Standard ACDB Specification

Uploaded by

kjuneja212
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

3 in 1 Out ACDB with 200A MCCB - IP 54 X 1 NOS

S.NO DESCRIPTION SPECIFICATION

Conzerve 6400NG suitable for 5A 0.5 Class, 3P,


1 ENERGY METER
4Wire, with RS485

2 CT 630/5A, 415V, Class 0.5, Resin Cast


200A, 415V, 36kA, MCCB 4P WITH O/C & S/C with
3 INCOMING MCCB
ROH AND SPREADER LINK
500A, 415V, 36kA, MCCB 4P WITH O/C & S/C & E/F
4 OUTGOING MCCB
with ROH AND SPREADER LINK
5 SPD 3P, 415V, 36kA, TYPE 2 SPD
ELECTROLYTE GRADE 63401-WP as per IS: 5082.
BUS BARS SUPPORTED ON 1.1KV
STANDARD INSULATED AL BUS BAR
6 550A AL INSULATED BUSBAR SYSTEM SHOULD BE
(WITH INSULATORS)
SUITABLE FOR 415V
3PH-4WIRE,50HZ.

CRCA, MINIMUM 1.6MM SHEET, POWDER COATED


RAL-7032 (minimum coating thickness should be 80
micron), FRONT COVER SHOULD BE TRANSPARENT
(METER AND INDICATION SHOULD BE VISIBLE
WITHOUT OPENING THE DOOR) COMPARTMENT
TYPE DESIGN WITH CABLE ALLEY.

AMBIENT TEMP. CONDITIONS:- 0°C TO +50 °C


DESIGN TEMP. CONDITIONS:- -0°C TO +80 °C
DEGREE OF PROTECTION : IP54(SINGLE DOOR)
7 ENCLOSURE STAND MOUNT WITH EPDM RUBBER GASKET
STAND MOUNT WITH 800 MM BOTTOM
CLEARANCE
BOTTOM ENTRY AND BOTTOM EXIT

I/P CABLE FROM INVERTER 3R 120 SQ MM 4 CORE


AL UARM AND O/P CABLE 3R 240 SQ MM 4 CORE
AL ARM.

GLAND PLATE SHOULD BE MINIMUM 3 MM THICK


REMOVABLE WITH EPDM GASKET WITH UV
PROTECTED.

LED INDICATION LAMP COMMON RED/YELLOW/BLUE 240V AC WITH 6A SP MCB 3


8
((INCOMING OUTGOING) WITH MCB NOS

AL BUSBAR FOR THE CONNECTION OF


A) INPUT GROUNDING CABLES OF 1R X1Cx70
GROUNDING BUSBAR (WITH SQ.MM, CU PVC CABLE x 3 nos
9
INSULATORS) B) GROUNDING CABLE FROM SPD, 1RX1CX16.0
SQ.MM, PVC UNARM CABLE

CABLE GLANDS BRASS SINGLE COMPRESSION GLAND SUITABLE FOR 3 RUN


10
(INCOMMING GROUND) OF 1C, 70 SQ.MM CU, PVC, UNARMOURED CABLE.
11 WIRE PVC CHANNEL STANDARD PVC

12 LED WITH HOLDER 230V AC with DOOR LIMIT


EQUIPMENT AREA LIGHTNING SWITCH IN CABLE ALLEY
PLUG & SOCKET WITH 16A DP MCB (Industrial Type
External)
13 PLUG & SOCKET
PLUG & SOCKET WITH 10A TP MCB (Industrial Type
External)
14 MCB DP 16A FOR AUXILIARY LOAD
15 WARRANTY SHOULD BE NOT&LESS THAN 5 YEARS as per
a) G. A Drawing Busbar calculation
standard.
b) Single Line Diagram & Two line diagram
c) Bill of material (with specifications & quantities)
16 Required drawings from Vendor
d) Product datasheet of the items to be shown in
bill of material
F) Heat dissipation calculation
Note: Vendor to confirm above specifications.
Vendor can also recommend any deviations or suggestions as per their best knowledge.
All componenets should have rigid mounting & Properly mounted with identification/ ferrul numbers.
Vendor will provide the inspection/ internal test report with BOM list
All wiring should have proper lugs and proper indication.
All in/out going cables shall have proper marking and color coding.
Below Legend, circuit diagram and cabling diagram of the system paste properly and printed on aluminum plate
printed.
As built drawings required.
Mention project code on ACDB.
Use the cable glad selection as provided.
Danger Board should be available in ACDB.
Drawing pocket required.
Sufficient space should be consider during design considering respective cable bending radius.
All the hardware should be SS 304 grade.
provide Sealing Plug for all cable gland.
1 NOS
MAKE QUANTITY UNIT
SCHNEIDER,
SECURE & L&T/ 1 No
EQUIVELENT
AE/REPUTE 3 No
L&T/ABB/
3 No
Schneider Depends on inverter size and number
L&T/ABB/
1 No
Schneider Depends on inverter size and number
L&T/CITEL 1 No

1 SETS

1 No
Depends on indoor or outdoor

The incommer side Indicatation


Teknic & L&T 1 SET should not remain ON condition
while Inverter OFF

1 NO

ITC 3 NO
TO BE DISCUSSED WITH VENDOR
1 SET TO BE DISCUSSED WITH VENDOR

1 SET
REPUTE & TEKNIC

SCHNEIDER & L&T 1


NO TO BE DISCUSSED WITH VENDOR

SCHNEIDER & L&T 1


NO TO BE DISCUSSED WITH VENDOR
L&T 2 NO
TO BE DISCUSSED WITH VENDOR
1 SET
1 SET
1 SET

1
SET
1 SET

owledge.
cation/ ferrul numbers.

ly and printed on aluminum plate or a screen

bending radius.