CHAPTER 5 - FUNCTION LIST

Drive Group
Address
Min/M Adj.
LED for Parameter Factory
ax Description during Page
display communi name defaults
range run
cation
0.00 A100 [Frequency 0~ This parameter sets the frequency that the 0.00 O 7-1
command] 400 inverter is commanded to output.
[Hz] During Stop: Frequency Command
During Run: Output Frequency
During Multi-step operation:
Multi-step frequency 0.
It cannot be set greater than F21- [Max
frequency].
ACC A101 [Accel 0~ During Multi-Accel/Decel operation, this 5.0 O 7-12
time] 6000 parameter serves as Accel/Decel time 0.
dEC A102 [Decel [Sec] 10.0 O 7-12
time]
drv A103 [Drive 0~4 0 Run/Stop via Run/Stop key on the keypad 1 X 7-8
mode]
FX: Motor forward run 7-8
1
TerminalRX: Motor reverse run
operation
FX: Run/Stop enable
2
RX: Reverse rotation select
3 RS485 communication 7-9
4 Set to Field Bus communication 1) -
Frq A104 [Frequency 0~9 0 Digital Keypad setting 1 0 X 7-1
setting 1 Keypad setting 2 7-1
method]
2 V1 1: -10 ~ +10 [V] 7-2
3 V1 2: 0 ~ +10 [V] 7-3
4 Terminal I: 0 ~ 20 [mA] 7-4
Analog Terminal V1 setting 1 + 7-5
5
Terminal I
Terminal V1 setting 2+ 7-6
6
Terminal I
7 RS485 communication 7-5
8 Digital Volume 7-6
9 Set to Field Bus communication 1) -
St1 A105 [Multi-Step 0~ Sets Multi-Step frequency 1 during Multi-step 10.00 O 7-7
frequency 400 operation.
1] [Hz]
St2 A106 [Multi-Step Sets Multi-Step frequency 2 during Multi-step 20.00 O 7-7
frequency operation.
2]
St3 A107 [Multi-Step Sets Multi-Step frequency 3 during Multi-step 30.00 O 7-7
frequency operation.
3]
CUr A108 [Output Displays the output current to the motor. - - 9-1
current]
rPM A109 [Motor Displays the number of Motor RPM. - - 9-1
RPM]
dCL A10A [Inverter Displays DC link voltage inside the inverter. - - 9-1
DC link
voltage]
1)
: This function can be available with iG5A Communication Option Module.

5-1
Drive Group
Address
Min/M Adj.
LED for Parameter Factory
ax Description during Page
display communi name defaults
range run
cation
vOL A10B [User This parameter displays the item selected at vOL - 9-2
display H73- [Monitoring item select].
select] vOL Output voltage
POr Output power
tOr Torque
nOn A10C [Fault Displays the types of faults, frequency and - - 9-4
Display] operating status at the time of the fault
drC A10D [Direction F, r Sets the direction of motor rotation when drv - F O 7-8
of motor [Drive mode] is set to either 0 or 1.
rotation F Forward
select]
r Reverse
drv2 A10E [Drive 0~4 0 Run/Stop via Run/Stop key on the keypad 1 X 8-24
mode 2]
Terminal FX: Motor forward run
1
operationRX: Motor reverse run
FX: Run/Stop enable
2
RX: Reverse rotation select
3 RS-485 communication
4 Set to Filed Bus Communication 3)
1)
Frq2 A10F [Frequency 0~9 0 Digital Keypad setting 1 0 X 8-24
setting 1 Keypad setting 2
method 2]
2 Analog V1 1: -10 ~ +10 [V]
3 V1 2: 0 ~ +10 [V]
4 Terminal I: 0 ~ 20 [mA]
Terminal V1 setting 1 +
5
Terminal I
Terminal V1 setting 2+
6
Terminal I
7 RS485 communication
8 Digital Volume
9 Set to Filed Bus Communication 3)
2)
rEF A110 PID control 0~400 If H58 is 0, it is expressed as a [Hz] unit. 0.00 0 8-11
standard [Hz] or If H58 is 1, it is expressed as a [%] unit.
value 0~100 In [Hz] unit, you can’t set Max. frequency
setting [%] more than (F21).
In [%] unit, 100% means Max. frequency.
Fbk2) A111 PID control It indicates a feedback amount in PID - - 8-11
feedback control.
amount If H58 is 0, it is expressed as a [Hz] unit.
If H58 is 1, it is expressed as a [%] unit.
1)
: Only displayed when one of the Multi-function input terminals 1-8 [I17~I24] is set to “22”.
2)
: It is indicated when H49(PID control selection) is 1.
3)
: This function can be available with iG5A Communication Option Module.

5-2
Function group 1
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display communi er name range defaults
run
cation
F0 A200 [Jump 0 ~ 71 Sets the parameter code number to jump. 1 O 4-5
code]
F1 [Forwar 0~2 0 Fwd and rev run enable 0 X 7-10
d/
A201 1 Forward run disable
Reverse
run Reverse run disable
2
disable]
F2 A202 [Accel 0~1 Linear 0 X 7-15
0
pattern]
F3 A203 [Decel S-curve
1
pattern]
F4 A204 [Stop 0~3 0 Decelerate to stop 0 X 7-20
mode 1 DC brake to stop
select]
2 Free run to stop
3 Power Braking stop 8-26
1)
F8 A208 [DC 0.1 ~ 60 This parameter sets DC brake start 5.00 X 8-1
Brake [Hz] frequency.
start It cannot be set below F23 - [Start
frequen frequency].
cy]
F9 A209 [DC 0 ~ 60 When DC brake frequency is reached, 0.1 X
Brake [sec] the inverter holds the output for the
wait setting time before starting DC brake.
time]
F10 A20A [DC 0 ~ 200 This parameter sets the amount of DC 50 X
Brake [%] voltage applied to a motor.
voltage] It is set in percent of H33 – [Motor rated
current].
F11 A20B [DC 0 ~ 60 This parameter sets the time taken to 1.0 X
Brake [sec] apply DC current to a motor while motor
time] is at a stop.
F12 A20C [DC 0 ~ 200 This parameter sets the amount of DC 50 X 8-2
Brake [%] voltage before a motor starts to run.
start It is set in percent of H33 – [Motor rated
voltage] current].
F13 A20D [DC 0 ~ 60 DC voltage is applied to the motor for DC 0 X
Brake [sec] Brake start time before motor
start accelerates.
time]
F14 A20E [Time 0 ~ 60 This parameter applies the current to a 0.1 X 8-15
for [sec] motor for the set time before motor
magneti accelerates during Sensorless vector
zing a control.
motor]
F20 A214 [Jog 0 ~ 400 This parameter sets the frequency for 10.00 O 8-3
frequen [Hz] Jog operation.
cy] It cannot be set above F21 – [Max
frequency].
1)
: Only displayed when F 4 is set to 1 (DC brake to stop).

5-3
Function group 1
Address
Adj.
LED for Paramete Min/Max Factory
Description during Page
display communi r name range defaults
run
cation
F211) A215 [Max 40 ~ 400 This parameter sets the highest frequency 60.00 X 7-21
frequency [Hz] the inverter can output.
] It is frequency reference for Accel/Decel
(See H70)

Caution

Any frequency cannot be set above Max


frequency except Base frequency

F22 A216 [Base 30 ~ 400 The inverter outputs its rated voltage to the 60.00 X 7-17
frequency [Hz] motor at this frequency (see motor
] nameplate).
F23 A217 [Start 0.1 ~ 10 The inverter starts to output its voltage at 0.50 X 7-21
frequency [Hz] this frequency.
] It is the frequency low limit.
F24 A218 [Frequen 0~1 This parameter sets high and low limit of 0 X 7-21
cy run frequency.
high/low
limit
select]
F25 A219 [Frequen 0 ~ 400 This parameter sets high limit of the run 60.00 X
2)
cy high [Hz] frequency.
limit] It cannot be set above F21 – [Max
frequency].
F26 A21A [Frequen 0.1 ~ 400 This parameter sets low limit of the run 0.50 X
cy low [Hz] frequency.
limit] It cannot be set above F25 - [Frequency
high limit] and below F23 – [Start
frequency].
F27 A21B [Torque 0~1 0 Manual torque boost 0 X 7-19
Boost 1 Auto torque boost
select]
F28 A21C [Torque 0 ~ 15 This parameter sets the amount of torque 2 X 7-19
boost in [%] boost applied to a motor during forward
forward run.
direction] It is set in percent of Max output voltage.
F29 A21D [Torque This parameter sets the amount of torque 2 X 7-19
boost in boost applied to a motor during reverse
reverse run.
direction] It is set as a percent of Max output voltage
1)
: If H40 is set to 3 (Sensorless vector), Max. frequency is settable up to 300Hz.
2)
: Only displayed when F24 (Frequency high/low limit select) is set to 1.

5-4
Function group 1
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu name range defaults
run
nication
F30 A21E [V/F 0~2 0 {Linear} 0 X 7-17
pattern] 1 {Square} 7-17
2 {User V/F} 7-18
F311) A21F [User V/F 0 ~ 400 It is used only when V/F pattern is set to 15.00 X 7-18
frequency [Hz] 2(User V/F)
1] It cannot be set above F21 – [Max
F32 A220 [User V/F 0 ~ 100 frequency]. 25 X
voltage 1] [%] The value of voltage is set in percent of
H70 – [Motor rated voltage].
F33 A221 [User V/F 0 ~ 400 The values of the lower-numbered 30.00 X
frequency [Hz] parameters cannot be set above those of
2] higher-numbered.
F34 A222 [User V/F 0 ~ 100 50 X
voltage 2] [%]
F35 A223 [User V/F 0 ~ 400 45.00 X
frequency [Hz]
3]
F36 A224 [User V/F 0 ~ 100 75 X
voltage 3] [%]
F37 A225 [User V/F 0 ~ 400 60.00 X
frequency [Hz]
4]
F38 A226 [User V/F 0 ~ 100 100 X
voltage 4] [%]
F39 A227 [Output 40 ~ 110 This parameter adjusts the amount of 100 X 7-18
voltage [%] output voltage.
adjustment The set value is the percentage of input
] voltage.
F40 A228 [Energy- 0 ~ 30 This parameter decreases output voltage 0 0 8-17
saving [%] according to load status.
level]
F50 A232 [Electronic 0~1 This parameter is activated when the 0 0 10-1
thermal motor is overheated (time-inverse).
select]
1)
: Set F30 to 2(User V/F) to display this parameter.

5-5
Function group 1
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu name range defaults
run
nication
F51 A233 [Electronic 50 ~ 200 This parameter sets max current capable of 150 0 10-1
1)
thermal [%] flowing to the motor continuously for 1 minute.
level for 1 The set value is the percentage of H33 –
minute] [Motor rated current].
It cannot be set below F52 –[Electronic thermal
level for continuous].
F52 A234 [Electronic 50 ~ 150 This parameter sets the amount of current to 100 0
thermal [%] keep the motor running continuously.
level for It cannot be set higher than F51 – [Electronic
continuous] thermal level for 1 minute].
F53 A235 [Motor 0~1 0 Standard motor having cooling fan 0 0
cooling directly connected to the shaft
method]
1 A motor using a separate motor to
power a cooling fan.
F54 A236 [Overload 30 ~ 150 This parameter sets the amount of current to 150 0 10-2
warning [%] issue an alarm signal at a relay or multi-
function output terminal (see I54, I55).
level]
The set value is the percentage of H33- [Motor
rated current].
F55 A237 [Overload 0 ~ 30 [Sec] This parameter issues an alarm signal when 10 0
warning the current greater than F54- [Overload
time] warning level] flows to the motor for F55-
[Overload warning time].
F56 A238 [Overload 0~1 This parameter turns off the inverter output 1 0 10-2
trip select] when motor is overloaded.
F57 A239 [Overload 30 ~ 200 This parameter sets the amount of overload 180 0
trip level] [%] current.
The value is the percentage of H33- [Motor
rated current].
F58 A23A [Overload 0 ~ 60 [Sec] This parameter turns off the inverter output 60 0
trip time] when the F57- [Overload trip level] of current
flows to the motor for F58- [Overload trip time].
1)
: Set F50 to 1 to display this parameter.

5-6
Function group 1
Address
Adj.
LED for Paramete Min/Max Factory
Description during Page
display commun r name range defaults
run
ication
F59 A23B [Stall 0~7 This parameter stops accelerating during 0 X 10-3
preventio acceleration, decelerating during constant
speed run and stops decelerating during
n select]
deceleration.
During During During Accel
Decel constant
run
Bit 2 Bit 1 Bit 0
0 - - -
1 - -
2 - -
3 -
4 - -
5 -
6 -
7
F60 A23C [Stall 30 ~ This parameter sets the amount of current to 150 X 10-3
preventio 200 activate stall prevention function during Accel,
n level] [%] Constant or Decel run.
The set value is the percentage of the H33-
[Motor rated current].
F61 A23D [When 0~1 In Stall prevention run during deceleration, if 8-26
1) Stall you want to limit output voltage, select 1
preventio
n during
decelerati
on,
voltage
limit
select
F63 A23F [Save 0~1 This parameter decides whether to save the 0 X 8-4
up/down specified frequency during up/down
frequency operation.
select] When 1 is selected, the up/down frequency is
saved in F64.
F64 A240 [Save If ‘Save up/down frequency’ is selected at 0.00 X 8-4
2)
up/down F63, this parameter saves the frequency
frequency before the inverter stops or decelerated.
]
F65 A241 [Up-down 0~2 We can select up-down mode among three 0 X 8-5
mode thing
select] 0 Increases goal frequency as a
standard of Max. frequency/Min.
frequency
1 Increases as many as step
frequency according to edge input
2 Available to combine 1 and 2
1)
: It is indicated when setting bit 2 of F59 as 1
2)
: Set F63 to 1 to display this parameter.

5-7
Function group 1
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commun name range defaults
run
ication
F66 A242 [Up-down 0~400[ In case of choosing F65 as a 1 or 2, it means 0.00 X 8-5
step Hz] increase or decrease of frequency according
frequency] to up-down input
F70 A246 [Draw run 0~3 0 Inverter doesn’t run as a draw 0 X 8-28
mode mode
select] 1 V1(0~10V) input draw run
2 I(0~20mA) input draw run
3 V1(-10~10V) input draw run
F71 A247 [Draw rate] 0~100[ Sets rate of draw 0.00 0 8-28
%]

5-8
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu name range defaults
run
nication

H0 A300 [Jump 0~95 Sets the code number to jump. 1 4-5


O
code]
H1 A301 [Fault - Stores information on the types of faults, nOn 9-4
-
history 1] the frequency, the current and the
H2 A302 [Fault - Accel/Decel condition at the time of fault. nOn
The latest fault is automatically stored in -
history 2]
the H 1- [Fault history 1].
H3 A303 [Fault - nOn
-
history 3]
H4 A304 [Fault - nOn
-
history 4]
H5 A305 [Fault - nOn
-
history 5]
H6 A306 [Reset 0~1 Clears the fault history saved in H 1-5. 0
fault O
history]
H7 A307 [Dwell 0.1~400 When run frequency is issued, motor 5.00 X 8-7
frequency] [Hz] starts to accelerate after dwell frequency
is applied to the motor during H8- [Dwell
time].
[Dwell frequency] can be set within the
range of F21- [Max frequency] and F23-
[Start frequency].
H8 A308 [Dwell 0~10 Sets the time for dwell operation. 0.0 X
time] [sec]
H10 A30A [Skip 0~1 Sets the frequency range to skip to 0 X 7-22
frequency prevent undesirable resonance and
select] vibration on the structure of the machine.
H111) A30B [Skip 0.1~400 Run frequency cannot be set within the 10.00 X
frequency [Hz] range of H11 thru H16. The frequency
low limit 1] values of the low numbered parameters
H12 A30C [Skip cannot be set above those of the high 15.00 X
frequency numbered ones. Settable within the
high limit range of F21 and F23.
1]
H13 A30D [Skip 20.00 X
frequency
low limit 2]
H14 A30E [Skip 25.00 X
frequency
high limit
2]
H15 A30F [Skip 30.00 X
frequency
low limit 3]
H16 A310 [Skip 35.00 X
frequency
high limit
3]
1)
: only displayed when H10 is set to 1. # H17, H18 are used when F2, F3 are set to 1 (S-curve).

5-9
Function group 2
Adj.
LED Address for Parameter Min/Max Factory
Description during Page
display communication name range defaults
run
H17 A311 [S-Curve 1~100 Set the speed reference value to form a 40 X 7-15
accel/decel [%] curve at the start during accel/decel. If it is
start side]
set higher, linear zone gets smaller.
H18 A312 [S-Curve 1~100 Set the speed reference value to form a 40 X
accel/decel [%] curve at the end during accel/decel. If it is set
end side] higher, linear zone gets smaller.
H19 A313 [Input/output 0~3 0 Disabled 1 Output phase 0 O 10-4
phase loss protection
protection 2 Input 3 Input/output phase
select] phase protection
protection
H20 A314 [Power On 0~1 This parameter is activated when drv is set to 0 O 7-11
Start select] 1 or 2 (Run/Stop via Control terminal).
Motor starts acceleration after AC power is
applied while FX or RX terminal is ON.

H21 A315 [Restart 0 ~1 This parameter is activated when drv is set to 0 O 7-11
after fault 1 or 2 (Run/Stop via Control terminal).
reset Motor accelerates after the fault condition is
selection] reset while the FX or RX terminal is ON.

H22 [Speed 0 ~ 15 This parameter is active to prevent any 0 O 8-17


1)
Search possible fault when the inverter outputs its
Select] voltage to the running motor.
1. H20- 2. 3. 4.
[Power Restart Operation Normal
accel
On start] after after fault
instant
power
failure
Bit 3 Bit 2 Bit 1 Bit 0
0 - - - -
1 - - -
2 - - -
3 - -
4 - - -
1)
Normal acceleration has first priority. Even though #4 is selected along with other bits, Inverter performs Speed search
#4.

5-10
Function group 2
Address Factor
Adj.
LED for Paramete Min/Max y
Description during Page
display communic r name range default
run
ation s
H22 A316 1. H20- 2. 3. 4. O 8-17
1)
[Power Restart Operati Nor
mal
On after on after
accel
start] instant fault
power
failure
Bit 3 Bit 2 Bit 1 Bit 0
5 - -
6 - -
7 -
8 - - -
9 - -
10 - -
11 -
12 - -
13 -
14 -
15
H23 A317 [Current 80~200 This parameter limits the amount of current 100 O 8-17
level [%] during speed search.
during The set value is the percentage of the H33-
Speed [Motor rated current].
search]
H24 A318 [P gain 0~9999 It is the Proportional gain used for Speed 100 O
during Search PI controller.
Speed
search]
H25 A319 [I gain 0~9999 It is the Integral gain used for Speed search 200 O
during PI controller.
speed
search]
H26 A31A [Number 0 ~10 This parameter sets the number of restart 0 O 8-20
of Auto tries after a fault occurs.
Restart Auto Restart is deactivated if the fault
try] outnumbers the restart tries.
This function is active when [drv] is set to 1 or
2 {Run/Stop via control terminal}.
Deactivated during active protection function
(OHT, LVT, EXT, HWT etc.).

5-11
Function group 2
Address
LED for Parameter Min/Max Factory Adj.
Description Page
display communi name range defaults during run
cation
H27 A31B [Auto Restart 0~60 [sec] This parameter sets the time 1.0 O 8-20
time] between restart tries.
H30 A31E [Motor type 0.2~ 22.0 0.2 0.2kW 7.51) X 8-16
select] ~ ~
22.0 22.0kW
H31 A31F [Number of 2 ~ 12 This setting is displayed via rPM 4 X
motor poles] in drive group.

H32 A320 [Rated slip 0 ~ 10 2.33 2) X


⎛ rpm × P ⎞
frequency] [Hz] fs = fr − ⎜ ⎟
⎝ 120 ⎠
Where, f s = Rated slip frequency
f r = Rated frequency
rpm = Motor nameplate
RPM
P = Number of Motor
poles

H33 A321 [Motor rated 0.5~150 Enter motor rated current on the 26.3 X
current] [A] nameplate.
H34 A322 [No Load 0.1~ 50 [A] Enter the current value detected 11 X
Motor Current] when the motor is rotating in rated
rpm after the load connected to
the motor shaft is removed.
Enter the 50% of the rated current
value when it is difficult to
measure H34 – [No Load Motor
Current].
H36 A324 [Motor 50~100 Enter the motor efficiency (see 87 X
efficiency] [%] motor nameplate).
H37 A325 [Load inertia 0~2 Select one of the following 0 X 8-1
rate] according to motor inertia.

0 Less than 10 times


1 About 10 times
2 More than 10 times
1)
: H30 is preset based on inverter rating.
2)
: H32 ~ H36 factory default values are set based on OTIS-LG motor.

5-12
Function group 2
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display communi er name range defaults
run
cation
H39 A327 [Carrier 1 ~ 15 This parameter affects the audible sound 3 O 8-21
frequen [kHz] of the motor, noise emission from the
cy inverter, inverter temp, and leakage
select] current. If the set value is higher, the
inverter sound is quieter but the noise
from the inverter and leakage current will
become greater.
H40 A328 [Control 0~3 0 {Volts/frequency Control} 0 X 7-17
mode 1 {Slip compensation control} 8-8
select]
3 {Sensorless vector control} 8-15
H41 A329 [Auto 0~1 If this parameter is set to 1, it 0 X 8-14
tuning] automatically measures parameters of
the H42 and H44.
H42 A32A [Stator 0 ~ 28 This is the value of the motor stator - X
resistan [Ω] resistance.
ce (Rs)]
H44 A32C [Leakage 0~ 300.0 This is leakage inductance of the stator - X
inductanc [mH] and rotor of the motor.
e (Lσ)]
H45 A32D [Sensorl 0~ 32767 P gain for Sensorless control 1000 O
1)
ess P
gain]
H46 A32E [Sensorl I gain for Sensorless control 100 O
ess I
gain]
H47 A32F [Sensorl 100~220[ Limits output torque in sensorless mode,. 180.0 X
ess %]
torque
limit]
H48 A330 PWM 0~1 If you want to limit a inverter leakage 0 X 8-30
mode current, select 2 phase PWM mode.
select It has more noise in comparison to
Normal PWM mode.
0 Normal PWM mode
1 2 phase PWM mode
H49 A331 PID 0~1 Selects whether using PID control or not 0 X 8-10
select
H50 A332 [PID F/B 0~1 0 Terminal I input (0 ~ 20 mA) 0 X 8-10
2)
select] 1 Terminal V1 input (0 ~ 10 V)
H51 A333 [P gain 0~ 999.9 This parameter sets the gains for the PID 300.0 O
for PID] [%] controller.
H52 A334 [Integral 0.1~32.0 1.0 O
time for [sec]
PID
H53 A335 [Differen 0 ~ 30.0 0.0 O
tial time [sec]
for PID
(D
gain)]
H54 A336 [PID 0~1 Selects PID control mode 0 X 8-10
control 0 Normal PID control
mode
select] 1 Process PID control
1)
: Set H40 to 3 (Sensorless vector control) to display this parameter.
2)
: Set H49 to 1 (PID control) to display this parameter.

5-13
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu- name range defaults
run
nication
H55 A337 [PID output 0.1 ~ This parameter limits the amount of the 60.00 O 8-10
frequency 400 output frequency through the PID control.
high limit] [Hz] The value is settable within the range of
F21 – [Max frequency] and F23 – [Start
H56 A338 [PID output 0.1 ~ frequency]. 0.50 O
frequency 400
low limit] [Hz]

H57 A339 [PID 0~4 Selects PID standard value. 0 X 8-10


standard Standard value is indicated in “rEF” of
value select] Drive group.
0 Loader digital setting 1
1 Loader digital setting 2
2 V1 terminal setting 2: 0~10V
3 I terminal setting: 0~20mA
4 Setting as a RS-485
communication
H58 A33A PID control 0~1 Selects a unit of the standard value or 0 X
unit select feedback amount.
0 Frequency[Hz]
1 Percentage[%]
H60 A33C [Self- 0~3 0 Self-diagnostic disabled 0 X 8-22
diagnostic
select] 1 IGBT fault/Ground fault

2 Output phase short & open/


Ground fault
3 Ground fault (This setting is
unable when more than 11kW)
H611) A33D [Sleep delay 0~2000[ Sets a sleep delay time in PID drive. 60.0 X 8-13
time] s]
H62 A33E [Sleep 0~400[H Sets a sleep frequency when executing a 0.00 O
frequency] z] sleep function in PID control drive.
You can’t set more than Max.
frequency(F21)
H63 A33F [Wake up 0~100[ Sets a wake up level in PID control drive. 35.0 O
level] %]
H64 A340 [KEB drive 0~1 Sets KEB drive. 0 X 8-28
select]
H65 A341 [KEB action 110~140 Sets KEB action start level according to 125.0 X
start level] [%] level.
H66 A342 [KEB action 110~145 Sets KEB action stop level according to 130.0 X
stop level] [%] level.

(KEB does not operate when cut power after loading ting input (about 10%).

5-14
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu- name range defaults
run
nication
H67 A343 [KEB action 1~2000 Sets KEB action gain. 1000 X 8-28
gain] 0
H70 A346 [Frequency 0~1 0 Based on Max freq (F21) 0 X 7-12
Reference
for 1 Based on Delta freq.
Accel/Decel]
H71 A347 [Accel/Decel 0~2 0 Settable unit: 0.01 second. 1 O 7-13
time scale]
1 Settable unit: 0.1 second.

2 Settable unit: 1 second.

H72 A348 [Power on 0 ~ 15 This parameter selects the parameter to 0 O 9-2


display] be displayed on the keypad when the
input power is first applied.
0 Frequency command
1 Accel time
2 Decel time
3 Drive mode
4 Frequency mode
5 Multi-Step frequency 1
6 Multi-Step frequency 2
7 Multi-Step frequency 3
8 Output current
9 Motor rpm
10 Inverter DC link voltage
11 User display select (H73)
12 Fault display
13 Direction of motor rotation
select

14 Output current 2
15 Motor rpm 2
16 Inverter DC link voltage 2
17 User display select 2
H73 A349 [Monitoring 0~2 One of the following can be monitored 0 O 9-2
item select] via vOL - [User display select].

0 Output voltage [V]


1 Output power [kW]
2 Torque [kgf ⋅ m]
H74 A34A [Gain for 1~ This parameter is used to change the 100 O 9-1
Motor rpm 1000 motor rotating speed (r/min) to
display] [%] mechanical speed (m/mi) and display it.
H75 A34B [DB resistor 0~1 0 Unlimited 1 O 10-8
operating
rate limit 1 Use DB resistor for the H76 set
select] time.

5-15
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu- name range defaults
run
nication
H76 A34C [DB resistor 0~ Set the percent of DB resistor operating 10 O
operating 30[%] rate to be activated during one sequence
rate] of operation.

H771) A34D [Cooling fan 0~1 0 Always ON 0 O 8-30


control]
1 Keeps ON when its temp is
higher than inverter protection
limit temp.
Activated only during operation
when its temp is below that of
inverter protection limit.
H78 A34E [Operating 0~1 0 Continuous operation when 0 O 8-31
method cooling fan malfunctions.
select when
cooling fan 1 Operation stopped when
malfunctions cooling fan malfunctions.
]
H79 A34F [S/W 0 ~ 10.0 This parameter displays the inverter 1.0 X -
version] software version.
H812) A351 [2nd motor 0~ This parameter actives when the 5.0 O 8-21
Accel time] 6000 selected terminal is ON after I17-I24 is
H82 A352 [2nd motor [sec] set to 12 {2nd motor select}. 10.0 O
Decel time]
H83 A353 [2nd motor 30 ~ 60.00 X
base 400 [Hz]
frequency]
H84 A354 [2nd motor 0~2 0 X
V/F pattern]
H85 A355 [2nd motor 0 ~ 15 5 X
forward [%]
torque
boost]
H86 A356 [2nd motor 5 X
reverse
torque
boost]
H87 A347 [2nd motor 30~150 150 X 8-21
stall [%]
prevention
level]
1)
Exception: Since SV004iG5A-2/SV004iG5A-4 is Natural convection type, this code is hidden.
2) nd
: It is indicated when choosing I17~I24 as a 12 (2 motor select).

5-16
Function group 2
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display commu- name range defaults
run
nication
nd
H88 A358 [2 motor 50~200 150 O
Electronic [%]
thermal
level for 1
min]
H89 A359 [2nd motor 50~150 100 O
Electronic [%]
thermal
level for
continuous]
nd
H90 A35A [2 motor 0.1~100 26.3 X
rated [A]
current]
H911) A35B [Parameter 0~1 Copy the parameters from inverter and 0 X 8-32
read] save them into remote loader.
H92 A35C [Parameter 0~1 Copy the parameters from remote loader 0 X
write] and save them into inverter.
H93 A35D [Parameter 0~5 This parameter is used to initialize 0 X 8-32
initialize] parameters back to the factory default
value.
0 -
1 All parameter groups are
initialized to factory default
value.
2 Only Drive group is initialized.
3 Only Function group 1 is
initialized.
4 Only Function group 2 is
initialized.
5 Only I/O group is initialized.
H94 A35E [Password 0~ Password for H95-[Parameter lock]. Set 0 O 8-33
register] FFFF as Hexa value.
H95 A35F [Parameter 0~ This parameter is able to lock or unlock 0 O 8-33
lock] FFFF parameters by typing password
registered in H94.

UL (Unlock) Parameter change


enable
L (Lock) Parameter change
disable
1)
H91,H92 parameters are displayed when Remote option is installed.

5-17
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communi name range defaults
run
cation
I0 A400 [Jump code] 0 ~ 87 Sets the code number to jump. 1 O 4-5

I2 A402 [NV input 0 ~ -10 Sets the minimum voltage of the NV (- 0.00 O 7-2
Min voltage] [V] 10V~0V) input.
I3 A403 [Frequency 0 ~ 400 Sets the inverter output minimum 0.00 O
correspondi [Hz] frequency at minimum voltage of the NV
ng to I 2] input.
I4 A404 [NV input 0 ~ -10 Sets the maximum voltage of the NV 10.0 O
Max [V] input.
voltage]
I5 A405 [Frequency 0 ~ 400 Sets the inverter output maximum 60.00 O
correspondi [Hz] frequency at maximum voltage of the
ng to I 4] NV input.
I6 A406 [Filter time 0 ~ 9999 Adjusts the responsiveness of V1 input 10 O 7-2
constant for (0 ~ +10V).
V1 input]
I7 A407 [V1 input 0 ~ 10 Sets the minimum voltage of the V1 0 O
Min voltage] [V] input.
I8 A408 [Frequency 0 ~ 400 Sets the inverter output minimum 0.00 O
correspondi [Hz] frequency at minimum voltage of the V1
ng to I 7] input.
I9 A409 [V1 input 0 ~ 10 Sets the maximum voltage of the V1 10 O
Max [V] input.
voltage]
I10 A40A [Frequency 0 ~ 400 Sets the inverter output maximum 60.00 O
correspondi [Hz] frequency at maximum voltage of the
ng to I 9] V1 input.
I11 A40B [Filter time 0 ~ 9999 Sets the input section’s internal filter 10 O 7-4
constant for constant for I input.
I input]
I12 A40C [I input Min 0 ~ 20 Sets the minimum current of I input. 4.00 O
current] [mA]
I13 A40D [Frequency 0 ~ 400 Sets the inverter output minimum 0.00 O
correspondi [Hz] frequency at minimum current of I input.
ng to I 12]
I14 A40E [I input Max 0 ~ 20 Sets the Maximum current of I input. 20.00 O
current] [mA]
I15 A40F [Frequency 0 ~ 400 Sets the inverter output maximum 60.00 O 7-4
correspondi [Hz] frequency at maximum current of I
ng to I 14]
input.
I16 A410 [Criteria for 0~2 0: Disabled 0 O 10-7
Analog Input 1: activated below half of set value.
Signal loss] 2: activated below set value.
I17 A411 [Multi- 0 ~ 27 0 Forward run command 0 O 7-8
function
input
terminal P1 1 Reverse run command
define]

I18 A412 [Multi- 2 Emergency Stop Trip 1 O -


function
input
terminal P2 3 Reset when a fault occurs {RST} -
define]

5-18
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communi name range defaults
run
cation
I19 A413 [Multi- 4 Jog operation command 2 O 8-3
function
input 5 Multi-Step freq – Low 7-7
terminal P3
define]
I20 A414 [Multi- 6 Multi-Step freq – Mid 3 O
function
input 7 Multi-Step freq – High
terminal P4
define]
I21 A415 [Multi- 8 Multi Accel/Decel – Low 4 O 7-14
function
input 9 Multi Accel/Decel – Mid
terminal P5
define]
I22 A416 [Multi- 10 Multi Accel/Decel – High 5 O
function
input 11 DC brake during stop 8-2
terminal P6
define]
I23 A417 [Multi- 12 2nd motor select 6 O 8-21
function
13 -Reserved- -
input
terminal P7
define]
I24 A418 [Multi- 14 -Reserved- 7 O -
function
input 15 Up- Frequency increase 8-4
terminal P8 down (UP)
define] command
16 Frequency decrease
command (DOWN)
17 3-wire operation 8-7
18 External trip: A Contact (EtA) 10-5
19 External trip: B Contact (EtB)
20 Self-diagnostic function 8-22
21 Change from PID operation to 8-10
V/F operation
22 nd
2 Source 8-24
23 Analog Hold 7-6
24 Accel/Decel Disable 7-16
25 Up/Down Save Freq. Initialization 8-4
26 JOG-FX 8-3
27 JOG-RX
* See “Chapter 14 Troubleshooting and maintenance” for External trip A/B contact.
* Each multi-function input terminal must be set differently.

5-19
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communic name range default
run
ation
I25 A419 [Input BIT BIT BIT BIT BIT BIT BIT BIT 0 O 9-3
terminal 7 6 5 4 3 2 1 0
status P8 P6 P5 P3 P2 P1
P7 P4
display]
I26 A41A [Output BIT1 BIT0 9-3
terminal O
0
status 3AC MO
display]
I27 A41B [Filtering 1 ~ 15 If the value is set higher, the 4 O -
time responsiveness of the Input terminal is
constant getting slower.
for Multi-
function
Input
terminal]
I30 A41E [Multi- 0 ~ 400 It cannot be set greater than F21 – [Max 30.00 7-7
Step [Hz] frequency].
O
frequency
4]
I31 A41F [Multi- 25.00
Step
O
frequency
5]
I32 A420 [Multi- 20.00
Step
O
frequency
6]
I33 A421 [Multi- 15.00
Step
O
frequency
7]
I34 A422 [Multi- 0~ 6000 3.0 O 7-14
Accel time [sec]
1]
I35 A423 [Multi- 3.0
Decel
time 1]
I36 A424 [Multi- 4.0
Accel time
2]
I37 A425 [Multi- 4.0
Decel
time 2]
I38 A426 [Multi- 5.0
Accel time
3]
I39 A427 [Multi- 5.0
Decel
time 3]
I40 A428 [Multi- 6.0
Accel time
4]
I41 A429 [Multi- 6.0
Decel
time 4]

5-20
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communic name range default
run
ation
I42 A42A [Multi- 7.0
Accel time
5]
I43 A42B [Multi- 7.0
Decel
time 5]
I44 A42C [Multi- 8.0
Accel time
6]
I45 A42D [Multi- 8.0
Decel
time 6]
I46 A42E [Multi- 9.0
Accel time
7]
I47 A42F [Multi- 9.0
Decel
time 7]
I50 A432 [Analog 0~3 Output Output to 10[V] 0 O 9-6
output item
item 200V 400V
select]
0 Output Max frequency
freq.
1 Output 150 %
current
2 Output AC 282V AC 564V
voltage
3 Inverter DC 400V DC 800V
DC link
voltage
I51 A433 [Analog 10~200 Based on 10V. 100 O 9-6
output [%]
level
adjustmen
t]
I52 A434 [Frequenc 0 ~ 400 Used when I54 or I55 is set to 0-4. 30.00 9-7
y [Hz] Cannot be set higher than F21.
O
detection
level]
I53 A435 [Frequenc 10.00
y
detection O
bandwidth
]
I54 A436 [Multi- 0 ~ 19 0 FDT-1 12 O 9-8
function FDT-2
1
output
terminal 2 FDT-3 9-9
select] FDT-4 17
3
I55 A437 [Multi- 4 FDT-5 9-10
function
relay 5 Overload (OLt) 9-10
select] 6 Inverter Overload (IOLt)
7 Motor stall (STALL)

5-21
Input/output group
Address
Adj.
LED for Parameter Min/Max Factory
Description during Page
display communic name range default
run
ation
8 Over voltage trip (Ovt)
9 Low voltage trip (Lvt)

10 Inverter Overheat (OHt)

11 Command loss

12 During Run 9-11

13 During Stop

14 During constant run

15 During speed searching

16 Wait time for run signal input

17 Multi-function relay select

18 Warning for cooling fan trip

19 Brake signal select

5-22
Input/Output Group
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display commun er name range defaults
run
ication
I56 A438 [Fault 0~7 When When the When the 2 O 9-7
relay setting the trip other low voltage
output] H26– than low trip occurs
[Number of voltage trip
auto occurs
restart try]
Bit 2 Bit 1 Bit 0
0 - - -
1 - -
2 - -
3 -
4 - -
5 -
6 -
7
I57 A439 [Output 0~3 Multi-function Multi-function 0 O 9-12
terminal relay output terminal
select Bit 1 Bit 0
when
0 - -
commun
ication
1 -
error
2 -
occurs]
3

I59 A43B [Commu 0 ~1 Set communication protocol. 0 X 11-2


nication
protocol 0 Modbus RTU
select] 1 LS BUS
I60 A43C [Inverter 1 ~ 250 Set for RS485 communication 1 O 11-2
number]
I61 A43D [Baud 0~4 Select the Baud rate of the RS485. 3 O 11-2
rate]
0 1200 [bps]
1 2400 [bps]
2 4800 [bps]
3 9600 [bps]
4 19200 [bps]
I62 A43E [Drive 0~2 It is used when freq command is given via 0 O 10-7
mode V1 /I terminal or RS485.
select 0 Continuous operation at the frequency
after before its command is lost.
loss of
frequenc 1 Free Run stop (Output cut-off)
y 2 Decel to stop
comman
d]
I63 A43F [Wait 0.1 ~ 120 This is the time inverter determines 1.0 O 10-7
time [sec] whether there is the input frequency
after command or not. If there is no frequency
loss of command input during this time, inverter
frequenc starts operation via the mode selected at
y I62.
comman
d]

5-23
Input/Output Group
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display commun er name range defaults
run
ication
I64 A440 [Commu 2 ~ 100 Frame communication time 5 O -
nication [ms]
time
setting]
I65 A441 [Parity/st When the protocol is set, the O O -
op bit communication format can be set.
setting] 0 Parity: None, Stop Bit: 1
0~3
1 Parity: None, Stop Bit: 2
2 Parity: Even, Stop Bit: 1
3 Parity: Odd, Stop Bit: 1
I66 A442 [Read 5 O 11-11
address
register
1]
I67 A443 [Read 6
address
register
2]
I68 A444 [Read 7
address
register
3]
I69 A445 [Read 8
address
register
4] The user can register up to 8
0~42239 discontinuous addresses and read them all
I70 A446 [Read with one Read command. 9
address
register
5]
I71 A447 [Read 10
address
register
6]
I72 A448 [Read 11
address
register
7]
I73 A449 [Read 12
address
register
8]
I74 A44A [Write The user can register up to 8 5 O 11-11
address 0~42239 discontinuous addresses and write them
register all with one Write command
1]
I75 A44B [Write 6
address
register
2]
I76 A44C [Write 7
address
register
3]

5-24
Input/Output Group
Address
Adj.
LED for Paramet Min/Max Factory
Description during Page
display commun er name range defaults
run
ication
I77 A44D [Write 8
address
register
4]
I78 A44E [Write 5
address
register
5]
I79 A44F [Write 6
address
register
6]
I80 A450 [Write 7
address
register
7]
I81 A451 [Write 8
address
register
8]
1821) A452 [Brake 0~180 Sets current level to open the brake. 50.0 O 8-26
open [%] It is set according to H33’s (motor rated
current] current) size
183 A453 [Brake 0~10 Sets Brake open delay time. 1.00 X
open [s]
delay
time]
184 A454 [Brake 0~400 Sets FX frequency to open the brake 1.00 X
open FX [Hz]
frequenc
y]
185 A455 [Brake 0~400 Sets RX frequency to open the brake 1.00 X
open RX [Hz]
frequenc
y]
186 A456 [Brake 0~19 Sets delay time to close the brake 1.00 X
close [s]
delay
time]
187 A457 [Brake 0~400 Sets frequency to close the brake 2.00 X
close [Hz]
frequenc
y
1):
It is indicated when choosing I54~I55 as a 19 (Brake signal).