Chapter Five and Six
Chapter Five and Six
Instead of three return path, we can have only one return path for all three sources
Thinner conductors can be used to transmit the same kVA at the same
voltage,
Which reduces the amount of copper required (typically about 25% less)
and in turn reduces construction and maintenance costs.
The lighter lines are easier to install, and the supporting structures can be
less massive and farther apart.
In general, most larger motors are three phase because they are
essentially self-starting and do not require a special design.
Terminals a and a’ , for example, stand for one of the ends of coils going
into and the other end coming out of the page.
As the rotor rotates, its magnetic field “cuts” the flux from the three coils
and induces voltages in the coils.
Because the coils are placed 120◦ apart, the induced voltages in the coils
are equal in magnitude but out of phase by 120◦ (Fig. below b).
Since each coil can be regarded as a single-phase generator by itself, the
three-phase generator can supply power to both single-phase and three-
phase loads.
b. delta-connected as in Fig.(b).
The voltages Van, Vbn, and Vcn are respectively between lines a, b, c, and
the neutral line n. These voltages are called phase voltages.
If the voltage sources have the same amplitude and frequency ω and are
out of phase with each other by 120◦, the voltages are said to be
balanced.
(2_ (2)
Phase sequences: (a) abc or positive sequence, (b) acb or negative sequence
Since the three-phase voltages are 120◦ out of phase with each other,
There are two possible combinations.
(4)
It is easy to show that the voltages in Eqs. (3) or (4) satisfy Eqs. (1) and (2).
For example, from Eq. (3)
The phase sequence is the time order in which the voltages pass through their
respective maximum values
(5)
(a) A balanced Y-Y system, showing the source, line, and load
impedances. (b) Balanced Y-Y connection
ASTU, DEPARTMENT OF ELECTRICAL POWER AND CONTROL ENGINEERING 10 December 2024
BALANCED WYE-WYE CONNECTION
31
(d)
(c)
Assuming the positive sequence, the phase voltages (or line-to neutral voltages) are
The line-to-line voltages or simply line voltages Vab, Vbc, and Vca are related to the
phase voltages.
For example
Thus, the magnitude of the line voltages VL is √3 times the magnitude of the phase
voltages Vp, or
Applying KVL to each phase in Fig. (c & d), we obtain the line currents as
Calculate the line currents in the three wire Y-Y system of figure below.
Solution
We obtain Ia from the single phase analysis as
Showingthat the line voltages are equal to the voltages across the load
impedances for this system configuration.
From these voltages, we can obtain the phase currents as
(1)
These currents have the same magnitude but are out of phase with each
other by 120◦.
.
Another way to get these phase currents is to apply KVL. For example,
applying KVL around loop aABbn a gives:
which is the same as Eq. (1). This is the more general way of finding
the phase currents.
The line currents are obtained from the phase currents by applying
KCL at nodes A,B, and C. Thus
showing that the magnitude IL of the line current is √3 times the magnitude
Ip of the phase current, or
3𝑉𝐿 𝐼𝐿
𝑃3𝑝=3𝑃1𝑃 = cos 𝜃 = 3𝑉𝐿 𝐼𝐿 𝑐𝑜𝑠𝜃, and similarly Q3𝑝= 3𝑉𝐿 𝐼𝐿 𝑠𝑖𝑛𝜃
3
𝑃3𝑃 = 𝑃𝑎+𝑃𝑏+𝑃𝑐
𝑄3𝑃 = 𝑄𝑎+𝑄𝑏+𝑄𝑐,
Where Pa, Pb, Pc, Qa, Qb and Qc are calculated from their own phase values of
voltage, current and phase shift angle.
Electromagnetism.
Materials that can be magnetized, which are also the ones that are
strongly attracted to a magnet, are called ferromagnetic (or
ferrimagnetic).
These include iron, nickel, cobalt, some alloys of rare earth metals, and
some naturally occurring minerals such as lodestone.
When two loops with or without contacts between them affect each other through the
magnetic field generated by one of them, it called magnetically coupled.
Example: transformer
An electrical device designed on the basis of the concept of magnetic coupling.
Used magnetically coupled coils to transfer energy from one circuit to another.
+
Φ
i(t) V
Fig. 1
ASTU, DEPARTMENT OF ELECTRICAL POWER AND CONTROL ENGINEERING 10 December 2024
According to Faraday’s Law, the voltage, v induced in the coil is
proportional to N number of turns and rate of change of the magnetic
flux, Φ;
d
vN .......(1)
dt
But a change in the flux Φ is caused by a change in current, i.
Hence;
d d di
.......(2)
dt di dt
ASTU, DEPARTMENT OF ELECTRICAL POWER AND
10 December 2024 57
CONTROL ENGINEERING
Thus, (2) into (1) yields;
d di
v N .......(3)
di dt
or
di
v L .......(4)
dt
From equation (3) and (4) the self inductance L is define as;
d
L N H ........(5)
The unit is in Henrys (H)
di
ASTU, DEPARTMENT OF ELECTRICAL POWER AND
10 December 2024 58
CONTROL ENGINEERING
b) Mutual Inductance
59
Φ12
+ L1 L2 +
i1(t) V1 V2
Φ11
_ _
N1 turns N2 turns
Fig. 2
ASTU, DEPARTMENT OF ELECTRICAL POWER AND CONTROL ENGINEERING 10 December 2024
Magnetic flux Φ1 from coil 1 has two components;
* Φ11 links only coil 1.
* Φ12 links both coils.
V1 V2 i2(t)
Fig. 3
_ Φ22 _
N1 turns N2 turns
M 21 M12 M
Mutual inductance M is measured in Henrys (H)
M or
k M k L1 L2
L1 L2
Read about the Dot Convention
-j4Ω j3Ω
120 V + I1 I2 12Ω
j5Ω j6Ω
3
From eqn. 2 and ,
I1 (2 - j4)I 2 (4.472 - 63.43 ) (2.9114.04 )
13.01 - 49.39 A
ASTU, DEPARTMENT OF ELECTRICAL POWER AND
10 December 2024 70
CONTROL ENGINEERING
Application of Electromagnetism
71
THANK YOU!!!
10 December 2024
ASTU, DEPARTMENT OF ELECTRICAL POWER AND CONTROL ENGINEERING
Read More
73
THANK YOU!!!
10 December 2024
ASTU, DEPARTMENT OF ELECTRICAL POWER AND CONTROL ENGINEERING