PRM LS iG5A
PRM LS iG5A
Drive Group
Address
Min/M Adj.
LED for Parameter Factory
ax Description during Page
display communi name defaults
range run
cation
0.00 A100 [Frequency 0~ This parameter sets the frequency that the 0.00 O 7-1
command] 400 inverter is commanded to output.
[Hz] During Stop: Frequency Command
During Run: Output Frequency
During Multi-step operation:
Multi-step frequency 0.
It cannot be set greater than F21- [Max
frequency].
ACC A101 [Accel 0~ During Multi-Accel/Decel operation, this 5.0 O 7-12
time] 6000 parameter serves as Accel/Decel time 0.
dEC A102 [Decel [Sec] 10.0 O 7-12
time]
drv A103 [Drive 0~4 0 Run/Stop via Run/Stop key on the keypad 1 X 7-8
mode]
FX: Motor forward run 7-8
1
TerminalRX: Motor reverse run
operation
FX: Run/Stop enable
2
RX: Reverse rotation select
3 RS485 communication 7-9
4 Set to Field Bus communication 1) -
Frq A104 [Frequency 0~9 0 Digital Keypad setting 1 0 X 7-1
setting 1 Keypad setting 2 7-1
method]
2 V1 1: -10 ~ +10 [V] 7-2
3 V1 2: 0 ~ +10 [V] 7-3
4 Terminal I: 0 ~ 20 [mA] 7-4
Analog Terminal V1 setting 1 + 7-5
5
Terminal I
Terminal V1 setting 2+ 7-6
6
Terminal I
7 RS485 communication 7-5
8 Digital Volume 7-6
9 Set to Field Bus communication 1) -
St1 A105 [Multi-Step 0~ Sets Multi-Step frequency 1 during Multi-step 10.00 O 7-7
frequency 400 operation.
1] [Hz]
St2 A106 [Multi-Step Sets Multi-Step frequency 2 during Multi-step 20.00 O 7-7
frequency operation.
2]
St3 A107 [Multi-Step Sets Multi-Step frequency 3 during Multi-step 30.00 O 7-7
frequency operation.
3]
CUr A108 [Output Displays the output current to the motor. - - 9-1
current]
rPM A109 [Motor Displays the number of Motor RPM. - - 9-1
RPM]
dCL A10A [Inverter Displays DC link voltage inside the inverter. - - 9-1
DC link
voltage]
1)
: This function can be available with iG5A Communication Option Module.
5-1
Drive Group
Address
Min/M Adj.
LED for Parameter Factory
ax Description during Page
display communi name defaults
range run
cation
vOL A10B [User This parameter displays the item selected at vOL - 9-2
display H73- [Monitoring item select].
select] vOL Output voltage
POr Output power
tOr Torque
nOn A10C [Fault Displays the types of faults, frequency and - - 9-4
Display] operating status at the time of the fault
drC A10D [Direction F, r Sets the direction of motor rotation when drv - F O 7-8
of motor [Drive mode] is set to either 0 or 1.
rotation F Forward
select]
r Reverse
drv2 A10E [Drive 0~4 0 Run/Stop via Run/Stop key on the keypad 1 X 8-24
mode 2]
Terminal FX: Motor forward run
1
operationRX: Motor reverse run
FX: Run/Stop enable
2
RX: Reverse rotation select
3 RS-485 communication
4 Set to Filed Bus Communication 3)
1)
Frq2 A10F [Frequency 0~9 0 Digital Keypad setting 1 0 X 8-24
setting 1 Keypad setting 2
method 2]
2 Analog V1 1: -10 ~ +10 [V]
3 V1 2: 0 ~ +10 [V]
4 Terminal I: 0 ~ 20 [mA]
Terminal V1 setting 1 +
5
Terminal I
Terminal V1 setting 2+
6
Terminal I
7 RS485 communication
8 Digital Volume
9 Set to Filed Bus Communication 3)
2)
rEF A110 PID control 0~400 If H58 is 0, it is expressed as a [Hz] unit. 0.00 0 8-11
standard [Hz] or If H58 is 1, it is expressed as a [%] unit.
value 0~100 In [Hz] unit, you can’t set Max. frequency
setting [%] more than (F21).
In [%] unit, 100% means Max. frequency.
Fbk2) A111 PID control It indicates a feedback amount in PID - - 8-11
feedback control.
amount If H58 is 0, it is expressed as a [Hz] unit.
If H58 is 1, it is expressed as a [%] unit.
1)
: Only displayed when one of the Multi-function input terminals 1-8 [I17~I24] is set to “22”.
2)
: It is indicated when H49(PID control selection) is 1.
3)
: This function can be available with iG5A Communication Option Module.
5-2
Function group 1
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display communi er name range defaults
run
cation
F0 A200 [Jump 0 ~ 71 Sets the parameter code number to jump. 1 O 4-5
code]
F1 [Forwar 0~2 0 Fwd and rev run enable 0 X 7-10
d/
A201 1 Forward run disable
Reverse
run Reverse run disable
2
disable]
F2 A202 [Accel 0~1 Linear 0 X 7-15
0
pattern]
F3 A203 [Decel S-curve
1
pattern]
F4 A204 [Stop 0~3 0 Decelerate to stop 0 X 7-20
mode 1 DC brake to stop
select]
2 Free run to stop
3 Power Braking stop 8-26
1)
F8 A208 [DC 0.1 ~ 60 This parameter sets DC brake start 5.00 X 8-1
Brake [Hz] frequency.
start It cannot be set below F23 - [Start
frequen frequency].
cy]
F9 A209 [DC 0 ~ 60 When DC brake frequency is reached, 0.1 X
Brake [sec] the inverter holds the output for the
wait setting time before starting DC brake.
time]
F10 A20A [DC 0 ~ 200 This parameter sets the amount of DC 50 X
Brake [%] voltage applied to a motor.
voltage] It is set in percent of H33 – [Motor rated
current].
F11 A20B [DC 0 ~ 60 This parameter sets the time taken to 1.0 X
Brake [sec] apply DC current to a motor while motor
time] is at a stop.
F12 A20C [DC 0 ~ 200 This parameter sets the amount of DC 50 X 8-2
Brake [%] voltage before a motor starts to run.
start It is set in percent of H33 – [Motor rated
voltage] current].
F13 A20D [DC 0 ~ 60 DC voltage is applied to the motor for DC 0 X
Brake [sec] Brake start time before motor
start accelerates.
time]
F14 A20E [Time 0 ~ 60 This parameter applies the current to a 0.1 X 8-15
for [sec] motor for the set time before motor
magneti accelerates during Sensorless vector
zing a control.
motor]
F20 A214 [Jog 0 ~ 400 This parameter sets the frequency for 10.00 O 8-3
frequen [Hz] Jog operation.
cy] It cannot be set above F21 – [Max
frequency].
1)
: Only displayed when F 4 is set to 1 (DC brake to stop).
5-3
Function group 1
Address
Adj.
LED for Paramete Min/Max Factory
Description during Page
display communi r name range defaults
run
cation
F211) A215 [Max 40 ~ 400 This parameter sets the highest frequency 60.00 X 7-21
frequency [Hz] the inverter can output.
] It is frequency reference for Accel/Decel
(See H70)
Caution
F22 A216 [Base 30 ~ 400 The inverter outputs its rated voltage to the 60.00 X 7-17
frequency [Hz] motor at this frequency (see motor
] nameplate).
F23 A217 [Start 0.1 ~ 10 The inverter starts to output its voltage at 0.50 X 7-21
frequency [Hz] this frequency.
] It is the frequency low limit.
F24 A218 [Frequen 0~1 This parameter sets high and low limit of 0 X 7-21
cy run frequency.
high/low
limit
select]
F25 A219 [Frequen 0 ~ 400 This parameter sets high limit of the run 60.00 X
2)
cy high [Hz] frequency.
limit] It cannot be set above F21 – [Max
frequency].
F26 A21A [Frequen 0.1 ~ 400 This parameter sets low limit of the run 0.50 X
cy low [Hz] frequency.
limit] It cannot be set above F25 - [Frequency
high limit] and below F23 – [Start
frequency].
F27 A21B [Torque 0~1 0 Manual torque boost 0 X 7-19
Boost 1 Auto torque boost
select]
F28 A21C [Torque 0 ~ 15 This parameter sets the amount of torque 2 X 7-19
boost in [%] boost applied to a motor during forward
forward run.
direction] It is set in percent of Max output voltage.
F29 A21D [Torque This parameter sets the amount of torque 2 X 7-19
boost in boost applied to a motor during reverse
reverse run.
direction] It is set as a percent of Max output voltage
1)
: If H40 is set to 3 (Sensorless vector), Max. frequency is settable up to 300Hz.
2)
: Only displayed when F24 (Frequency high/low limit select) is set to 1.
5-4
Function group 1
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu name range defaults
run
nication
F30 A21E [V/F 0~2 0 {Linear} 0 X 7-17
pattern] 1 {Square} 7-17
2 {User V/F} 7-18
F311) A21F [User V/F 0 ~ 400 It is used only when V/F pattern is set to 15.00 X 7-18
frequency [Hz] 2(User V/F)
1] It cannot be set above F21 – [Max
F32 A220 [User V/F 0 ~ 100 frequency]. 25 X
voltage 1] [%] The value of voltage is set in percent of
H70 – [Motor rated voltage].
F33 A221 [User V/F 0 ~ 400 The values of the lower-numbered 30.00 X
frequency [Hz] parameters cannot be set above those of
2] higher-numbered.
F34 A222 [User V/F 0 ~ 100 50 X
voltage 2] [%]
F35 A223 [User V/F 0 ~ 400 45.00 X
frequency [Hz]
3]
F36 A224 [User V/F 0 ~ 100 75 X
voltage 3] [%]
F37 A225 [User V/F 0 ~ 400 60.00 X
frequency [Hz]
4]
F38 A226 [User V/F 0 ~ 100 100 X
voltage 4] [%]
F39 A227 [Output 40 ~ 110 This parameter adjusts the amount of 100 X 7-18
voltage [%] output voltage.
adjustment The set value is the percentage of input
] voltage.
F40 A228 [Energy- 0 ~ 30 This parameter decreases output voltage 0 0 8-17
saving [%] according to load status.
level]
F50 A232 [Electronic 0~1 This parameter is activated when the 0 0 10-1
thermal motor is overheated (time-inverse).
select]
1)
: Set F30 to 2(User V/F) to display this parameter.
5-5
Function group 1
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu name range defaults
run
nication
F51 A233 [Electronic 50 ~ 200 This parameter sets max current capable of 150 0 10-1
1)
thermal [%] flowing to the motor continuously for 1 minute.
level for 1 The set value is the percentage of H33 –
minute] [Motor rated current].
It cannot be set below F52 –[Electronic thermal
level for continuous].
F52 A234 [Electronic 50 ~ 150 This parameter sets the amount of current to 100 0
thermal [%] keep the motor running continuously.
level for It cannot be set higher than F51 – [Electronic
continuous] thermal level for 1 minute].
F53 A235 [Motor 0~1 0 Standard motor having cooling fan 0 0
cooling directly connected to the shaft
method]
1 A motor using a separate motor to
power a cooling fan.
F54 A236 [Overload 30 ~ 150 This parameter sets the amount of current to 150 0 10-2
warning [%] issue an alarm signal at a relay or multi-
function output terminal (see I54, I55).
level]
The set value is the percentage of H33- [Motor
rated current].
F55 A237 [Overload 0 ~ 30 [Sec] This parameter issues an alarm signal when 10 0
warning the current greater than F54- [Overload
time] warning level] flows to the motor for F55-
[Overload warning time].
F56 A238 [Overload 0~1 This parameter turns off the inverter output 1 0 10-2
trip select] when motor is overloaded.
F57 A239 [Overload 30 ~ 200 This parameter sets the amount of overload 180 0
trip level] [%] current.
The value is the percentage of H33- [Motor
rated current].
F58 A23A [Overload 0 ~ 60 [Sec] This parameter turns off the inverter output 60 0
trip time] when the F57- [Overload trip level] of current
flows to the motor for F58- [Overload trip time].
1)
: Set F50 to 1 to display this parameter.
5-6
Function group 1
Address
Adj.
LED for Paramete Min/Max Factory
Description during Page
display commun r name range defaults
run
ication
F59 A23B [Stall 0~7 This parameter stops accelerating during 0 X 10-3
preventio acceleration, decelerating during constant
speed run and stops decelerating during
n select]
deceleration.
During During During Accel
Decel constant
run
Bit 2 Bit 1 Bit 0
0 - - -
1 - -
2 - -
3 -
4 - -
5 -
6 -
7
F60 A23C [Stall 30 ~ This parameter sets the amount of current to 150 X 10-3
preventio 200 activate stall prevention function during Accel,
n level] [%] Constant or Decel run.
The set value is the percentage of the H33-
[Motor rated current].
F61 A23D [When 0~1 In Stall prevention run during deceleration, if 8-26
1) Stall you want to limit output voltage, select 1
preventio
n during
decelerati
on,
voltage
limit
select
F63 A23F [Save 0~1 This parameter decides whether to save the 0 X 8-4
up/down specified frequency during up/down
frequency operation.
select] When 1 is selected, the up/down frequency is
saved in F64.
F64 A240 [Save If ‘Save up/down frequency’ is selected at 0.00 X 8-4
2)
up/down F63, this parameter saves the frequency
frequency before the inverter stops or decelerated.
]
F65 A241 [Up-down 0~2 We can select up-down mode among three 0 X 8-5
mode thing
select] 0 Increases goal frequency as a
standard of Max. frequency/Min.
frequency
1 Increases as many as step
frequency according to edge input
2 Available to combine 1 and 2
1)
: It is indicated when setting bit 2 of F59 as 1
2)
: Set F63 to 1 to display this parameter.
5-7
Function group 1
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commun name range defaults
run
ication
F66 A242 [Up-down 0~400[ In case of choosing F65 as a 1 or 2, it means 0.00 X 8-5
step Hz] increase or decrease of frequency according
frequency] to up-down input
F70 A246 [Draw run 0~3 0 Inverter doesn’t run as a draw 0 X 8-28
mode mode
select] 1 V1(0~10V) input draw run
2 I(0~20mA) input draw run
3 V1(-10~10V) input draw run
F71 A247 [Draw rate] 0~100[ Sets rate of draw 0.00 0 8-28
%]
5-8
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu name range defaults
run
nication
5-9
Function group 2
Adj.
LED Address for Parameter Min/Max Factory
Description during Page
display communication name range defaults
run
H17 A311 [S-Curve 1~100 Set the speed reference value to form a 40 X 7-15
accel/decel [%] curve at the start during accel/decel. If it is
start side]
set higher, linear zone gets smaller.
H18 A312 [S-Curve 1~100 Set the speed reference value to form a 40 X
accel/decel [%] curve at the end during accel/decel. If it is set
end side] higher, linear zone gets smaller.
H19 A313 [Input/output 0~3 0 Disabled 1 Output phase 0 O 10-4
phase loss protection
protection 2 Input 3 Input/output phase
select] phase protection
protection
H20 A314 [Power On 0~1 This parameter is activated when drv is set to 0 O 7-11
Start select] 1 or 2 (Run/Stop via Control terminal).
Motor starts acceleration after AC power is
applied while FX or RX terminal is ON.
H21 A315 [Restart 0 ~1 This parameter is activated when drv is set to 0 O 7-11
after fault 1 or 2 (Run/Stop via Control terminal).
reset Motor accelerates after the fault condition is
selection] reset while the FX or RX terminal is ON.
5-10
Function group 2
Address Factor
Adj.
LED for Paramete Min/Max y
Description during Page
display communic r name range default
run
ation s
H22 A316 1. H20- 2. 3. 4. O 8-17
1)
[Power Restart Operati Nor
mal
On after on after
accel
start] instant fault
power
failure
Bit 3 Bit 2 Bit 1 Bit 0
5 - -
6 - -
7 -
8 - - -
9 - -
10 - -
11 -
12 - -
13 -
14 -
15
H23 A317 [Current 80~200 This parameter limits the amount of current 100 O 8-17
level [%] during speed search.
during The set value is the percentage of the H33-
Speed [Motor rated current].
search]
H24 A318 [P gain 0~9999 It is the Proportional gain used for Speed 100 O
during Search PI controller.
Speed
search]
H25 A319 [I gain 0~9999 It is the Integral gain used for Speed search 200 O
during PI controller.
speed
search]
H26 A31A [Number 0 ~10 This parameter sets the number of restart 0 O 8-20
of Auto tries after a fault occurs.
Restart Auto Restart is deactivated if the fault
try] outnumbers the restart tries.
This function is active when [drv] is set to 1 or
2 {Run/Stop via control terminal}.
Deactivated during active protection function
(OHT, LVT, EXT, HWT etc.).
5-11
Function group 2
Address
LED for Parameter Min/Max Factory Adj.
Description Page
display communi name range defaults during run
cation
H27 A31B [Auto Restart 0~60 [sec] This parameter sets the time 1.0 O 8-20
time] between restart tries.
H30 A31E [Motor type 0.2~ 22.0 0.2 0.2kW 7.51) X 8-16
select] ~ ~
22.0 22.0kW
H31 A31F [Number of 2 ~ 12 This setting is displayed via rPM 4 X
motor poles] in drive group.
H33 A321 [Motor rated 0.5~150 Enter motor rated current on the 26.3 X
current] [A] nameplate.
H34 A322 [No Load 0.1~ 50 [A] Enter the current value detected 11 X
Motor Current] when the motor is rotating in rated
rpm after the load connected to
the motor shaft is removed.
Enter the 50% of the rated current
value when it is difficult to
measure H34 – [No Load Motor
Current].
H36 A324 [Motor 50~100 Enter the motor efficiency (see 87 X
efficiency] [%] motor nameplate).
H37 A325 [Load inertia 0~2 Select one of the following 0 X 8-1
rate] according to motor inertia.
5-12
Function group 2
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display communi er name range defaults
run
cation
H39 A327 [Carrier 1 ~ 15 This parameter affects the audible sound 3 O 8-21
frequen [kHz] of the motor, noise emission from the
cy inverter, inverter temp, and leakage
select] current. If the set value is higher, the
inverter sound is quieter but the noise
from the inverter and leakage current will
become greater.
H40 A328 [Control 0~3 0 {Volts/frequency Control} 0 X 7-17
mode 1 {Slip compensation control} 8-8
select]
3 {Sensorless vector control} 8-15
H41 A329 [Auto 0~1 If this parameter is set to 1, it 0 X 8-14
tuning] automatically measures parameters of
the H42 and H44.
H42 A32A [Stator 0 ~ 28 This is the value of the motor stator - X
resistan [Ω] resistance.
ce (Rs)]
H44 A32C [Leakage 0~ 300.0 This is leakage inductance of the stator - X
inductanc [mH] and rotor of the motor.
e (Lσ)]
H45 A32D [Sensorl 0~ 32767 P gain for Sensorless control 1000 O
1)
ess P
gain]
H46 A32E [Sensorl I gain for Sensorless control 100 O
ess I
gain]
H47 A32F [Sensorl 100~220[ Limits output torque in sensorless mode,. 180.0 X
ess %]
torque
limit]
H48 A330 PWM 0~1 If you want to limit a inverter leakage 0 X 8-30
mode current, select 2 phase PWM mode.
select It has more noise in comparison to
Normal PWM mode.
0 Normal PWM mode
1 2 phase PWM mode
H49 A331 PID 0~1 Selects whether using PID control or not 0 X 8-10
select
H50 A332 [PID F/B 0~1 0 Terminal I input (0 ~ 20 mA) 0 X 8-10
2)
select] 1 Terminal V1 input (0 ~ 10 V)
H51 A333 [P gain 0~ 999.9 This parameter sets the gains for the PID 300.0 O
for PID] [%] controller.
H52 A334 [Integral 0.1~32.0 1.0 O
time for [sec]
PID
H53 A335 [Differen 0 ~ 30.0 0.0 O
tial time [sec]
for PID
(D
gain)]
H54 A336 [PID 0~1 Selects PID control mode 0 X 8-10
control 0 Normal PID control
mode
select] 1 Process PID control
1)
: Set H40 to 3 (Sensorless vector control) to display this parameter.
2)
: Set H49 to 1 (PID control) to display this parameter.
5-13
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu- name range defaults
run
nication
H55 A337 [PID output 0.1 ~ This parameter limits the amount of the 60.00 O 8-10
frequency 400 output frequency through the PID control.
high limit] [Hz] The value is settable within the range of
F21 – [Max frequency] and F23 – [Start
H56 A338 [PID output 0.1 ~ frequency]. 0.50 O
frequency 400
low limit] [Hz]
(KEB does not operate when cut power after loading ting input (about 10%).
5-14
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu- name range defaults
run
nication
H67 A343 [KEB action 1~2000 Sets KEB action gain. 1000 X 8-28
gain] 0
H70 A346 [Frequency 0~1 0 Based on Max freq (F21) 0 X 7-12
Reference
for 1 Based on Delta freq.
Accel/Decel]
H71 A347 [Accel/Decel 0~2 0 Settable unit: 0.01 second. 1 O 7-13
time scale]
1 Settable unit: 0.1 second.
14 Output current 2
15 Motor rpm 2
16 Inverter DC link voltage 2
17 User display select 2
H73 A349 [Monitoring 0~2 One of the following can be monitored 0 O 9-2
item select] via vOL - [User display select].
5-15
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu- name range defaults
run
nication
H76 A34C [DB resistor 0~ Set the percent of DB resistor operating 10 O
operating 30[%] rate to be activated during one sequence
rate] of operation.
5-16
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu- name range defaults
run
nication
nd
H88 A358 [2 motor 50~200 150 O
Electronic [%]
thermal
level for 1
min]
H89 A359 [2nd motor 50~150 100 O
Electronic [%]
thermal
level for
continuous]
nd
H90 A35A [2 motor 0.1~100 26.3 X
rated [A]
current]
H911) A35B [Parameter 0~1 Copy the parameters from inverter and 0 X 8-32
read] save them into remote loader.
H92 A35C [Parameter 0~1 Copy the parameters from remote loader 0 X
write] and save them into inverter.
H93 A35D [Parameter 0~5 This parameter is used to initialize 0 X 8-32
initialize] parameters back to the factory default
value.
0 -
1 All parameter groups are
initialized to factory default
value.
2 Only Drive group is initialized.
3 Only Function group 1 is
initialized.
4 Only Function group 2 is
initialized.
5 Only I/O group is initialized.
H94 A35E [Password 0~ Password for H95-[Parameter lock]. Set 0 O 8-33
register] FFFF as Hexa value.
H95 A35F [Parameter 0~ This parameter is able to lock or unlock 0 O 8-33
lock] FFFF parameters by typing password
registered in H94.
5-17
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communi name range defaults
run
cation
I0 A400 [Jump code] 0 ~ 87 Sets the code number to jump. 1 O 4-5
I2 A402 [NV input 0 ~ -10 Sets the minimum voltage of the NV (- 0.00 O 7-2
Min voltage] [V] 10V~0V) input.
I3 A403 [Frequency 0 ~ 400 Sets the inverter output minimum 0.00 O
correspondi [Hz] frequency at minimum voltage of the NV
ng to I 2] input.
I4 A404 [NV input 0 ~ -10 Sets the maximum voltage of the NV 10.0 O
Max [V] input.
voltage]
I5 A405 [Frequency 0 ~ 400 Sets the inverter output maximum 60.00 O
correspondi [Hz] frequency at maximum voltage of the
ng to I 4] NV input.
I6 A406 [Filter time 0 ~ 9999 Adjusts the responsiveness of V1 input 10 O 7-2
constant for (0 ~ +10V).
V1 input]
I7 A407 [V1 input 0 ~ 10 Sets the minimum voltage of the V1 0 O
Min voltage] [V] input.
I8 A408 [Frequency 0 ~ 400 Sets the inverter output minimum 0.00 O
correspondi [Hz] frequency at minimum voltage of the V1
ng to I 7] input.
I9 A409 [V1 input 0 ~ 10 Sets the maximum voltage of the V1 10 O
Max [V] input.
voltage]
I10 A40A [Frequency 0 ~ 400 Sets the inverter output maximum 60.00 O
correspondi [Hz] frequency at maximum voltage of the
ng to I 9] V1 input.
I11 A40B [Filter time 0 ~ 9999 Sets the input section’s internal filter 10 O 7-4
constant for constant for I input.
I input]
I12 A40C [I input Min 0 ~ 20 Sets the minimum current of I input. 4.00 O
current] [mA]
I13 A40D [Frequency 0 ~ 400 Sets the inverter output minimum 0.00 O
correspondi [Hz] frequency at minimum current of I input.
ng to I 12]
I14 A40E [I input Max 0 ~ 20 Sets the Maximum current of I input. 20.00 O
current] [mA]
I15 A40F [Frequency 0 ~ 400 Sets the inverter output maximum 60.00 O 7-4
correspondi [Hz] frequency at maximum current of I
ng to I 14]
input.
I16 A410 [Criteria for 0~2 0: Disabled 0 O 10-7
Analog Input 1: activated below half of set value.
Signal loss] 2: activated below set value.
I17 A411 [Multi- 0 ~ 27 0 Forward run command 0 O 7-8
function
input
terminal P1 1 Reverse run command
define]
5-18
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communi name range defaults
run
cation
I19 A413 [Multi- 4 Jog operation command 2 O 8-3
function
input 5 Multi-Step freq – Low 7-7
terminal P3
define]
I20 A414 [Multi- 6 Multi-Step freq – Mid 3 O
function
input 7 Multi-Step freq – High
terminal P4
define]
I21 A415 [Multi- 8 Multi Accel/Decel – Low 4 O 7-14
function
input 9 Multi Accel/Decel – Mid
terminal P5
define]
I22 A416 [Multi- 10 Multi Accel/Decel – High 5 O
function
input 11 DC brake during stop 8-2
terminal P6
define]
I23 A417 [Multi- 12 2nd motor select 6 O 8-21
function
13 -Reserved- -
input
terminal P7
define]
I24 A418 [Multi- 14 -Reserved- 7 O -
function
input 15 Up- Frequency increase 8-4
terminal P8 down (UP)
define] command
16 Frequency decrease
command (DOWN)
17 3-wire operation 8-7
18 External trip: A Contact (EtA) 10-5
19 External trip: B Contact (EtB)
20 Self-diagnostic function 8-22
21 Change from PID operation to 8-10
V/F operation
22 nd
2 Source 8-24
23 Analog Hold 7-6
24 Accel/Decel Disable 7-16
25 Up/Down Save Freq. Initialization 8-4
26 JOG-FX 8-3
27 JOG-RX
* See “Chapter 14 Troubleshooting and maintenance” for External trip A/B contact.
* Each multi-function input terminal must be set differently.
5-19
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communic name range default
run
ation
I25 A419 [Input BIT BIT BIT BIT BIT BIT BIT BIT 0 O 9-3
terminal 7 6 5 4 3 2 1 0
status P8 P6 P5 P3 P2 P1
P7 P4
display]
I26 A41A [Output BIT1 BIT0 9-3
terminal O
0
status 3AC MO
display]
I27 A41B [Filtering 1 ~ 15 If the value is set higher, the 4 O -
time responsiveness of the Input terminal is
constant getting slower.
for Multi-
function
Input
terminal]
I30 A41E [Multi- 0 ~ 400 It cannot be set greater than F21 – [Max 30.00 7-7
Step [Hz] frequency].
O
frequency
4]
I31 A41F [Multi- 25.00
Step
O
frequency
5]
I32 A420 [Multi- 20.00
Step
O
frequency
6]
I33 A421 [Multi- 15.00
Step
O
frequency
7]
I34 A422 [Multi- 0~ 6000 3.0 O 7-14
Accel time [sec]
1]
I35 A423 [Multi- 3.0
Decel
time 1]
I36 A424 [Multi- 4.0
Accel time
2]
I37 A425 [Multi- 4.0
Decel
time 2]
I38 A426 [Multi- 5.0
Accel time
3]
I39 A427 [Multi- 5.0
Decel
time 3]
I40 A428 [Multi- 6.0
Accel time
4]
I41 A429 [Multi- 6.0
Decel
time 4]
5-20
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communic name range default
run
ation
I42 A42A [Multi- 7.0
Accel time
5]
I43 A42B [Multi- 7.0
Decel
time 5]
I44 A42C [Multi- 8.0
Accel time
6]
I45 A42D [Multi- 8.0
Decel
time 6]
I46 A42E [Multi- 9.0
Accel time
7]
I47 A42F [Multi- 9.0
Decel
time 7]
I50 A432 [Analog 0~3 Output Output to 10[V] 0 O 9-6
output item
item 200V 400V
select]
0 Output Max frequency
freq.
1 Output 150 %
current
2 Output AC 282V AC 564V
voltage
3 Inverter DC 400V DC 800V
DC link
voltage
I51 A433 [Analog 10~200 Based on 10V. 100 O 9-6
output [%]
level
adjustmen
t]
I52 A434 [Frequenc 0 ~ 400 Used when I54 or I55 is set to 0-4. 30.00 9-7
y [Hz] Cannot be set higher than F21.
O
detection
level]
I53 A435 [Frequenc 10.00
y
detection O
bandwidth
]
I54 A436 [Multi- 0 ~ 19 0 FDT-1 12 O 9-8
function FDT-2
1
output
terminal 2 FDT-3 9-9
select] FDT-4 17
3
I55 A437 [Multi- 4 FDT-5 9-10
function
relay 5 Overload (OLt) 9-10
select] 6 Inverter Overload (IOLt)
7 Motor stall (STALL)
5-21
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communic name range default
run
ation
8 Over voltage trip (Ovt)
9 Low voltage trip (Lvt)
11 Command loss
13 During Stop
5-22
Input/Output Group
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display commun er name range defaults
run
ication
I56 A438 [Fault 0~7 When When the When the 2 O 9-7
relay setting the trip other low voltage
output] H26– than low trip occurs
[Number of voltage trip
auto occurs
restart try]
Bit 2 Bit 1 Bit 0
0 - - -
1 - -
2 - -
3 -
4 - -
5 -
6 -
7
I57 A439 [Output 0~3 Multi-function Multi-function 0 O 9-12
terminal relay output terminal
select Bit 1 Bit 0
when
0 - -
commun
ication
1 -
error
2 -
occurs]
3
5-23
Input/Output Group
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display commun er name range defaults
run
ication
I64 A440 [Commu 2 ~ 100 Frame communication time 5 O -
nication [ms]
time
setting]
I65 A441 [Parity/st When the protocol is set, the O O -
op bit communication format can be set.
setting] 0 Parity: None, Stop Bit: 1
0~3
1 Parity: None, Stop Bit: 2
2 Parity: Even, Stop Bit: 1
3 Parity: Odd, Stop Bit: 1
I66 A442 [Read 5 O 11-11
address
register
1]
I67 A443 [Read 6
address
register
2]
I68 A444 [Read 7
address
register
3]
I69 A445 [Read 8
address
register
4] The user can register up to 8
0~42239 discontinuous addresses and read them all
I70 A446 [Read with one Read command. 9
address
register
5]
I71 A447 [Read 10
address
register
6]
I72 A448 [Read 11
address
register
7]
I73 A449 [Read 12
address
register
8]
I74 A44A [Write The user can register up to 8 5 O 11-11
address 0~42239 discontinuous addresses and write them
register all with one Write command
1]
I75 A44B [Write 6
address
register
2]
I76 A44C [Write 7
address
register
3]
5-24
Input/Output Group
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display commun er name range defaults
run
ication
I77 A44D [Write 8
address
register
4]
I78 A44E [Write 5
address
register
5]
I79 A44F [Write 6
address
register
6]
I80 A450 [Write 7
address
register
7]
I81 A451 [Write 8
address
register
8]
1821) A452 [Brake 0~180 Sets current level to open the brake. 50.0 O 8-26
open [%] It is set according to H33’s (motor rated
current] current) size
183 A453 [Brake 0~10 Sets Brake open delay time. 1.00 X
open [s]
delay
time]
184 A454 [Brake 0~400 Sets FX frequency to open the brake 1.00 X
open FX [Hz]
frequenc
y]
185 A455 [Brake 0~400 Sets RX frequency to open the brake 1.00 X
open RX [Hz]
frequenc
y]
186 A456 [Brake 0~19 Sets delay time to close the brake 1.00 X
close [s]
delay
time]
187 A457 [Brake 0~400 Sets frequency to close the brake 2.00 X
close [Hz]
frequenc
y
1):
It is indicated when choosing I54~I55 as a 19 (Brake signal).
5-25