Product Kevin) (Compatibility Mode)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 47

Emerson Network Power DC PowerProduct Introduction

Presentation Contents
DC Products
Mini Power Systems Small Power Systems Medium Power Systems Large Power Systems 19-inch Subrack Power S t 19 i h S b k P Systems Advanced Controller Features

DC Products Mini P Mi i Power Systems S t

Mini Power Systems


GIE 19 system
System Type GIE4815/3A/2.55KW GIE4815/2A/1.7KW GIE4815/2A/1.6KW GIE4805/2A-2 Height 2U 2U 1U 1U Weight 10 kg 17 kg 8 kg 6,5 kg Rectifier Module # of rectifiers Power output 850W, 850W, 800W, 300W, 3 2 2 2 2,6 kW 1,7 kW 1,6 kW 600 W

NetSure system
System Type Actura 48201 Height Weight Rectifier Module # of rectifiers Power output 2U 15kg 800W 3 2,4kW( 2 4kW( can reach up to 4,8kW)

GIE4815/3A/2.55KW
Rectifier: 850W, fan cooled Performance: Dimensions: 132.5(H)x482.6(W)x350(D) mm Capacity:2.55 kW / 3 rectifiers Configuration: - DC distribution branch: 1*50A MCB 2*20A MCB 1*10A MCB BAT 1*63A MCB

GIE4815/2A/1.7KW
Rectifier: 850W, fan cooled Performance: Dimensions: 88.1(H)482.6(W)341(D) mm Capacity: 1.7 kW / 2 rectifiers Configuration: - DC distribution branch: 2*20A Fuse 1*10A Fuse 2 5A 2*5A Fuse BAT 1*50A MCB

GIE4815/2A/1.6KW
Rectifier: 800W, fan cooled Performance: Dimensions: 45.6(H)482.6(W)325(D) mm Capacity:1.6 kW / 2 rectifiers Configuration: - DC distribution branch: 1*10A Fuse 1 20A 1*20A Fuse BAT 1*20A Fuse

GIE4805/2A/500-2
Rectifier: 300W, fan cooled Performance: Dimensions: 41.6(H)x482.6(W)x325(D) mm Capacity: 600 W / 2 rectifiers Configuration: - DC distribution branch: 2*10A Fuse BAT 1*10A Fuse 1 10A

NetSure 201 A60 (formerly known as ACTURA Flex 48201)


Rectifier: 800W, fan cooled Performance: Dimensions: Single subrack: 88.1(H)x482.6(W)x341(D) mm Single subrack :176 2(H)x482 6(W)x341(D) mm :176.2(H)x482.6(W)x341(D) Capacity: Single subrack: 2.4 kW / 3 rectifiers Dual subrack: 4.8 kW / 6 rectifiers Configuration: - DC distribution branch: Single subrack:6 MCB( 16~63A ) Dual subrack: 12 MCB( 16 63A ) 16~63A

DC Products Small P S ll Power Systems S t

Small Power Systems


System Type PS48120/1800 PS48300/1800 PS48300-3B/2900 Actura 48420 Actura 48330 Actura 48200 Height 2m 1.6m 1.6m 2m 2m 1.6m 4 banks 4 banks 2 banks Integrate rack 3banks BAT Rectifier Module R48-1800A R48-1800A R48-2900U R48-1800 R48-3200 R48-3200 # of rectifiers 4 10 6 12 5 3 Power output 6,96kW 17,4 kW 17,4 kW 20,88 kW 16kW 9,6k W

11

PS48120/1800
Rectifier: R48-1800A Controller: M500D Performance: Dimensions: 2000(H)600(W)600(D) mm Capacity:7.2 kW / 4 rectifiers Space for 3 strings of 12V FT battery Configuration: Single phase AC input,63A/2P 2, Battery 2100A NT00 Fuse 7 DC distribution branches: 163A/1PMCB)232A/1PMCB), 110A/1PMCB)1100A NT00FUSE), 150A NT00 (FUSE)16A NT00FUSE

12

PS48300/1800-X1
Rectifier: R48-1800A Controller: M500D Performance: Dimensions: 1600(H)x600(W)x600(D) mm Capacity: 18 kW / 10 rectifiers Configuration: 3 phase AC input, 100A/3P2 Battery 2250A NT00 Fuse 12 DC distribution branches: LLVD:100A 5(Fuse), 63A/1P 1(MCB) BLVD: 63A/1P 2, 32A/1P 2, 10A/1P 2(MCB)

13

PS48300-3B/2900-X1
Rectifier: R48-2900U Controller: M500S Performance: Dimensions: 1600(H)x600(W)x400(D) mm Capacity: 17.4 kW / 6 rectifiers Configuration: 3 phase AC input, 100A/3P Battery 2250A NT00 Fuse 12 DC distribution branches: LLVD:100A 5(Fuse) 63A/1P 1(MCB) 5(Fuse), BLVD: 63A/1P 2, 32A/1P 2, 10A/1P 2(MCB)

14

PS48300-3B/2900-W6
Rectifier: R48-2900U Controller: M500S Performance: Dimensions: 800(H)x600(W)x400(D) mm Capacity: 17.4 kW / 6 rectifiers Configuration: 3 phase AC input, 63A/3P Battery 2160A NT00 Fuse 17 DC distribution branches: BLVD: 10A/1P 4 16A/1P 5 40A/1P 8(MCB) 4, 5,

15

NetSure 501 AC0 (formerly known as ACTURA Flex 48420)


Product characteristic System: NetSure 501 AC0 Rectifier: R48-1800 Controller: M501D, M800D EMC: class B Safety: EN60950 . Dimension: 2000(H)*600(W)*600(D) mm 2000(H)*600(W)*400(D) mm 1800(H)*600(W)*600(D) mm Up to 20.4kW and 720Ah in one cabinet, can be mounted against wall and with cabinets on either side, configurable number of distribution/battery circuit breakers, various AC options with/without SPD and AC breakers.

16

NetSure 701 A30 (formerly known as ACTURA Optima 48200)


Product characteristic S t System: NetSure 701 A30 N tS Rectifier: R48-3200, R48-2900 Controller :M501D, M800D EMC: class B Safety: EN60950 . Dimension: 1600(H) 600(W) 600(D) 1600(H)*600(W)*600(D) mm Low cost open frame battery rack, provides up to 9.6kw one rack together with up to 360AH of batteries. Front access and top cabling design for installation and maintenance AC input optional maintenance, optional.

17

NetSure 701 A50 (formerly known as ACTURA Flex 48330)


Product characteristic S t System: NetSure 701 A50 N tS Rectifier: R48-3200, R48-2900 Controller: M501D, M800D EMC: class B Safety: EN60950 . Dimension: 2000(H)*600(W)*600(D) mm ( ) ( ) ( ) 2000(H)*600(W)*400(D) mm 700(H)*600(W)*600(D) mm Provides up to 14.5kw in one rack together with up to 720AH of batteries.Front access and top cabling design for installation and maintenance, AC input optional.

18

DC Products Medium Power Systems M di P S t

Medium Power Systems


System Type PS48600-3/2900 Height Integrate BAT rack Rectifier Module # of rectifiers Power output 2m No No R48-2900U R48-2900U 12 12 34,8kW 34,8 kW

PS48600-3B/2900 1.6m

20

PS48600-3/2900
Product characteristic S t System: PS48600-3/2900 PS48600 3/2900 Rectifier: R48-2900U Controller: M500F EMC: class A Safety: EN60950 . Dimension: 2000(H) 600(W) 600(D) 2000(H)*600(W)*600(D) mm Provides up to 34.8kw in one cabinet,applicable to single or three phase AC input. Front access and top cabling design for installation and maintenance.

21

PS48600-3B/2900

Product characteristic System: PS48600-3B/2900 Rectifier: R48-2900U Controller: M500S EMC: class A Safety: EN60950 . Dimension: 1600(H)*600(W)*400(D) mm

22

DC Products Large Power Systems L P S t

Large Power Systems


NETSURE 801 AG0 PS481600/5800 S / 2350*600*600 * * 270kg Rectifer cabinet f 16 Nos. rectifier f 1 battery unit and 2 HOD or 2 LOD or 1Fuse unit 1 battery unit and 6 HOD or 6 LOD or 3Fuse unit 1 battery unit and 6 HOD or 6 LOD or 3Fuse unit

PD482000DD

2350*600*600

260kg

DC distribution cabinet, bottom cabling

2000A DC

PD482000DU

2350*600*600

260kg

DC distribution cabinet, top 2000A DC cabling Rectifer moudle Controller 5800W

R48-5800 M800D

88*244*372 88*244*161

7,8kg 2kg g

24

NetSure 801 AG0


System Output Capacity: 278.4 kW or 5800 A

Rectifier Cabinet Output Capacity: 92.8 kW or 1930 A Distribution Cabinet Rating: Input Voltage: Output V lt O t t Voltage: Temperature Range: Relative Humidity: 96 kW or 2000 A

260 530 VAC 50/60 Hz/3 Phase -48VDC 48V -5C to +45C 0% to 95%

25

Large Power Systems Rectifier Cabinet


Dimension: 2350(H) x 600(W) x 600(D) ( ) ( ) ( ) Up to 16 pcs R48-5800 rectifiers Each rectifier outputs 5.8 kW Provides up to 92.8 kW per cabinet ACU (M800D) as standard equipment Battery distribution Unit as standard equipment Fuse Unit, LOD HOD as optional F U it LOD, ti l config

26

NetSure 801 AG0 Distribution Cabinet


Dimension: 2350(H) x 600(W) x 600(D) Battery distribution Unit as standard equipment Fuse Unit, LOD, HOD as optional config

27

NetSure 801 CA

28

NetSure 801 CA

Rack 1000-6 -Dimension: 2000(H) x 600(W) x 600(D) -Capacity:Up to 58KW/10 rectifier

Rack 2000-6 -Dimension: 2000(H) x 600(W) x 600(D) Dimension: -Capacity:Up to 101.6KW/20 rectifier

29

NetSure 801 CA

DC Distribution Cabinet

30

DC Products 19 i h S b k Power Systems inch Subrack P S t

19 Inch Subrack Power Systems

NetSure 501A50

NetSure 701A51

NetSure 501AA0

32

NetSure 501 A50


High power and battery density Up to 8.5kW 19 , 6U sub-rack, Front Access Can be mounted in 19 inch cabinet High flexibility and wide variety of ordering options Output power, system: 1.7 8.5kW Standard or advanced controller Configurable number of distribution circuit breakers, and sizes Configurable number of battery circuit breakers, and sizes With or without Priority and Non-Priority Low Voltage Non Priority Disconnect Various AC options with/without SPD Battery rack available Base on Global Building Block (Rectifier and Controller) Utilizes UL approved rectifier R48-1800 Hot pluggable rectifier and controller (ACU or SCU) Wide operating range Input voltage range (85-300Vac) I Input temperature range (-5 t +55C) tt t ( 5 to 55C)

NetSure 501A50

33

NetSure 501 A50


System Layout

Positive terminals

Load MCB AC input MCB

Battery MCB

Monitoring module

Rectifier

Dummy plate

34

NetSure 501 AA0


High power and battery density Up to 17.0kW 19 11U High sub-rack, Front Access Can be mounted in 19 inch cabinet High flexibility and wide variety of ordering options Output power, system: 1.7 17.0kW Standard or advanced controller Configurable number of distribution circuit breakers, and sizes Configurable number of battery circuit breakers, and sizes With or without Priority and Non-Priority Low Voltage Non Priority Disconnect Various AC options with/without SPD Battery rack available Base on Global Building Block (Rectifier and Controller) Utilizes UL approved rectifier R48-1800 Hot pluggable rectifier and controller (ACU or SCU) Wide operating range Input voltage range (85-300Vac) I Input temperature range (-5 t +55C) tt t ( 5 to 55C)

NetSure 501AA0

35

NetSure 501 AA0


System Layout

Positive terminals Load MCB Load MCB Positive terminals Battery MCB

AC input MCB

Monitoring module

Rectifier Dummy plate

36

NetSure 701 A51


High power and battery density Up to 16kW 19 10 U High sub-rack, Front Access Can be mounted in 19 inch cabinet High flexibility and wide variety of ordering options Output power, system: 3.2 16kW Standard or advanced controller Configurable number of distribution circuit breakers, and sizes Configurable number of battery circuit breakers, and sizes With or without Priority and Non-Priority Low Voltage Non Priority Disconnect Various AC options with/without SPD Battery rack available Base on Global Building Block (Rectifier and Controller) Utilizes UL approved rectifier R48-3200 Hot pluggable rectifier and controller (ACU or SCU) Wide operating range Input voltage range (85-290Vac) I Input temperature range (-5 t +55C) tt t ( 5 to 55C)

NetSure 701A51

37

NetSure 701 A51


System Layout

Positive terminals Load MCB Load MCB Positive terminals Battery MCB

AC input MCB

Monitoring module

Rectifier

Dummy plate

38

NetSure 701 A51


Battery Rack 4L Layers rack k

3 Layers rack 2L Layers rack k

750mm(H)*600mm(W)*600mm(D)

1200mm(H)*600mm(W)*600mm(D)

1500mm(H)*600mm(W)*600mm(D)

39

DC Products Advanced Controller Features Ad d C t ll F t

ACU - Energy Saving and Rectifier Redundancy


The function maintains a configured redundancy level by switching on/off rectifiers depending on the actual load on the system. This increases the individual switched on rectifier efficiency. Periodical cycling of the switched on/off rectifiers will increase rectifiers life.

ON 20%

ON 20%

ON 20%

ON 20%

ON 20%

Normal F N l Function ti

ON 50%

ON 50%

OFF 0%

OFF 20%

OFF 20%

OFF 0%

OFF 0%

ON 50%

ON 50%

OFF 0%

Feature Activated

41

ACU - Energy Saving and Rectifier Redundancy

Load Share
30

Average efficiency 88.5

30

30

Working Standby Energy Saving

Standby

Average efficiency 90

90

Energy SavingAverage efficiency 92.3% (Turn off) (T ff)


42

90

ACU - Energy Saving and Rectifier Redundancy


Case Study
System with R48 2900 Modules R48-2900 Site 1: 3 modules, Load is 12A/53.5V Site 2: 5 modules, Load is 19A /53.5V

90 61 32.2 28.4
Unit: kWh/ Day
Before energy saving After energy saving

Site 1

Site 2

Due to use energy saving program, Site 1 saves 12%, site 2 saves 32%
43

ACU - PowerSplit Function


Allows extension of legacy DC power supply and battery backup.

-48V

500A

1000A

Battery

Battery

NetSure 801 Msater System

Legacy Slave System

44

ACU - PowerSplit Function


Low load condition As long as the Slave Power output is lower than the Current Limit Set Value, Slave Power shall feed the whole load.

Normal load condition When the load of the system exceeds Slave Powers the Current Limit Set Value, Master Power shall start to take load.

High load condition When Master Power reaches it maximum output power, system voltage will decrease as the load increases (overload situation for Master Power).

Over load condition When the load is higher than the sum of the master and the slave maximum power. The master and the slave and the battery shall feed the load.

45

ACU - PowerSplit Function

46

ACU -SM support


Allows adding SM modules (supervision modules) to the M800D. There are three different SM modules SM BAT for battery supervision y p
SM IO for generic supervision SM AC for mains and generator supervision

SM modules are optional add-on items

NetSure 801
M800D CAN SM BAT SM IO SM AC

RS485

R1 R2 RN

47

You might also like