Section 4 Economic Dispatch
Section 4 Economic Dispatch
University
Dr.Audih 0
0
Part 4
Dr.Audih 2
2
INTRODUCTION
In power generation our main aim is to
generate the required amount of power
with minimum cost and losses.
Economic load dispatch means that the
generator’s real and reactive power are
allowed to vary within certain limits so as
to meet a particular load demand with
minimum fuel cost
This allocation of loads are based on
some constraints.
Dr.Audih 3
3
DIFFERENT CONSTRAINTS IN ECONOMIC
LOAD DISPATCH
▪ Voltage constraints
Vmin ≤ V ≤ Vmax ,
δmin ≤ δ ≤ δmax
▪ Generator constraints
KVA loading of generator should not exceed
Pmin ≤ Pg ≤ Pmax
Qmin ≤ Qg ≤ Qmax
▪ Transmission Line Constraints
Flow of power through transmission line should
be less than its thermal capacity
Current thermal capacity Current loads
Dr.Audih 4
4
Basic Gas Turbine
Dr.Audih 9
9
Generator Cost Curves
⚫ Electrical power generation costs are based on the fuel
cost .
⚫ Generator costs are typically represented by different
curves
–fuel-cost curve (relation between fuel input as Btu/h and power output).
–heat-rate curve (relation between fuel cost $/h and power output).
–incremental cost curve (relation between cost of MWh and power output).
⚫ For reference
- 1 Btu (British thermal unit) = 1054 Joule
- 1 MBtu = 1x106 Btu
- 1 MBtu = 0.293 MWh
- 3.41 Mbtu = 1 MWh
Cost
fi ,
$/h
In all practical cases, the fuel cost curves of generator not smooth
and can be represented as a quadratic function of real power
generation Dr.Audih 11
11
A quadratic function of fuel cost
The curves can usually be adequately approximated
using a quadratic function for the generator the a
quadratic function for fuel cost of generator $/h can be
formulated as:
2
f i ( P ) = i + Pgi + Pgi $/hr (fuel-cost)
gi
Where:
f=Fuel cost function $/hr.
i=number of units
Pg=power generated MW
α, γ , β are constants
Dr.Audih 12
12
The input to the thermal plant is generally
measured in Btu/h, and the output is measured in
MW. By plotting the derivative of the fuel-cost curve
versus the real power we get the incremental fuel-
cost curve
2
f = + P + P $/hr
i (P )
gi i i gi i gi
Dr.Audih 13
13
Converting the fuel cost $/h to power produce cost
$/MW.h we get:
f i ( P )
gi
= = i + 2 i Pgi $ / MW .h
Pgi
Dr.Audih 14
14
Economic dispatch neglecting losses
f1 f2 fng
Dr.Audih 15
15
The problem is to find the real power generation
for each plant such that the objective function
(total production cost) as defined by the equation
n
f total = i + i Pi + i P 2 $ / hr
i
i =1
Therefore the condition for optimum dispatch is
f total ( P ) f 1 f f
i = = 2 = ........ = n
Pi P P P
1 2 n
or = 1 = 2 = ...... = n
And = + 2 P $ / MW .h
i i i
Dr.Audih 16
16
when losses are neglected with no generator
limits, for most economic operation. all
plants must operate at equal incremental
production cost (λ)
= i + 2 i Pi
Production from each plant can be found by
− i
Pi =
2 i
.
And since losses is neglected the power
demand(PD) =power generated (Pi). For
analytic solution
Dr.Audih 17
17
n
− i
n
i =1
Pi = PD Where Pi = PD =
i =1 2 i
or
n
n
i n
n
i
PD = − = PD + or
i =1 2 i i =1 2 i i =1 2 i i =1 2 i
i
n
PD +
n
1 n
i i =1 2 i
. = PD + or = n
i =1 2 i i =1 2 i 1
i =1 2 i
Dr.Audih 18
18
an iterative technique
Starting with a value of (λ) and the process is continued
until ∆Pi is within a specified accuracy.
Corresponding to this λ ,
Update value of λ by
Dr.Audih 19
19
Incremental Cost Example
For a two generator system assume
f 1 (Pg 1 ) = 1000 +20Pg 1 + 0.01Pg21 $ / hr
f 2 (Pg 2 ) = 400 +15Pg 2 + 0.03Pg22 $ / hr
Then
1 = 20 + 0.02Pg 1 $/MWh
2 = 15 + 0.06Pg 2 $/MWh
If Pg1 = 250 MW and Pg2 = 150 MW
Then
= 20 + 0.02 250 = 25 $/MWh
1
f1
f2
f3
b)
Solution
Dr.Audih 21
21
MW
− i
Pi = MW
2 i
MW
Dr.Audih 22
22
b)
− i
Pi =
2 i
P
( k ) =
1
2
i
Dr.Audih 23
23
n
f total = i + i Pi + i P 2 $ / hr
i
i =1
ft
Dr.Audih 24
24
Economic dispatch neglecting losses and including
generation limits.
For generation restricted between maximum and minimum limits
the power generation for each plant is given by the following
constrain
Dr.Audih 26
26
Solution:
975
975
9.1
Out of limits
− i
Pi =
2 i
Dr.Audih 27
27
Or assume the initial value of
Dr.Audih 28
28
Dr.Audih 29
29
Dr.Audih 30
30
n
f total = i + i Pi + i P 2 $ / hr
i
i =1
ft
Dr.Audih 31
31
ECONOMIC DISPATCH
INCLUDING LOSSES
When power is transmitted over long distances
transmission losses are a major factor that affect
the optimum dispatch of generation
One common practice for including the effect of
transmission losses is to express the total
transmission loss as a quadratic function of the
generator power outputs. The simplest quadratic
form is
Dr.Audih 32
32
ft
ft fi
Dr.Audih 33
33
n
Using the langrange multiplier L = f t + ( PD + PL − P )
i =1
i
f t fi
A lso f t = f 1 + f 2 + .... + f n and = then
Pi Pi
f i PL f i PL
+ − ) = 0 = + − 1 or
Pi Pi Pi Pi
Dr.Audih 34
34
−1
f i PL
= . − 1
Pi Pi
−1
If we note that PL 1
− 1 = = Li where i = 1....n
Pi PL
P − 1
i
Where L is penalty factor then:
1
f i Li =
= .Li PL
P − 1
Pi
and
i
Dr.Audih 35
35
Itration method
Initially assume a λ value. Then find out the generation from
each plant using the equation
calculate
Dr.Audih 36
36
Update value of λ
Dr.Audih 37
37
EXAMPLE
f1
f2
f3
Dr.Audih 38
38
SOLUTION
We select 100MW base to change P in per unit and the result of P in
pu is multiplied by base to give us actually value is actual value
Out of limits
Dr.Audih 39
39
If
Dr.Audih 40
40
Dr.Audih 41
41
Dr.Audih 42
42
Dr.Audih 43
43
Dr.Audih 44
44
ft
Dr.Audih 45
45
Economic Dispatch - Summary
Dr.Audih 46
46
47