Installation- & Operation manual

[Doc. id: mi-335gb_181204]

Micaflex FD ver 4
Differential pressure and flow transmitter MF-FD
with microcontroller and digital indication ver 4
NOTE ! ZERO ADJUSTMENT
Read through the entire manual before you begin in- Switch on the main supply and wait at least 60 sec.
stallation and programming. Set the manifold valve in position calibration (if there
is no valve, loosen the pressure tubes from the MF-
APPLICATION FD). Remove the cover to access the Zero-setting
MF-FD is a pressure transmitter designed for flow key on the main circuit board. Check that the minia-
measuring. ture switch no 2 is in position ”OFF”. Press down the
Zero-setting key, the LED starts flashing. Keep the
MOUNTING key pressed until the LED turns off. Release the key
MF-FD is designed for wall mounting but can be fitted and the zero-setting is finished.
with an optional frame kit, MFM-PANEL, for recessed
mounting in a wall or through a cabinet door. OUTPUT SIGNAL SELECTION
MF-FD is screwed to the wall using four screws, max Volt and mA signal have different wiring terminals.
ø 4mm. Location of screw holes are shown on the re- Verify that the correct output is connected.
verse of the enclosure.
SETTING OF DAMPING
PRESSURE CONNECTIONS MF-FD offers a possibility to set different damping
Pressure connection to measuring device is done (time constant). At delivery of MF-FD, the damping is
with HT-plastic tube 8/6 mm. set to 1,5 seconds damping. Setting is adjusted with
the miniature switch no 4 and 5 (the switch is situated
Pressure connections [+] and [-] are connected to the
on the bottom left edge of the main circuit board).
flow measuring device according to its guidelines.

Adjustment keys FORCED OUTPUT SIGNAL


See instructions on our web site.
Max output signal (10 Volt and 20 mA) is obtained
when miniature switch no 3 is set to position ”ON”. This
function can be used to check the receiving system.
Programming keys

Miniature switch LED

ADJUSTING THE MEASURING RANGE


The measuring range can be adjusted to correct a
Zero-setting key measuring deviation. Instruction can be found on our
website, www.micatrone.com.

[© AB Micatrone, mi-335gb_181204] Page 1 of 4


DISPLAY UNIT ALARM
MF-FD is fitted with a 4-digit LED display and LED’s MF-FD include a visual alarm indicated by a flashing
for flow or pressure indication. display on alarm state, if this function is activated.
Shifting between flow or pressure indication is done By using an optional plug-in module, a potentialfree
with the arrow-keys on the display circuit board. This changing relay output can be obtained.
function does not affect the selected output signal, P01, Alarm limit [Flow]
only the indication of measured flow or pressure. Parameter for the flow at which the alarm will be trig-
Programming of all parameters is done by four keys gered. Number of decimals determined in P06.
on the display circuit board. Example 1:
P01 = 024.0 l/s
P02 = 010 s
P03 = Hi
Alarm is triggered when the flow is above 24 l/s (i.e.
Flow ind. 24.5 l/s) for more than 10 seconds.
Example 2:
Pressure ind. P01 = 05.00 m3/h
P02 = 060 s
P03 = Lo
Alarm is triggered when the flow is below 5 m3/h (i.e.
4.8 m3/h) for more than 60 seconds.
Programming keys
The alarm is reset automatically when alarm condition
no longer exists.
P02, Time delay [seconds]
PROGRAMMING
Parameter for setting the time delay in seconds be-
MF-FD is programmable and include following para-
fore the alarm is triggered.
meters that can be programmed:
P03, Alarm function
No Description Min Max Preset Parameter to obtain alarm at increasing flow (High
P01 Alarm limit [Flow] 0000 [P05] 0000
alarm), decreasing flow (Low alarm) or no alarm (Off).
P02 Time delay [seconds] 000 600 000
P03 Alarm function
off = Off
off Lo off
Hi = High alarm
Lo = Low alarm
P05 Flow indication at max. 0000 9999 0000
pressure
P06 Number of decimals for 0 3 0
flow indication
P07 Selection of output
P = Pressure linear
P F F
F = Flow linear
Keep the PGM key pressed until P is shown in dis-
play. Use the arrow-keys to select the parameter to
change. Press the PGM key to access the selected
parameter.
P01, P02, P05 & P06:
To change the value of the parameter, press the PGM
key again. The first digit will begin to flash, indicating
that the digit can be changed. Adjust the value of the
digit by pressing the arrow-keys. Confirm each digit
FLOW INDICATION
by pressing the PGM key. When the last digit is pro-
Calculate the flow for max. pressure of the transmit-
grammed and confirmed with the PGM key, all digits
ter. The max. pressure is noted on the label situated
will flash fast and then turn to show the parameter.
on the right side of the enclosure.
P03 & P07:
Programming of the calculated flow at max. pressure
To change the value of the parameter, press the PGM
is done in P05 with 4 digits [0000 ... 9999] and num-
key again. The display will begin to flash, indicating
ber of decimals in P06 with 1 digit [0 ... 3].
that the value can be changed. Adjust the value by
pressing the arrow-keys. Confirm by pressing the Example:
PGM key. The display will flash fast and then turn to Max. pressure gives a flow of 10.50 m3/h.
show the parameter. Program the value 1050 in parameter P05
Program the value 2 i parameter P06
Press the ESC key to return to normal indication of
Check that P05 shows 10.50
actual flow or pressure.
After 5 minutes, with no key has been used, the pro-
gramming is terminated automatically.

Page 2 of 4 [© AB Micatrone, mi-335gb_181204]


TECHNICAL DATA SERVICE
Supply voltage: 24 ± 15% VAC, 20...32 VDC MF-FD normally needs no service, but we recom-
24, 115, 230 VAC (with mend to check the zero point once a year.
transformer) 50/60 Hz
Power Max 4 VA (24 VAC) CLEANING
consumption: Max 2 W (24 VDC) MF-FD should be cleaned with a soft cloth and a light
Max 8 VA (230 VAC) detergent. Do not use scouring powder or solvent.
Range: 0...50 Pa
0...100 Pa TRANSFORMER (OPTIONAL)
0...200 Pa The output signal is normally not galvanically se-
0...500 Pa parated from the supply voltage. To obtain galvanic
0...1 kPa separation between the output signal and the supply
0...2 kPa voltage on a standard transmitter, the apparatus must
0...5 kPa
be equipped with a plug-in transformer. Plug-in trans-
Other ranges on request.
former can be obtained for 24, 115 or 230 VAC.
Overload: Max 50 kPa
Accuracy: < ± 0,5 % of the full range plus ALARM MODULE (OPTIONAL)
± 0,5 Pa The MF-FD can be fitted with a built-in alarm module.
Temperature drift: < ± 0,5 % /10 °C The alarm module include a potentialfree changing
Damping: Selectable time constants of relay output for max. 48 volt / 5 A. The figure show
0.05, 0.7, 1.5 and 2.2 s. the relay output in an unpowered state [NC], i.e.
alarm state.
Output signal: 4...20 mA max RL = 400 Ohm
0...10 Volt Ri = 0 Ohm
Both mA and Volt signal can
be used simultaneously.
0 ... 20 mA can be ordered.
Inverted signal can be ordered.
Ambient temp.: 0...50°C
Degree of protec.: IP 65, ABS plastic
El. connections,
- solid conductor: 1 x 2,5 mm2 / terminal
- stranded conductor: 1 x 1,5 mm2 / terminal
Cable entries: 2 pcs threaded holes M16x1,5 CONNECTION ALARM MODULE
(cable glands not included) (Alarm module and Transformer can’t be
used at the same time.)
Pressure. conn.: 8/6 mm HT-plastic tube
Dimensions: WxHxD = 122x120x90 mm
Weight: 0.60 kg

EMC/LVD/ROHS II
AB Micatrone declare under sole responsibility that
MF-FD is in conformity with the essential require-
ments in the EMC-, the LVD- and the RoHS II direc-
tive. The full text of Manufacturers declaration of con-
formity is available on Micatrones website.

CONNECTION 24 VAC / 20...32 VDC CONNECTION 24 / 115 / 230 VAC


(without transformer) (with built-in transformer)

[© AB Micatrone, mi-335gb_181204] Page 3 of 4


MODBUS RTU (OPTIONAL)
MF-FD can be fitted with a built-in expansion module
for network communication with a computer via RS-
485 serial connection. See separate instruction for
Modbus RTU.
Modbus RTU can NOT be used with Alarm module or
Transformer.

AB Micatrone Telephone: +46-8-470 25 00


Aldermansvagen 3
SE-171 48 SOLNA Internet: www.micatrone.com
SWEDEN E-mail: [email protected]
Page 4 of 4 [© AB Micatrone, mi-335gb_181204]