Atc 900
Atc 900
Description Page
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Hardware Description . . . . . . . . . . . . . . . . . . . . . . . . 6
3. Operator Panel and Display Menus . . . . . . . . . . . . . . . 12
4. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5. Setpoint Programming and I/O Programming
Using the Color Display . . . . . . . . . . . . . . . . . . . . . . . . 18
6. Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . 26
7. Historical & Event Display . . . . . . . . . . . . . . . . . . . . . 30
Appendix A: Feature List and Status Display Messages . 32
Appendix B: I/O Descriptions . . . . . . . . . . . . . . . . . . . 41
Appendix C: Operational Flowcharts . . . . . . . . . . . . . . 43
This document and other information from Eaton, its subsidiaries 1.1.1 Warranty and Liability Information
and authorized distributors provide product or system options for NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WAR-
users having technical expertise. RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OF MER-
This product is not intended for users who do not have technical CHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF
expertise. The user, through its own analysis and testing, is DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE
solely responsible for making the final selection of the system INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CON-
and components and assuring that all performance, endurance, TAINED HEREIN. In no event will Eaton be responsible to the pur-
maintenance, safety and warning requirements of the application chaser or user in contract, in tort (including negligence), strict
are met. The user must analyze all aspect of the application, fol- liability or otherwise for any special, indirect, incidental or conse-
low applicable industry standards, and follow the information quential damage or loss whatsoever, including but not limited to
concerning the product in the current product catalog and in any damage or loss of use of equipment, plant or power system, cost
other materials provided from Eaton or its subsidiaries or autho- of capital, loss of power, additional expenses in the use of existing
rized distributors. power facilities, or claims against the purchaser or user by its cus-
To the extent that Eaton or its subsidiaries or authorized distribu- tomers resulting from the use of the information and descriptions
tors provide component or system options based upon data or contained herein. analyze all aspects of the application,follow
specifications provided by the user, the user is responsible for applicable industry standards, and follow the information concern-
determining that such data and specifications are suitable and ing the product in the current product catalog and in any other
sufficient for all appliations and all reasonable foreseeable uses materials
of the components or systems.
1.1.2 Safety Precautions
Section 1: Introduction All safety codes, safety standards, and/or regulations must be
strictly observed in the installation, operation, and maintenance of
Description this device.
Eaton’s ATC-900 brings intelligence, adaptability, supervisory and
programming capabilities to automatic transfer switch equipment.
The smartESTTM (smart Eaton Switch Technology) brings a new WARNING
standard in Automatic Transfer Switches. THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PRO-
Extreme reliability makes the ATC-900 ideal for mission critical CEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONNEL SAFETY
applications in healthcare, wastewater, data center and other AND PROTECTION OF EQUIPMENT FROM DAMAGE.
industries. Typically used for utility-to-utility, utility-to-generator,
generator-to-generator and three source transfer systems, the
ATC-900 can address virtually any system requirements. WARNING
Ease-of-use is a major benefit of the ATC-900 controller. With a
simple, powerful user interface, many intuitive operating features COMPLETELY READ AND UNDERSTAND THE MATERIAL PRE-
SENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION,
are included. LED indications and a TFT based color display pro- OPERATION OR APPLICATION OF THE EQUIPMENT. IN ADDITION,
vide high visibility. Simple arrow keys are used for quick screen ONLY QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM
navigation. No codes or abbreviations are used to avoid potential ANY WORK ASSOCIATED WITH THE EQUIPMENT. ANY WIRING
confusion and/or slow operation, and data screens are grouped for INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOL-
ease of viewing and edits. LOWED PRECISELY. FAILURE TO DO SO COULD CAUSE BODILY
INJURY, DEATH AND/OR PERMANENT EQUIPMENT DAMAGE.
The ATC-900 is available in one standard model that offers a vari-
ety of monitoring and control features such as selective and auto-
matic load shedding, remote load testing, and event logging/
recording. Flexibility is another important benefit, allowing field
1.4.2 Standard and Optional Features The switch type also dictates what can be programmed. For
A variety of programmable features are available to meet a wide example, a two position contactor switch cannot have feature
array of application requirements. Individual features or feature TDN (Time Delay Neutral), as it has no neutral position available.
combinations provide the information required to tailor switches to A motor MCS/MCCB type transfer switch with motor operator
individual needs. cannot have closed transition as the switching mechanism is not
Unlike earlier controllers, the ATC-900 comes with standard fea- fast enough and will not meet the time line.
tures that are ready to use, with the exception of Closed Transi-
tion, Current metering, and Ethernet. Another advancement is that 1.5.2 In-Phase Operation
there are four (4) standard inputs and four (4) standard outputs The In-Phase operation of an Automatic Transfer Switch is an
that the operator can easily program by choosing from a wide open type transfer. It will allow a transfer between two available
array of predefined functions. Additional inputs and outputs can sources if the phase angle has a difference of eight degrees or
be added in groups of four (4) up to sixteen (16) for a maximum of less. Appendix A (32C, 32D, 32F) shows detailed descriptions of
twenty (20) in total. The inputs are DC wetted (24 Volts at 10 the different scenarios that can be performed using In-Phase.
ma) connections for various functional inputs.
As shown in the feature list of Appendix A for In-Phase, there are
1.5 Glossary of Terms and Features three scenarios for In-Phase:
32C= In-Phase default to Load Voltage Decay
NOTICE 32D= In-Phase default to Time Delay Neutral
WITH RESPECT TO THEIR USE IN THIS DOCUMENT AND AS THEY 32F= In-Phase
RELATE TO AUTOMATIC TRANSFER SWITCH OPERATION, THE FOL- The user setpoints for In-phase transition are similar to this:
LOWING WORDS OR PHRASES ARE DEFINED.
• Disabled (In-Phase not used)
Available
• Alarm on Synchronization Fail (Will not switch and will show
A source is defined as available when it is within its undervoltage/ an alarm)
overvoltage/underfrequency/overfrequency (if applicable) setpoint
• Fallback to Open on Synchronization Fail (To TDN or LVD)
ranges for the nominal voltage and frequency setting.
For example, with the setpoint at Fallback, using a two position
Unavailable
contactor, the switch will transfer, if no synchronisation occurs,
A source is defined as failed when it is outside of its undervoltage/ to the other source. The three position will allow the use of TDN.
overvoltage/underfrequency/overfrequency (if applicable) setpoint A two or three position could also use Load Voltage Decay.
ranges for the nominal voltage and frequency setting.
Normal Source 1.5.3 Closed Transition Operation
The Normal Source is defined as the source that is preferred. The Several Options for Closed Transition
Preferred Source setting allows the operator to select Source 1, Once an ATS is in the field, other uses or changes may occur that
Source 2 or NONE as the Preferred Source. If NONE is chosen, the could require changes from the original requirements. One area is
Preferred Source or the Normal Source will be the source that is the closed transition type switches. An application may initially
presently attached to the load. The default is set as being Source require that only a closed transition should be used and if it does
1 as the Preferred and Normal Source. not synchronize because of maybe frequency, then the switch will
Emergency Source not switch to the other source and will show an alarm signalling
this issue. If the requirements now have change, for example, and
The Emergency Source is defined as the source that is not pre- the switch must now transfer using open transition if closed does
ferred. If NONE is chosen for the Preferred Source setting, the not occur; instead of sending the controller back to the factory for
Emergency Source will be the source that is presently not reprogramming, one can easily change the user setpoints to
attached to the load. Therefore, in this condition after a transfer, accomplish any scenario. One may go from closed transition
the Normal and Emergency Sources will switch between Source 1 directly to Time Delay Neutral for example. All options are avail-
and 2. able to the user.
1.5.1 Features If closed transition is available on the switch, the user will receive
47 D and all of the other options 47 C, E, F, G which can be
The ATC-900 has many features that are available to the user. changed by the setpoints to disable or enable the functions (see
These features are standard and are available depending on the below). Screen 3 of 3 in the System Setup menu (See section
type of transfer switch used (i.e. Contactor, Power Case Switch/ 3.4.1) is where the user will set the transition types of the switch.
Breaker, or Molded Case Switch/Breaker, 2 or 3 position). Appen- If the switch can perform closed transition the user will set up the
dix A has a list of all of the features including any acronyms used setpoints depending on the scenario required as shown below.
along with a brief description. The feature numbers corresponds
to the internal codes and some of these numbers may be on the Closed Transition to Alarm (47D) or by changing the setpoints,
product drawings. See Table 5 "ATC-900 Features" for a compact Closed Transition > In-Phase > TDN
list of features, including a full list of available I/O. Consult
Closed Transition > In-Phase > LVD
Appendix B for I/O descriptions. For some transfer switch configu-
rations, standard input(s) and/or standard output(s) will be fixed at Closed Transition > TDN
the factory to support system functionality and will not be pro- Closed Transition > LVD
grammable in the field. An example of this is Service Entrance;
The user can disable closed transition and just use the following:
which requires Go To Neutral to be a fixed input. The programma-
ble I/Os are covered in Section 5. In-Phase > TDN
The only item that is optional for the transfer switch is the closed In-Phase > LVD
transition optional feature. The closed transition operation is cov- Also with Closed Transition and In-Phase disabled:
ered in section 1.5.3
TDN or LVD
The user setpoints for closed transition are similar to this: Optional Feature 47F: Closed/Load Voltage Decay
• Disabled (Closed transition not used) Closed Transition is a feature that will temporarily parallel two live
• Alarm on Synchronization Fail (Will not switch and will show sources in a make-before-break scheme when performing a trans-
an alarm) fer. This achieves a transfer between sources with no power inter-
• Fallback to Open on Synchronization Fail (To in-phase, TDN, ruption. Both sources must be synchronized in frequency, phase,
and/or LVD) and voltage before the transfer is initiated.
Time Delay Load Voltage Decay utilizes the load voltage measure-
Optional Feature 47C: Closed/In-phase Transition/Load Voltage ments to sense back EMF that is generated when the transfer
Decay switch is in the neutral position. It provides a delay in transfer in
either direction if an unacceptable level is sensed as established
Closed Transition is a feature that will temporarily parallel two live by a customer programmed level. The transfer will not take place
sources in a make-before-break scheme when performing a trans- until the back EMF decays below the acceptable programmed
fer. This achieves a transfer between sources with no power level. This feature has a separate setting of enabling or disabling
interruption. Both sources must be synchronized in frequency, the operation. If disabled, the transfer switch will not delay in the
phase, and voltage before the transfer is initiated. neutral position and will transfer between the sources as fast as
In-phase transition is a feature that will allow a transfer between possible.
two live sources only when the phase difference between the two
sources is near zero. This is an open transition transfer that pre- Optional Feature 47G: Closed/Time Delay Neutral
vents in-rush currents from exceeding normal starting currents in Closed Transition is a feature that will temporarily parallel two live
the case where motor loads are being transferred. sources in a make-before-break scheme when performing a trans-
Load Voltage Decay utilizes the load voltage measurements to fer. This achieves a transfer between sources with no power inter-
sense back EMF that is generated when the transfer switch is in ruption. Both sources must be synchronized in frequency, phase,
the neutral position. It provides a delay in transfer in either direc- and voltage before the transfer is initiated.
tion if an unacceptable level is sensed as established by a cus- Time delay neutral provides a time delay in the transfer switch
tomer programmed level. The transfer will not take place until the neutral position when both breakers/contactors are open. This
back EMF decays below the acceptable programmed level. This delay takes place when the load is transferred in either direction to
feature has a separate setting of enabling or disabling the opera- prevent excessive in-rush currents due to out of phase switching
tion. If disabled, the transfer switch will not delay in the neutral of large motor loads.
position and will transfer between the sources as fast as possible.
Optional Feature 29G: Type of Operation (Selectable Automatic or
Optional Feature 47D: Closed Transition Only Manual)
Closed Transition is a feature that will temporarily parallel two live This feature provides two door mounted selector switches marked
sources in a make-before-break scheme when performing a trans- Auto/Manual and S1-Trip-S2 which permits the selection of auto-
fer. This achieves a transfer between sources with no power matic or manual operation. In manual operation, the user can man-
interruption. Both sources must be synchronized in frequency, ually initiate and electrically operate between S1, Trip, or S2. On
phase, and voltage before the transfer is initiated. If the two avail- the Contactor Bypass's, 29G uses the top switch and the bottom
able sources do not synchronize in a certain settable sync time, switch. See the switch instruction booklet for operating instruc-
the switch will not transfer and an output alarm will be present as tions. The controller is in Monitor Mode during the manual opera-
well as a red flashing banner on the controller stating; Failed to tion meaning the controller will not attempt to change the switch
Sync -(Frequency, Voltage, or Phase angle) position but will monitor the voltage availability and the switch
If the logic is forced into a fail safe mode (i.e. loss of connected positions. The ATC-900's display will show "MONITOR".
source), the logic will perform an open transfer.
Optional Feature 47E: Closed/In-Phase Transition/Time Delay
Neutral
Closed Transition is a feature that will temporarily parallel two live
sources in a make-before-break scheme when performing a trans-
fer. This achieves a transfer between sources with no power
interruption. Both sources must be synchronized in frequency,
phase, and voltage before the transfer is initiated.
In-phase transition is a feature that will allow a transfer between
two live sources only when the phase difference between the two
sources is near zero. This is an open transition transfer that pre-
vents in-rush currents from exceeding normal starting currents in
the case where motor loads are being transferred.
Time delay neutral provides a time delay in the transfer switch
neutral position when both breakers/contactors are open. This
delay takes place when the load is transferred in either direction to
prevent excessive in-rush currents due to out of phase switching
of large motor loads.
9 6
8 10
1. ATC-900 Faceplate (UV resistant) 6. Help Pushbutton (provides help information in any
operational mode)
2. Operational Mode LEDs (highlighting ATC-900’s pres-
ent operational condition) 7. Increase/Decrease Pushbuttons (used individually,
pushbuttons move displayed information/setting up or
3. System Status Mimic Bus (easy-to-read and under- down through all possibilities)
stand LED type)
8. Lamp Test (test all LEDs on the mimic bus #3)
4. Color Display Window (easy-to-read monitored param-
eters, setpoints, and messages) 9. Enter Pushbutton (used to enable the screen selec-
tions)
5. Bypass Timer (used simultaneously to bypass timers
such as TDNE, TDEN, and TDEC) 10. Engine Test Pushbutton (used to start/stop a self-test)
TOP VIEW
SW1 Modbus
Terminator
J1, J2, J3
Source/Load J12 User Modbus
Connectors J9 J5 J14 J13
4 Programmable RS-232 DCT RS-422 J11 I/O
Wet Inputs Module(s)
Module Interface
Interface
J8 USB Front Panel Interface
(Thumb Drive)
J6
J15 S1 & S2 Generator
Switch Position Start
Contacts
K1=S2 Open Earth Controller Ground
K2=S1 Open
K3=S1 Close
K4=S2 Close
J4 (4 Programmable Form C Dry Outputs)
J7
Sources 1 and 2 J4 Source
Control Power Available Outputs
2.5 External Hardware The DCT Module also has a 24 Vdc input for powering the ATC-
900 controller. If 120 VAC and 24 Vdc is supplied to the control-
External hardware is viewed as any optional device mounted ler simultaneously, then the 120 Vac will be the powering supply.
directly to or remotely from the ATC-900, such as a DCT Module,
I/O Module, or an Ethernet device. Since the ATC-900 is always 61F is an option to add a DCT module and a 24VDC power supply
supplied with the necessary communications ports, these modules with a power buffer. This will allow the controller to stay on over
can be retrofitted to the ATC-900 at any time. It is recommended 20 seconds when power is removed, more than enough time to
that the control power to the ATC-900 (J7) be removed prior to ride through the power loss. The controller will then be able to
connecting or disconnecting the modules. See Figures 2, for con- continue to communicate over ie, the MODbus.
nections and section 2.5.2 for interface connections. The following Table 1 is a list of readings and accuracy available
2.5.1 DCT Module Description (Integrated Metering) on the display. Accuracy is for 5 amp secondary WYE or Delta
connections. The meter was tested at the full range of tempera-
The DCT (Direct Current-Current Transformer) Module is a current tures. The accuracies stated are for the meter components (DCT
transformer interface to the ATC-900 allowing current to be Module and ATC-900) only, not the CTs. CTs can be ordered
metered along with voltage and frequency that is already inte- with different accuracies (typically in the 1-2% range). Accuracy
grated into the controller. The DCT Module simply secures to the also can be affected by the CT not being in the correct range of
ATC-900 back using four #8 x less than 1/2 inch screws. With the current being measured, i.e. using a 600:5 CT for a 400 amp
the DCT module installed, the depth of the two units is 3.60 application. Although not a revenue meter, the measurements are
inches. The ribbon cable then plugs into J14 (see Figure 3). When highly accurate for most switch applications.
equipped with a DCT module, the ATC-900 serves as a multifunc-
tion power meter and provides multifunction measurement of
most electrical parameters including voltage, current, power, fre-
quency, energy, etc. The meter capabilities is specified as a 1%
class energy meter. The information is displayed on the color dis-
play on the front of the ATC-900. Readings can also be moni-
tored through the RS-485 modbus on the controller. The DCT is
used to measure load current when selective load shed is enabled.
SHLD
CMN
CMN
B(+)
B(+)
A(-)
A(-)
J3 J18 2 66A8190H05
#3 #4 I/O Module
I/O MODULE I/O MODULE J1 120VAC Power 4 1268C07H31
#1 #2
J2 Inputs and GND 10 67A2590H28
J3 Communications 4 66A8190H02
Figure 5. I/O Module(s) Wiring. J4 Outputs Form C 12 67A2590H32
5.00 (127.0)
3.63 (92.1)
Top view
10.25 9.31
(260.4) (236.5)
Figure 6. Dimensions. Depth of 3.60 inches with DCT module installed. Same footprint as the ATC-600/800.
Section 3: Operator Panel and Display Menus Source 2 Preferred - Status LED
This LED is lit green if Source 2 is the preferred source choice.
3.1 General
Source 2 Connected - Status LED
The operator panel, which is normally accessible from the outside
of a panel or door, provides a means for being alerted to specific This LED is lit red if Source 2 is connected. This is accomplished
conditions, receiving functional help, programming, and parameter by sensing the Source 2 breaker/contactor via the S2 closed auxil-
monitoring/selection (Figure 1). For the purpose of familiarization, iary contact.
the panel is divided into three sub-sections and discussed individu- 3.3 Pushbuttons
ally:
• LEDs The front operations panel supports seven blue membrane push-
buttons. Pushbuttons accomplish their function when pressed and
• Pushbuttons released. Certain pushbuttons, like the Increase and Decrease
• Color Display Window (not a touch screen). Pushbuttons, will also continue to scroll if they are pressed and
not released.
7. Historical Data
a. Event Summary
b. Event Details
c. Hi-Speed Captures
d. Event Data
8. System Info (Figure 7b)
a. Style
b. Transitions
c. GO Number
d. Serial Number
e. Fixed I/O
f. Firmware Versions
g. Time & Date
9. USB Menu
a. Save Setpoints Figure 7b. System Info Screen.
b. Load Setpoints
c. Save Statistics
d. Save Events
e. Save Hi-Speed
There are deeper menus (ie, Prog I/O) but they will be discussed in
sections 5 and 7. Section 5 is "Setpoint Programming and I/O Pro-
gramming. Section 7 is "Historical & Event Display". Figure 7b
shows the System Info screen. System information is shown
including the GO#, Style number, and revisions. The Set Time &
Date button provides time/date change..
The color display also features a status bar that appears across
the top whenever any of the following conditions are present:
Currently Active Controller Features (e.g. Emergency Inhibit,
Engine Test, etc.)
Currently Active Alarms (banner turns red)
Appendix A shows a list of Status Display Messages
Transfer Operation Connections Output Relays K1, K2, K3, K4 Manual Re-Transfer (Input)
K1, K2, K3, and K4 on J6 pins 5 through 12 are factory wired to With manual retransfer enabled, a momentary closure allows the
operate the transfer switch. The relay contacts for each are rated ATC-900 to proceed with a re-transfer operation at the operators
for 10 A, 1/3 HP @ 250 Vac. The DC rating is 10 A @30 Vdc. discretion. Should a failure of the emergency source occur while
The K relay outputs are used to control the transfer device. Cer- waiting for the manual return, the re-transfer proceeds automati-
tain configurations of power use only the Open K relays. The K cally (failsafe).
relays default configuration is: Emergency Inhibit (Load Shed) (Input)
This input is enabled when the Emergency Inhibit (36) is enabled.
K1 = S2 Open (Trip) The contact is closed for normal operation. Opening this contact
K2 = S1 Open (Trip) will activate the Emergency Inhibit input.
K3 = S1 Close If the Emergency Inhibit contact is opened when the load is con-
K4 = S2 Close nected to the Normal Source, no action will be taken if the Normal
Source is available. If the Normal Source is not available, an imme-
diate transfer to the Neutral position will occur.
The user should refer to the switch drawings for usage. The relays
mementarily energize until the ATC-900 senses that the switching If the Emergency Inhibit contact is opened when the load is con-
device has closed or opened (Using AUX-illary contacts) and then nected to the Emergency Source, the ATC-900 will transfer the
de-energizes the K relay to the normally open state. load to the Normal Source if it is available. If the Normal Source is
not available, an immediate transfer to the Neutral position will
4.2.2 Popular Inputs and Outputs (Programmable I/O) occur if the Emergency Source is available.
The following are some popular I/Os that can be programmed. See The Emergency Inhibit input is only active when either Source 1 or
the I/O Table 5 in Section 5.5 and Appendix B for all of the I/O Source 2 is preferred. This input is ignored if the Preferred Source
Descriptions. A configurable (programmable) input can only be selection is set to None.
defined to one contact while an output can have multiple con- The Emergency Inhibit input takes priority over the Go To Emer-
tacts. A fixed input or output is one that is not user programma- gency input if both inputs are activated at the same time. In this
ble as it is fixed from the factory. It is tied to a switch or function case, the generator will start but a transfer to the Emergency
of a switch that requires that input or output. Source will be inhibited until the Emergency Inhibit input is de-acti-
vated. If the preferred source is lost during this time, the switch
Lockout (Input) will transfer to the Neutral position.
The Lockout contact is closed to enable normal, automatic opera-
tion. Opening this contact will Inhibit all automatic operation. Three Source ATS Control (Master (output)/Slave (Input))
This feature is used when non-automatic control is required. The The ATC-900 Master/Slave controller functionality provides the
ATC-900 continues to monitor source status and will accurately user with the ability to control a three-source system consisting of a
display status on the controller's mimic bus. After the controller utility and two generator sources. In a three-source system, the
has been locked, the user must reset the controller by simultane- Master ATS controls the engine starting and stopping of the Slave
ously pressing the Help and Enter buttons. ATS. See Feature list, 90A and 90B for a full functionality write-up.
Note: The Slave ATS requires the DCT module for a DC power inputto keep
Go To Emergency (Input) the controller powered or a UPS if desired.
When the Go to Emergency contact is closed, a transfer to the The Master ATS handles all transfer time delays between the Util-
Emergency Source will be initiated. If the Emergency Source fails ity to Generator transfer. The master is the Generator Start from
and the Normal Source is available, the ATC-900 will initiate a the first ATS.
transfer back to the Normal Source (failsafe).
The Go To Emergency input is only usable when either Source 1 4.4 Test Mode
or Source 2 is preferred. This input will be disabled when the Pre-
ferred Source selection is set to None. The Engine Test is intended to allow periodic system tests. The
exact test conditions are determined by the programmed set-
The Emergency Inhibit input takes priority over the Go To Emer-
points. The operator-selected parameters include setting the
gency input if both are activated at the same time. In this case,
engine run time and the Test Mode. Refer to Table 4 for test pro-
the generator will start but a transfer to the Emergency Source
gramming details.
will be inhibited until the Emergency Inhibit input is de-activated.
There are three test modes:
Bypass Timers (Input)
1 No Load Engine Run Test;
This momentary contact will bypass the timer for TDEN, TDNE,
2 Load Transfer Engine Test; or
TDN, TDES, and TDEC. By pushing the Help and Enter buttons on
3 Disabled.
the front of the controller (Bypass Timer) at the same time the
countdown will be set to 0 for the current countdown. The next IF THE ATS IS UNABLE TO PROCESS A ENGINE TEST REQUEST
timer will then start. There is also a programmable input that will DUE TO THE ATS STATUS, THE REQUEST IS IGNORED.
allow the bypass timer to be completed remotely if desired.
When the Engine Test pushbutton is pressed, the display will
Go To Neutral (Input) prompt the user to input a password (factory set to 0900). Use
A maintained closed contact forces the controller to switch to the the arrow keys to enter the password, then press the right arrow
Neutral position, thereby disconnecting the load from both key to highlight the "Enter Password" icon and press the Enter
sources. key.
The ATC-900 will display the Time Delay on Engine Starting
(TDES) timer countdown. Once the TDES countdown reaches
zero, the ATC-900 Controller will initiate an engine start. The
engine run duration will be per the Engine Run Test Time setpoint.
If Test Mode is set to "Engine Run", then the switch will start the 4.5 USB Interface (Event Status-Setpoints)
non-preferred generator, but will not initiate a transfer to the non-
Every ATC-900 transfer switch includes a front panel, NEMA 4X
preferred source.
rated USB port for use in configuring set points or downloading
If Test Mode is set to "Load Transfer", then the switch will start event data to a USB flash drive. The USB interface is brought to
the non-preferred generator and initiate a transfer to the non-pre- the front of the enclosure to enable flash memory (memory stick)
ferred source once the generator output has reached the specified to be plugged in to upload or download data such as History Data
setpoints. Logging, or Setpoints. The USB interface will only work with
memory devices and not laptop computers.
All enabled and programmed time delays will be performed per the
setpoints during an engine test. The time delays will appear on the 4.5.1 Upload/Download Setpoints via USB
LCD Display with “countdown to zero” when active. Depending To reduce the time spent on site for commissioning, set points
on the setpoints and the optional features selected with the ATC- can be configured at a PC using the ATC-900 configuration
900 Controller, these can include: software and saved to a USB flash drive to be uploaded to one or
• Time Delay Engine Start (TDES); multiple controllers. Set points are also easily copied from one
controller to another.
• Time Delay Normal to Emergency (TDNE);
• Time Delay Emergency to Normal (TDEN); 4.5.2 Downloading Statistics and Event logs via USB
• Time Delay for Engine Cooldown (TDEC); Downloading statistics and event capture data provides the user
• Time Delay Neutral (TDN); and the ability to more thoroughly analyze high speed capture data
• Pre-transfer Delay Signal (TD PRE-TRAN). using a PC, or data can be emailed to Eaton's Technical Support
• Post-transfer Delay Signal (TD POST-TRAN). Team when off site troubleshooting support is required. Section
7.1 shows the instructions for downloading event capture data.
All operations are “Failsafe”, meaning they prevent disconnection
from the only available power source and also force a transfer or 4.6 Communications
re-transfer operation to the only available power source. ATC-900 is a Monitoring Protection and Control Communications
During an engine test, if the Engine Test pushbutton is pressed a compatible device. As such, it can be remotely monitored, con-
second time before the Engine Test is complete, the Engine Test trolled, and setpoint programmed. The ATC-900 is supplied
will be terminated. An engine test may also be aborted in the fol- equipped with a Modbus RTU (RS-485 physical layer) communica-
lowing ways: tions port as standard. This permits it to have the communications
option supplied from the factory. A COTS (Commercial Off The
1. If the Emergency Source does not become available within 90 Shelf) Ethernet to Modbus can also be used.
seconds of the ATC-900 providing the engine start command;
2. If, during the TDNE countdown, the Emergency Source goes 4.6.1 Power Distribution Software
unavailable more than three times (Each time, TDNE will The ATC-900 is also compatible with Eaton’s Power Xpert Gate-
restart); way for web-based monitoring, via Modbus TCP/IP, SNMP, or
BACnetT/IP Protocols. The Power Xpert Gateway can be used to
3. If the Emergency Source is powering the load and it goes consolidate data from up to 64 devices, including communications
unavailable for more than the TDEF (Time Delay Engine Fail- ready transfer switch controllers, trip units, and meters, as well as
ure) setting; and other Eaton devices. Certain Versions of the Power Xpert Gate-
4. If the Normal source becomes unavailable. way include email event notification and data-logging functional-
ity. Additional features include:
When an engine test is aborted due to an unavailable source dur- • System/device alarm logging and reporting;
ing TDNE countdown, the Alarm relay will energize, a “TEST • Time/event historical data logging;
ABORTED” message with appear on the display, and the event
will be logged into the Transfer History as “Aborted Test” • Data trending;
Aborted. • Information storage/retrieval by device event;
• Hardware diagnostics;
• Dedicated computer not required;
• Security password protection; and
• Gateway interface for connectivity to other information net-
works.
Using the left/right arrow keys, navigate to the desired screen icon 4. Historical Data
and press the Enter key. The "Change Setpoints" screen will See Section 7 for Historical and Event displays.
require a password to access (factory default is 0900).
5. System Info
1. Load Metering
System Information is an area where the switch configuration,
The Load Metering screen presents (Figure 8) the different mea-
GO, Serial, and version numbers can be viewed. It also provides
surements of the Load. Note that the DCT module is required to
time/date change.
display Load current, Watts, VAR, VA, and power factor. Other-
wise only voltage measurements will be shown. See Section 2 for 6. USB Menu
the DCT Module specifications.
See Section 4.5 for USB operation.
This will allow the user to view the: 5.4 Programmable Features/Setpoints
• System Setups: 3 Screens;
• Time Delays;
NOTICE
• Dropouts / Pickups;
CHANGING THE SYSTEM NOMINAL VOLTAGE OR FREQUENCY SET-
• Engine Test / PE; and POINTS WILL AUTOMATICALLY CHANGE ALL THE PICKUP AND
• Programmable I/O. DROPOUT SETTINGS TO NEW DEFAULT VALUES.
All ATC-900 programmable features and associated setpoint pos-
sibilities with any required explanations are presented in Table 4.
As mentioned earlier, when "Change Setpoints" is selected, the
display will show the following icons:
• System Setups: default screen, 3 total;
• Time Delays;
• Dropouts / Pickups: Multiple Screens;
• Engine Test / PE: Multiple Screens; and
• Programmable I/O: Multiple Screens.
The System Setpoints screen contains normal voltage/frequency,
preferred source, CT Ratio, communications, closed or open, and
several more. After the initial setting of these system setpoints,
they usually will not be changed.
The following example explains how to change a time delay.
Figure 9. Time Delays.
NOTICE
IF NO PUSHBUTTON ACTIVITY IS DETECTED FOR APPROXIMATELY
2 MINUTES WHILE IN THE PROGRAM MODE, THE SETPOINTS
SCREEN IS CLEARED SHOULD THIS OCCUR. ANY PREVIOUSLY
MADE SETPOINT CHANGES ARE NOT SAVED TO THE SAME PER-
CENTAGE OF NOMINAL AS THE ORIGINAL VALUES.
OPTION FACTORY Source settings (Both sources have the same ranges and defaults)
NUMBER DESCRIPTION RANGE DEFAULT
26/5P Source 1/2 undervoltage dropout 70–97% of nominal 80%
General settings
Source 1/2 undervoltage pickup (dropout + 2%) 90%
— Set new password 0000–9999 0900 to 99% of nominal
— Selected language English, French or Spanish English 26/5K Source 1/2 overvoltage dropout 105–120% of nominal 115%
— Nominal frequency 50 or 60 Hz As ordered (0 = disabled)
— Nominal voltage 110–600V As ordered Source 1/2 overvoltage pickup 103% of nominal to 110%
— Number of phases 1 or 3 As ordered (dropout - 2%) (0 = disabled)
— Number of generators 0, 1 or 2 1 26/5J Source 1/2 underfrequency dropout 90–97% of nominal 94%
— Preferred source Source 1, Source 2, External*or Source 1 (0 = disabled)
None Source 1/2 nderfrequency pickup (dropout + 1 Hz) to 99%
96%
— PT ratio 2:1–500:1 As ordered of nominal (0 = disabled)
— CT ratio 200–5000 — 26/5N Source 1/2 overfrequency dropout 103–110% (0 = disabled) 106%
— Daylight Saving Time On or Off 1 Source 1/2 overfrequency pickup 101% to (dropout - 1 Hz) 104%
— Operating mode Stand-alone/Master or Slave* Master (0 = disabled)
— Phase sequence check ABC, CBA or Off Off 26/5L Source 1/2 percent for unbalanced 5–20% neg./pos. sequence voltage 12%
voltage dropout V2/V1 (0 = disabled)
— Commitment to transfer in TDNE Yes or No No
Source 1/2 percent for unbalanced 3% to (dropout - 2%) 10%
— Manual retransfer Auto, Manual* or External * Auto
voltage pickup (0 = disabled)
— Modbus address 1–247 1
26/5M Source 1/2 voltage phase loss drop- 20-60% V2/V1 (0 = disabled) 40%
— Modbus baud rate 0 = 9600, 1, Even 0 out
1 = 9600, 1, Odd —
Source 1/2 voltage phase loss pickup 18% to (dropout - 2%) (0 = dis- 30%
2 = 9600, 2, None —
abled)
3 = 9600, 1, None —
- Load current unbalance dropout 5-60% neg./pos. sequence current 12%
4 = 19,200, 1, Even —
I2/I1 (0 = disabled)
5 = 19,200, 1, Odd —
6 = 19,200, 2, None — - Load current unbalance pickup 3% to (dropout - 2%) (0 = disabled) 10%
7 = 19,200, 1, None — - Load current unbalance enable 1-100% of rated current 10%
threshold
Transition settings
Engine test/plant exerciser (PE1 and PE2 are independently programmable)
47 Closed transition
6B Engine test pushbutton on panel Load
Closed transition Disabled, On to Alarm, On to Open As ordered
Test mode No load, load transfer, disabled transfer
Closed voltage difference 1–5% 2%
Engine run test time 0–600 minutes 30 minutes
Closed frequency difference 0.0–0.3 Hz 0.3
23M PE time delay normal to emergency 0–9999 seconds 00:02
32f/32d Open—in-phase transition
PE time delay emergency to normal 0–9999 seconds 00:02
In-phase Disabled, On to Alarm, On to Open As ordered
PE time delay engine cooldown 0–9999 seconds 5 minutes
In-phase frequency difference 0.0–3.0 Hz 1.0
PE1/PE2 test mode No load, load transfer, disabled Disabled
— Synchronization timer 1–60 minutes 5
PE1/PE2 run time 0–600 minutes 30 minutes
32a/32d Open—delayed transition
PE1/PE2 schedule Off, daily, 7-day, 14-day, 28-day or
Time delay neutral 10 Minutes 0 calendar date (up to 12 user-speci-
Load voltage decay 2–30% of nominal voltage 6% fied dates)
Time delays PE1/PE2 calendar date Month: 1–12; Day: 1–31
1a Time delay normal to emergency 0–9999 seconds 0:00 PE1/PE2 day of week 1 Sunday, 2 Monday, 3 Tuesday, 4
Wednesday, 5 Thursday, 6 Friday or
3a Time delay emergency to normal 0–9999 seconds 5:00 7 Saturday
35A Time delay pre-transfer 0–120 seconds 0:01 PE1/PE2 plant start time HH:MM AM/PM
35C Time delay post-transfer 0–120 seconds 0:10
2A Time delay engine 1 start 259 Minutes ** 0:03
— Time delay engine 2 start 259 Minutes ** 0:03
4A Time delay engine cool-off 0–9999 seconds 5:00
7A Time delay engine fail timer 0–6 seconds 0:06
— Unbalance/phase loss time delay 10–30 seconds 0:20
* Requires the associated programmable input to be configured/connected.
** Any TDES value above two minutes, with no power on the controller, will start the genera-
tor (fail-safe) after two minutes.
Table 4 is continued in column 2 of this page.
0:00:00 is Hours : Minutes : Seconds
# Timers
1B Time Delay Normal to Emergency (TDEN) Adjustable 0-9999 S S S S S S S S S
2A Time Delay Engine Start (TDES) Adjustable 0 - 259 Minutes S S S S S S S S S
3B Time Delay Emergency to Normal (TDEN) Adjustable 0-9999 Sec S S S S S S S S S
4B Time Delay Engine Cooldown (TDEC) Adjustable 0-9999 S S S S S S S S S
Emergency (S2) Source Sensing
5H Phase Reversal Protection S S S S S S S S S
5J All Phase Undervoltage/Underfrequency S S S S S S S S S
5K All Phase Overvoltage/Overfrequency S S S S S S S S S
5L All Phase Voltage Unbalance S S S S S S S S S
5M All Phase Voltage Phase Loss) S S S S S S S S S
System or Engine Test
6B Engine Test Pushbutton on Panel S S S S S S S S S
6C Remote Engine Test (INPUT) P P P P P P P P P I
7B Time Delay Engine Fail (TDEF) Adjustable 0 - 6 Sec S S S S S S S S S
Pushbutton Bypass
8E Bypass Timers (can also initiate on front of controller) S S S S S S S S S I
8F Bypass Timers w external push button OF OF OF OF OF OF OF OF OF I
Preferred Source Selector
10A Preferred Source Selector (INPUT) P P P P P P P P P I
10B Utility to Utility or Utility to Generator S S S S S S S S S
10C Preferred Source Selector w/selector switch OF OF OF OF OF OF OF OF OF I
10D Generator to Generator S S S S S S S S S
Indicating Lights/LEDs
12C Normal (S1) Source Connected S S S S S S S S S
12D Emergency (S2) Source Connected S S S S S S S S S
12G Normal (S1) Source Available S S S S S S S S S
12H Emergency (S2) Source Available S S S S S S S S S
Source Avail Relay Contacts
14 Normal (S1) Source Available Program Form Cs P P P P P P P P P
14 Emergency (S2) Source Available Program Form Cs P P P P P P P P P
Position Aux Contacts
15 Normal (S1) Source Position Form Cs P P P P P P P P P
15 Emergency (S2) Source Position Form Cs P P P P P P P P P
Metering
18J Integrated Metering (S1, S2, or LOAD Side D (DCT-Module)) O O O O O O O O O
18K 24VDC Input Power for ATC-900 O O O O O O O O O
Plant Exerciser
23M Selectable - Disabled 7, 14, 28, 365 Day interval, 0-600 min, S S S S S S S S S
Load/No Load, with Failsafe 2 Exercisers
Normal (S1) Source Sensing
26D Go to Emergency (S2) (INPUT) P P P P P P P P P I
26E Go to Emergency (S2) Input w/selector Switch OF OF OF OF OF OF OF OF OF I
26H Phase Reversal Protection S S S S S S S S S
26J All Phase Undervoltage/Underfrequency S S S S S S S S S
26K All Phase Overvoltage/Overfrequency S S S S S S S S S
26M All Phase Voltage Phase Loss S S S S S S S S S
Programmable Outputs
80B Input Terminal Blocks 0 0 0 S S 0* 0* S S
80C Output Terminal Blocks 0 0 0 S S O O S S
81A General Alarm Indication Contact (OUTPUT) P P P P P P P P P O
81B ATS Not in Automatic (OUTPUT) P P P P P P P P P O
81C ATS in Test (OUTPUT) P P P P P P P P P O
81D Engine Test Aborted (OUTPUT) P P P P P P P P P O
81E Cooldown in Process (OUTPUT) P P P P P P P P P O
81F Engine Start Contact Status Gen 1 & Gen 2 (OUTPUT) P P P P P P P P P O
81G LOAD SHED - S2 Inhibit On (OUTPUT) P P P P P P P P P O
81GL LOAD SHED - S2 Inhibit On w/white indicating light OF OF OF OF OF OF OF OF OF O
81H ATS on Bypass (OUTPUT) P P P P P P P P P O
Only one type NO or NC may be programmed per system.
81J Lockout PF PF PF PF PF PF PF PF PF I
81K Monitor Mode (NC or NO) P P P P P P P P P I
81M Load Bank Control P P P P P P P P P 0
81N Health P P P P P P P P P 0
Three Source ATS Control (Master/Slave)
90A Master Control Gen 2 Start Status (OUTPUT) P P P P P P P P P O
90B Slave Input (INPUT) P P P P P P P P P I
* Contactor D & E Wallmount and D & E frame Closed Transition have Input Terminals Blocks with S2 Engine Start.
6.3.1 Transfer Switch Appears Inoperative Step 6: Is the Preferred power source available?
Step 1: Verify that all plugs and sockets are properly intercon-
nected. If YES:Proceed to Step 8.
Step 2: If the source available LED is not on or the display shows If NO: Apply the correct system voltage to Preferred
the wrong voltage, make sure the controller setpoints Source
match the system voltage. Verify that the correct system connections. or change the setpoints on the
voltage is at the switch. controller to match the system voltage
Step 3: Verify that the voltage selection plug on the transformer Step 7: Is the switch connected to the Non-preferred source?
is in the proper position to match the system voltage.
If YES:Proceed to Step 8.
Step 4: Look for any obviously burned components. Determine
the cause and rectify, if possible. Replace defective com-
If NO: Proceed to Step 9.
ponents after the cause is determined.
Step 8: If a problem persists, contact Eaton.
Step 5: Is switch closed on source 1? Verify whether or not the
system voltage now appears on the load terminals.
6.3.3 Transfer Switch Will Not Automatically Transfer To the
Non-Preferred Source
If YES: Proceed to check logic for problems in respective
logic instruction book. Step 1: If the alternate source is a generator, is it running?
If NO: Check all power connections and the switching If YES: Proceed to Step 2.
mechanism. What does the controller show for
voltages on the main screen? If NO: Check the generator. Check the engine start
contacts.
6.3.2 Transfer Switch Will Not Automatically Transfer to Normal Step 2: Is the correct line voltage and frequency available at the
Step 1: Is Option 29G installed? If so, there is a switch on the Non-preferred source terminals? Record the readings.
door Labeled Auto Manual with either push buttons for
S1 close, Trip, S2 Close or a three position switch with If YES: Proceed to Step 3.
the same. The Auto Manual selector-switch must be in
Auto for it to run with the controller. If NO: Verify that there is output voltage from the
generator.
Step 2: Is Option 9B installed? If so, there is a selector switch
labeled “Maintenance”(or "Monitor Mode" for contactor- Step 3: Is the voltage selector plug in the correct position?
based switches.
If YES: Proceed to Step 4.
If YES: Verify selector switch is in the “Operate”
position. If NO: Position plug correctly.
Step 3: Are the correct line voltage and frequency available at ter- If YES: Proceed to Step 5.
minals N1, N2, and N3? Record the readings.
If NO: Proceed to Step 6.
If YES: Proceed to Step 4.
Step 5: Is a test Engine Test or Plant Exerciser being run, or is
If NO: Check Preferred source. the "Go to Emergency" input energized?
Step 4: Is the transformer voltage selector plug in the correct If YES: Proceed to step 6.
position?
If NO: STOP! The transfer switch should not transfer to
If YES: Proceed to Step 5. the Non-preferred source if the preferred source is avail-
able and connected.
If NO: Position plug correctly.
Step 5: Check the voltage on transformer NT1 by measuring volt-
age between voting relay KV-1 and GND. Is the voltage
measured 120 Vac (+/- 10 volts)? Record the reading.
Step 6: Make sure that the setpoints are set according to the 6.4 Replacement
system voltage.
Follow these steps to replace the ATC-900.
If YES: Proceed to Step 7. Step 1: Turn off control power at the main disconnect or isola-
tion switch of the control power supply and lock it out to
If NO: .Adjust system voltage setpoints to match sys- guard against other personnel accidentally turning it on.
tem voltage and phase. Step 2: Verify that all “foreign” power sources wired to the ATS
Step 7: Is the Non-preferred switching device charged? Switch are de-energized. These may also be present on
some of the terminal blocks.
If YES: Proceed to Step 8. Step 3: Before disconnecting any wires from the unit, make sure
they are individually identified to ensure reconnection
If NO: Consult Magnum Breaker troubleshooting manual can be correctly performed. Taking a picture may help
on how to charge the breaker before proceeding. with re-connections.
Step 8: Is the Preferred switching device OPEN? Step 4: Disconnect all plugs and connectors going to the ATC-
900.
If YES: Proceed to Step 10.
If YES: Refer to the Magnum Breaker maintenance Step 5: Remove the 6 mounting screws holding the unit against
manual IB#2C12060 and check the shunt trip the door or panel. These are accessed from the rear of
Preferred switch. the unit.
Step 6: Set the screws aside for later use.
If NO: Check the wiring to B10 and B11.
Step 7: Mount the replacement unit.
Step 10: If this is a Magnum measure the voltage between termi-
nals B12 and B13 on the Non-preferred switching device Step 8: Secure the ATC-900 to the panel with the 6 mounting
(spring release coil). Is the voltage measured 120 Vac screws.
(+/- 10 volts)? Record the reading.
Step 9: Re-connect all plugs and connectors to their proper
socket on the ATC-900. Make certain that each plug is
If YES: Refer to the Magnum Breaker maintenance
securely seated.
manual IB#2C12060 and check the spring
release coil Non-preferred switching device. Step 10: Clear out all personnel, close all ATS panels, remove any
lockouts, and restore control power. Ensure all setpoints
If NO: Check the wiring to B12 and B13. are correct.
Step 11: If a problem persists, contact Eaton. 6.5 Maintenance and Care
The ATC-900 is designed to be a self contained and maintenance
free unit. The printed circuit boards are calibrated and conformally
For ATS assistance, call Eaton Care at: coated at the factory. They are to be serviced by factory trained
877-386-2273 option 2, option 4, and then option 3 personnel only. The front panel including the display can be
cleaned lightly with a soap and water mixture.
Historical Data
Figure 15. Historical Data Screen For event details, the time-stamping resolution is 0.1 seconds
The Historical Data display indicates historical and cumulative Events Details
counter values as follows:
• Source 1 Available
• Source 1 Connected
• Source 1 Engine Run
• Source 2 Available
• Source 2 Connected
• Source 2 Engine Run
• Tier 4 Timer
•· Load Energized
• Number of Transfers
Historical counter resets are date and time stamped events that
are captured in the event log.
Hi-Speed Capture Save Statistics – saves all statistical controller data to the USB
flash drive.
Save Events – saves all event data to the USB flash drive.
Save Hi-Speed – saves all high speed capture data to the USB
flash drive.
To save current controller setpoints, use the arrow keys to navi-
gate to the “Save Setpoints” icon and press Enter. The screen
will display “Saving DSP Setpoints.” Once it has finished, it will
display “Saved Setpoints to File: STPmmddyy-##.CSV”, where
mmddyy is the current date, and ## is the numerical id (e.g. 1, 2,
3, etc.) If there is not enough free space on the drive, the screen
will display “Insufficient Memory”.
To load controller setpoints from a setpoint file on your USB flash
drive, use the arrow keys to navigate to the “Load Setpoints” icon
and press Enter. The "Load Setpoints" feature will require a pass-
word to access (factory default is 0900). Once the password is
entered correctly the screen will display a list of all setpoint files
on the USB flash drive. Use the up/down arrow keys to highlight
the desired setpoint file and press Enter. The controller will save
Figure 18. Hi Speed Capture Screen
a backup of the current setpoints to “STPmmddyy-BAK-##.CSV”
The ATC-900 stores 4 seconds of metered data every 20 mil-sec- and display a message confirming that setpoints were success-
onds or .002 seconds for certain events. The data is captured 2 fully loaded from the file.
seconds before and 2 seconds after the event. If the event is a
To save controller statistics (e.g. connected time, available time,
power failure, then the capture is 4 seconds before the power fail-
engine run time, etc.), use arrow keys to navigate to the “Save
ure.
Statistics” icon and press Enter. The screen will display “Saving
Oscillographic data for 10 events is stored in the controller and ATC- Statistics” while the file is being created. Upon completion,
may be downloaded over USB or displayed graphically on the TFT the display will show “Saved ATC-900 Statistics to File: HSTm-
display. Events include: mddyy-##.CSV”.
To save controller events (e.g. transfer events, power up events,
1. Source unavailability actions that initiate a transfer sequence
setpoint changes, etc.), use arrow keys to navigate to the “Save
(undervoltage, overvoltage, etc.)
Events” icon and press Enter. The screen will display a percent-
2. Successful transfers (at the point of breaker/contactor clo- age progress bar while event data is saved to the USB drive.
sure.) When it is complete, it will display “Saved Events to File: EVTm-
mddyy-##.CSV”.
3. Unsuccessful transfers (at the point of breaker/contactor fail-
ure to close or open.) To save high-speed capture data (i.e. time-stamped voltage and
current data), use arrow keys to navigate to the “Save Hi-Speed”
icon and press Enter. The screen will display “Saving High Speed
Captures” along with a progress bar. Once complete, it will dis-
NOTICE play “High Speed Capture Files Saved”.
THE REAL TIME CLOCK CORRECTS FOR LEAP YEAR, DAYLIGHT
SAVING TIME MAY BE ADJUSTED FOR BASED ON THE DAYLIGHT To access any of your saved files, simply remove the USB flash
SAVING TIME SETPOINT. drive and connect it to a USB port on your PC. Browse to your
USB drive and locate the “ATC-900” folder. Inside that folder
7.1 USB Operation should be two sub-folders: History and Setpoint. All setpoint
Insert a compatible USB flash drive into the USB port on the front saves and backups will be in the “Setpoint” folder. All Statistics,
panel. The ATC-900 will not accept a laptop directly hooked up Events, and High-Speed capture files will be in the “History”
to it, only a flash thumb drive (memory stick). When the USB folder. All files are viewable using a CSV file viewer such as
flash drive is recognized, the USB menu icon will turn from gray to Microsoft Excel, Notepad, or OpenOffice Calc.
blue. Use the arrow keys to navigate to the USB icon and press A user friendly setpoint program is available free of charge on line
Enter. at: www.eaton.com. Download "Eaton ATC-900 Setpoint Editor"
Note: if the USB drive has never been connected to an ATC-900 controller (EASE). This can be loaded on any personnel computer and will
before, it will automatically create the required folder structure.) allow for the user to view the current setpoints and also change
From here you can select from the following options: Main Menu, the setpoints. Once the setpoints have been saved to the USB
Save Setpoints, Load Setpoints, Save Statistics, Save Events, and thumb drive, that drive can be used to set several switches to the
Save Hi-Speed. same settings.
Main Menu – returns you to the Main Menu.
Save Setpoints – save current controller setpoints onto the USB
flash drive.
Load Setpoints – load setpoints from setpoint files on the USB
flash drive (USB to Controller).
Feature 5M: Voltage Phase Loss for Source 2 Feature 16: External Overcurrent Protection
This feature constantly monitors Source 2 for a phase loss condi- When integral overcurrent protection is provided for either one or
tion using symmetrical components voltage calculations. When both sources, the need for separate upstream overcurrent protec-
the ratio of negative sequence to positive sequence voltage (V2/ tion (in most instances) is eliminated. With this factory installed
V1) exceeds the phase loss dropout setting the Unbalance/Phase feature in the ATC-900, further automatic transfer operation is
Loss time delay starts counting. If the timer expires before the locked-out until the appropriate source breaker is reset. It will
phase loss is resolved the source will become unavailable. The continue to monitor the voltage availability and the switch posi-
phase loss must drop to a value that is below the pickup setting tions.
to stop the timer or to become available after the timer expires.
Feature 16T: Load Current Unbalance Monitoring
This can be disabled in the setpoint settings under menu 3 in the
(must have option 18J DCT Module)
Setpoints Dropouts/Pickups.
This feature constantly monitors the load current for an unbalance
Feature 7B: Time Delay (TD Engine Failure) condition using symmetrical components calculations. The current
TDEF (0 to 6 seconds) is used where at least one source is an unbalance enable threshold is used to avoid spurious unbalance
engine generator, TDEF will delay an available source from being detections under light loads. The unbalance calculations are not
declared unavailable in order to override momentary generator performed until the average load current exceeds this threshold.
fluctuations. This time delay is only implemented when the load is When the ratio of negative sequence to positive sequence current
connected to a generator source. TDEF is not displayed when the (I2/I1) exceeds the unbalance dropout setting the Unbalance/
number of generators is zero. TDEF is used for both generators in Phase Loss time delay starts counting. If the timer expires before
the Dual Generator mode. the unbalance is resolved the connected source will become
unavailable. The unbalance must drop to a value that is below the
Feature 8C/8D: Transfer Time Delay Bypass pickup setting to stop the timer or to become available after the
This feature allows a pushbutton input to be used to bypass the timer expires. This can be disabled in the setpoint settings under
timer for standard feature (TDNE) or standard feature (TDEN) indi- menu 3 in the Setpoints Dropouts/Pickups.
vidually, or both simultaneously. This pushbutton is on the front
of the controller (pushing "Enter" and "Help" at the same time. Feature 23: Plant Exerciser
One could also wire in a pushbutton remote switch to any of the This feature provides for the automatic test operation of the gen-
Inputs to do the same function. This feature is usually used in erator ata pre-selected weekly interval. When the test is running,
testing when it is not desirable to wait for completion of the tim- pressing and releasing the Engine Test pushbutton will cancel the
ing sequence. test. The day of the week, hour, and minute that exercising is
desired can be programmed into the ATC-900. Up to twelve sepa-
Feature 9B: Maintenance Mode (Monitor Mode) rate month and day combinations can be set. The type of test,
This is a two position switch that is labeled Maintenance Mode for whether a load transfer or just an engine test, can also be
breakers, power breakers (MG) and Monitor Mode for contractors. selected. Load testing is fail-safe. If the generator fails during test-
This will place the controller in Monitor Mode and no transfers will ing for any reason, the ATC-900 will signal the transfer switch to
occur and the controller will continue to monitor the availability, return to the Preferred source. The ATC-900 is factory shipped
connected state, and voltages. with this feature set to off.
Feature 26K: Overvoltage Monitoring for Source 1 Feature 32C: In-Phase/Load Voltage Decay
This feature constantly monitors Source 1 for an overvoltage con- In-phase transition is a feature that will allow a transfer between
dition. When the Source 1 voltage rises to a value equal to or two live sources only when the phase difference between the two
above the overvoltage dropout setting, the source will become sources is near zero. This is an open transition transfer that pre-
unavailable. The source’s voltage will then have to drop to a value vents in-rush currents from exceeding normal starting currents in
that is equal to or below the pickup setting to become available the case where motor loads are being transferred.
again. This can be disabled in the setpoint settings under menu 3 Load Voltage Decay utilizes the load voltage measurements to
in the Setpoints Dropouts/Pickups. sense back EMF that is generated when the transfer switch is in
Overfrequency Monitoring for Source 1 the Neutral position. It provides a delay in transfer in either direc-
tion if an unacceptable level is sensed as established by a cus-
This feature constantly monitors Source 1 for an overfrequency tomer programmed level. The transfer will not take place until the
condition. When the Source 1 frequency rises to a value equal to back EMF decays below the acceptable programmed level. This
or above the overfrequency dropout setting, the source will feature has a separate setting of enabling or disabling the opera-
become unavailable. The source’s frequency will then have to tion. If disabled, the transfer switch will not delay in the Neutral
drop to a value that is equal to or below the pickup setting to position and will transfer between the sources as fast as possible.
become available again. This can be disabled in the setpoint set- This feature is not available with the Time Delay Neutral (TDN)
tings under menu 3 in the Setpoints Dropouts/Pickups. Feature 32A.
Feature 26L: Voltage Unbalance Monitoring for Source 1 Feature 32D: In-Phase/Time Delay Neutral (3 Position)
This feature constantly monitors Source 1 for a voltage unbalance In-phase transition is a feature that will allow a transfer between
condition using symmetrical components calculations. When the two live sources only when the phase difference between the two
ratio of negative sequence to positive sequence voltage (V2/V1) sources is near zero. This is an open transition transfer that pre-
exceeds the unbalance dropout setting the Unbalance/Phase Loss vents in-rush currents from exceeding normal starting currents in
time delay starts counting. If the timer expires before the unbal- the case where motor loads are being transferred.
ance is resolved the source will become unavailable. The unbal-
ance must drop to a value that is below the pickup setting to stop Time Delay Neutral provides a time delay in the transfer switch
the timer or to become available after the timer expires. This can Neutral position when both breakers/contactors are open. This
be disabled in the setpoint settings under menu 3 in the Setpoints delay takes place when the load is transferred in either direction to
Dropouts/Pickups. prevent excessive in-rush currents due to out-of-phase switching
of large motor loads. This feature is not available with the Neutral
Feature 26M: Voltage Phase Loss for Source 1 Load Sense Delay feature.
This feature constantly monitors Source 1 for a phase loss condi- Feature 32F: In-Phase Transition
tion using symmetrical components voltage calculations. When
the ratio of negative sequence to positive sequence voltage (V2/ Provides In-Phase transition, which is a feature that will permit a
V1) exceeds the phase loss dropout setting the Unbalance/Phase transfer or re-transfer between two available sources that have a
Loss time delay starts counting. If the timer expires before the phase angle difference of eight degrees or less. The In-Phase tran-
phase loss is resolved the source will become unavailable. The sition feature includes permissible frequency difference and syn-
phase loss must drop to a value that is below the pickup setting to chronization time setpoints. In the event Source 1 and Source 2
stop the timer or to become available after the timer expires. This fail to synchronize within the permitted frequency difference and
can be disabled in the setpoint settings under menu 3 in the Set- time, the alarm relay will energize and “Failed to Sync” will be dis-
points Dropouts/Pickups. played on Line 1. After resetting the alarm, another in-phase tran-
sition may be attempted or a non-synchronized transfer may be
Feature 29J: Manual Retransfer initiated by failing the connected source. The adjustable frequency
This feature provides for a selection between an automatic trans- difference is 0.0 to 3.0 Hz. If the synchronization does not occur
fer and re-transfer mode or a manual pushbutton re-transfer to within a specified amount of time, the alarm relay will energize
Normal from the Emergency Source mode. If this option is not and the failure will be logged into the Transfer History as either
selected the factory default selection is automatic. “Sync Fail - Freq” or “Sync Fail - Phase” depending on whether
the frequency difference or the phase difference was excessive.
Feature 32A: Time Delay Neutral
Feature 35A: Pre-Transfer Signal
This feature provides a time delay in the transfer switch Neutral
position when both breakers/contactors are open. This delay takes Typically associated with elevator controls, this feature provides
place when the load is transferred in either direction to prevent of a form C output to remotely signal an elevator that a re-transfer
excessive in-rush currents due to out-of-phase switching of large is about to take place. If there is a power outage, the Pre-Transfer
motor loads. This feature is not available with the Neutral Load (TPRE) is skipped. The ATC-900 has a programmed pre-transfer
Sense Delay (TDNLD) feature. delay timer that can be set from 0 to 120 seconds. Timers, such
as TDNE, will time out before the PRE-Transfer signal occurs.
Feature 32B: Load Voltage Decay
Feature 35D: Post-Transfer Signal
This feature utilizes the load voltage measurements to sense back
EMF that is generated when the transfer switch is in the Neutral This feature provides a form C output from the ATC-900 to signal
position. It provides a delay in transfer in either direction if an that the switch did transfer. It can be set for 0 to 120 seconds.
unacceptable level is sensed as established by a customer pro- The Post Transfer output is enabled during neutral (Time Delay
grammed level. The transfer will not take place until the back EMF Neutral) but it does not start to count down TDPOST until con-
decays below the acceptable programmed level. This feature has a nected to the new source.
separate setting of enabling or disabling the operation. If disabled,
the transfer switch will not delay in the Neutral position and will
transfer between the sources as fast as possible. This feature is
not available with the Time Delay Neutral (TDN) Feature 32A.
Slave-In goes
Active
No No
Emergency
TDES=0?
Yes
-Turn on Emergency Source Gen
Start
No No
No
-Turn off Preferred and Emergency Source Gen
Starts
-Set Preferred and Emergency Sources to Idle
state
Slave-In goes
Active
No No
No
1 Engine Test aborted While in engine test, if either S1 or S2 is removed, the warning will display
2 Uncommanded Transfer If a transfer is completed without the use of the controller
3 Closed Transition Fail (1->2) In Closed Transition, the switching device failed to operate correctly from S1 to S2
4 Closed Transition Fail (2->1) In Closed Transition, the switching device failed to operate correctly from S2 to S1
5 In-phase Transition Fail (1->2) With In-Phase, the switching device failed to operate correctly from S1 to S2
6 In-phase Transition Fail (2->1) With In-Phase, the switching device failed to operate correctly from S2 to S1
7 Open Transition Fail (1->2) In Open Transition, the switching device failed to operate correctly from S1 to S2
8 Open Transition Fail (2->1) In Open Transition, the switching device failed to operate correctly from S2 to S1
9 Generator Unavailable When directed to transfer and genertor is not available
10 Failed to Sync - Frequency With In-Phase or Closed Transition, Failed to sync because of Frequency
11 Failed to Sync - Voltage With In-Phase or Closed Transition, Failed to sync because of Voltage
12 Failed to Sync - Phase Angle With In-Phase or Closed Transition, Failed to sync because of Phase Angle
13 Source 1 Mech Failed to Open The Source 1 Mechanism for a breaker or contactor did not open
14 Source 1 Mech Failed to Close The Source 1 Mechanism for a breaker or contactor did not close
15 Source 2 Mech Failed to Open The Source 2 Mechanism for a breaker or contactor did not open
16 Source 2 Mech Failed to Close The Source 2 Mechanism for a breaker or contactor did not close
17 Overran Neutral (S1->N) The mechanism is connected to Source 2 instead of remaining in Neutral.
18 Overran Neutral (S2->N) The mechanism is connected to Source 1 instead of remaining in Neutral.
19 Factory Options Error Internal controller failure. (clear alarms/reboot)
20 Setpoints Error Internal controller failure. (clear alarms/reboot)
21 Cal factor Error Internal controller failure. (clear alarms/reboot)
22 State Error Internal controller failure. (clear alarms/reboot)
23 Timer Error Internal controller failure. (clear alarms/reboot)
24 Clock Error Internal controller failure. (clear alarms/reboot)
25 RAM test Error Internal controller failure. (clear alarms/reboot)
26 ROM test Error Internal controller failure. (clear alarms/reboot)
27 Watchdog Internal controller failure. (clear alarms/reboot)
28 Self-test Error Internal controller failure. (clear alarms/reboot)
29 Gen Start Communications Internal controller failure. (clear alarms/reboot)
30 Acc I/O Communications Lost communications to the Accessory I/O Module(s).
Note: S2 Permit (Input), S2 Request (Output), and TDNF (Timer) are used
on a private switch, please see switch instruction booklet for information
on operation of each.
Appendix C: Operational Flowcharts Note: These flowcharts assume that Source 1 is the Preferred (Normal)
Source
• Utility - Generator Transfer Switch or Dual Utility
• In-phase Transition Implementation
• Closed/In-phase/Open Transition Flowchart
Note: These flowcharts refer to “breaker” or “contactor.”
Source 1 is available
Close Source 1
(Momentarily energize K3)
N
Is Source 1
Send “Engine Start” signal available yet?
(Energize Gen Start relay)
Y
Is Source 2 N
available?
Send Pretransfer signal. TPRE times out.
(if Pretransfer enabled)
Y
Open Source 1
(Energize K2)
Close Source 1
(Momentarily energize K3)
Close Source 2
(Momentarily energize K4) Post Transfer times out
(if enabled)
Close Source 1
(Momentarily energize K3)
Is Source 2 N
available?
Sources
N
synchronized
TDN timer times out
before Sync timer
times out?
Close Source 2
(Momentarily energize K4)
This instruction booklet is published solely for information purposes and should not be considered all-inclusive. If further information is
required, you should consult an authorized Eaton sales representative.
Closed
The sale of the product shown / In-phase
in this literature is subject/toOpen Transistion
the terms Flowchart
and conditions outlined Example
in appropriate Eaton selling policies or
other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract.
The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANT-
ABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMA-
TION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be responsible to the purchaser or user
in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss
whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power,
additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the
use of the information, recommendations and description contained herein.
CSA is a registered trademark of the Canadian Standards Association. National Electrical Code and NEC are registered trademarks of
the National Fire Protection Association, Quincy, Mass. NEMA is the registered trademark and service mark of the National Electrical
Manufacturers Association. Uniform Building Code (UBC) is a trademark of the International Conference of Building Officials (ICBO). UL
is a federally registered trademark of Underwriters Laboratories Inc.
TDN/LVD
Note: There are also other options for closed transition such as Closed
Transition and Closed Transition to Load Decay or Time Delay Neutral.
Notes:
Notes:
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122
United States
For Transfer Switches:
877-ETN CARE (877-366-2273)
option 2, option 4, and then
option 3
Eaton.com
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. IB140012EN/TBG1123
June 2015