1Ph Transformer RSC
1Ph Transformer RSC
It consists of two inductive coils with high mutual inductance which are
electrically separated but magnetically coupled as show in fig. If one coil is
connected to an alternating voltage, an alternating flux is set up in the
laminated core. This flux is linked with the other coil & produces a mutually
induced e.m.f. If the 2nd. Coil is closed, a current flows in it & so electric energy is
transferred entirely magnetically from 1st. coil to the 2nd. Coil. The 1st. coil which
is fed from the a.c supply is called primary winding & the 2nd. Coil from which
energy is drawn out is called secondary winding.
CONSTRUCTION:-
(a) A laminated steel core & two coils having mutual inductance.
( c ) Oil→ insulating medium for the core & its winding from container
+ cooling by circulation.
Core:-
The cores are constructed of high grade silicon steel, the silicon
content reducing losses & preventing ageing, in laminations about
0.014 inch. thick, cut in rectangular strips, punched & then annealed
to recondition the material. Each lamination is coated with a tough
flash enamel insulation resistant to hot transformer oil. Laminations
are assembled in the required shape, the corners being inter leaved to
add to rigidity and to reduce the reluctance of the magnetic circuit.
Since core flux is alternating, it is essential that the core be laminated
to reduce eddy current losses or CRGO ( Cold Rolled Grain Oriented)
laminations improve the working flux density & reduce the
transformer size considerably & lower iron losses at higher operating
flux densities & lower cost.
From the constructional point of view a transformer can be classified
according to the type of core used.
Tank:-
The assembled core & winding are placed in a tank which contains oil.
Radiator or tubes are provided on the sides of the tank if smooth tank
surface is not sufficient to radiate the heat produced.
Transformer Oil:-
It serves the dual purpose of insulation & cooling. All oils are good insulators but
animal & vegetable oils are not suitable for use in transformer because these
tend to form destructive fatty acids which attacks fibrous materials used as
winding insulation. The oil used in transformer is called transformer oil & is a
mineral oil obtained from fractional distillation of crude petroleum. The
breakdown strength of transformer oil is reduced in presence of moisture.
Transformer oil has a disadvantage of its sludging. Sometimes to prevent
sludging certain chemicals called inhibitors are added to transformer oil. To
prevent the risk of fire & explosion synthetic transformer oil are developed.
Chlorinated diphenyl normally called ASKAREL is a synthetic oil suitable for use
but under the influence of power arcs this gets decomposed & form hydrochloric
acid which is a corrosive & toxic substance.
Method of Type
cooling Abbreviation
The voltage induced in any winding depends only upon the number of
turns in the winding & the rate of change of the flux linking it. It
makes no difference how the change in flux is produced.
Let Øm be the maximum value of the flux linking a transformer coil &
assume this flux to vary sinusoidally with respect to time.
Ø= Øm Sin ωt
If N1 is the number of turns in the coil, the voltage rise (voltage rise is
considered as +ve & a drop in voltage is as –ve) induced in the coil at
any instant by the flux Ø is
Hence the no load input current I0 is not at 900 behind V1 but lags it by
an angle ˂ 900.
Iµ = I0 Sin Ø0
[ Note:-
Transformer on load:-
When secondary is loaded secondary current I2 flows and its
magnitude & phase with respect to secondary terminal voltage V2
depends upon the type of load. Due to the secondary amp-turns N2I2 a
flux Ø2 is set up in the core which acts in opposition to the main flux
Ø. This secondary amp-turns N2I2 is known as demagnetizing
amp-turns. The flux Ø2 weakens the main flux Ø momentarily & hence
primary back emf E1 tends to reduce. So for a moment V1 gains upper
hand over E1 & causes more current to flow in primary.
Let this additional primary current be I2′ & this is known as load
component of primary current. This current flowing in primary due to
the application of load in secondary & is anti phase with I2 . The
additional primary amp-turns N1 I2′ sets up its own flux Ø2′ which acts
in opposition of Ø2 but in same direction of Ø & equal in magnitude of
Ø2. So the two cancels each other out & the magnetic effects of I2 are
immediately neutralized by additional primary current I2′.
Hence under any load conditions the net flux passing through the core
is same at no load. As the core flux is constant under any load
condition, the core loss is also same under all load condition.
Assuming K=1 & for lagging load the vector diagram is shown below.
V2 = E2 – I2 R2 (vector difference)
By convention
Or, V1 = - E1 + I1 R1
Equivalent Resistance:-
So we can write,
R1′ = K2 R1
Magnetic Leakage:-
All flux linked with primary does not linked with the secondary. A part
of its say ØL1 completes its magnetic circuit by passing through air. This
flux is due to primary amp-turns & is proportional to primary
amp-turns & in phase with I1 . It induces an emf say eL1 in primary.
Similarly is for the secondary.
For secondary V2 = E2 – I2 R2 - I2 X2
Leakage reactance can also be transferred from one side to other side
in the same way as resistance.
Equivalent Circuit:-
X0 = E1 / Iµ & R0 = E1 / Iw
E2 /E1 = N2 /N1 = K
Iµ = I0 Sin Ø0 , Iw = I0 Cos Ø0
[Note:-
2) O.C. test can also be done by supplying H.V winding keeping L.V
side open. But this needs a high voltage source & for a transformer
of voltage rating say 132KV / 6.6KV this is hazardous.
L.V winding is short circuited & the H.V winding is supplied from a
sinusoidal voltage of low value at rated frequency. The value of
applied voltage is adjusted to have rated current Irated flowing in H.V
winding. The readings of ammeter, voltmeter & wattmeter are noted
as Irated , Es , Ps respectively.
difficult.
(3) As a small supply voltage is required for this test & since a
preferable to short circuit the L.V winding & supply the H.V ]
[Note that kVA rating of transformer is same for both primary &
secondary]
Regulation:-
Percentage Impedance:-
We know, I2′ N1 = I2 N2
Therefore Pcu = I12 [R1 + (N1 /N2)2 R2 ] = I12 [R1 + (R2 /K2 )] as K= N2 /N1
(ii) Core losses are divided into two (a) hysteresis loss & (b)
eddy current loss.
Pe is proportional to t2,
proportional to Bmax2,
inversely proportional to ρ.
f = frequency
These losses vary with flux density in the core & frequency. Under
normal operating conditions the core flux in a transformer remains
approximately constant. That is the core losses can be considered
unaffected by load current.
Efficiency:-
The volt-amp rating of a transformer is its output quantity & thus the
efficiency is determined in terms of output power.
= V2 I2 Cos Ø2 + Pcu + Pi
All-day Efficiency:-
The efficiency as discussed above are power efficiency i.e they are the
ratio of the power output to the power input under definite load
condition. Most transformers do not operate under constant load. As
a rule all except those in central station or in substations are
permanently connected to the power lines on their H.V side &
consume power during 24 hr of each day corresponding to their core
losses whether or not the transformer are loaded. For transformers
which operate on definite load cycles, it is the energy efficiency that is
important. Energy efficiency is the ratio of total KWh output to total
KWh input during the load cycle, which is usually a period of 24 hr.
This efficiency is called All-day efficiency.
Problem-1-
[Ans: 96.39%]
Hints:
= 96.39%
Problem-3-
Hints:
Cu loss at 25A =200W & Pi =120W, p.f & kVA given find efficiency.