Chapter 2
Chapter 2
EEE 322
Electromechanical Energy Conversion – II
By
Prof. Dr. A. Mete VURAL
[email protected]
CHAPTER 2
SYNCHRONOUS GENERATORS
1
04-Feb-24
Synchronous Generators
Synchronous generators (alternators) are synchronous machines used to convert mechanical power to AC electric
power.
The rotor is being replaced inside the stator of a large synchronous generator in a hydro power plant
3
Synchronous Generators
2
04-Feb-24
Reference: https://www.youtube.com/watch?v=tiKH48EMgKE
Reference: http://www.studyelectrical.com
3
04-Feb-24
120𝑓𝑒
𝑛𝑚 =
𝑃
higher
If 𝑓𝑒 =50 Hz;
120𝑥50 = 6000 = 𝑛𝑚 𝑃
lower
Cylindrical rotor 7
120𝑓𝑒
𝑛𝑚 =
𝑃
higher
If 𝑓𝑒 =50 Hz;
120𝑥50 = 6000 = 𝑛𝑚 𝑃
4
04-Feb-24
slip rings
brushes
Regular
maintenance
is required
Reference: http://users.ece.utexas.edu/~kwasinski/EE394J10DGFa12.html 9
Reference: https://www.quora.com
5
04-Feb-24
11
Option 2
𝑛𝑚 𝑃
𝑓𝑒 =
120
𝑛𝑚 is also equals to the rotor speed of synchronous machines (also called “synchronous speed”)
6
04-Feb-24
𝐸𝐴 = 2𝜋𝑁𝐶 ∅𝑓
𝐸𝐴 = 𝐾∅w
2
𝐾= 𝑁 (a constant related with the machine)
2 𝐶
14
7
04-Feb-24
15
16
8
04-Feb-24
17
𝑉∅ = 𝐸𝐴 + 𝐸𝑆𝑇𝐴𝑇
• On the other hand, the net magnetic field in the generator becomes the sum of the rotor and stator magnetic fields
𝐵𝑛𝑒𝑡 = 𝐵𝑅 + 𝐵𝑆
18
9
04-Feb-24
• This three-phase stator current produce a magnetic field (BS) of its own
in the machine.
• The stator magnetic field (BS) distorts the original rotor magnetic field
(BR)
𝐵𝑆 = 0
𝐵𝑛𝑒𝑡 = 𝐵𝑅 (without load) 𝐵𝑛𝑒𝑡 ≠ 𝐵𝑅 (with load) (armature reaction)
𝐵𝑛𝑒𝑡 = 𝐵𝑅 + 𝐵𝑆 𝐵𝑛𝑒𝑡 = 𝐵𝑅 + 𝐵𝑆
19
• First; the voltage ESTAT lies at an angle of 90° behind the armature current IA
• Second; the voltage ESTAT is directly proportional to the armature current IA
𝐼𝐴 𝐵𝑆 𝐸𝑆𝑇𝐴𝑇
• Since;
𝑉∅ = 𝐸𝐴 + 𝐸𝑆𝑇𝐴𝑇
𝑉∅ = 𝐸𝐴 − 𝑗𝑋𝐼𝐴
20
10
04-Feb-24
• In addition to armature reaction, the stator coils have a self-inductance (LA) and a resistance (RA)
• These parameters can also be used in the mathematical model for more accurate calculations:
• If;
𝑉∅ = 𝐸𝐴 − 𝑗𝑋𝐼𝐴 − 𝑗𝑋𝐴 𝐼𝐴 − 𝑅𝐴 𝐼𝐴
21
𝑋𝑆 = 𝑋 + 𝑋𝐴 (synchronous reactance)
• The final form of the voltage equation for the stator is obtained as:
𝑉∅ = 𝐸𝐴 − 𝑗𝑋𝑆 𝐼𝐴 − 𝑅𝐴 𝐼𝐴
11
04-Feb-24
Phase-A
Phase-C
23
Rotor side Stator side (armature windings)
12
04-Feb-24
𝑉𝐴𝐵
𝑉𝐿𝐿 = 𝑉∅ 𝑉∅1 𝐼𝐴1
𝐼𝐴3
𝑉𝐶𝐴
𝑉𝐴𝐵 = 𝑉𝐵𝐶 = 𝑉𝐶𝐴 = 𝑉𝐿𝐿
𝐼𝐿 = 3. 𝐼𝐴
𝐼𝐴2 𝐼𝐿2
𝐼𝐴1 = 𝐼𝐴2 = 𝐼𝐴3 = 𝐼𝐴
B
𝑉𝐵𝐶
𝐼𝐿1 = 𝐼𝐿2 = 𝐼𝐿3 = 𝐼𝐿
𝑉∅2
𝐼𝐿3 C
Equivalent circuit of stator connected in ∆
Line-to-line voltage (VLL) = line voltage = terminal voltage (VT)
25
Field circuit
NOTE: By changing RF, we can control the magnitude of EA
𝑅𝐹 𝐼𝐹 𝑅𝐹 𝐼𝐹 𝐸𝐴
𝐸𝐴
26
13
04-Feb-24
𝑛𝑚 𝑃
𝑓𝑒 =
120
14
04-Feb-24
Y-connected stator
𝑉𝑇 = 3. 𝑉∅ 𝑃𝑜𝑢𝑡 = 3. 3. 𝑉∅ . 𝐼𝐴 . 𝑐𝑜𝑠𝜃
𝐼𝐿 = 𝐼𝐴 𝑃𝑜𝑢𝑡 = 3. 𝑉∅ . 𝐼𝐴 . 𝑐𝑜𝑠𝜃
∆-connected stator
𝑉𝑇 = 𝑉∅
𝑃𝑜𝑢𝑡 = 3. 𝑉∅ . 3. 𝐼𝐴 . cosθ
𝐼𝐿 = 3. 𝐼𝐴 𝑃𝑜𝑢𝑡 = 3. 𝑉∅ . 𝐼𝐴 . 𝑐𝑜𝑠𝜃
29
𝑆𝑜𝑢𝑡 = 𝑃𝑜𝑢𝑡 + 𝑗𝑄𝑜𝑢𝑡 Three-phase output complex power of the synchronous generator
𝑆𝑜𝑢𝑡 = 𝑃𝑜𝑢𝑡 2 + 𝑄𝑜𝑢𝑡 2 Three-phase output apparent power of the synchronous generator
The unit is: VA or kVA or MVA
30
15
04-Feb-24
𝐸𝐴 𝑠𝑖𝑛𝛿 = 𝑋𝑆 𝐼𝐴 𝑐𝑜𝑠𝜃
𝑉∅ 𝑐𝑜𝑠𝜃 = 𝐸𝐴 𝑐𝑜𝑠𝛾
𝐸𝐴 𝑠𝑖𝑛𝛿 = 𝑋𝑆 𝐼𝐴 𝑐𝑜𝑠𝜃
𝐸𝐴 𝑠𝑖𝑛𝛿
𝐼𝐴 𝑐𝑜𝑠𝜃 =
𝑋𝑆
• And since;
𝑃𝑜𝑢𝑡 = 3. 𝑉∅ . 𝐼𝐴 . 𝑐𝑜𝑠𝜃
𝐸𝐴 𝑠𝑖𝑛𝛿
𝑃𝑜𝑢𝑡 = 3𝑉∅ (if RA is ignored)
𝑋𝑆
32
16
04-Feb-24
3𝑉∅ 𝐸𝐴
𝑃𝑜𝑢𝑡(𝑚𝑎𝑥) = (when 𝛿 = 90°)
𝑋𝑆
𝑃𝑐𝑜𝑛𝑣 ≅ 𝑃𝑜𝑢𝑡
• Since;
𝑃𝑜𝑢𝑡 = 3. 𝑉∅ . 𝐼𝐴 . 𝑐𝑜𝑠𝜃
𝑃𝑜𝑢𝑡 = 3. 𝐼𝐴 . 𝐸𝐴 𝑐𝑜𝑠𝛾
𝑉∅ 𝑐𝑜𝑠𝜃 = 𝐸𝐴 𝑐𝑜𝑠𝛾
𝜏𝑖𝑛𝑑 𝑤𝑚 ≅ 3. 𝐼𝐴 . 𝐸𝐴 𝑐𝑜𝑠𝛾
𝑃𝑐𝑜𝑛𝑣 ≅ 𝑃𝑜𝑢𝑡
𝐸𝐴 𝑐𝑜𝑠𝛾
𝜏𝑖𝑛𝑑 ≅ 3. 𝐼𝐴 . (If RA is ignored)
𝑤𝑚
34
17
04-Feb-24
• Since;
𝑃𝑐𝑜𝑛𝑣 ≅ 𝑃𝑜𝑢𝑡
𝐸𝐴 𝑠𝑖𝑛𝛿
𝑃𝑜𝑢𝑡 = 3𝑉∅
𝑋𝑆
𝐸𝐴 𝑠𝑖𝑛𝛿
𝜏𝑖𝑛𝑑 𝑤𝑚 ≅ 3𝑉∅
𝑋𝑆
𝐸𝐴 𝑠𝑖𝑛𝛿
𝜏𝑖𝑛𝑑 = 3𝑉∅ (if RA is ignored)
𝑤𝑚 𝑋𝑆
35
1) The relationship between field current IF and flux ∅ (or between IF and armature voltage EA)
2) Synchronous reactance, XS
3) Armature resistance, RA
36
18
04-Feb-24
❑ İf stator is Y-connected:
𝑉𝑇(𝑂𝐶)
𝑉𝑇(𝑂𝐶) = 3. 𝐸𝐴 → 𝐸𝐴 =
3
❑ İf stator is Δ-connected:
𝑉𝑇(𝑂𝐶) = 𝐸𝐴
V
➢ The measured points are plotted to obtain open-circuit characteristics
37
Saturation begins • When the iron finally saturates, the reluctance of the iron
increases dramatically, and the flux increases much more
slowly with an increase in magnetomotive force
19
04-Feb-24
39
40
20
04-Feb-24
𝑉∅ = 𝐸𝐴 + 𝐸𝑆𝑇𝐴𝑇 = 0 (Short-circuit)
𝐸𝐴 = −𝐸𝑆𝑇𝐴𝑇
41
Short-circuit
𝐸𝐴 𝐸𝐴
𝐼𝐴 = 𝐼𝐴 = (The magnitude of armature current)
𝑅𝐴 + 𝑗𝑋𝑆 2 2
𝑅𝐴 + 𝑋𝑆
𝑍𝑆 (synchronous impedance)
42
21
04-Feb-24
𝑍𝑆 ≅ 𝑋𝑆
𝐸𝐴 𝑉∅(𝑂𝐶)
𝑋𝑆 ≅ =
𝐼𝐴 𝐼𝐴
43
𝑋𝑆(𝑢𝑛𝑠𝑎𝑡𝑢𝑟𝑎𝑡𝑒𝑑)
44
Low values of IF
22
04-Feb-24
45
0 0
ohmmeter
23
04-Feb-24
2
𝑜ℎ𝑚𝑚𝑒𝑡𝑒𝑟 𝑟𝑒𝑎𝑑𝑖𝑛𝑔 = 𝑅𝐴
3
𝑜ℎ𝑚𝑚𝑒𝑡𝑒𝑟 𝑟𝑒𝑎𝑑𝑖𝑛𝑔
ohmmeter 𝑅𝐴 =
2/3
0 0
0
Applying armature resistance measurement test
to Δ-connected stator
47
Short-circuit ratio
• The short-circuit ratio (SCR) of a synchronous generator is defined as the ratio of the field current required
for the rated voltage at open circuit to the field current required for the rated armature current at short
circuit
• SCR is also the reciprocal of the per-unit value of the approximate saturated synchronous reactance
48
24
04-Feb-24
Short-circuit ratio
Example: A 200-kVA, 480-V, 50-Hz, Y-connected synchronous generator with a rated field current of 5 A was
tested, and the following data were taken:
1. VT,OC at the rated field current was measured to be 540 V
2. IL,SC at the rated field curretn was measured to be 300 A
3. When a DC voltage of 10 V was applied to the two of the terminals of the stator, a current of 25 A
was measured.
Find the values of the armature resistance and the approximate synchronous reactance in
ohms that would be used in the generator model at the rated conditions.
49
Short-circuit ratio
Solution:
𝑜ℎ𝑚𝑚𝑒𝑡𝑒𝑟 𝑟𝑒𝑎𝑑𝑖𝑛𝑔
𝑅𝐴 =
2
10𝑉/25𝐴
𝑅𝐴 = = 0.2 𝑜ℎ𝑚
2
50
25
04-Feb-24
Short-circuit ratio
Solution:
• The internal generated voltage at the rated field current is equal to:
𝑉𝑇 540𝑉
𝐸𝐴 = 𝑉∅(𝑂𝐶) = = = 311.8 𝑉
3 3
• The short-circuit current is equal to the line current, since the generator is Y-connected:
Short-circuit ratio
Solution:
• The resulting per-phase equivalent circuit of the synchronous generator is shown below:
52
26
04-Feb-24
53
➢ An increase in the load means that the load’s real and/or reactive power taken from the generator is increased
➢ Such a load increase increases the load current drawn from the generator
PLOAD ILOAD
➢ The magnitude of the internal generated voltage EA does not change when the load increases, because;
✓ we do not change field current IF, hence the flux in the machine (φ) is constant
✓ the speed of the prime mover is constant (w)
𝐸𝐴 = 𝐾∅𝑤
constant
constant 54
27
04-Feb-24
The results:
1) Phase voltage of the generator decreases
2) Torque angle increases
55
The results:
1) Phase voltage of the generator decreases
2) Torque angle increases
56
28
04-Feb-24
The results:
1) Phase voltage of the generator increases
2) Torque angle increases
57
58
29
04-Feb-24
𝑅𝐹 𝐼𝐹 ∅ 𝐸𝐴 = K∅𝑤 𝑉∅ 𝑉𝑇
60
30
04-Feb-24
(b) How much field current must be supplied to the generator to make the terminal voltage 480 V at no load?
(c) If the generator is now connected to a load and the load draws 1200 A at 0.8 PF lagging, how much field
current will be required to keep the terminal voltage equal to 480 V?
(d) How much power is the generator now supplying? How much power is supplied to the generator by the prime
mover? What is this machine's overall efficiency?
(e) If the generator's load were suddenly disconnected from the line, what would happen to its terminal voltage?
(j) Finally, suppose that the generator is connected to a load drawing 1200 A at 0.8 PF leading. How much field
current would be required to keep VT at 480 V? 61
62
OCC characteristics of the synchronous generator
31
04-Feb-24
(c) What is the efficiency of this generator (ignoring electrical losses) when it is operating at the rated
current and 0.8 PF lagging?
(d) How much shaft torque must be applied by the prime mover at full load? How large is the induced
torque ?
(e) What is the voltage regulation of this generator at 0.8 PF lagging? At 1.0 PF? At 0.8 PF leading?
63
32
04-Feb-24
• Adjusting the line voltage of the oncoming generator is done by adjusting its field current.
• By using voltmeter, the field current of the oncoming generator should be adjusted until its
terminal voltage becomes equal to the line voltage of the running system.
65
Gen1 Positive phase sequence Gen2 Gen1 Negative phase sequence Gen2
66
33
04-Feb-24
Option 2: use a
small three-phase
induction motor
and observe its
rotation direction
Option 1: use phase
sequence indicator
67
34
04-Feb-24
120𝑓𝑒
𝑛𝑚 =
𝑃
69
70
35
04-Feb-24
71
Frequency-Power characteristics
• All generators are driven by a prime mover, which is the generator's source of mechanical power.
Examples are steam turbine, diesel engines, gas turbines, water turbines, wind turbines, etc...
• All prime movers tend to behave in a similar fashion: The power drawn from them increases, the speed
at which they turn decreases.
36
04-Feb-24
Frequency-Power characteristics
• The speed droop (SD) of a prime mover is defined by the following equation:
𝑛𝑛𝑙 − 𝑛𝑓𝑙
𝑆𝐷 = 𝑥100%
𝑛𝑓𝑙
73
Frequency-Power characteristics
• Since the shaft of the synchronous generator (rotor) is connected to the prime mover, the prime mover
speed defines the electrical frequency output of the generator:
𝑛𝑚 𝑃
𝑓𝑒 =
120
74
37
04-Feb-24
Frequency-Power characteristics
• According to the figure:
𝑃 = 𝑠𝑝 𝑓𝑛𝑙 − 𝑓𝑠𝑦𝑠
75
Q = 𝑚 𝑉𝑇𝑛𝑙 − 𝑉𝑇
38
04-Feb-24
Example:
1000 kW
Figure shows a generator supplying a load. A second load is to
be connected in parallel with the first one. The generator has a
no-load frequency of 61.0 Hz and a slope sp of 1MW/Hz. Load 1
consumes a real power of 1000 kW at 0.8 PF lagging, while
800 kW
Load 2 consumes a real power of 800 kW at 0.707 PF lagging.
77
Solution:
(a) Before the switch is closed, the operating frequency of the system 1000 kW
is found as follows:
𝑃 = 𝑠𝑝 𝑓𝑛𝑙 − 𝑓𝑠𝑦𝑠
1𝑀𝑊
1000 𝑘𝑊 = 61.0 𝐻𝑧 − 𝑓𝑠𝑦𝑠 𝑓𝑠𝑦𝑠 = 60 𝐻𝑧 800 kW
𝐻𝑧
61.0 Hz
60.0 Hz
1000 kW
78
39
04-Feb-24
Solution:
𝑃 = 𝑠𝑝 𝑓𝑛𝑙 − 𝑓𝑠𝑦𝑠
1𝑀𝑊
(1000 𝑘𝑊 + 800 𝑘𝑊) = 61.0 𝐻𝑧 − 𝑓𝑠𝑦𝑠 𝑓𝑠𝑦𝑠 = 59.2 𝐻𝑧
𝐻𝑧
61.0 Hz
60.0 Hz
59.2 Hz 1800 kW
1000 kW
As seen, adding the load decreases the frequency of the system from 60 Hz to 59.2 Hz 79
Solution:
1𝑀𝑊
1800 𝑘𝑊 = 61.8 𝐻𝑧 − 𝑓𝑠𝑦𝑠
𝐻𝑧
60.0 Hz
61.8 𝐻𝑧 − 𝑓𝑠𝑦𝑠 = 1.8 𝐻𝑧 1800 kW
𝑓𝑠𝑦𝑠 = 60.0 𝐻𝑧
80
40
04-Feb-24
81
• The P-f and Q-V characteristics of an infinite bus are shown below.
82
41
04-Feb-24
House diagram
83
Infinite bus
• No-load frequency of the generator should be
slightly greater than the frequency of the infinite
bus. If this is so, the real power drawn by the
generator becomes positive and the synchronous
machine is operating like a generator, supplying
real power 𝑃𝐺 > 0
𝑃𝐺 > 0
84
42
04-Feb-24
Infinite bus
• If no-load frequency of the generator is smaller
than the frequency of the infinite bus, the real
power drawn by the generator becomes negative
and the synchronous machine is operating like a
motor, consuming real power
Infinite bus
• Assume that the generator has been connected to infinite bus and supplying real power of 𝑃𝐺1, what
happens when its governor set-point is increased?
governor set
• If we further increase the governor set-point: point is
increased
𝑓𝑛𝑙3 > 𝑓𝑛𝑙2
𝑃𝐺3 > 𝑃𝐺2
86
43
04-Feb-24
Infinite bus
• Now, what happens to the phasor diagram of the generator if its governor set-point is increased?
• We know that (from previous slide) the real power supplied by the generator increases.
constant
𝐸𝐴 𝑠𝑖𝑛𝛿
𝑃𝑜𝑢𝑡 = 3𝑉∅
𝑋𝑆 constant
constant
Infinite bus
• What happens now, if the output of the generator is further increased so that it exceeds the power consumed by
the load?
𝑃𝐺 > 𝑃𝑙𝑜𝑎𝑑
• If this occurs, the extra power generated by the generator flows back into the infinite bus.
• For example;
𝑃𝑙𝑜𝑎𝑑 = 1000 𝑘𝑊
𝑃𝐺 = 1300 𝑘𝑊
𝑃inf 𝑏𝑢𝑠 𝑃𝑙𝑜𝑎𝑑
𝑃inf 𝑏𝑢𝑠 = −300 𝑘𝑊 (generated)
44
04-Feb-24
Infinite bus
• So far we have seen that what happens to a synchronous generator connected to infinite bus when the governor set-
point is increased?
• Now, the next question will be what happens to a synchronous generator connected to infinite bus if its field current
is increased? (governor set-point is unchanged)
must be constant
must be constant
𝑃𝑜𝑢𝑡 = 3. 𝑉∅ . 𝐼𝐴 . 𝑐𝑜𝑠𝜃
𝐸𝐴 𝑠𝑖𝑛𝛿
𝑃𝑜𝑢𝑡 = 3𝑉∅
constant constant 𝑋𝑆 constant
constant constant
𝑄𝑜𝑢𝑡 = 3. 𝑉∅ . 𝐼𝐴 . 𝑠𝑖𝑛𝜃
constant increases
89
Infinite bus
• In summary, what happens to a synchronous generator connected to infinite bus if its field current is increased?
(governor set-point is unchanged)
➢ The real power output of the generator does not change (since governor set-point is unchanged)
➢ Since real power output of the generator is constant 𝐸𝐴 𝑠𝑖𝑛𝛿 must be constant
➢ Since real power output of the generator is constant 𝐼𝐴 𝑐𝑜𝑠𝜃 must be constant
➢ The magnitude (rms) of the armature current 𝐼𝐴 increases
➢ Since 𝐼𝐴 increases and 𝐼𝐴 𝑐𝑜𝑠𝜃 is constant, then 𝐼𝐴 𝑠𝑖𝑛𝜃 must increase
➢ Since 𝐼𝐴 𝑠𝑖𝑛𝜃 increases, 𝑄𝑜𝑢𝑡 increases as well.
So, as a result:
➢ increasing the field current in a synchronous generator operating in parallel with an infinite bus increases the
reactive power output of the generator
90
45
04-Feb-24
Infinite bus
To summarize;
1) The real and reactive powers supplied by the generator are fixed, and constrained to be equal to the power
demanded by the load
2) The frequency and terminal voltage are varied by the governor set points and the field current,
respectively.
1) The frequency and terminal voltage of the generator are controlled by the system to which it is connected.
2) The governor set points of the generator control the real power supplied by the generator to the system.
3) The field current in the generator controls the reactive power supplied by the generator to the system.
91
46
04-Feb-24
1) Increases the real power supplied by Gen-2, while reducing the real power supplied by Gen-1.
𝑃𝐿𝑜𝑎𝑑 = 𝑃𝐺1 + 𝑃𝐺2
2) Increases overall system frequency.
93
𝑓2 > 𝑓1
1) Increases the reactive power supplied by Gen-2, while reducing the reactive power supplied by Gen-1.
𝑄𝐿𝑜𝑎𝑑 = 𝑄𝐺1 + 𝑄𝐺2
2) Increases system terminal voltage.
94
𝑉𝑇2 > 𝑉𝑇1
47
04-Feb-24
61.5 Hz
𝑃𝐺2
61.0 Hz
Required equations
𝑃𝐿𝑜𝑎𝑑 = 𝑃𝐺1,𝑛𝑒𝑤 + 𝑃𝐺2,𝑛𝑒𝑤 = 3.5 𝑀𝑊 to find 𝑓𝑠𝑦𝑠,𝑛𝑒𝑤
𝑃𝐺1,𝑛𝑒𝑤 = 𝑠𝑝1 𝑓𝑛𝑙1 − 𝑓𝑠𝑦𝑠,𝑛𝑒𝑤 𝑃𝐺1,𝑛𝑒𝑤
𝑓𝑠𝑦𝑠,𝑛𝑒𝑤
𝑃𝐺2,𝑛𝑒𝑤
𝑃𝐺2,𝑛𝑒𝑤 = 𝑠𝑝2 𝑓𝑛𝑙2 − 𝑓𝑠𝑦𝑠,𝑛𝑒𝑤
kW
𝑃𝐺1,𝑛𝑒𝑤 𝑃𝐺2,𝑛𝑒𝑤
96
48
04-Feb-24
𝑃𝐺2
𝑃𝐿𝑜𝑎𝑑 = 𝑃𝐺1,𝑛𝑒𝑤 + 𝑃𝐺2,𝑛𝑒𝑤 = 3.5 𝑀𝑊 Required equations
to find 𝑓𝑠𝑦𝑠,𝑛𝑒𝑤
𝑃𝐺1,𝑛𝑒𝑤 = 𝑠𝑝1 𝑓𝑛𝑙1 − 𝑓𝑠𝑦𝑠,𝑛𝑒𝑤
𝑃𝐺1,𝑛𝑒𝑤
𝑃𝐺2,𝑛𝑒𝑤 = 𝑠𝑝2 𝑓𝑛𝑙2,𝑛𝑒𝑤 − 𝑓𝑠𝑦𝑠,𝑛𝑒𝑤 𝑃𝐺2,𝑛𝑒𝑤
97
• The solution is
• To decrease the governor set point of the other generator so as to keep the system frequency constant
𝑃𝐿𝑜𝑎𝑑 = 𝑃1 + 𝑃2 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝑃𝐿𝑜𝑎𝑑 = 𝑃1 ′ + 𝑃2 ′ = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝑃2′ > 𝑃2
𝑃1′ < 𝑃1
98
49
04-Feb-24
• The solution is
• To decrease the field current of the other generator so as to keep the system voltage constant
𝑄𝐿𝑜𝑎𝑑 = 𝑄1 + 𝑄2 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝑄𝐿𝑜𝑎𝑑 = 𝑄1 ′ + 𝑄2 ′ = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝑄2′ > 𝑄2
𝑄1′ < 𝑄1
99
• To adjust 𝑓𝑠𝑦𝑠 without changing the real power sharing of the generators, simultaneously increase or decrease
both generators' governor set points.
• To adjust 𝑉𝑇 without changing the reactive power sharing of the generators, simultaneously increase or
decrease both generators' field currents
100
50
04-Feb-24
101
120𝑓𝑒
𝑛𝑚 =
𝑃
𝐸𝐴 = 𝐾∅w
𝐸𝐴 = 𝐾∅2π𝑓
𝑤 = 2𝜋𝑓
• The answer is Yes. But we have to derate (reduce) the voltage rating of the generator.
• Otherwise in order to get the same voltage, we need more flux. That can cause saturation of the machine.
102
51
04-Feb-24
0 ≤ 𝐼𝐴 ≤ 𝐼𝐴(𝑚𝑎𝑥)
• This current limit defines apparent power rating of the generator. That is;
0 ≤ 𝑰𝑭 ≤ 𝑰𝑭(𝒎𝒂𝒙)
103
52
04-Feb-24
• Since;
𝛽 = 90° − 𝜃
• We assume that;
➢ Phase voltage of the generator (𝑉∅ ) is constant (generator is connected to infinite bus)
➢ Armature resistance 𝑅𝐴 is ignored
➢ Power factor of the load is lagging
106
53
04-Feb-24
𝑋𝑠 𝐼𝐴 𝑐𝑜𝑠𝜃
𝑋𝑠 𝐼𝐴 𝑠𝑖𝑛𝜃
3𝑉∅
𝑋𝑠 𝐼𝐴 𝑐𝑜𝑠𝜃 x 𝑃 = 3𝑉∅ 𝐼𝐴 𝑐𝑜𝑠𝜃
𝑋𝑠
107
3𝐸𝐴𝑉∅
Radius =
𝑋𝑆
108
54
04-Feb-24
109
(a) Sketch the capability curve for this generator, including the prime-mover power limit.
(b) Can this generator supply a line current of 56A at 0.7 PF lagging? Why or why not?
(c) What is the maximum amount of reactive power that this generator can produce?
(d) If the generator supplies 30 kW of real power, what is the maximum amount of reactive power that can be
simultaneously supplied? (Hint: Use circle equation)
110
55
04-Feb-24
480
𝑉∅ = = 277 𝑉
3
𝑆𝑟𝑎𝑡𝑒𝑑 50𝑘𝑉𝐴
𝐼𝐴(𝑚𝑎𝑥) = = = 60 𝐴
3𝑉∅ 3(277𝑉)
111
3𝐸𝐴𝑉∅
Radius =
𝑋𝑆
3𝐸𝐴 𝑉∅ (3)(317)(277)
= = = 263.427 𝑘𝑉𝐴
𝑋𝑆 1
3𝑉∅ 2
=− = −230.187 kVAR
𝑋𝑆 112
56
04-Feb-24
3𝐸𝐴𝑉∅
Radius =
𝑋𝑆
3𝐸𝐴 𝑉∅ (3)(317)(277)
= = = 263 𝑘𝑉𝐴
𝑋𝑆 1
3𝑉∅ 2
=− = −230. kVAR
𝑋𝑆 113
3𝐸𝐴𝑉∅
Radius =
𝑋𝑆
3𝐸𝐴 𝑉∅ (3)(317)(277)
= = = 263 𝑘𝑉𝐴
𝑋𝑆 1
3𝑉∅ 2
=− = −230 kVAR
𝑋𝑆 114
57
04-Feb-24
END OF CHAPTER 2
SYNCHRONOUS GENERATORS
115
58