Modbus connection document description
IP :192.168.0.105
subnet :255.255.255.0
gateway:192.168.0.1
Port : 4002
PC TCP IPV4
IP :192.168.0.101(Consistent with CM module gateway)
subnet :255.255.255.0
HTTP://HUASU-TECH.COM// TEL:0571-87967915
Modbus connection document description
PC TCP IPV4
IP :192.168.0.107(IP cannot be repeated with CM module)
subnet :255.255.255.0
gateway:192.168.0.1
HTTP://HUASU-TECH.COM// TEL:0571-87967915
Modbus connection document description
Modbus poll
IP:192.168.0.105(Different IP addresses need to be entered for different CM modules)
Port:4002
If the CM module changes the IP, subnet and gateway, restart the CM module (power off /
on) after the change
Device ID : 17
Cm module address: 1 ,
CM module address: D.setup – PIN 2022 – 3.setup – 3.2GL Set –
HTTP://HUASU-TECH.COM// TEL:0571-87967915
Modbus connection document description
HTTP://HUASU-TECH.COM// TEL:0571-87967915
Modbus connection document description
HTTP://HUASU-TECH.COM// TEL:0571-87967915
Modbus connection document description
Baud rate:19200
(TA module, TC module 9600, CM module 19200)
Data bits: 8
Parity: none
Stop: 1
Device ID : 17
Cm module address: 1 . first battery string : 1
HEX:11, DEC: 17
Modbus poll slave ID : 17
CM module address: D.setup – PIN 2022 – 3.setup – 3.2GL Set –