Four Pole, Non-Directional, IDMT 3 O/C + 1 E/F Relay With


Inst. Highset For Both O/C And E/F Elements
JRC 068

JVS ELECTRONICS PVT. LTD.


#121,Manchanayakanahalli,
Bangalore Mysore Highway, Bidadi,
Ramanagara District - 562 109, Karnataka, India
+91 94808 26272, +91 94808 26260
[email protected], www.jvselectronics.in
Four Pole, Non-Directional, IDMT 3 O/C + 1 E/F Relay With
Inst. Highset For Both O/C And E/F Elements
JRC 068
FEATURES
 So�ware based design
 Programmable �me current characteris�cs
 Choice of four IDMT curves
 Draw out case

APPLICATIONS
The relay provides �me graded phase and earth
fault protec�on of Genrators, Transformers, feeder,
capacitors etc.,

PRINCIPAL OPERATION
The relay measures the line current from each of the phases and if exceeds the set threshold, then
relay extends a trip signal a�er the opera�ng �me. The relays opera�ng �me is determined by
selec�ng one of the four inverse �me current characteris�cs. The relay has facility to ac�ve /
inhibit the high set protec�on feature. The relay output contacts are self reset / hand reset type.
Relay opera�on without any fault current is determinated by trip test facility.

TECHNICAL DATA
RATINGS
Current ra�ng : 1A / 5A
Auxiliary Supply : 1) 20-60V DC
: 2) 75 – 150V AC / DC
: 3) 175 – 300V DC
: 185 – 250V AC
SETTINGS
Opera�ng characteris�cs : 1) 3.0s Normal Inverse
: 2) 1.3s Normal Inverse
: 3) 1.5s Very Inverse
: 4) 0.8s Extremely Inverse
: 5) 0.6s Extermely Inverse
Phase Overcurrent : 50% to 200% in steps of 10% or
: 20% to 140% in steps of 10%
Earth fault : 5 to 80% in steps of 5%
TMS : 0.1 to 1.0 in steps of 0.01(Seperate for O/C & E/F)
Phase Hi-set : 200% to 3200% in steps of 200%
Earth fault Hi-set : 50% to 800% in steps of 50%

OVER LOAD RATINGS


Current input : 2 �mes rated con�nuously
: 20 �mes Rated for 3s
: 40 �mes of rated for 1s

[email protected], www.jvselectronics.in
Four Pole, Non-Directional, IDMT 3 O/C + 1 E/F Relay With
Inst. Highset For Both O/C And E/F Elements
JRC 068
BURDEN
Current input : 0.2VA per phase (rated 5A)
: 0.05VA per phase (rated 1A)
Auxiliary supply : Less than 8W(Non operated)
: Less than 10W(Operated)

ACCURACY
Opera�ng value : 105% to 120% of se�ng
Drop-off / pick-up : Between 80% to 95%
Opera�ng �me : +/-5% or +/- 30ms whichever is higher
High set opera�ng value : +/-5% or +/- 30ms whichever is higher
High set opera�ng �me : Less than 30ms @ 2 �mes current se�ng
Reset Time : 160ms to 180ms

CONTACT RATINGS
Trip / Alarm : 10A at 24V DC/230V AC

CONTACTS DURABILITY
Unloaded contact : 10,000 Opera�ons
Loaded contact : 20,000 Opera�ons

MECHANICAL DESIGN
Weight : Approx. 2500 gms
Case size : 144 sq mm with depth of 232 mm
Installa�on : Flush moun�ng
Panel cutout : 138 X 138 mm

STANDARD COMPLIANCE
Accuracy test : IEC 60255-3
Insula�on test : IEC 60255-5

[email protected], www.jvselectronics.in
Four Pole, Non-Directional, IDMT 3 O/C + 1 E/F Relay With
Inst. Highset For Both O/C And E/F Elements
JRC 068

TERMINAL DIAGRAM

ORDERING INFORMATION
Relay Type : JRC 068
Current ra�ng : 1A or 5A
Aux Supply : 1) 20-60V DC
: 2) 75 – 150V AC / DC
: 3)175 – 300V DC / 185 – 250V AC