Section 15813 Humidifiers
Section 15813 Humidifiers
1.0 Humidifiers shall be of the jacketed dry steam or self contained steam types. Pan, wetted
drum, and power wetted element humidifiers are prohibited. Infrared pan type
humidifiers are allowed in self-contained Computer Room units only, refer to Section
15785.
2.0 All humidifiers shall use a steam dispersion manifold. The preferred locations for
humidifiers are in the air handling unit up-stream of the cooling coil. Review applications
with the University Representative. All controls, valves, and traps, etc. must be located
outside of the air stream.
3.0 The Campus central steam system may be used as a humidification source and can be
directly dispersed into the air stream. (Preferred Method).
4.0 All steam humidifiers shall operate with low pressure steam (less than 12 PSI). All
control valves shall be rated for 150% of the operating pressure, otherwise, pressure
reducing valves shall be provided.
5.0 All free standing space humidifiers shall be of the self contained type.
C. Steam separator.
D. Separating baffles.
E. Steam trap(s).
G. Drying chamber.
7.0 Self-contained humidifiers shall be of the electrode steam generator type and contain the
following:
A. Disposable cylinders.
B. Microprocessor controls.
C. Automatic cylinder fill and drain controls to maintain water conductivity and
minimize energy waste. Built-in timers for repetitive drain cycles are prohibited.
8.0 Designer shall review the control of all humidifiers to ascertain that system response can meet
or exceed expected load variations and maintain desired humidity levels. The suggested
control options are as follows:
C. Return air humidity sensors shall not be used to control space humidity levels.
9.0 Minimum winter season humidity levels must be maintained at a minimum 25% relative
humidity. Special spaces such as vivariums and data centers may require higher humidity
levels. Confirm humidification requirements and humidity levels with the project program
requirements. In no case shall the level be in excess of that which the existing structure can
maintain without resulting in the formation of condensation. In new buildings, the
Engineer must work with the Architect to design building walls and glazing
components which will permit winter period humidity levels that meet present indoor
air quality requirements. The Engineer shall submit calculations showing the anticipated
wall and window temperature gradients based upon a 0°F and 93°F ambient temperatures.
Special consideration shall be given to structural steel exposed to space conditions.
10.0 The locations of humidifiers shall generally be restricted to Mechanical Rooms. Where
individual humidifiers are duct mounted, the duct construction must be watertight stainless
steel for 150 percent of the humidifier’s absorption distance. The duct section shall have a
drain connection piped to the nearest floor drain.
END OF SECTION