TP 6866
TP 6866
Controls:
Decision-Makerr MPAC 1200
Transfer Switch Models:
KCS/KCP/KCC
KSS/KSP
KSSB
TP-6866 6/21e
Table of Contents
4.10 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4.11 Set Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4.12 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
4.13 Setting the Current to Zero . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4.14 Reset Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Section 5 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.2 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.2.1 USB Port SiteTech Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.2.2 Modbus Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.2.3 Ethernet Connection (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.3 Communications Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.3.1 Modbus Serial Communication Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.3.2 Network Communication Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.3.3 Setup Using the Controller Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.3.4 Setup Using SiteTech . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.4 Parameter Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5.5 Controller Firmware Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Section 6 Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
6.2 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.2.1 Weekly Generator Set Exercise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.2.2 Monthly Automatic Control System Test . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.3 Inspection and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.3.1 External Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.3.2 Internal Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
6.3.3 SPD Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
6.3.4 Other Inspections and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
6.4 Service Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Section 7 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
7.2 Accessory Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
7.2.1 Input/Output (I/O) Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
7.2.2 External Battery Supply Module (EBSM) . . . . . . . . . . . . . . . . . . . . . . . . . 85
7.2.3 Alarm Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
7.3 Controller Disconnect Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
7.4 Current Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
7.5 Digital Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
7.6 Ethernet Communication Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
7.7 Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
7.8 Line-to-Neutral Voltage Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
7.9 Load Shed (Forced Transfer to OFF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
7.9.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
7.9.2 Customer Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
This manual provides operation instructions for Kohlerr perform required service at the prescribed intervals.
Decision-Makerr MPAC 1200 automatic transfer switch Obtain service from an authorized service distributor/
controls and related accessories. dealer to keep equipment in top condition.
The Decision-Makerr MPAC 1200 controller is available Read this manual and carefully follow all procedures
for the transfer switch models shown below. and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Model Description Safety Precautions and Instructions section at the
KCS Standard-Transition Any Breaker ATS * beginning of this manual. Keep this manual with the
KCP Programmed-Transition Any Breaker ATS * equipment for future reference.
KCC Closed-Transition Any Breaker ATS [
KSS Standard-Transition Specific Breaker ATS *
List of Related Materials
KSP Programmed-Transition Specific Breaker ATS *
KSSB Standard-Transition Specific Breaker ATS * A separate transfer switch installation manual provided
* Available with automatic or non-automatic controller with the unit contains instructions for transfer switch
[ Available with automatic controller only installation instructions, and manual operation
procedures.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to Literature Item Part Number
change this literature and the products represented
Specification Sheet, MPAC 1200 Controller G11-127
without notice and without any obligation or liability
Installation Manual, Model KCS/KCP/KCC TP-6833
whatsoever.
Installation Manual, Model KSS/KSP TP-6834
The equipment service requirements are very important Installation Manual, Model KSSB TP-7191
to safe and efficient operation. Inspect parts often and Operation Manual, Modbus Protocol TP-6113
1.1 Introduction Source 2 is the standby generator set. The engine start
contacts are associated with Source 2.
This section contains operation instructions, including:
The Preferred Source is the source that will be used if
D User interface panel, with display, pushbuttons, and
both sources are available. Typically, this is the normal
LED indicators
utility source 1. If the transfer switch is equipped with the
D Main menu optional alarm module, the Set Preferred Source menu
D System status, warnings, and faults allows the operator to select either source as the
D Passwords preferred source. Source 2 (connected to the
D Tests
emergency side of the contactor) can be set as the
preferred source using this menu. See Section 4.6.3 for
D Warnings and Faults more information about preferred source selection.
D Reset Data
Other applications may use different configurations,
such as the gen-gen configuration which uses two
1.2 Source Names generator set sources and no utility.
Throughout this manual, the sources are referred to as
follows. Source 1 (S1) is connected to the Normal side
of the transfer switch and is also referred to as Source N.
1.3 User Interface Panel
Source 2 (S2) is connected to the Emergency side of the The user interface panel is located on the transfer switch
transfer switch and is also called Source E. For the door. Figure 1-1 shows the user interface pushbuttons
MPAC 1200 controller, Source 1 is the utility source, and and LED indicators.
1 2 3 4
GM85884
1. Source N Available LED 4. Source E Available LED 6. System Alert LED 8. Pushbuttons (4)
2. Source N Position LED 5. USB port for SiteTecht 7. Not in Auto LED 9. Display
3. Source E Position LED connection
Set Common Alarms Set Common Alarms Modify Alarm Alarm Description Alarm Description
Alarm Group 1 Common Audible Common Y Audible N
B Y " Main B Y " Back B Y " Back B Y " Back Back Save
B Y " Back
Back Save
OK 7
Set Time ##:##
Back Save
Press the open UP arrow button to
increase the first digit of the password
from 0 through 9.
Press the open up arrow
Note: The default password is 0000. button to increase the first
digit. (Use 00:00 to 23:59 for
time.)
3 Enter Password
Time to Enter #:##
0???
OK
8
Set Time 1#:##
OK
9
Set Time 14:37
Set Time/Date
5
Press Save.
B Y " Main
Test Password. The test password controls access to Press the open right arrow button to step to the next digit.
Repeat for all four digits.
the test sequence menus. The test password is
required to initiate a loaded, unloaded, or auto-loaded
test, and also to initiate a sync check test on
closed-transition models. Enter Password
Time to Enter #:##
>0000<
If the correct password is not entered within 30 seconds,
the display returns to the main menu. OK
System Ready
B Y Main
LD Exer 12/14 @ 16:00
Norm 480V Emer 480V
Emer AB BC AC
B View Set Test ##Hz ###V ###V ###V
Norm L1 L2 B Y Main
##Hz ###V ###V
Lamp Emer AN BN CN
B Y Test Main ##Hz ###V ###V ###V
B Y Main
Emer L1 L2
##Hz ###V ###V
Amps LA LB LC
#### #### ####
B Y Main
B Y Main
Amps L1 L2
#### ####
Time/Date
09:10 DST 01/13/06
B Y Main
B Y Main
Time/Date
09:10 DST 01/13/06
Daylight Saving Time
Clock Ahead 1 Hour
B Y Main
Sun 03/12/06
B Y Main
Daylight Saving Time
Clock Ahead 1 Hour
Daylight Saving Time
Sun 03/12/06
Clock Back 1 Hour
B Y Main
Sun 11/05/06
B Y Main
Daylight Saving Time
Clock Back 1 Hour Normal Preferred
Sun 11/05/06 Util-Gen Operation
B Y Main No Commit Transfer
B Y Main
Normal Preferred
Util-Gen Operation Standard Transition
No Commit Transfer Phase Rotation ABC
B Y Main In Phase Enabled
B Y Main
Standard Transition
Type of Test
Press the Test button to enter the
Loaded
Test mode. A password is required.
B Main Start
Type of Test
Unloaded
B Main Start
Type of Test
Sync Check
B Main Start
Enter Password Use the open arrow buttons to enter the Test
Time to Enter #:## password. See Section 1.5 for instructions. Then
>????<
press the OK button.
OK
Type of Test
Auto Load Press the down arrow button to step to the
Time :## min loaded test screen.
B Main " Start
B Main Start
Figure 1-21 Fault Reset If one or more accessory modules are disconnected
from the controller, the message Module Status Change
appears. See Figure 1-24. Pressing the Reset button
1.11 Accessory Module Faults displays the message Check Module Setup to Clear
Fault. Use the following Module Uninstall Procedure to
Accessory modules are optional equipment. uninstall modules after disconnection.
4. Press the down arrow to step to the Set Inputs/ Procedure to Clear a Module Status Conflict
Outputs menu.
1. Disconnect power to the transfer switch.
5. Navigate to the Set Auxiliary I/O menu. See
Figure 1-25. Press the right arrow button to see the 2. Disconnect the module.
status of module 1. Press the down arrow to step to 3. Close the enclosure door and reconnect power to
the next module, if necessary, until the menu the ATS. The display will show Module Status
shows Status: Lost. Change.
6. Press the right arrow button to move to the 4. Press the button labeled Reset. The display will
Uninstall Module menu. Verify that the menu says show Check Module Setup to Clear Fault.
Uninstall Module Yes. (Press the open arrow
button to toggle no/yes, if necessary.) 5. Follow the procedure in Section 1.11.1 to uninstall
the module through the ATS controller keypad.
7. When Yes is displayed, press Save to uninstall the
module. 6. Disconnect power to the ATS.
8. Repeat the uninstall procedure for additional 7. Connect the new module.
modules, if necessary.
8. Close the enclosure door and reconnect power to
Other Module Status Change Conditions the ATS. The display will show Module Status
Change. See Figure 1-22.
A Module Status Change message that cannot be
cleared as described in this section may indicate a 9. Press the button labeled Reset to display Reset
failure of the controller’s real-time clock. Carefully follow New Module. Press the reset button from that
the Module Connection or Module Uninstall procedures menu. The controller will now recognize the new
to attempt to reset the fault. If the fault cannot be reset, module type.
the controller’s logic board may need to be replaced.
Contact an authorized distributor/dealer for service. 10. Navigate to the Set Auxiliary I/O menu to check the
status and settings for the new module. See
Figure 1-25. Press the right arrow button to see the
status of module 1. Press the down arrow to step to
the next module, if necessary,
Set
Set Inputs/Outputs Main Board I/O
Use the Reset Data menus to set records or parameters 1.12.2 Reset Event History
back to factory default settings. See Figure 1-26. Resetting the event history clears the events from the
event history log. The history lists the 100 most recent
1. Use the black arrow buttons to step to the desired
transfer switch events, including transfers and DIP
menu.
switch setting changes as well as faults and alarms.
2. Press the open up arrow button to toggle Yes or No
until Yes is displayed.
Reset
Reset Data Maintenance Records
Yes/No
B Y " Main B Save Back
Reset
Event History
Yes/No
B Save Back
Reset
Test Password
Yes/No
B Save Back
This section explains the transfer switch sequence of 2.1 Controller Power-up/Reset
operation during the following events:
Following is an explanation of the sequence of operation
D Controller power-up or reset for the MPACr 1200 ATS Controller when power is
initially applied to the controller or a controller reset
D Preferred source loss and return occurs.
D Test 1. Controller self test is executed.
D Exercise 2. System parameters are downloaded from
nonvolatile memory.
D Emergency source loss and return
3. Contactor position and source availability are
The Sequence of Operation descriptions in Sections 2.2
determined.
through 2.4 describe the transfer switch normal
operation for standard, programmed, and closed 4. If neither source is acceptable, the contactor does
transition models. Operation can be affected by faults not change position.
such as the normal or emergency contacts failing to
open or close when signaled to do so. 5. If both sources are available, the controller
immediately transfers the contactor to the
preferred source.
Operation can be affected by faults such as the normal Unloaded Exercise Sequence Starts
or emergency contacts failing to open or close when
signaled to do so. 1. Exerciser timer begins.
4. The generator starts and the standby source Loaded Exercise Sequence Starts
becomes available.
1. Exerciser timer begins.
5. Preferred-to-standby time delay expires.
2. The generator is signaled to start.
6. Contactor transfers to standby.
3. The generator starts and the standby source
7. Post-transfer load control sequences run. becomes available.
4. Post-transfer load control sequences and engine Emergency Source Fails (Normal Source is
cooldown time delay expire. available)
5. Load control contacts close. 1. Exerciser is deactivated.
6. The engine start contacts open, signaling the 2. Load control contacts open.
generator to stop.
3. Contactor immediately transfers to preferred.
5. Load control contacts close. 5. Post-transfer load control sequences and engine
cooldown time delay expire.
6. The engine start contacts open, signaling the
generator to stop. 6. Load control contacts close.
3. The load bank control is activated. 4. Post-transfer load control sequences and engine
cooldown time delay expire.
Unloaded Test Function is Ended
5. Load control contacts close.
1. The load bank control is deactivated.
6. The engine start contacts open, signaling the
2. Engine cooldown time delay expires. generator to stop.
Operation can be affected by faults such as the normal Loaded Exercise Sequence Starts
or emergency contacts failing to open or close when
signaled to do so. 1. Exerciser timer begins.
4. The generator starts and the standby source 7. Off-to-standby time delay expires.
becomes available.
8. Contactor transfers to standby source.
5. Preferred-to-standby time delay expires.
9. Post-transfer load control sequences run.
6. Contactor transfers to OFF position.
10. Load control contacts close.
7. Off-to-standby time delay expires.
Emergency Source Fails (Normal Source is
8. Contactor transfers to standby source. available)
9. Post-transfer load control sequences run. 1. Exerciser is deactivated.
10. Load control contacts close. 2. Immediate failure to acquire standby alarm.
6. Post-transfer load control sequences and engine 9. Engine start contacts open.
cooldown time delay expire.
7. Load control contacts close. 7. Post-transfer load control sequences and engine
cooldown time delay expire.
8. The engine start contacts open, signaling the
generator to stop. 8. Load control contacts close.
1. The generator is signaled to start (engine start 4. Off-to-preferred time delay expires.
contacts close).
5. Contactor transfers to preferred.
2. The generator starts and the standby source
becomes available. 6. Post-transfer load control sequences and engine
cooldown time delay expire.
3. Pre-transfer load control time delays expire and
load control contacts open. 7. Load control contacts close.
4. Preferred-to-standby time delay expires. 8. The engine start contacts open, signaling the
generator to stop.
5. Contactor transfers to the OFF position.
Preferred Source Fails If the sources do not synchronize before the Fail to Sync
time delay expires, the programmed-transition override
1. Load control contacts open. function can initiate a transfer. The override function
transfers to the other source using programmed-
2. Engine start time delay runs and expires. transition mode, which causes an interruption in power
to the load during transfer. The contactor stops in the
3. The generator is signaled to start (engine start OFF position for a programmed period of time, which is
contacts close). set by the off-to-preferred or off-to-standby time delay.
The override function can be set to operate
4. The generator starts and the standby source
automatically or to require manual activation.
becomes available.
D If Automatic programmed-transition override is
5. Preferred-to-standby time delay expires.
selected, a programmed-transition transfer will be
6. Preferred source contacts open. initiated automatically when the Fail to Sync time
delay expires.
7. Off-to-standby time delay expires.
D If Manual programmed-transition override is
8. Emergency power contacts close. selected, an operator can initiate a programmed-
transition transfer by entering the setup password
9. Post-transfer load control sequences run and load and pressing a button after the Fail to Sync time delay
control contacts close, as programmed through the expires. If a manual transfer is not initiated, the
Load Add settings. controller continues to monitor the sources and
transfers if synchronization occurs.
Preferred Source Returns
See Section 4.9, Set System, to set the
1. Standby-to-preferred and pre-transfer load control programmed-transition override function to automatic or
time delays expire. manual. See Section 4.5, Time Delays, to set the
off-to-preferred and off-to-standby time delays.
2. Load control contacts open according to the Load
Disconnect time delay settings. Programmed-Transition Override Sequence
3. Check/wait for source synchronization. 1. Fail to Sync time delay expires.
Note: If the sources do not synchronize before the 2. If Automatic programmed-transition override is
Fail to Sync time delay expires, the enabled, go to step 4.
programmed-transition override function
operates. See Section 2.4.2. 3. If manual programmed-transition override is
enabled, the Manual Transfer screen opens. The
4. When sources are synchronized, preferred source
contacts close.
2. Engine start time delay runs and expires. 8. The generator is signaled to stop (engine start
contacts open).
3. The generator is signaled to start (engine start
contacts close).
2.4.4 Test Sequence, Closed Transition
4. The generator starts and the standby source
becomes available. Unloaded Test Sequence
The unloaded test sequence is the same as for standard
5. Load control contacts open.
transition. See Section 2.2.3.
6. Check/wait for source synchronization.
Loaded Test Sequence is Initiated
Note: If the sources do not synchronize before the
Fail to Sync time delay expires, the 1. Engine start time delay runs and expires.
programmed-transition override function
operates. See Section 2.4.2. 2. The generator is signaled to start (engine start
contacts close).
7. When sources are synchronized, emergency
source contacts close. 3. The generator starts and the standby source
becomes available.
8. Normal source contacts open within 100
milliseconds. 4. Load control contacts open.
Note: If the normal contacts do not open, the 5. Check/wait for source synchronization.
emergency contacts will be signaled to open
Note: If the sources do not synchronize before the
and a Fail to Transfer fault will be activated.
Fail to Sync time delay expires, the
programmed-transition override function
operates. See Section 2.4.2.
Press the View button to navigate to the View screens View View
shown in the following sections. System Setup Inputs/Outputs
The display returns to the main screen after 10 minutes B Y " Main B Y " Main
of no activity (no buttons pressed). See Section 1.6 for
View View
instructions to view system status from the main screen.
Source Setup Common Alarm
System Setup
Remote Test Loading
Loaded/Unloaded
B Y Back
System Setup
Peak Shave TD Bypass
Enabled/Disabled
B Y Back
B Y Back
B Y Back
B Y Back
B Y Back
B Y Back
B Y Back
Module #1
Output ##
Function Description
See Section 4.7 for input and output function descriptions. B Y Back
Use the Setup menus to change the controller pickup After entering the system password, use the black arrow
and dropout settings, inputs, outputs, time delays, and keys to step through the setup menus as shown in
options, if necessary. Figure 4-1.
Settings can also be assigned using a personal Timeout. After 10 minutes of no activity (no buttons
computer with Kohlerr SiteTecht software or over pressed) the controller exits the setup mode and returns
Modbus. SiteTecht software is available to authorized to the main menu.
Kohler distributors. See TP-6701, SiteTech Software
Operation Manual, for instructions to change settings The following sections discuss the setup menus in the
using SiteTech software. See TP-6113, Modbus order of appearance on the controller.
Protocol Manual, for Modbus register maps.
System Ready
LD Exer ##/## @ ##:## Press the Set button in the main menu to enter the Setup menus.
Norm ###V Emer ###V The setup password is required.
B View Set Test
Set Time/Date
Press the down arrow B button to step to the next menu.
Press the right arrow " button to enter the detailed setup menu.
B Y " Main
Press the down arrow B button. Press the down arrow B button.
<
Enable Daylight Saving
Example:
2nd Sun of Mar Time
YES/NO
Back Save
Interval Daily, weekly, monthly, or day/month. This setting works with the repeat rate to set the time interval between
exercise runs.
The day/month selection allows you to set the exerciser to run on the same day every month. For example, the
exerciser can be set to run the first Sunday of every month. Use caution with the day/month selection. For
example, selecting day/month on the 5th Friday of the month will cause the exerciser to run only during months
that have five Fridays.
Repeat Rate The repeat rate works with the interval to set the time interval between exercise runs. For example, if Day is
selected as the interval, and 5 is selected as the repeat rate, then the exercise will repeat every 5 days. Select
a number from 1 to 12.
Duration Enter the exercise run duration in hours:minutes. For example, a run time of 00:30 will run the generator set for
30 minutes. The maximum run time is 24 hours.
Start Date Enter the date, month/date/year, of the first exercise event. Subsequent events will be scheduled based on the
interval and repeat rate.
Start Time Enter the desired start time of the exercise run in hours:minutes. The time settings range from 00:00 to 23:59,
with 00:00=midnight.
Weekly
Monthly
1- 12 Exerciser Event ##
Day/Month
Daily Start Time HR:MM
Back Save
Fail to Acquire Stby If the standby source does not reach acceptable
voltage and stabilize within the allowed time, the Fail to 1 min 0 - 60 min
Acquire Standby Source fault is activated.
Fail to Synch For closed-transition models only. Found in the Set
Sources menu. Operates when two sources are
available. If the sources do not synchronize before the 1 min 10 seconds - 15 min
Fail to Sync time delay expires, the programmed-
transition override function operates. See Section 4.9.
In-Phase Xfr Fail (found in the For in-phase monitoring: the time allowed for the two
Set Sources menu) sources to come into synchronization within specified
phase angle before a Fail to Sync fault is activated. 30 sec
See Section 4.6.
Load # Disc N>E Disconnect load before-transfer to standby source.
Used for time-based load control. See Section 4.5.5. 0 sec
Load # Rec N>E Reconnect load after-transfer to standby source. Used 0- 60 min
for time-based load control. See Section 4.5.5. 0 sec
* The optional external battery module allows extended engine start time delays from 0- 60 min.
B
Load #? Rec E>N
Min:Sec
Back Save
B
Load #? Reconn N>E
Min:Sec
Back Save
Example 1: The transfer time delay is longer than the load control pre-transfer time delays.
Example 2: One or more load control pre-transfer time delays are longer than the transfer time delay.
Figure 4-8 Preferred Source Selection Effect on System Parameters and Time Delays
Set Synchronization
Voltage Differential ? ? Percent
Set Synchronization
Frequency Differential ? ? Hz
Preferred Source
Alarm module Set Preferred Source Normal/Emergency
required
Normal Source
Set Normal Source Set Number of Phases Single/Three Phase
Emergency
B Y " Back B Y " Back Save Back
Continue to next page for additional menus for Emergency source only
B Y " Back B
Emergency Source Pickup
Set Under Frequency ??? % of Nominal
Pickup 80- 95%
B Y " Back Save Back
Each programmable input and output requires a See Section 7.2.1 for I/O module connection
connection to the transfer switch. Do not change the information.
programmable input/output assignments without
Set Inputs/Outputs Press the right arrow button to enter the Set Inputs/Outputs menu.
B Y " Main
<
Module #?
Uninstall Module?
Yes/No
Save Back
«
Programmable Inputs * LED LED Display Message
Forced Transfer to OFF* (programmed-transition None Flashing Forced Off
models only; requires load shed accessory)
Inhibit Transfer (maintenance mode) None Flashing Inhibit Transfer
Low Battery Voltage Steady None Low Battery Voltage
Peak Shave Mode None None Peak Shave
Remote End Time Delay None None None
Remote Common Alarm Steady None Remote Common Alarm
Remote Test None None Normal test sequence menus. See
Section 1.7.
Remote Monitor In #1- 4 None None None
* See Figure 4-11 for factory-set input functions for selected models. Do not change the factory settings.
Emergency (standby)
source available
Engine cooldown
Set Common Alarms Set Common Alarms Modify Alarm Alarm Description Alarm Description
Alarm Group 1 Audible N Common Y Audible N Common Y
B Y " Main B Y " Back B Y " Back B Y " Back Back Save
D One utility source and one generator set If a manual transfer is not initiated, the controller
continues to monitor the sources and transfers if
4.9.3 Transition Type synchronization occurs.
The transition type is factory set for each model and D Set the Xfr Off>Stby (transfer off-to-standby) time
should not require change except in the case of delay for the desired “off” time during the transfer.
controller replacement. Select standard, programmed, See Section 4.5 for the default time delays.
or closed transition, if necessary.
Note: The transition type is determined by the ATS 4.9.4 Rated Current
model as indicated Figure 4-18. Do not attempt This value is factory-set for each unit and should not
to change the transition type to one that is not require adjustment. If necessary, enter the rated current
listed for your model. from the transfer switch nameplate.
Peak Shave Operation. When the peak shave input is D If the Peak Shave TD Bypass is disabled, the
activated, the generator set starts immediately, retransfer (standby to preferred) time delay executes
bypassing the engine start time delay. The pre/post- before the ATS transfers back to the preferred source.
transfer time delays, programmed-transition time Transfer is delayed by the retransfer time delay. The
delays, and in-phase monitor are active if enabled. The retransfer time delay is adjustable, with a 15-minute
ATS transfers the load to the standby source. factory setting.
Peak Shave TD Bypass. In normal operation, If the standby source is lost during peak shave
retransfer from standby to preferred is delayed operation, the unit transfers back to the preferred
(15 minutes default setting) to ensure that the preferred source.
source is stable before transfer. The Peak Shave TD
Note: For three-phase models, the voltage and current for L1, L2, and L3 will appear and can be calibrated.
GM85888
1. USB connection (below port cover)
Set the following communication parameters for serial Modbus TCP Unit ID. The unit ID is required for
communication. Also see Figure 5-6 for a summary of Modbus over TCP communication. The unit ID for TCP
these settings. communication is analogous to the Modbus address for
serial communication through the RS-485 ports. The
Note: Modbusr applications require a Modbus factory default setting is 2.
software driver written by a trained and qualified
systems programmer. Modbus TCP Server Enabled. Enable (set to True) to
enable TCP if the transfer switch is connected to a
Modbus Enabled. Set to True to allow Modbus network for TCP/IP communication (for example,
communication. ethernet communication).
Modbus Baud Rate. Required for serial connections. MAC address. The MAC hardware address is
The baud rate must match the baud rate of the factory-set. It can be seen in the View>Communications
connected PC. Setup menus but not viewed or changed in the setup
menus.
Modbus Slave Addr. Assign a unique address
between 001 and 247 to the serial port.
5.3.3 Setup Using the Controller
5.3.2 Network Communication Setup Keypad
Work with your local network administrator to set the Use the Set Communications menu to set the
following communication parameters for Ethernet communication parameters for serial or ethernet
communication. connections. See Figure 5-4.
See Figure 5-6 for a summary of the following settings. The Modbus port on the controller circuit board is Port 0.
DHCP Enabled. Factory set to False. Setting this 5.3.4 Setup Using SiteTech
parameter to True enables dynamic host configuration
protocol (DHCP), which allows a DHCP server to Use a USB cable, male USB A to male USB mini-B, to
automatically assign a dynamic IP address, subnet connect the MPAC controller to a personal computer.
mask, and default gateway to the MPAC controller. Then use Kohler SiteTech software to set the
Work with your local network administrator to determine communication parameters for serial or Ethernet
whether DHCP is required. connections. See Figure 5-5 and TP- 6701, SiteTech
Software Operation Manual.
Static IP Address. The transfer switch may have a
default IP address assigned at the factory. Change the SiteTech software is available only to Kohler authorized
IP address to a static IP address owned by the user. distributor and dealers.
Obtain an IP address, subnet mask, and default
gateway information from the local network Some parameter names in SiteTech are slightly different
administrator. than what is shown the controller display. Figure 5-6
shows both names.
Figure 5-4 Communications Setup from the Controller Display and Keypad
1200
*
*
*
*
Figure 5-5 Communications Setup using Kohlerr SiteTecht Software (typical screen shown)
SiteTech: Modbus Baud Rate 9600, 19200, 57600 19200 Baud rate in bits per second for serial communication
Controller: Baud Rate between the controller and a personal computer’s
COM port.
SiteTech: Modbus Slave Address 001-247 0 Address for the RS-485 serial port (on the logic
Controller: Modbus Address board).
SiteTech: DHCP Enabled True or False False Dynamic host communication protocol. Enable if
Controller: DHCP Status Enabled or Disabled Disabled required; check with your local network administrator.
SiteTech: Static IP Address See notes. * Obtain from your local network administrator. Every
Controller: IP Address device on the network must have a unique IP
address.
SiteTech: Static Subnet Mask See notes. * Obtain from your local network administrator.
Controller: Subnet Mask All devices that communicate with each other on the
same local network must use the same subnet mask.
SiteTech: Static Default Gateway See notes. * Obtain from your local network administrator.
Controller: Default Gateway
SiteTech: DHCP Server Read only — Displayed in SiteTech for information only.
Controller: (not shown on controller)
SiteTech: Modbus TCP Unit ID 001-247 002 The unit ID is required for Modbus over TCP
Controller: Modbus TCP Unit ID communication.
SiteTech: Modbus TCP Server Enabled True or False True Enable (set to True) to enable TCP/IP communication
Controller: Modbus Server TCP Enabled or Disabled Enabled (for example, Ethernet communication).
SiteTech: MAC Address Not Adjustable Factory- Hardware address, entered at the factory. Not
Controller: MAC Address (view menu only) set adjustable.
* Do not use the factory settings for IP address, subnet mask, or default gateway. Obtain these settings from your local network
administrator.
Keep records of all maintenance or service. Disconnect all power sources before
opening the enclosure.
Replace all barriers and close and lock the enclosure
door after maintenance or service and before reapplying DANGER
power.
WARNING
Hazardous voltage.
Will cause severe injury or death.
Only authorized personnel should
Accidental starting. open the enclosure.
Can cause severe injury or death.
Disconnect the battery cables before DANGER
working on the generator set.
Remove the negative (- ) lead first
when disconnecting the battery.
Reconnect the negative (- ) lead last
when reconnecting the battery.
Hazardous voltage. Moving parts.
Disabling the generator set. Accidental starting can Will cause severe injury or death.
cause severe injury or death. Before working on the Operate the generator set only when
generator set or equipment connected to the set, disable the all guards and electrical enclosures
generator set as follows: (1) Move the generator set master are in place.
switch to the OFF position. (2) Disconnect the power to the
battery charger. (3) Remove the battery cables, negative (- )
lead first. Reconnect the negative (- ) lead last when
reconnecting the battery. Follow these precautions to prevent
starting of the generator set by an automatic transfer switch,
remote start/stop switch, or engine start command from a
remote computer.
Disconnect all power sources, open the transfer switch On transfer switches equipped with optional surge
enclosure door, and inspect internal components protective devices (SPDs), check the following items
monthly or when any condition noticed during an every two months:
external inspection may have affected internal
components. D SPD status indicators
Adjust,
See Visually Repair,
System Component or Procedure Section Inspect Check Replace Clean Test Frequency
Electrical System
Check for signs of overheating or loose connections:
6.3.1 X X Y
discoloration of metal, melted plastic, or a burning odor
Check the contactor’s external operating mechanism D (clean
6.3.1 X Y
for cleanliness; clean and relubricate if dirty * and lube)
Inspect wiring insulation for deterioration, cuts, or
abrasion. Repair or replace deteriorated or damaged 6.3.1 X D D Y
wiring
Tighten control and power wiring connections to
2 D D Y
specifications
Check the transfer switch’s main power switching
contacts’ condition; clean or replace the main contacts S/M D D D Y
or replace the contactor assembly as necessary
Control System
Exercise the generator set under load 6.2.1 X W
Test the transfer switch’s automatic control system 6.2.2
X X M
1.8
Test all indicators (LEDs) and all remote control
I/M X D D D Y
systems for operation
General Equipment Condition
Inspect the outside of the transfer switch for any signs
of excessive vibration, leakage, high temperature, 6.3.1 X X M
contamination, or deterioration *
Check that all external hardware is in place, tightened,
6.3.1 X X X M
and not badly worn
Inspect the inside of transfer switch for any signs of
excessive vibration, leakage, high temperature, 6.3.4 D D D Y
contamination, or deterioration *
Check that all internal hardware is in place, tightened,
6.3.4 X D D Y
and not badly worn
SPD Modules (if equipped)
Check status indicators 7.11 X D Every
Check condition of connecting leads 7.11 X D 2 months
* Service more frequently if the transfer switch is operated in dusty or dirty areas.
See Section: Read these sections carefully for additional information before attempting maintenance or service.
Visually Inspect: Examine these items visually.
Check: Requires physical contact with or movement of system components, or the use of nonvisual indications.
Adjust, Repair, Replace: Includes tightening hardware and lubricating the mechanism. May require replacement of components depending
upon the severity of the problem.
Clean: Remove accumulations of dirt and contaminants from external transfer switch’s components or enclosure with a vacuum cleaner or by
wiping with a dry cloth or brush. Do not use compressed air to clean the switch because it can cause debris to lodge in the components and cause
damage.
Test: May require tools, equipment, or training available only through an authorized distributor/dealer.
Symbols used in the chart:
X= The transfer switch operator can perform these tasks. W=Weekly
D=An authorized distributor/dealer must perform these tasks. M=Monthly
I/M = Transfer Switch Installation Manual Q=Quarterly
S/M = Service Manual. An authorized distributor/dealer must perform S=Semiannually (every six months)
these tasks. Y=Yearly (annually)
7.1 Introduction 1
This section describes the hardware options that will
interface with the Decision-Makerr MPAC 1200
controls. The following accessories are available:
D Accessory modules
D Controller disconnect switch 2
D Current monitoring
D Digital meter: displays voltage, frequency, current,
power, and more (factory-installed)
2
D Ethernet communication board
D Load shed module (available on programmed-
transition and closed-transition models only)
D Line-to-neutral voltage monitoring 2
D Supervised transfer control switch
D Surge protection device (SPD)
D User interface cover
3
3
GM42186
4
1. Input LEDs 1 and 2
2. Input connector
3. Output connector
4. Output LEDs 3- 5 for outputs 1, 2, and 3
4
2
GM42227-A
1. Connector P20
2. LED indicators
3. Battery input connection terminal block TB13
4. 12/24 volt DIP switch SW11-1. OFF=12 VDC, ON = 24 VDC
See Figure 7-10 for the alarm module. There are four DIP switches on the alarm module board.
Some of the switches are not used. See Figure 7-11. To
The functions provided by this board are: enable the preferred source selection, set DIP switch 1
to ON. If the supervised transfer switch is installed on
D 90 dB Audible alarm (any alarm function can be the ATS, set DIP switch 2 to ON.
programmed to trigger the audible alarm)
DIP Switch Function
D Chicago alarm operation 1 Preferred source selection
2 Supervised transfer enable
D Preferred source selection
3 Not used
D Supervised transfer control (supervised transfer 4 Not used
control switch required)
Figure 7-11 Alarm Board DIP Switches
D Connection for external alarm
Preferred Source Selection
The alarm board has a fixed address = 5.
The alarm module is required for preferred source
selection. To enable the preferred source selection, set
1
DIP switch 1 to ON. Then see Section 4.6.3 for
instructions to select Source N or Source E as the
preferred source.
2 External Alarm
A customer-supplied external alarm horn can be
connected to the alarm module at terminal block TB14.
Connect to the normally open or normally closed contact
as recommended by the alarm manufacturer’s
instructions. See Figure 7-12.
Item Specification
Wire Size #12-22 AWG Cu
1. Supervised Transfer Switch Connection, P22 Figure 7-12 External Alarm Connection
2. External Alarm Connection, TB 14 Specifications
3. Alarm Indicator, LED1
4. DIP Switches
Audible Alarm Setup
Figure 7-10 Alarm Module
The alarm board is equipped with a 90 dB audible alarm.
The audible alarm can be set to sound under selected
fault conditions. Use the Common Alarms Setup menu
to assign functions to the audible alarm. See Section 4.8
for instructions to set Audible Alarm: Y for each function
that should trigger the alarm.
For Chicago Alarm Mode, use the Common Alarm System Ready
Setup menu to assign the necessary faults and LD Exer 12/14 @ 16:00
conditions to the audible alarm. See Section 4.8. Be Norm 480V Emer 480V
sure to assign the Contactor in Standby condition to Alarm View Set Test
trigger the audible alarm.
Reset
A remote alarm or indicator light can also be connected To Silence Alarm
to the alarm board to indicate the alarm condition as
described previously. See External Alarm. B Y Reset Main
The Alarm Silenced condition can be assigned to a Figure 7-13 Alarm Silence
programmable output. See Section 4.7 for instructions
to assign outputs.
Accidental starting. The switch has two positions, auto (I) and disconnect
Can cause severe injury or death. (0). Move the controller disconnect switch to the 0
position to disconnect power to the ATS controller. After
Disconnect the battery cables before
maintenance or service, move the switch to the I position
working on the generator set.
Remove the negative (- ) lead first to reconnect power. Follow the instructions in the
when disconnecting the battery. generator set documentation to reenable the generator
Reconnect the negative (- ) lead last set.
when reconnecting the battery.
The controller disconnect switch is not available for
service entrance models, which are equipped with a
Disabling the generator set. Accidental starting can control circuit isolation switch as standard equipment.
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (- ) lead first. Reconnect the negative
(- ) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
DANGER
Hazardous voltage.
Will cause severe injury or death.
Only authorized personnel should
open the enclosure.
GM89028
1. Current transformers on load bus 2. Terminal block TB1 (see wiring diagram GM47803)
TP- 7168
the following models can include either an enclosure 1. 120 VAC power connection terminal block
heater or a surge protection device (SPD), but not both: 2. Circuit breaker
3. Relative humidity adjustment control
D Model KCS 30- 200 Amps
D Model KSS/KSSB 40- 225 Amps Figure 7-19 Hygrostat Assembly, Typical
HYGROSTAT
CIRCUIT
BREAKER
2
TERMINAL
BLOCK HEATER
7.9.1 Description
The load shed (forced transfer to off) accessory allows
the removal of non-critical loads from the Source E
generator set. The accessory requires an external
signal (contact closure) to initiate transfer to the OFF
position.
TB1
12
6
MLB Input 2
(alternate
MLB connection)
Input 1
7
1
Figure 7-22 Forced Transfer to Off Input Connection (for load shed kits)
The switch has maintained AUTO and MANUAL 3. MANUAL TRANSFER is displayed on the
positions and a momentary TRANSFER position. The controller and the Not-in-Auto LED flashes.
key can be removed in either the AUTO or MANUAL
position. The key cannot be removed when the switch is 4. Turn the keyswitch to the TRANSFER position and
in the TRANSFER position. Figure 7-23 shows the release.
switch.
5. The load is transferred to the standby source, if
available.
AUTO position
Figure 7-23 Supervised Transfer Control Switch
On an automatic transfer switch, when the Supervised
7.10.1 Manual Transfer Transfer Control switch is in the AUTO position, the
controller responds normally to transfer requests, and
Moving the switch to the TRANSFER position will not will automatically transfer to a source if that source is
cause the ATS to transfer unless an event such as a loss available.
of utility, a loaded test, or a loaded exercise has initiated
a transfer sequence. The transfer sequence executes MANUAL Position
all programmed time delays and signals the generator
set engine to start. Wait for the time delays to expire, or On an automatic transfer switch with the Supervised
press the End Time Delay button. Transfer Control Switch in the MANUAL Position, the
contactor will automatically transfer to the available
MANUAL TRANSFER is displayed on the controller source if the connected source is not available. In this
display and the Not-in-Auto LED flashes when the ATS case, no user action is required to initiate the transfer.
is ready to transfer. Turn the switch to TRANSFER and
release it to allow a transfer. It is not necessary to hold Operation with Test and Peak Shave
the switch in the TRANSFER position.
On an automatic transfer switch, a test, peak shave, or
The MANUAL mode allows the system to run on the loaded exercise command will be recognized and a
standby source indefinitely, even if the preferred source transfer sequence to the standby source will operate
is available. normally when the Supervised Transfer Control Switch
Figure 7-24 Supervised Transfer Control Switch Operation for Automatic and Non-Automatic Transfer Switches
GM49947
SPD Specifications
Maximum
Max. Limiting Voltage, (L-N/N-G/L-G) Continuous
Nominal Discharge UL VPR 3rd Ed (kV) Short Circuit Operating
Voltage Current (L-N/N-G/L-G) Withstand Voltage
(V ±15%) (kA) Phase Poles (kV) at 3kAmps at 10kAmp Current (kA) (VAC)
120 / 240 40 Split 3 0.6 / 1.2 / 0.7 0.6 / 0.4 / 0.6 0.8 / 0.7 / 0.8 200 175 / 350
120 / 208 40 Wye 4 0.6 / 1.2 / 0.7 0.6 / 0.4 / 0.6 0.8 / 0.7 / 0.8 200 175 / 350
277 / 480 40 Wye 4 1.0 / 1.2 / 1.1 1.0 / 0.4 / 1.0 1.2 / 0.7 / 1.2 200 320 / 640
120 / 240 40 HLD 4 1.0 / 1.2 / 1.1 1.0 / 0.4 / 1.0 1.2 / 0.7 / 1.2 200 320 / 640
347 / 600 40 Wye 4 1.3 / 1.2 / 1.4 1.3 / 0.4 / 1.3 1.5 / 0.7 / 1.5 200 440 / 880
Figure 7-26 SPD Specifications
5
7.11.3 SPD Replacement
4 2 Replace the module when the SPD indicator turns red.
Follow the replacement procedure in this section.
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
serviced by qualified electrical
personnel.
GM89934
Servicing the transfer switch. Hazardous voltage will
1. Decal, remote status indicator wiring cause severe injury or death. Deenergize all power sources
2. Fuse blocks
before servicing. Turn off the main circuit breakers of all
3. Surge suppressors
4. SPD status indicator location
transfer switch power sources and disable all generator sets
5. Remote status indicator connections as follows: (1) Move all generator set master controller
switches to the OFF position. (2) Disconnect power to all
battery chargers. (3) Disconnect all battery cables, negative
Figure 7-28 SPD Assembly, Typical
(- ) leads first. Reconnect negative (- ) leads last when
reconnecting the battery cables after servicing. Follow these
7.11.2 SPD Remote Status Indicator precautions to prevent the starting of generator sets by an
automatic transfer switch, remote start/stop switch, or engine
A customer-supplied indicator for the SPD can be start command from a remote computer. Before servicing any
connected to provide remote indication when the SPD components inside the enclosure: (1) Remove all jewelry. (2)
Stand on a dry, approved electrically insulated mat. (3) Test
needs to be replaced. The contact changes state when
circuits with a voltmeter to verify that they are deenergized.
the SPD module needs replacement.
1. Disable the generator set to prevent starting as 11. Reconnect the generator set engine starting
follows: battery, negative (- ) lead last.
a. Move the generator set master switch to the 12. Reconnect power to the battery charger.
OFF position.
13. Close and lock the ATS enclosure door.
b. Disconnect power to the battery charger.
14. Move the generator set master switch to the AUTO
c. Disconnect the generator set engine starting position.
battery, negative (- ) lead first.
2. Disconnect power to the transfer switch: Open the 7.12 User Interface Cover
normal and emergency source circuit breakers
upstream of the transfer switch. The gasket-sealed, hinged user interface cover
prevents unauthorized access to the transfer switch
3. Remove the enclosure’s inner panel , if equipped. controls and protects the user interface from harsh
environmental conditions. Use a customer-supplied
4. Open the fuse holder. padlock to lock the cover.
5. Remove the cartridge by pulling straight out. The cover is available as an optional accessory for
NEMA 1 enclosures. NEMA 3R enclosures include the
6. Replace the SPD cartridge with the appropriate cover as standard equipment.
service part.
For reference, this section lists the items displayed during normal operation, and the information and settings shown in
the View screens and Setup menus.