Transformer components

Type K current limiting fuse canister


Technical information and installation guide

The Type K current limiting fuse canister


provides an air-insulated receptacle for
general-purpose current limiting fuses
used on pad-mounted or submersible
transformers.
Description
The canister is typically mounted on the front wall of a single compresses the cylindrical gasket against the inside walls of the
or three-phase distribution transformer. The Type K canister canister. This action seals the canister. Moving the operating
allows the operator easy access to the current limiting fuse lever into the open (upright) position relaxes the gasket and
for inspection or replacement. The Type K canister is of the internal assembly can be removed for fuse replacement or
dead break construction once it is properly installed onto the inspection.
transformer.
Two spring clips provide grounding of the external metal parts.
Ratings The spring clips are fixed to the body of the canister by the
The Type K current limiting fuse canister is available in three stainless steel hose clamp.
versions:
—— 8.5 kV / 95 kV BIL, 175 A The coil spring contacts at the top and bottom of the fuse
—— 15 kV / 125 kV BIL, 175 A assure positive fuse to transformer circuit connections. The
—— 23 kV / 125 kV BIL, 175 A top spring fits over the fuse attachment clamp on the holder
assembly. The bottom spring is part of the fiberglass tube
Details assembly and makes contact when the fuse assembly is
The Type K current limiting canister features dead front inserted into the holder and locked into position.
construction, hermetic sealing, self-aligning spring contacts and
stainless steel, corrosion-resistant components. The fuse Interlocking
canister is a dead break device and ABB recommends that it be The Type K current limiting canister is a dead break device.
used in conjunction with an interlocked load break oil switch, ABB recommends that the fuse canister be mechanically
such as ABB’s LBOR. interlocked to an LBOR switch or other mechanism so that
the fuse cannot be removed from or inserted into an energized
The Type K, current limiting fuse canister consists of two major transformer.
components. The first, is a reinforced fiberglass tube welded
to the tank by means of a stainless steel flange or bolted Mounting
to the tank by means of an optional plated steel clamp and The Type K canister can be welded or bolted onto the
gasket. The second component, is a removable fuse assembly transformer tank. If the canister is welded onto the transformer,
consisting of the top closure, an insulated operating shaft, the you must use heat sinks to prevent the welding heat from
fuse attachment clamp, top spring contact and guide washer. damaging the canister. The fuse canister can be bolted onto
the transformer by using the optional mounting clamp and nitrile
When in the closed position, the Type K utilizes a “bottle gasket. The mounting flange has a lip to capture the mounting
stopper” type seal between the inside of the canister and the gasket for these applications. Note that the grounding clips
atmosphere. This is accomplished using an operating lever must be removed in order to slide the mounting flange into
combined with a cylindrical gasket to create an over toggle place. Once the mounting flange is secured, reinstall the
mechanism. Moving the operating lever into the closed position grounding clips.
Fuse capability
The Type K canister accepts current limiting fuses of the type
known as Full Range or General Purpose such as the Hi-Tech
Trans-Guard™ FX fuse. The table below provides the maximum
fuse dimensions for proper fit into the Type K canister.

Voltage Maximum Maximum total Connector Connector


class (kV) OD A (in) length B (in) length C (in) OD D (in)

8.3 2.25 10.2 1.05 0.326

15.5 2.25 14.4 1.05 0.625

23 2.25 17.3 1.05 0.625

Ordering details

Dimensions
Item number Voltage BIL X Y Z Clamp Gasket
4260079-901 8.5 95 18.75 20.31 9.97 N/A N/A
4260079-902 15 125 23.13 24.69 14.35 N/A NA
4260079-903 23 125 25.94 27.50 17.16 N/A N/A
4260079-904 8.5 95 18.75 20.31 9.97 9820A33H01 1210221-021
4260079-905 15 125 23.13 24.69 14.35 9820A33H01 1210221-021
4260079-906 23 125 25.94 27.50 17.16 9820A33H01 1210221-021

For more details see fuse holder drawing 44-887 page 15

2 Type K current limiting fuse cansiter


Notes

Type K current limiting fuse cansiter 3


Note:

1ZUA5670-301, rev. 1
For more information please contact: We reserve the right to make technical changes or modify the contents of this document
without prior notice. The information, recommendations, description and safety
notations in this document are based on our experience and judgment. This information
ABB Inc. should not be considered all inclusive or covering all contingencies. ABB does not
1128 South Cavalier Drive accept any responsibility whatsoever for potential errors or possible lack of information in
this document. If further information is required, ABB Inc. should be consulted.
Alamo, Tennessee 38001, USA
Phone: +1 731 696 5561 We reserve all rights in this document and in the subject matter and illustrations
Main: +1 800 955 8399 contained therein. Any reproduction in whole or in parts is forbidden without prior written
consent from ABB Inc.
Fax: +1 731 696 5377
With regard to purchase orders, the agreed particulars shall prevail. In no event will
ABB Inc. be responsible to the user in contract, in tort (including negligence), strict
www.abb.com/electricalcomponents liability or otherwise for any special, indirect, incidental, or consequential damage or loss
whatsoever including but not limited to use of equipment, plant or power system, cost
of capital, profits or revenues, cost of replacement power, additional expenses in the use
of existing power facilities, or claims against the user by its customers resulting from the
use of the information, recommendations, description and safety notations contained
herein.

Copyright © 2011 ABB.


All rights reserved.
ASSEMBLY kV
BIL.
NUMBER CLASS
Tank Wall
4260079-901 8.5 95
4260079-902 15 125
4260079-903 23 125

FUSE (NOT INCLUDED)


CANISTER ASSEMBLY
FOR DIMENSIONAL INFORMATION
SEE DRAWING 44-887 PAGE15

GROUND PROVISION
1260077-901

FIBER WASHER
1260030-000
NOT REQUIRED ON 2" FUSES
INSULATED ROD ASSEMBLY
6260009-901
ABB Inc.
ALAMO, TN U.S.A.
TITLE:
TYPE K FUSE HOLDER
WELD IN INSTALLATION
INSTRUCTION
UNITS = IN [mm] DRAWING NO:

SHEET 1 OF 1 REV.2 LANG. = ENGLISH 1ZUA5670-302


ASSEMBLY kV THREE MOUNTING STUDS
BIL.
NUMBER CLASS 0.375 [9.5mm] DIAMETER
4260079-904 8.5 95 1.75 [44.45mm] LONG Tank Wall
4260079-905 15 125 SEPARATED BY 120
ON A 4.48 [113.79]
4260079-906 23 125 BOLT HOLE CIRCLE

GASKET
1210221-021

FIBER WASHER
1260030-000
CLAMP
NOT REQUIRED ON 2" FUSES
9820A33H01

FUSE (NOT INCLUDED)


CANISTER ASSEMBLY
FOR DIMENSIONAL INFORMATION
SEE DRAWING 44-887 PAGE15

MOUNT NUTS AND WASHERS


TO MATCH TANK MOUNTING STUDS
TORQUE TO 90 in-lbs

GROUND PROVISION
1260077-901

INSULATED ROD ASSEMBLY


6260009-901
ABB Inc.
ALAMO, TN U.S.A.
TITLE:
TYPE K FUSE HOLDER
BOLT IN INSTALLATION
INSTRUCTION
UNITS = IN [mm] DRAWING NO:

SHEET 1 OF 1 REV.2 LANG. = ENGLISH 1ZUA5670-303


ALAMO,TN