Air System Sizing Summary for airsystem

Project Name: oneroom 11/25/2024


Prepared by: HVAC SIMPLIFIED AMK 03:21PM

Air System Information


Air System Name .................................... airsystem Number of zones ......................................................... 1
Equipment Class ...................................... CW AHU Floor Area ............................................................ 100.0 ft²
Air System Type .......................................... SZCAV Location .............................................. New Delhi, India

Sizing Calculation Information

Calculation Months ................................ Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................ Calculated Space CFM Sizing ........... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ..................................................... 6.8 Tons Load occurs at ................................................ Aug 1700
Total coil load ................................................... 81.3 MBH OA DB / WB ................................................ 104.8 / 71.4 °F
Sensible coil load .............................................. 81.1 MBH Entering DB / WB .......................................... 75.8 / 62.8 °F
Coil CFM at Aug 1700 ..................................... 4170 CFM Leaving DB / WB ........................................... 57.3 / 56.1 °F
Max block CFM ................................................ 4170 CFM Coil ADP ................................................................. 55.2 °F
Sum of peak zone CFM ................................... 4170 CFM Bypass Factor ...................................................... 0.100
Sensible heat ratio .......................................... 0.998 Resulting RH ............................................................. 49 %
CFM/Ton ........................................................ 615.7 Design supply temp. ............................................... 58.0 °F
ft²/Ton ............................................................... 14.8 Zone T-stat Check ................................................ 1 of 1 OK
BTU/(hr·ft²) ..................................................... 812.7 Max zone temperature deviation ............................... 0.0 °F
Water flow @ 10.0 °F rise ............................... 16.26 gpm

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max CFM .............................................. 4170 CFM Fan motor BHP ....................................................... 2.28 BHP
Standard CFM ................................................. 4064 CFM Fan motor kW ......................................................... 1.81 kW
Actual max CFM/ft² ......................................... 41.70 CFM/ft² Fan static ................................................................ 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 32 CFM CFM/person ......................................................... 16.00 CFM/person
CFM/ft² ............................................................. 0.32 CFM/ft²

Hourly Analysis Program 5.10 Page 1 of 14


Zone Sizing Summary for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

Air System Information


Air System Name .................................... airsystem Number of zones ......................................................... 1
Equipment Class ...................................... CW AHU Floor Area ............................................................ 100.0 ft²
Air System Type .......................................... SZCAV Location .............................................. New Delhi, India

Sizing Calculation Information

Calculation Months ................................ Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................ Calculated Space CFM Sizing ........... Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20.0 °F (MBH) @ 20.0 °F (CFM)
Zone 1 4045 4045 40.45 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 72.4 Sep 1700 3.3 100.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
room 1 72.4 Sep 1700 4045 3.3 100.0 40.45

Hourly Analysis Program 5.10 Page 2 of 14


Ventilation Sizing Summary for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

1. Summary
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................ 32 CFM

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
room 1 100.0 2.0 4044.8 10.00 0.12 0.0 0.0 32.0
Totals (incl. Space Multipliers) 4044.8 32.0

Hourly Analysis Program 5.10 Page 3 of 14


Air System Design Load Summary for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 104.8 °F / 71.4 °F HEATING OA DB / WB 44.0 °F / 36.9 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 20 ft² 552 - 20 ft² - -
Wall Transmission 352 ft² 2895 - 352 ft² 2270 -
Roof Transmission 100 ft² 691 - 100 ft² 313 -
Window Transmission 20 ft² 308 - 20 ft² 296 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 28 ft² 227 - 28 ft² 218 -
Floor Transmission 100 ft² 0 - 100 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 75 W 256 - 0 0 -
Task Lighting 1000 W 3090 - 0 0 -
Electric Equipment 20000 W 62856 - 0 0 -
People 2 352 240 0 0 0
Infiltration - 105 -4 - 228 1
Miscellaneous - 1000 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 72333 236 - 3326 1
Zone Conditioning - 72457 236 - 3211 1
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 4170 CFM 0 - 4170 CFM 0 -
Ventilation Load 32 CFM 987 -43 32 CFM 855 5
Supply Fan Load 4170 CFM 6182 - 4170 CFM -6182 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 2% 1447 - 2% 67 -
>> Total System Loads - 81073 193 - -2050 6
Central Cooling Coil - 81073 196 - 0 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 81073 196 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 4 of 14


Zone Design Load Summary for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 102.8 °F / 70.4 °F HEATING OA DB / WB 44.0 °F / 36.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 20 ft² 911 - 20 ft² - -
Wall Transmission 352 ft² 2777 - 352 ft² 2270 -
Roof Transmission 100 ft² 546 - 100 ft² 313 -
Window Transmission 20 ft² 286 - 20 ft² 296 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 28 ft² 210 - 28 ft² 218 -
Floor Transmission 100 ft² 0 - 100 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 75 W 256 - 0 0 -
Task Lighting 1000 W 3090 - 0 0 -
Electric Equipment 20000 W 62856 - 0 0 -
People 2 352 240 0 0 0
Infiltration - 98 -9 - 228 1
Miscellaneous - 1000 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 72381 231 - 3326 1

Hourly Analysis Program 5.10 Page 5 of 14


Space Design Load Summary for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

TABLE 1.1.A. Component Loads For Space "room" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 102.8 °F / 70.4 °F HEATING OA DB / WB 44.0 °F / 36.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 20 ft² 911 - 20 ft² - -
Wall Transmission 352 ft² 2777 - 352 ft² 2270 -
Roof Transmission 100 ft² 546 - 100 ft² 313 -
Window Transmission 20 ft² 286 - 20 ft² 296 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 28 ft² 210 - 28 ft² 218 -
Floor Transmission 100 ft² 0 - 100 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 75 W 256 - 0 0 -
Task Lighting 1000 W 3090 - 0 0 -
Electric Equipment 20000 W 62856 - 0 0 -
People 2 352 240 0 0 0
Infiltration - 98 -9 - 228 1
Miscellaneous - 1000 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 72381 231 - 3326 1

TABLE 1.1.B. Envelope Loads For Space "room" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 100 0.248 - 543 - 645
E EXPOSURE
WALL 100 0.248 - 927 - 645
W EXPOSURE
WALL 72 0.248 - 535 - 464
DOOR 28 0.300 - 210 - 218
S EXPOSURE
WALL 80 0.248 - 772 - 516
WINDOW 1 20 0.570 0.887 286 911 296
H EXPOSURE
ROOF 100 0.121 - 546 - 313

Hourly Analysis Program 5.10 Page 6 of 14


Hourly Air System Design Day Loads for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

DESIGN MONTH: JUNE


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 88.3 513 12.4 12.4 0.0 0.0 0.0 0.0 0.0 0.0
0100 87.2 488 11.8 11.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 86.1 465 11.2 11.2 0.0 0.0 0.0 0.0 0.0 0.0
0300 85.3 441 10.7 10.7 0.0 0.0 0.0 0.0 0.0 0.0
0400 84.6 419 10.1 10.1 0.0 0.0 0.0 0.0 0.0 0.0
0500 84.4 398 9.6 9.6 0.0 0.0 0.0 0.0 0.0 0.0
0600 84.8 383 9.2 9.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 85.9 373 9.0 9.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 87.9 4170 75.1 75.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 90.7 4170 76.0 76.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 93.9 4170 76.8 76.8 0.0 0.0 0.0 0.0 0.0 0.0
1100 97.6 4170 78.0 78.2 0.0 0.0 0.0 0.0 0.0 0.0
1200 101.0 4170 78.7 78.8 0.0 0.0 0.0 0.0 0.0 0.0
1300 103.6 4170 79.3 79.5 0.0 0.0 0.0 0.0 0.0 0.0
1400 105.4 4170 79.7 79.7 0.0 0.0 0.0 0.0 0.0 0.0
1500 106.0 4170 80.4 80.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 105.4 4170 80.7 81.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 103.8 4170 80.7 80.8 0.0 0.0 0.0 0.0 0.0 0.0
1800 101.5 1304 32.0 32.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 98.7 1291 31.7 31.7 0.0 0.0 0.0 0.0 0.0 0.0
2000 95.8 1280 31.4 31.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 93.5 1270 31.2 31.2 0.0 0.0 0.0 0.0 0.0 0.0
2200 91.3 1259 30.9 30.9 0.0 0.0 0.0 0.0 0.0 0.0
2300 89.6 1247 30.6 30.6 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 89.3 517 12.5 12.5 0.0 0.0 0.0 0.0 0.0 0.0
0100 88.2 493 11.9 11.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 87.1 469 11.3 11.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 86.3 446 10.8 10.8 0.0 0.0 0.0 0.0 0.0 0.0
0400 85.6 424 10.2 10.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 85.4 403 9.7 9.7 0.0 0.0 0.0 0.0 0.0 0.0
0600 85.8 387 9.3 9.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 86.9 376 9.1 9.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 88.9 4170 75.4 75.4 0.0 0.0 0.0 0.0 0.0 0.0
0900 91.7 4170 76.1 76.1 0.0 0.0 0.0 0.0 0.0 0.0
1000 94.9 4170 76.9 76.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 98.6 4170 78.2 78.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 102.0 4170 78.6 78.6 0.0 0.0 0.0 0.0 0.0 0.0
1300 104.6 4170 79.5 79.5 0.0 0.0 0.0 0.0 0.0 0.0
1400 106.4 4170 80.0 80.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 107.0 4170 80.6 80.8 0.0 0.0 0.0 0.0 0.0 0.0
1600 106.4 4170 80.8 81.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 104.8 4170 81.0 81.2 0.0 0.0 0.0 0.0 0.0 0.0
1800 102.5 1308 32.1 32.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 99.7 1295 31.8 31.8 0.0 0.0 0.0 0.0 0.0 0.0
2000 96.8 1285 31.5 31.6 0.0 0.0 0.0 0.0 0.0 0.0
2100 94.5 1275 31.3 31.3 0.0 0.0 0.0 0.0 0.0 0.0
2200 92.3 1264 31.0 31.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 90.6 1252 30.7 30.7 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.10 Page 7 of 14


Hourly Zone Loads for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

ZONE: Zone 1
DESIGN MONTH: JUNE
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 88.3 80.2 40 497.3 12447.0 11607.6 0.0 0.0 0.0
0100 87.2 80.2 40 473.7 11868.3 11053.9 0.0 0.0 0.0
0200 86.1 80.2 40 450.6 11300.9 10510.6 0.0 0.0 0.0
0300 85.3 80.1 40 428.2 10752.7 9983.6 0.0 0.0 0.0
0400 84.6 80.1 40 406.6 10227.5 9477.2 0.0 0.0 0.0
0500 84.4 80.1 40 386.2 9731.7 8997.9 0.0 0.0 0.0
0600 84.8 80.1 41 371.3 9368.3 8648.5 0.0 0.0 0.0
0700 85.9 80.1 41 361.9 9136.8 8428.8 0.0 0.0 0.0
0800 87.9 76.8 49 4044.8 66912.7 67230.1 0.0 0.0 0.0
0900 90.7 76.5 49 4044.8 67691.0 68005.6 0.0 0.0 0.0
1000 93.9 76.8 49 4044.8 68473.8 68624.3 0.0 0.0 0.0
1100 97.6 75.7 50 4044.8 69248.9 69689.7 0.0 0.0 0.0
1200 101.0 76.1 50 4044.8 69967.1 70220.0 0.0 0.0 0.0
1300 103.6 76.3 49 4044.8 70589.7 70756.2 0.0 0.0 0.0
1400 105.4 76.8 49 4044.8 71110.8 71081.6 0.0 0.0 0.0
1500 106.0 75.9 49 4044.8 71542.0 71751.6 0.0 0.0 0.0
1600 105.4 75.8 49 4044.8 71878.7 72088.6 0.0 0.0 0.0
1700 103.8 76.5 49 4044.8 72135.6 72098.9 0.0 0.0 0.0
1800 101.5 80.4 40 1264.6 31141.9 29881.6 0.0 0.0 0.0
1900 98.7 80.4 40 1252.1 30735.1 29580.4 0.0 0.0 0.0
2000 95.8 80.4 40 1241.8 30427.7 29332.5 0.0 0.0 0.0
2100 93.5 80.4 40 1232.2 30143.9 29101.1 0.0 0.0 0.0
2200 91.3 80.4 40 1221.4 29837.6 28841.1 0.0 0.0 0.0
2300 89.6 80.4 40 1209.7 29514.8 28559.2 0.0 0.0 0.0

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 89.3 80.2 40 501.6 12562.8 11709.6 0.0 0.0 0.0
0100 88.2 80.2 40 478.1 11983.9 11157.2 0.0 0.0 0.0
0200 87.1 80.2 40 455.1 11416.6 10615.5 0.0 0.0 0.0
0300 86.3 80.2 40 432.7 10868.8 10090.2 0.0 0.0 0.0
0400 85.6 80.1 40 411.2 10344.0 9585.2 0.0 0.0 0.0
0500 85.4 80.1 40 390.8 9848.7 9107.4 0.0 0.0 0.0
0600 85.8 80.1 40 375.0 9461.4 8735.0 0.0 0.0 0.0
0700 86.9 80.1 40 365.2 9220.0 8506.3 0.0 0.0 0.0
0800 88.9 76.3 48 4044.8 66995.2 67443.9 0.0 0.0 0.0
0900 91.7 76.5 48 4044.8 67772.9 68066.5 0.0 0.0 0.0
1000 94.9 76.7 48 4044.8 68569.0 68732.9 0.0 0.0 0.0
1100 98.6 75.5 50 4044.8 69357.4 69854.8 0.0 0.0 0.0
1200 102.0 76.6 48 4044.8 70087.4 70179.0 0.0 0.0 0.0
1300 104.6 76.2 49 4044.8 70718.2 70895.9 0.0 0.0 0.0
1400 106.4 76.3 49 4044.8 71239.2 71341.2 0.0 0.0 0.0
1500 107.0 75.8 49 4044.8 71663.4 71884.2 0.0 0.0 0.0
1600 106.4 75.9 49 4044.8 72004.0 72167.8 0.0 0.0 0.0
1700 104.8 75.9 49 4044.8 72262.9 72397.8 0.0 0.0 0.0
1800 102.5 80.4 40 1268.6 31264.8 29978.2 0.0 0.0 0.0
1900 99.7 80.4 40 1256.5 30859.1 29686.1 0.0 0.0 0.0
2000 96.8 80.4 40 1246.2 30551.1 29439.9 0.0 0.0 0.0
2100 94.5 80.4 40 1236.6 30264.3 29207.3 0.0 0.0 0.0
2200 92.3 80.4 40 1225.8 29955.6 28946.6 0.0 0.0 0.0
2300 90.6 80.4 40 1214.1 29631.4 28664.7 0.0 0.0 0.0

Hourly Analysis Program 5.10 Page 8 of 14


System Psychrometrics for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

August DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 104.8 0.00924 32 400 987 -43
Vent - Return Mixing Outlet 75.8 0.00953 4170 801 - -
Central Cooling Coil Outlet 57.3 0.00952 4170 801 81073 196
Central Heating Coil Outlet 57.3 0.00952 4170 801 0 -
Supply Fan Outlet 58.7 0.00952 4170 801 6182 -
Cold Supply Duct Outlet 59.0 0.00952 4045 801 - -
Zone Air - 76.1 0.00953 4045 804 72457 236
Return Plenum Outlet 76.1 0.00953 4045 804 0 -
Duct Leakage Air Outlet 58.7 0.00952 125 801 - -
Return Duct Outlet 75.5 0.00953 4170 804 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.053 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4626.4 BTU/(hr-CFM)
Site Altitude = 708.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 72333 Cooling 72457 76.1 4045 804 0 0

Hourly Analysis Program 5.10 Page 9 of 14


System Psychrometrics for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 44.0 0.00312 32 400 -855 -5
Vent - Return Mixing Outlet 69.2 0.00315 4170 797 - -
Central Cooling Coil Outlet 69.2 0.00315 4170 797 0 0
Central Heating Coil Outlet 69.2 0.00315 4170 797 0 -
Supply Fan Outlet 70.6 0.00315 4170 797 6182 -
Cold Supply Duct Outlet 70.1 0.00315 4045 797 - -
Zone Air - 69.3 0.00315 4045 800 -3211 -1
Return Plenum Outlet 69.3 0.00315 4045 800 0 -
Duct Leakage Air Outlet 70.1 0.00315 125 797 - -
Return Duct Outlet 69.4 0.00315 4170 800 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.053 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4626.4 BTU/(hr-CFM)
Site Altitude = 708.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -3326 Heating -3211 69.3 4045 800 0 0

Hourly Analysis Program 5.10 Page 10 of 14


Hourly Air System Design Day Loads for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

Data for June

Total Cooling Total Heating


80

70

60
Load ( MBH )

50

40

30

20

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Data for July

Total Cooling Total Heating


80

70

60
Load ( MBH )

50

40

30

20

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.10 Page 11 of 14


Hourly Zone Design Day Loads for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

Zone: Zone 1
Data for June

Zone Sensible Zone Conditioning


70000

60000

50000
BTU/hr

40000

30000

20000

10000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning

70000

60000

50000
BTU/hr

40000

30000

20000

10000

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.10 Page 12 of 14


System Psychrometrics for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

Location: New Delhi, India


Altitude: 708.0 ft.
Data for: August DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Duct Heat
6. Room Air
7. Return Duct Outlet
0.016

Specific Humidity ( lb/lb )


0.014

0.012
3 45 26 1 0.010
7

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.10 Page 13 of 14


System Psychrometrics for airsystem
Project Name: oneroom 11/25/2024
Prepared by: HVAC SIMPLIFIED AMK 03:21PM

Location: New Delhi, India


Altitude: 708.0 ft.
Data for: WINTER DESIGN HEATING
0.020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Duct Heat 0.018
5. Duct Heat
6. Room Air
7. Return Duct Outlet
0.016

Specific Humidity ( lb/lb )


0.014

0.012

0.010

0.008

0.006

1 2 3 5 0.004
76 4
0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.10 Page 14 of 14