Fuel Analysis Report Report date
LAKDHANAVI LTD 25-Oct-2021
FENI LANKA POWER (BANGLADESH)
Sample Number SNG21F038269
98 °C
Sent From Dhaka separation temperature
Date Sent 06-Oct-2021
Arrived at Lab 11-Oct-2021
Product Type HFO
Sampling Point HFO FEEDER NO.1 INLET
Sampling Date 03-Oct-2021
Sampling Method Not Stated
Seal Data 2451659 (VPS, Intact)
1 SNG21F038269
FENI LANKA POWER (BANGLADESH)
Test Results
Unit Test Results Test Method
Density @ 15°C kg/m3 985.1 ASTM D7042
Viscosity @ 50°C mm2/s 161.5 ASTM D7042
Water %V/V 0.10 ASTM D6304-C
Micro Carbon Residue %m/m 12.58 ISO 10370
Sulfur %m/m 2.66 ISO 8754
Total Sediment Potential %m/m 0.02 ISO 10307-2
Ash %m/m 0.033 LP 1001
Vanadium mg/kg 94 IP 501
Vanadium mg/kg 94.2 -
Sodium mg/kg 14.2 -
Sodium mg/kg 14 IP 501
Aluminium mg/kg 3 IP 501
Silicon mg/kg 9 IP 501
Iron mg/kg 7 IP 501
Nickel mg/kg 32 IP 501
Calcium mg/kg 8 IP 501
Calcium mg/kg 7.6 -
Magnesium mg/kg <1 LP 1101
Lead mg/kg <1 LP 1101
Lead mg/kg 0.4 -
Zinc mg/kg 15 IP 501
Phosphorus mg/kg <1 IP 501
Potassium mg/kg <1 LP 1101
Potassium mg/kg 0.5 -
Pour Point degC < 24 LP 1304
Flash Point degC > 70.0 ISO 2719-B
Net Specific Energy¹ MJ/kg 40.38 ISO 8217
CCAI (Ignition Quality)¹ - 856 ISO 8217
Aluminium + Silicon mg/kg 12
Acid Number mg KOH/g 0.16 ASTM D664
¹ Calculated value
Approximate fuel temperatures
Injection 125 °C for 10 mm²/s, 110 °C for 15 mm²/s, 100 °C for 20 mm²/s,
95 °C for 25 mm²/s
Transfer 35 °C
Note
Na, K, Pb, Ca and V are listed in one decimal place as per client’s request
Best Regards,
On behalf of Veritas Petroleum Services BV
Chong Su Wei
Technical Support Engineer
For assistance or further information on this report please contact your nearest VPS office or contact us
directly at Tel : +65 67792475, Email : [email protected]
Reference to part(s) of this report which may lead to misinterpretation is prohibited.
2 SNG21F038269