System Input Data

Project Name: HVAC lab 22 06/10/2024


Prepared by: HAP22 07:58pm

1. General Details:
Air System Name System
Equipment Type Split AHU
Air System Type Single Zone CAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 55.0 °F
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:


Supply Temperature 95.0 °F
Heating Source Electric Resistance
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 0.00 in wg
Overall Efficiency 54 %
Fan Control 1-speed fan, cooling and heating

Duct System Data:


Supply Duct Data:
Duct Heat Gain 5 %
Duct Leakage 5 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
Bedroom 1 x1
Bedroom 2 x1
Dinning room x1
living Room x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 75.0 °F
Cooling T-stat: Unocc. 80.0 °F
Heating T-stat: Occ. 70.0 °F
Heating T-stat: Unocc. 65.0 °F
T-stat Throttling Range 1.50 °F
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 CFM
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Sample Schedule


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type Diffuser
Minimum Airflow 0.00 CFM/person

Hourly Analysis Program v4.90 Page 1 of 2


System Input Data
Project Name: HVAC lab 22 06/10/2024
Prepared by: HAP22 07:58pm

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Electric Resistance


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 55.0 °F
Supply Fan Airflow 1411.3 CFM
Ventilation Airflow 0.0 CFM
Heating Supply Temperature 95.0 °F

Hydronic Sizing Specifications:


Chilled Water Delta-T 10.0 °F
Hot Water Delta-T 20.0 °F

Safety Factors:
Cooling Sensible 5 %
Cooling Latent 5 %
Heating 5 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(CFM) (MBH) (MBH) (CFM)
1 1340.8 - -

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 29.9 MBH
Design OAT 95.0 °F
Equipment Sizing Auto-Sized
Capacity Oversizing Factor 0 %
ARI Performance Rating 11.000 EER
DX System Configuration 1-stage compression, 1 circuit
Conventional Cutoff OAT 55.0 °F
Low Temperature Operation Used
Low Temperature Cutoff OAT 0.0 °F

Hourly Analysis Program v4.90 Page 2 of 2