ComfortPoint™ Open

CPO-PC410 PLANT CONTROLLER

PRODUCT DATA

Trademark Information • Ring LED to show the operational status of the


ComfortPoint™ Open is a trademark of Honeywell controller.
International Inc.
• Internal Ethernet switch with two external ports and
BACnet® is a registered trademark of ASHRAE Inc. status LEDs to allow quick connection of local
Ethernet-based tools, remote IO, or additional IP
Disclaimer based controllers and devices to reduce the number
All images used in this document are for illustrative of IP drops.
purposes only and may not match the actual product. • An MMI interface to connect with the CPO-MMI
device which helps to monitor and manage the
controller data.
• Four RS485 interfaces to support Panel bus, BACnet
MS/TP, Field Bus, Modbus, M-Bus, CP-IO protocols,
and C-Bus global data sharing.
• Dual Core Processor to isolate BACnet IP network
communications from DDC application and device
communications.
• Built-in advanced diagnostics software facilitating
troubleshooting.
• FRAM to store the live data for the controller
including storing last known values when power is
removed.
• DDR3L for Random Access Memory to achieve twice
APPLICATION the rate of data transfer with low power consumption.
• EMMC for program storage and boot flash memory.
CPO-PC410 is an advanced and advanced plant controller
of the ComfortPoint™ Open (CPO) Plant Controller • BACnet Trending with Backfill and storage up to 1M
platform. It is an Ethernet-based, freely programmable, data samples.
and native BACnet® Building Controller (B-BC). • UTF-8 and UCS-2 character encoding formats are
supported.
CPO-PC410 is designed for a wide variety of complex
applications. This device features numerous RS485 • Supports Peer-to-Peer communication.
communication interfaces, two standard Ethernet • A reset button to restore the factory default settings.
interfaces, an MMI interface, and two USB interfaces.
• Removable screw-type terminal block.
CPO-PC410 can be mounted on either a DIN rail or remote
mounted in a horizontal or vertical position. • Built-in Webserver with HTML5 graphics support.
• Watchdog relay to enhance system reliability and
safety.
FEATURES • A micro USB and USB Type A ports to quickly connect
with a laptop and mobile/tablet devices.
• Conforms to BACnet Standard 135 protocol version
1.14 (ISO 16484-5). NOTE: The USB Type A port is only available for use with
• Three pairs of LEDs indicating the transmission and a future firmware release.
reception (respectively) of data via the RS485
interfaces 1,2, and 3.
CPO-PC410 PLANT CONTROLLER

INTERFACES AND TERMINALS

4 3 2 13 1

10
9 6 8
11

12

7 5

Table 1. Controller Terminals Table 1. Controller Terminals (Continued)

Type Legend Signal Comment Type Legend Signal Comment

Connect to earth (+) for RS485


RS485 Interface 1

FGND CH1+
ground in the field interface 1
Power Supply
Terminals

Terminals

Power supply (-) for RS485


1 24V0 4 CH1-
common interface 1

Power supply (24 GND1 RS485


24V~ GND1
Vac/dc) interface 1

(+) for RS485 Tx1 LED


RS485 Interface 3

CH3+
interface 3 (green)
Terminals

(-) for RS485 Rx1 LED


2 CH3-
interface 3 (green)

GND3 for RS485 Tx2 LED


GND3 Transmit and receive
interface 3 (green)
an indication for
LED

5
Rx2 LED RS485 interfaces 1
(+) for RS485
RS485 Interface 2

CH2+ to 3
interface 2 (green)
Terminals

(-) for RS485 Tx3 LED


3 CH2-
interface 2 (green)

GND2 for RS485 Rx3 LED


GND2 (green)
interface 2

Indicates the
LED

6 Ring LED operational status of


the controller

EN0B-0077 IE10 R0220


Part Number: 39-00017-01 2
CPO-PC410 PLANT CONTROLLER

Table 1. Controller Terminals (Continued) Tx LED and Rx LED


Type Legend Signal Comment CPO-PC410 is equipped with three Tx LEDs and three
corresponding Rx LEDs. These LEDs indicate the
Ethernet 1 transmission and reception of data by the three RS485
Interface

interfaces.
RJ45

7 10/100 base-T/TX
Ethernet 2 Table 2. Behavior and meaning of RS485 LEDs
LED Status Description
~ (24V~) Accessory power
No communication over the given
supply output (24 OFF
RS485 interface.
Vac/dc)
Transmit data over the given RS485
Tx ON
0 (24V0) Accessory power interface.
supply output Receive data over the given RS485
RS485 Interface 4

common Rx ON
interface.
Terminals

FGND Connect to earth


8 ground in the field Interfaces and Bus Connections
GND GND RS485 Via its various interfaces and bus connections, CPO-
interface 4 PC410 can be connected to a variety of devices and
systems.
- (CH4-) (-) for RS485
interface 4 Ethernet 1 and 2 Interfaces
+ (CH4+) (+) for RS485 The two Ethernet interfaces 1 and 2 are internally
interface 4 connected to a single Ethernet switch.

(+) for Both Ethernet 1 and 2 can connect the controller with a
RS485 laptop/PC using Ethernet crossover cable. The user can
interface 5 upload, download, and debug the controller application
MMI interface for using ComfortPoint™ Open Studio from the laptop/PC.
(-) for power supply(5 Vdc) This connection also establishes Internet connectivity.
Interface
RJ11

RS485 to MMI device, and


9 CPO-PC410 can be operated via a standard browser. By
interface 5 RS485 interface for
communication with default, an integrated web-server provides all operation
output MMI. pages for full browser-based operation. While browsing,
5Vdc the controller can remain connected in the Ethernet
network without interruption.
GND
USB Interfaces
Micro USB Temporary CPO-PC410 is built with USB ports that support USB 2.0.
10
port connection for
Interface

laptops, tablets, and


USB

Table 3. USB Interfaces


USB Type mobiles. For
11 programming and
A port USB Port Types Purpose
temporary use only.
Micro USB To connect with laptops and
Reset button to reset
Button

mobile/tablet devices by using a


Reset

12 the device to factory USB cable for monitoring and


default troubleshooting the controller.

Open - Normal USB Type A This option is only available for use
operation.
Closed - Failed due with a future firmware release.
NC to:
• No power to unit,
or
Watchdog

• Controller failure.
Relay

13
COM Common

Closed - Normal
operation.
Open - Failed due to:
NO
• No power to unit,
or
• Controller failure.

3 EN0B-0077 IE10 R0220


Part Number: 39-00017-01
CPO-PC410 PLANT CONTROLLER

TECHNICAL DATA Current Consumption


Table 7. Current Consumption
Hardware Specifications
Power
Table 4. Hardware Specifications Controller
24 VAC 24 VDC
Feature Specifications
CPO-PC410 500 mA 500 mA
FRAM 768 KBytes
CPO-PC410 and 800 mA 800 mA
DDR3L 1 GByte CPO-MMI

EMMC 4 GBytes CPO-PC410 w/ 2.1A 2.6 A 2.6 A


Accessory Load
CPU Dual core: Arm Cortex-A9
Frequency: 800 MHz
Arm Cortex-M4 Frequency: Standards
227MHz
Table 8. Standards
Operating System LINUX/RTOS

Real-Time Clock +/- 5 ppm: +/- 2.63 minutes per Protection IP20
Timekeeping year (+/- 0.43 seconds per day) Class
Accuracy
Product UL60730-1, UL60730-2-9, UL916,
Real-Time Clock Buffered for 72 hours by gold Standards EN60730-1, EN60730-2-9,
Retention capacitor CAN/CSA-E60730-1:02

Testing IEC68
Electrical
System Data Components

Table 5. System Data Certification cUL60730-1, UL916, CE, BTL B-BC,


BACnet Standard 135 version 1.14,
Operating ISO 16484-5, FCC Part15, Subpart B,
19 to 29 Vac (50/60Hz)
Voltage (AC) CAN ICES-3 (B)/NMB-3(B), BQB,
RCM, AMEV AS-B, KBOB, EAC, RoHS
Operating II, Ethernet Protocol version IEEEC
19 to 29 Vdc
Voltage (DC) 802.3, EN-1434-3, EN-13757-3,
UUKL, and Class III equipment per
Overvoltage Protected against overvoltages of
IEC 61140.
Protection max. 29 Vac or 40 Vdc. Terminals
protected against short-circuiting. System The system transformer(s) must be
Transformer safety isolating transformers
according to IEC 61558-2-6. In the
Power Consumption U.S.A. and Canada, NEC Class 2
transformers must be used.
Table 6. Power Consumption

Power
Controller
24 Vac 24 Vdc

CPO-PC410 Max. 12 VA Max. 12 W

CPO-PC410 and Max. 15 VA Max. 15 W


CPO-MMI

CPO-PC410 w/ 2.1A Max. 65 VA Max. 65 W


Accessory Load

EN0B-0077 IE10 R0220


Part Number: 39-00017-01 4
CPO-PC410 PLANT CONTROLLER

Operating Environment Connection to Buses


Table 9. Operating Environment Table 11. Connection to Buses

Ambient 0 to 50 °C (32 to 122 °F)

RS485-1

RS485-2

RS485-3

RS485-4
Max. No. of
Operating Protocols Devices per
Temperature Channel

Ambient 5 to 95% relative humidity (non-


Operating condensing) Panel Bus 16 Yes Yes Yes Yes
Humidity
CP-IO Bus 16 No No No Yes
Storage -28.9 to +70 °C (-20 to 158 °F)
Temperature Field Bus 31 Yes Yes Yes No

Ambient 5 to 95% relative humidity (non- MSTP 30 Yes Yes Yes No


Storage condensing)
Humidity Modbus 30 Yes Yes Yes No

Vibration 0.024” double amplitude (2 to 30 Hz), M-Bus**


60 Yes** Yes** Yes** No
Under 0.6 g (30 to 300 Hz)
Operation
C-Bus* 30 Yes* Yes* Yes* No
Dust, Vibration According to EN60730-1
NOTES:
RFI, EMI Residential, commercial, and light- — The communication rate across each commu-
industrial environments nication interface is dependent upon the given
communication protocol.
MTBF (Mean 11.5 years
— *Not more than one channel can be configured
Time Between
as C-Bus channel.
Failure)
— **Not more than one channel can be configured
as M-Bus channel.
— **The CPO-PC410 controller can function as an
Controller Parameters M-Bus Master. It uses a standard level con-
verter (e.g. PW60) to connect to the M-Bus
Table 10. Controller Parameters devices.

Parameters Max. Number


Communication Baud Rates
Hardware Points
(AI, AO, BI, BO, MI, 500 Table 12. Communication Baud Rates
MO, ACC)
Ethernet 10/100 Mbit/s, RJ45
Software Points
1500
(AV, BV, MV, AF, BF) BACnet MSTP 9.6, 19.2, 38.4, 76.8, 115.2 Kbps
Time Schedules 100 Modbus RTU 0.3 to 115.2 Kbps
Calendar Objects 100 Panel Bus 115.2 Kbps
Control Loops 64 CP-IO Bus 56.7 Kbps
Loop Objects 60 C-Bus 9.6, 38.4, and 76.8 Kbps
Trend Objects 500 M-Bus 0.3 to 19.2 Kbps
Event Enrollment Objects 500 Field Bus 38.4 Kbps
Event Log Object 1 MMI Port 5 Vdc power output and RS485
Event Log Object Associated
70000
Records

Point Name Characters 64

Description Characters 95

5 EN0B-0077 IE10 R0220


Part Number: 39-00017-01
CPO-PC410 PLANT CONTROLLER

Controller Part Numbers


Table 13. Controller

Part Number Description

CPO-PC410 CPO Controller

CPO-PC410-MMIDN CPO Controller including MMI with DIN Rail Base

CPO-PC410-MMIWL CPO Controller including MMI with Panel Door/Wall Base

Accessories Part Numbers


Table 14. Accessories

Part Number Description

CPO-MMI-DN MMI with DIN Rail Base

CPO-MMI-WL MMI with Panel Door/Wall Base

Replacement Terminal Covers (Small)


CPO-PC-TCVR
(Pack Quantity of 4)

Extended Terminal Covers (Large)


CPO-PC-EXT-TCVR
(Pack Quantity of 4)

CPO-MMI-ACCDN DIN Rail Base Accessory for CPO MMI

CPO-MMI-ACCWL Panel Door/Wall Base Accessory for CPO MMI

EN0B-0077 IE10 R0220


Part Number: 39-00017-01 6
CPO-PC410 PLANT CONTROLLER

DIMENSIONS
CPO-PC41O

145.8
135

~0
45

GND FGND
110

-
+

52

59

*ALL DIMENSIONS ARE IN MM

7 EN0B-0077 IE10 R0220


Part Number: 39-00017-01
CPO-PC410 PLANT CONTROLLER

GENERAL SAFETY Safety Information as per EN60730-1


INFORMATION The ComfortPoint™ Open System is intended for
residential, commercial, and light-industrial environments.

• When performing any work (installation, mounting, The ComfortPoint™ Open System is an independently
start-up), all manufacturer instructions and in mounted electronic control system with fixed wiring.
particular the Installation and Commissioning
Instructions (EN1B-0077IE10) are to be observed. The CPO-PC410 is suitable for mounting in fuse boxes
• The ComfortPoint™ Open System (including the CPO- conforming with standard DIN43880, and having a slot
PC410 Plant Controller, Panel Bus I/O modules, manual height of max. 45 mm.
disconnect modules, and the auxiliary terminal
packages) may be installed and mounted only by It is suitable for panel rail mounting on 35 mm standard
authorized and trained personnel. panel rail (both horizontal and vertical rail mounting
• Rules regarding electrostatic discharge should be possible).
followed. The CPO-PC410 is used for the purpose of building HVAC
• If the ComfortPoint™ Open System is modified in any control and is suitable for use only in non-safety controls
way, except by the manufacturer, all warranties for installation on or in appliances.
concerning operation and safety are invalidated.
• Make sure that the local standards and regulations are
Table 15. Safety Information as per EN60730-1
observed at all times. Examples of such regulations are
VDE 0800 and VDE 0100 or EN 60204-1 for earth
grounding. Electric Shock PELV
• Use only accessory equipment that comes from or has Protection
been approved by Honeywell.
Pollution Degree Pollution Degree 2, suitable for use
• It is recommended that devices be kept at room
in industrial environments.
temperature for at least 24 hours before applying power.
This is to allow any condensation resulting from low Installation Class 3
shipping/storage temperatures to evaporate.
• The ComfortPoint™ Open System must be installed in a Overvoltage 24 V-powered controls: Category I
manner (e.g., in a lockable cabinet) ensuring that Category
uncertified persons have no access to the terminals.
• Investigated according to United States Standard UL- Rated Impulse 330 Vac for Category I (SELV)
60730-1, UL-916, and UL60730-2-9. Voltage
• Investigated according to Canadian National
Standard(s) C22.2, No. 205-M1983 (CNL-listed). Automatic Type 1.C (micro interruption for the
• Do not open the CPO-PC410, as it contains no user- Action relay outputs)
serviceable parts inside!
• CE declarations according to LVD Directive Software Class Class A
2014/35/EU and EMC Directive 2014/30/EU.
• Product standards are EN 60730-1 and EN 60730-2-9. Enclosure IP20 according to EN-60529
• The CPO-PC410 smoke control system is a Non-
Dedicated system. Ball-pressure >75 °C for all housing and plastic
• The smoke-control system shall not activate an Test parts
automatic smoke-control sequence as a result of a Temperature >125 °C in the case of devices
signal input generated by the activation of a manual fire applied with voltage-carrying parts,
alarm pull station. connectors, and terminals.

Electromagnetic Tested at 230 Vac, with the


Interference modules in normal condition.

System Europe: safety isolating


Transformer transformers according to
IEC61558-2-6
U.S.A. and Canada: NEC Class-2
transformers

EN0B-0077 IE10 R0220


Part Number: 39-00017-01 8
CPO-PC410 PLANT CONTROLLER

9 EN0B-0077 IE10 R0220


Part Number: 39-00017-01
CPO-PC410 PLANT CONTROLLER

Honeywell Building Solutions


Honeywell International Inc.
1985 Douglas Drive North
® U.S. Registered Trademark
Golden Valley, MN 55422 © 2019 Honeywell International Inc.
EN0B-0077 IE10 R0220
customer.honeywell.com Part Number: 39-00017-01