21EE72 Module 1
21EE72 Module 1
Module-1
a) Introduction
b) Supervisory Control and Data Acquisition
c) Classification of SCADA
MODULE 1
Introduction
Electricity is a converted form of energy and is used extensively in industrial, commercial,
residential and transportation sectors. It can be generated and transmitted in bulk, economically, over long
distances. AC systems have become the most popular system for use, over DC, for the following reasons:
1. AC generators are simpler than DC generators.
2. Transformation of voltage levels is simple, providing great flexibility of different voltage levels at
generation, transmission and distribution.
3. AC motors, widely used, are simpler and more economical than DC motors. In modern power
systems, the grids are interconnected and vary widely in size and structure. However, they
comprise three phase systems, at both generation and transmission. Synchronous generators
(alternators) are used for generation.\
4. The prime movers (primarily turbines) act to convert mechanical energy into electric energy.
5. Thermal plants use coal as the primary fuel and hydel plants use water to run the turbine.
6. The generated power is transmitted over a wide geographical area, at voltage levels higher than
the generated voltage. At the consumer end, the voltage is again stepped down and distributed to
various consumers. Consumers of different types need voltages of different levels.
• Restorative state: This is a transitional state, where the inequality constraints are satisfied by the
emergency control actions taken, but the system has still not come to normalcy in terms of the
equality constraints. We can have a transition either to the alert state or to the normal state.
1.2 Objectives of Power System Control:
1. The system must be able to meet the changing demand in active and reactive power. The spinning
reserve maintained should be sufficient to take care of sudden variations in the demand.
2. The power quality (read voltage quality!!) should meet certain standards with regard to frequency,
amplitude and wave shape.
3. The energy should be supplied at a minimum cost.
To achieve the above objectives, we have several levels of controls that are integrated in a complex
way which are described as below:
The generators are provided essentially with excitation control, to keep the voltage at the desired
levels, and with prime mover control, to maintain the frequency at the desired level.
The prime mover control is concerned with regulation of the speed, and the controls are for the
associated parameters such as water discharge quantity, boiler pressure, temperature, flows, etc.
Power system stabilizers are used to damp oscillations of the generator following a disturbance. A
stabilizing signal is injected into the exciter system to damp the oscillations. Some of the
commonly used feedback signals are frequency and real power.
The system generation control maintains the required active power balance in the system. The
Automatic Generation Control (AGC) is responsible for maintaining this balance, which in turn is
required to hold the frequency around the nominal value. The AGC also maintains the scheduled
power flows in tie-lines, which are responsible for power transfer between different control areas.
The transmission controls include power and voltage control devices, which help maintain the
voltage levels within limits, maintain system stability, protect the system and result in reliable
operation of the system. The control devices are tap changing transformers, Flexible AC
Transmission (FACTS) controllers, shunt reactors, shunt capacitors, phase-shifting transformers
and HVDC controls.
Distribution level controls such as capacitors, wave shaping circuits, etc., are used to provide
quality power to the consumer. These devices maintain the system voltage at the correct frequency
and amplitude, and also help in removing harmonics injected into the load or the system.
The operation and control of the system should ultimately maintain the following:
1. Stability: Continued intact operation of the system, following a disturbance. This depends on the
operating condition and the nature of the disturbance.
2. Security: It is the degree of risk in the power system’s ability to survive contingencies without
interruption to the customer. It is related to the robustness of the system.
3. Reliability: It is the probability of satisfactory operation over a long period. It denotes the ability
of the system to supply adequate service on a nearly continuous basis, with a few intermittent
interruptions over an extended time period.
1.3.2 Balance reactive power generation and demand: This balance is required to maintain the
scheduled voltages. Reactive power sources are generators and capacitor banks. They must be
constantly adjusted to maintain the voltages at all levels, within permissible range, to protect the
equipment. The generator automatic voltage regulators control the voltage level of the generators.
Today, FACTS controllers are commonly used for reactive power control.
1.3.3 Ensure thermal limits are not exceeded: The heating limits of the overhead lines must not be
exceeded; otherwise, the lines will sag into the objects given below. There are many critical blackouts
which have resulted due to sagging of lines, leading to short circuits, relay tripping and ultimately grid
collapse.
1.3.4 Maintain system stability: “Power system stability is the ability of an electric power system, for
a given initial operating condition, to regain a state of operating equilibrium after being subjected to a
physical disturbance, with most system variables bounded so that practically the entire system remains
intact”. If a system loses stability, the grid may face a total collapse. Stability limits will specify the
maximum power that can be transferred over the lines.
Angle stability is the ability of the generators connected to the grid to remain in synchronism.
Voltage stability is the ability of the system to maintain steady acceptable voltages at all buses in the
system under normal operating conditions and also after a disturbance. Both are vital for the health of
the system.
1.3.5 Meet N−1 reliability criteria: This means that the system should remain operational and secure
even after the loss of the largest generator in the system. (N is the number of generators, N−1 indicates
loss of one generator!). Further, after a contingency, the operators must assess the health of the system
in the eventuality of another contingency, and take suitable control actions to maintain system security,
if it were to occur.
1.3.6 Plan, design and maintain to operate reliably: The planning, design and maintenance should
be such that the system should be operated reliably and within safe limits at all times. Planning
involves both short-term and long-term planning.
1.3.7 Prepare for emergencies: In spite of thorough planning and good design, emergencies such as
weather fluctuations, operator error, software failure, equipment failure, etc., can occur. Operators
must be trained to prepare for such emergencies.
3. Frequency instability: This is the inability of the system to maintain the frequency within the
prescribed limits. It arises due to an inability to match the generation and the demand.
4. Voltage instability: This arises when disturbances or increase in load demand can cause
uncontrollable voltage collapse.
5. Cascading effects of outages and overloads.
Preventive control is meant to keep the system in the normal state or bring it back to the normal state
from the alert state. Automatic controls are provided for frequency and voltage control. Preventive
control measures commonly used are as follows:
1. Rescheduling of active power generated by various units, to match the changing load.
2. Start-up of generation units and providing adequate spinning reserve.
3. Switching of shunt elements for reactive power control. This will help maintain the voltage within
desired limits.
4. Change of reference points of controllable devices such as FACTs controllers, phase-shifting trans
formers, etc.
5. Change in the voltage reference points of generators and voltage control devices.
6. Change of substation configuration, like bus-bar splitting, etc.
control actions based on the state of the system, such as preventive control/emergency
control/restorative control, etc. This subsystem should also take a decision on the VAR support to
be provided in the system for the voltage profile to be maintained.
The hierarchical control can be broadly classified into three levels:
1. Level 1: Load forecasting, unit commitment, trading (longer duration).
2. Level 2: Economic dispatch, optimal power flow, interchange evaluation (duration around 5–10
min).
3. Level 3: Automatic generation control, voltage control, state estimation (time in seconds). Level 1
functions require statistical data and hence probabilistic methods are used. The results of level 1
are used in level 2 and level 3 functions. These are mainly deterministic in nature.
i. SCADA: A SCADA system performs traditional operations of data acquisition and control
functions, including a limited amount of record keeping and data reporting.
ii. SCADA/AGC: It is similar to SCADA, except that AGC capabilities are included to calculate
the area control error, monitor system frequency and tie-line interchanges, and perform
economic dispatch.
1.7.2 EMS: Energy management systems incorporate all features of SCADA and also include other
computations, such as load flows, state estimation, contingency analysis, etc. It includes extensive
capabilities of record keeping and data exchange.
1.7.3 DMS: Distribution management systems are meant to monitor and control distribution feeder
loads. DMS today includes topology analysis and load flow programs that allow identification of
problems and restoration of services.
1.7.4 LMS: Load management system is meant to manage the peak load and is useful for demand-side
management. It can be a stand-alone program or integrated into EMS or DMS.
1.7.6 Telemetry: Telemetry refers to the technique used in transmitting and receiving information or
data over a medium. Typical data in a power system are the measurements of voltage, power
flows, circuit breaker status, etc. The information is transmitted over a medium, such as cable,
telephone, internet or radio. The information can come from multiple locations.
1.7.7 Data Acquisition It refers to the method used to access and control the information or data from
the equipment that is being controlled or monitored. The data are then forwarded via the
telemetry system. The information can be either in an analog or in a digital form. It is the data
obtained from sensors, meters, actuators, control equipment like relays, valves, etc.
The software of the SCADA system is programmed to tell the system what to monitor, what are the
operating ranges, when to initiate alarms, controls, etc. Further, the system may consist of intelligent
electronic devices (IEDs) that are smart sensors, at times combining a sensor, low level intelligent
control, a communication system and program memory in one device.
industries. It has very good programmability. Modern PLCs also have extensive communication features
and radio units for use with SCADA systems.
1.8.3 Communication Network : This refers to the communication equipment needed to transfer data to
and from different sites. Commonly used communication media are RS-232/RS-442/RS-485, dial-up
telephone lines or dedicated landline, microwave, satellite, X.25 packet protocols and radio via
trunked/VHF/UHF. Cables are normally used in factories and are not practical for systems spread over
wide geographical areas due to the high cost of cables. The use of radio lines is common. Dial-up
telephone lines are used for connecting remote stations economically. This is shown in Fig.
• Auxiliary Power Supply: An auxiliary power supply or source is basically an electric power
supplied by a backup alternate source other than the primary main source. IEDs always need an
auxiliary power supply, unlike older protection relays where an auxiliary power supply is of not
much significance. So, the acceptable power supply used by IEDs is in the range
between 15 to 150 volts in the case of DC. While 110 to 140 Volts when AC.
• Analog Inputs: In relays, inputs are provided by the current transformer and potential
transformers. However, IEDs may have sensor inputs.
• Digital Inputs: Digital inputs provided to the IEDs may be some sort of commands or any status
information. Some of these need potential free contacts while some understand with the
consideration of logic 0 or logic 1 as negative voltage and positive voltage respectively.
• Analog Outputs: Generally, transducers are used to get the output from the IEDs which is
programmable type. The output can be of active or passive nature but a passive type output
requires an external power supply.
• Digital Outputs: In the case of digital outputs, the potential contacts can be normally open,
normally closed, or solid-state contacts. Similar to digital inputs, digital outputs are also
commands or status information, and the switching capability must be properly checked as the
significant differences can be noticed.
1.10.3 Combination Systems: These are a combination of master stations and sub-master stations. These
are shown in Figure
1.10.4 Systems with Gateway Connections: With the prolific use of Ethernet, gateway connections
have become popular. Such a connection is shown in Fig.
1.10.5 Networked Systems :Drastic technological advancements in networking have made such systems
popular. They use WAN/LAN for networking, through routers as shown in Fig.
1.11Advantages of SCADA:
• The data can be displayed in a variety of formats based on the needs of the user.
• Real data simulations can be obtained with the assistance of operators.
• It provides an interface to connect thousands of sensors across the wide region for various
monitoring and controlling operations.
• The system is capable of storing large amounts of data.
• Real data simulations can be obtained with the assistance of operators.
• Many types of data can be gathered from RTUs connected with the master unit.
• Data can be monitored from anywhere, not just the local site, thanks to advanced protocols and
application software.
• It is fast in obtaining a response.
• The SCADA system incorporates unit redundancy to provide a backup in the event of faults or
failures. This strengthens the system.
Question Bank