0% found this document useful (0 votes)
8 views4 pages

C20-D6

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 4

Specification sheet

Diesel
generator set
X2.5 series
engine
15 kVA–27 kVA 50 Hz
10.8 kW–20 kW 60 Hz

Description
This Cummins® Power Generation Cooling system – Standard integral set-
commercial generator set is a fully integrated mounted radiator system, designed and tested
power generation system, providing optimum for rated ambient temperatures, simplifies facility
performance, reliability, and versatility design requirements for rejected heat.
for stationary standby, prime power, and
continuous duty applications. Control system – PowerStart control,
microprocessor-based generator set monitoring
and control system provides a simple operator
Features interface to the generator set, manual and
Cummins® heavy-duty engine – Rugged remote start/stop control and shutdown fault
4-cycle industrial diesel delivers reliable indication.
power, low emissions and fast response to
load changes. Enclosures – Optional weather-protective and
sound-attenuated enclosure.
Optional excitation boost system
(EBS) – Offers enhanced motor starting and Warranty – Backed by a comprehensive
fault clearing short circuit capability. warranty and Worldwide distributor network.

Alternator – Several alternator sizes offer


selectable motor starting capability with low
reactance 2/3 pitch windings; low waveform
distortion with non-linear loads and fault
clearing short-circuits capability.

3-Phase ratings 1-Phase ratings*


Standby rating Prime rating Standby rating Prime rating Data sheet
50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz
Model kVA (kW) kW (kVA) kVA (kW) kW (kVA) kVA (kW) kW (kVA) kVA (kW) kW (kVA)
C17 D5 17 (13.2) 15 (11.88) 13 (13) 11.8 (11.8) DS336-CPGK
C22 D5 22 (17.6) 20 (15.84) 17 (17) 15.5 (15.5) DS338-CPGK
C28 D5 28 (22) 25 (19.8) 22 (22) 20 (20) DS340-CPGK
C12 D6 12 (15) 10.8 (14) 12 (12) 10.9 (10.9) DS337-CPGK
C16 D6 16 (20) 14.4 (18) 16 (16) 14.5 (14.5) DS339-CPGK
C20 D6 20 (25) 18 (23) 20 (20) 18.1 (18.1) DS341-CPGK
* 1.0 PF

Our energy working for you. TM


cumminspower.com
© 2012 Cummins Power Generation Inc. | SS26-CPGK-RevA (05/12)
Generator set specifications
Governor regulation class ISO 8528 Part 1 G2
Voltage regulation, no load to full load +/- 1%
Random voltage variation +/- 1%
Frequency regulation Droop
Random frequency variation +/- 0.25%
Radio frequency emissions compliance Yes

Engine specifications
Design 4 cycle, in-line, naturally aspirated
Bore 91.7 mm
Stroke 127 mm
Displacement 2.5 liter (153 in3)
Cylinder block Alloy cast iron, in-line, 3 cylinder
Battery charging alternator 36 A
Starting voltage 12 volt, negative ground
Fuel system Direct injection
Fuel filter Spin on fuel filters with water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Spin on full flow filter, filtration efficiency 25 micron 99% (min)
Standard cooling system 122 °F (50 °C) ambient radiator with coolant recovery system

Alternator specifications
Design Brushless, single bearing
Stator 2/3 pitch
Insulation system Class H
Standard temperature rise 125–163 °C
Exciter type Self excited
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion (THDV) No load to full linear load < 5%. For any single harmonic < 3%
Telephone influence factor (TIF) < 50 per NEMA MG1-22.43
Telephone harmonic factor (THF) < 3%

Available voltages
50 Hz Line–Line/Line–Neutral 60 Hz Line–Line/Line–Neutral
3-Phase 1 Phase 3-Phase 1 Phase
• 240/416 • 127/220 • 220 • 277/480 • 127/220 • 220
• 255/480 • 120/208 • 230 • 240/416 • 120/208 • 230
• 230/400 • 115/200 • 240 • 255/440 • 240
• 220/380 • 110/190
Note: Consult factory for other voltages.

Generator set options and accessories


Engine Enclosure Control panel 500 litre fuel tank
Electronic engine governing Optional silent power PowerCommand 1.1 Warranty
Coolant heater 120/240 V canopy 2/4 pole main circuit 5 years for standby
Alternator breaker application
Cooling
Antifreeze 50/50 (ethylene Alternator heater Base frame 2 years for prime
glycol) Excite boost system (EBS) Dual skin fully contained application
fuel tank
Note: Some options may not be available on all models - consult factory for availability.

Our energy working for you. TM


cumminspower.com
© 2012 Cummins Power Generation Inc. | SS26-CPGK-RevA (05/12)
Control system Data logs – Includes engine run time and controller on
time.
Generator set control PowerStart 500 – Fault history – Provides a record of the most recent
The PowerStart control is a microprocessor-based fault conditions with control hour’s time stamp. Up to
generator set monitoring and control system. The 5 events are stored in the control non-volatile memory.
control provides a simple operator interface to the
generator set, manual and remote start/stop control and Alternator data
shutdown fault indication. The integration of all control
• Voltage (single or three phase line-to-line and line-to-
functions into a single control provides enhanced
neutral).
reliability and performance compared to conventional
generator set control systems. This control has been • Current (single or three phase).
designed and tested to meet the harsh environment in • KVA (three phase and total).
which gensets are typically applied. • Frequency.
• The PowerStart generator set control is suitable
for use on a wide range of generator sets in non- Engine data
paralleling applications. It is suitable for use with • Starting battery voltage.
reconnectable or non-reconnectable generators, can
• Engine running hours.
be configured for either 50 Hz or 60 Hz and voltage
and power connection from 190-600 VAC line-to-line. • Engine temperature.
• This control includes an intuitive operator interface • Engine oil pressure.
that allows for complete genset control as well as
system metering, fault annunciation, configuration and Service adjustments – The control includes
diagnostics. The interface includes seven generator provisions for adjustment and calibration of generator
set status LED lamps with both internationally set control functions. Functions include:
accepted symbols and English text to comply with • Voltage selection.
customer needs. The interface also includes an LED • Frequency selection.
backlit LCD display with tactile-feel soft-switches for
• Configurable input set up.
easy operation and screen navigation. The manual/
auto/stop switch function is integrated into the • Configurable output set up.
interface panel. • Meter calibration.
• All data on the control can be viewed by scrolling • Units of measurement.
through screens with the navigation keys. The control
displays the current active fault and a time-ordered Protective functions
history of the five previous faults.
On operation of a protective function the control
• Power for this control is derived from the generator set will indicate a fault by illuminating the appropriate
starting batteries and functions over a voltage range status LED, as well as display the fault code and fault
from 8 VDC to 16 VDC. description on the LCD. The nature of the fault and time
of occurrence are logged in the control. The service
Major features manual and InPower Service Tool provide service keys
• LCD display – 16 characters x 2 line alphanumeric and procedures based on the service codes provided.
LED backlight LCD.
Field control interface
• Generator set monitoring and protection.
• 12 VDC battery operation. Input signals to the base control include
• Engine starting – Includes solid state output to • Remote start.
operate external relays start the engine, fuel shut • Local and emergency stop.
FSO), and glow plugs. Start disconnect is achieved by • Configurable inputs: Control includes (4) input signals
monitoring main alternator frequency. from customer.
• Remote start capability – Interface to transfer switch.
• Environmental protection – The control is designed for Output signals from the control include
reliable operations in harsh environments. • Configurable output: Control includes (1) solid state
• Warranty and service – Backed by a comprehensive driver rated at 1 A. This output can be configured to
warranty and worldwide distributor service network. activate on ready to load, or common warning and
common shutdown condition.
• Certification – Suitable for use on generator sets
are designed, manufactured, tested and certified to Communications connections include
relevant ISO, IEC Mil Std. and CE standards.
• PC tool interface: This RS-485 communication port
allows the control to communicate with a personal
Base control functions
computer running InPower software.
LCD display – 16 character x 2 line alphanumeric LED Note – An RS-232 or USB to RS-485 converter is
backlight LCD. required for communication between PC and control.
Operation interface – Six tactile-feel membrane
switches for LCD navigation, genset operation and
control setup.
These switches are indicated by internationally PowerStart 500
accepted symbols and English text. control operator/
display panel

Our energy working for you. TM


cumminspower.com
© 2012 Cummins Power Generation Inc. | SS26-CPGK-RevA (05/12)
Ratings definitions OPEN

Emergency standby power (ESP):


Applicable for supplying power to varying electrical

C
load for the duration of power interruption of a reliable
utility source. Emergency standby power (ESP) is
in accordance with ISO 8528. Fuel stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and A B
BS 5514.

Limited-time running power (LTP):


ENCLOSED
Applicable for supplying power to a constant electrical
load for limited hours. Limited time running power
(LTP) is in accordance with ISO 8528.

C
Prime power (PRP):
Applicable for supplying power to varying electrical
load for unlimited hours. Prime power (PRP) is in
A B
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514. This outline drawing is to provide representative configuration
details for Model series only.
Base load (continuous) power (COP):
See respective model data sheet for specific model outline
Applicable for supplying power continuously to
drawing number.
a constant electrical load for unlimited hours.
Continuous power (COP) in accordance with
ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514. Do not use for installation design

Weight and dimensions


Open Enclosed
A B C Dry wt.* Wet wt.* A B C Dry wt.* Wet wt.*
Model mm mm mm (kg) (kg) mm mm mm (kg) (kg)
C17 D5 1667 930 1247 418.5 582 2082 930 1448 743.5 907
C22 D5 1667 930 1247 418.5 582 2082 930 1448 743.5 907
C28 D5 1667 930 1247 441.5 605 2082 930 1448 766.5 930
C12 D6 1667 930 1247 405 568.5 2082 930 1448 730 893.5
C16 D6 1667 930 1247 405 568.5 2082 930 1448 730 893.5
C20 D6 1667 930 1247 418.5 582 2082 930 1448 743.5 907
*Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Certifications
This generator set is designed in facilities
This generator set is available with
certified to ISO 9001 and manufactured in
CE certification.
facilities certified to ISO 9001 or ISO 9002.

The Prototype Test Support (PTS) program verifies the


performance integrity of the generator set design.
Cummins Power Generation products bearing the PTS
symbol meet the prototype test requirements of
NFPA 110 for Level 1 systems.

Cummins Power Generation

Americas Asia Pacific Europe, CIS, Middle East and Africa


1400 73rd Avenue N.E. 10 Toh Guan Road #07-01 Manston Park Columbus Ave
Minneapolis, MN 55432 USA TT International Tradepark Manston Ramsgate
Phone 763 574 5000 Singapore 608838 Kent CT12 5BF United Kingdom
Fax 763 574 5298 Phone 65 6417 2388 Phone 44 1843 255000
Fax 65 6417 2399 Fax 44 1843 255902

Our energy working for you. TM

© 2012 Cummins Power Generation Inc. All rights reserved.


Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower
and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names