is possible as the anchor
stiffness has a major impact on the load distribution results.
Design method: EN-based design using component-based FEM
Stand-off installation: eb = 0.0 mm (No stand-off); t = 8.0 mm
Profile: 80 x 80 x 5,0; (L x W x T x FT) = 80.0 mm x 80.0 mm x 5.0 mm x -
Material: S 275; Fy = 275.00 N/mm²; εlim = 5.00%
Eccentricity x: 0.0 mm
Eccentricity y: 0.0 mm
Base material: Cracked concrete; C25/30; fc,cyl = 25.00 N/mm²; h = 150.0 mm; E = 31,000.00 N/mm²; G = 12,916.67
N/mm²; v = 0.20
Welds (profile to anchor plate): Type of redistribution: Plastic
Material: S 275
Mesh size: Number of elements on edge: 8
Min. size of element: 10.0 mm
Max. size of element: 50.0 mm

2.2 Summary
Description Profile Anchor plate Welds [%] Concrete [%]
sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] Hole bearing
[%]
1 Combination 1 28.38 0.00 6.45 0.00 0 9 10
2.3 Anchor plate classification
Results below are displayed for the decisive load combinations: Combination 1
Anchor tension forces Equivalent rigid anchor plate (CBFEM) Component-based Finite Element Method
(CBFEM) anchor plate design
Anchor 1 0.000 kN 0.165 kN
Anchor 2 0.000 kN 0.165 kN

User accepted to consider the selected anchor plate as rigid by his/her engineering judgement. This means the anchor design guidelines can
be applied.

2.4 Profile/Stiffeners/Plate
Profile and stiffeners are verified at the level of the steel to concrete connection. The connection design does not replace the steel design for
critical cross sections, which should be performed outside of PROFIS Engineering.

2.4.1 Equivalent stress and plastic strain


Limit state criteria as per EN1993-1-5 Annex C.8, (1) 2.

Results
Part Load Material sEd [N/mm²] ePl [%] fy [N/mm²] gM0 fy/gM0 elim [%] Status
combination [N/mm²]
Plate Combination S 275 6.45 0.00 275.00 1.00 275.00 5.00 OK
1
Profile Combination S 275 28.38 0.00 275.00 1.00 275.00 5.00 OK
1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

Part Load Material sEd [N/mm²] ePl [%] fy [N/mm²] gM0 fy/gM0 elim [%] Status
combination [N/mm²]
Profile Combination S 275 28.38 0.00 275.00 1.00 275.00 5.00 OK
1
Profile Combination S 275 26.44 0.00 275.00 1.00 275.00 5.00 OK
1
Profile Combination S 275 26.44 0.00 275.00 1.00 275.00 5.00 OK
1

2.4.1.1 Equivalent stress


Results below are displayed for the decisive load combination: 1 - Combination 1

275.00 N/mm²

0.00 N/mm²

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

2.4.1.2 Plastic strain


Results below are displayed for the decisive load combination: 1 - Combination 1

5.00%

0.00%
2.4.2 Hole bearing
Decisive load combination: 1 - Combination 1
Plate hole bearing resistance, EN1993-1 - 8 section 3.6.1:

Equations

k1 ab fu d t
Fb,Rd =
gM2
VEd
Utilization =
Fb,Rd

Variables
k1 ab fu [N/mm²] d [mm] t [mm] gM2
Anchor 1 2.50 1.00 430.00 16.0 8.0 1.25
Anchor 2 2.50 1.00 430.00 16.0 8.0 1.25

Results
VEd [kN] Fb,Rd [kN] Utilization [%] Status
Anchor 1 0.000 110.080 0 OK
Anchor 2 0.000 110.080 0 OK

2.5 Welds
Profiles are modeled without taking the corner radius into account. Special rules for welding (e.g. for cold-formed profiles ...) are not taken into
account by the software.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

2.5.1 Anchor plate to profile


Decisive load combination: 1 - Combination 1
Weld design, EN1993-1-8 section 4.5.3.2
Minimum anchor plate to profile web thickness (amin): 3.0 mm

Minimum anchor plate to profile flange thickness (amin): 3.0 mm

Equations

sw,Ed = (s┴2 + 3 (t┴2 + t||2))0.5


fu
sw,Rd =
bw gM2
fu
s┴,Rd = 0.9
gM2
sw,Ed |s┴|
Utilization = max ( ; )
sw,Rd s┴,Rd
Variables
Weld bw fu [N/mm²] gM2
Web 0.85 430.00 1.25
Flange 0.85 430.00 1.25

Edge a [mm] L [mm] ePl [%] s┴ [N/mm²] t|| [N/mm²] t┴ [N/mm²]


Member 1-tfl 1 4.0 80.0 0.00 -21.48 0.10 -16.61
Member 1-bfl 1 4.0 80.0 0.00 -21.45 -0.10 16.64
Member 1-w 1 15.0 70.0 0.00 -8.43 2.89 -4.28
Member 1-w 2 15.0 70.0 0.00 -8.42 -2.89 4.28

Results
Edge sw,Ed [N/mm²] sw,Rd [N/mm²] s┴,Rd [N/mm²] Utilization [%] Utilizationc [%] Status
Member 1-tfl 1 35.91 404.71 309.60 9 8 OK
Member 1-bfl 1 35.93 404.71 309.60 9 8 OK
Member 1-w 1 12.28 404.71 309.60 4 2 OK
Member 1-w 2 12.28 404.71 309.60 4 2 OK

2.6 Concrete
Decisive load combination: 1 - Combination 1
According to EN1992-1-1 section 6.7(4), the concrete should have sufficient reinforcement to take into account the tensile forces that develop
due to the fixture attachment. The definition of the reinforcement in the concrete is out of scope of PROFIS Engineering.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

12
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 13
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

2.6.1 Compression in concrete under the anchor plate


1.96 N/mm²

0.00 N/mm²

2.6.2 Verification of compression in concrete under the anchor plate around the profile as per EN1992-1 section 6.7 and EN1993-1-8,
section 6.2.5

Equations

fjd
bj kj acc fck
=
gc
N
s = A
eff

Utilization =
s
fjd

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

13
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 14
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

Variables
N [kN] Aeff [mm²] bj kj acc fck [N/mm²] gc
27.747 10,395 0.67 2.47 1.00 25.00 1.50

Results
s [N/mm²] fjd [N/mm²] Utilization [%] Status
2.67 27.61 10 OK

2.7 Symbol explanation


a Throat thickness of weld
ab Factor
acc Long-term effects on maximum strength of concrete
Aeff Effective area
amin Minimum weld thickness
bj Joint coefficient βj
bw Correlation factor EN 1993-1-8 tab. 4.1
d Nominal diameter of the bolt
elim Limit plastic strain
ePl Plastic strain from CBFEM results
Fb,Rd Plate bearing resistance EN 1993-1-8 tab. 3.4
fck Characteristic compressive concrete strength
fjd The ultimate bearing strength of the concrete block
fu Ultimate strength
fy Yield strength
gc Service factor - SP 16, Table 41
gM0 Steel safety factor gamma M0
gM2 Steel safety factor gamma M2
k1 Factor for edge distance and bolt spacing perpendicular to the direction of load transfer - EN 1993-1-8 - Table 3.4
kj Concentration factor
L Length of weld
N Resulting compression force
s Average stress in concrete
s┴ Perpendicular stress
s┴,Rd Perpendicular stress resistance
sEd Equivalent stress
sw,Ed Equivalent stress
sw,Rd Equivalent stress resistance
t Thickness of the anchor plate
t┴ Shear stress perpendicular to weld axis
t|| Shear stress parallel to weld axis
Utilizationc Weld capacity utilization
VEd Anchor shear force

2.8 Warnings
● By using the CBFEM calculation functionality of PROFIS Engineering you may act outside the applicable design codes and your specified
anchor plate may not behave rigid. Please, validate the results with a professional designer and/or structural engineer to ensure suitability
and adequacy for your specific jurisdiction and project requirements.
● The anchor is modeled considering stiffness values determined from load displacement curves tested in an independent laboratory.
Please note that no simple replacement of the anchor is possible as the anchor stiffness has a major impact on the load distribution
results.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

14
Hilti PROFIS Engineering 3.1.5

www.hilti.com.qa
Company: Page: 15
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Nov 5, 2024 (1) Date: 24‫‏‏‬/11‫‏‏‬/2024
Fastening point:

3 Summary of results
Design of the anchor plate, anchor, welds and other elements are based on CBFEM (component based finite element method) and Eurocode
regulations.
Load combination Max. utilization Status
Anchors Combination 1 1% OK
Anchor plate Combination 1 3% OK
Welds Combination 1 9% OK
Concrete Combination 1 10% OK
Profile Combination 1 11% OK

Fastening meets the design criteria!

LOADING

Capacity = 3600kg

Equipment weight = 750kg

Total = 4350kg

Maximum Factored load = 5000kg

Load per Each Plate = 5000/2 = 2500kg = 25kN (vertical)

The base slab check was performed using a minimum slab thickness of 150 mm and two 16 mm bolts with an
anchorage of 80 mm; however, a 300 mm slab thickness and four 16 mm bars with an anchorage of 180 mm will be
supplied. The slab check found it safe, and the results are sufficient.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

15