Technical Specification ofDistribution Transformers (11/0.
416 kV) Ministry ofElectricity (MoE)
Schedule "A"
Schedule of the Guaranteed Performance and Other Technical
Particulars (To be filled by the Tenderer for each rated capacity o
100, 250, 400, 630, and 1000 kVA).
No. Description Unit
1 General
1.1 Manufacturer Name
1.2 Country of Manufacturing
1.3 Type
1.4 Model
1.5 Applicable Standards
1.6 Location of service
1.7 Short circuit Test Report
1.8 Date of carried out
1.9 Testing laboratory name and
country
1.10 Certificate Provided
2 Ratings
2.1 Continuous maximum rating KVA
2.2 Rated voltage ratio
. Primary kV
. Secondary kV
2.3 Number of phase
2.4 Frequency Hz
2.5 Vector group symbol
2.6 Cooling method
2.7 Maximum temperature rise at
rated power
. Top oil by thermometer K
. Winding by resistance K
. Hot spot of winding max K
ambient temperature (550 C)
2.8 Impedance voltage at continuous %
rated power
2.9 Winding connection:
. Primary
. Secondary
3 Rated insulation level for Primary
. Impulse withstand voltage kV peak
(1.2/50μs)
. One minute 50Hz withstand kV rms
voltage
4 Design Details
4.1 Off-load tap changer
. manufacturer
. Tapping range
. Tapping step
4.2 Exciting current referred to HV
side and 50 Hz
. At 90% rated voltage. A
. At 100% rated voltage. A
. At 110% rated voltage. A
4.3 Power factor of exciting current %
at 100% rated voltage and 50 Hz
4.4 Iron losses at 50 HZ
. At 90% rated voltage. kW
. At 100% rated voltage. kW
. At 110% rated voltage. kW
4.5 Copper losses at full load (on kW
rating) and at 750 C
4.6 Total losses. (kW)
4.7 Resistance voltage at full load (%)
and at 750.
4.8 Reactance voltage at full load (%)
and at 750
4.9 Impedance voltage at full load
750 :
. At normal tap. (%)
. At highest tap. (%)
. At lowest tap. (%)
4.10 Resistance of HV winding per Ω
phase at 200 C
4.11 Resistance of LV winding per Ω
phase at 200 C
4.12 Regulation at full load at 750 C
. At 1.0 power factor.
. At 0.8 p.flagging.
4.13 Efficiency at 750 C:
. At 100% load (%)
. At 75% load (%)
. At 50% load (%)
. At 25% load (%)
4.14 Calculated thermal time constant Hrs.
4.15 Maximum flux density at normal
voltage and frequency and at
normal ratio for:
. Core. (KI/sq.cm)
. Yoke. (KI/sq.cm)
4.16 Maximum flux density at 110%
voltage and frequency and at
normal voltage and frequency
and at normal ratio for:
. Core (KI/sq.cm)
. Yoke (KI/sq.cm)
4.17 Insulation level of:
. Core bolts. kV
. Core bolts washer. kV
. Side plates. kV
. Core laminations. kV
4.18 Current destiny in windings for:
. H.V. winding (Amps/sq.c
m)
. L.V. winding (Amps/sq.c
m)
4.19 Insulation on copper. kV
4.20 Insulation strength of winding.
a) Impulse full wave for:
(I) H.V. (kV)
(II) L.V. (kV)
b) Impulse chopped wave
for:
(I) H.V. (kV)
(II) L.V. (kV)
c) Applied voltage test (kV)
d) Induced voltage test (kV)
4.21 Insulation strength of terminals.
. Over voltage test (kV)
. Minimum wet withstand (kV)
voltage
. Minimum impulse withstand (kV)
. Minimum puncture or oil- (kV)
immersed withstand voltage
4.22 Type of core
4.23 Max. noise level at 0.3 meter (dB)
4.3 Type of oil (As per IEC
requirement )
4.4 Standards
4.5 Type of corrosion protection
• Inside tank
• Outside tank
4.6 Type of valves
5 Dimension And Weight
5.1 Dimension of Transformer
. Under base to top most point. mm
. Under base to bushing mm
mounting flanges.
. Overall breadth. mm
. Overall length. mm
. Crane lift for untanking mm
core and coils
. Crane lift for removal of mm
bushings
5.2 Overall shipping dimensions of mm
the largest package
5.3 Thickness of transformer tank
. Sides. (mm)
. Bottom. (mm)
. Corrugated radiators. (mm)
5.4 Volume of insulating oil (liter)
5.5 Net weight of insulating oil (Kg)
5.6 Total weight of transformer less (tons)
oil
5.7 Weight of the largest shipping (tons)
package
5.8 Net weight of core (Kg)
5.9 Net weight of copper
. H.V. (Kg)
. L.V. (Kg)
5.10 Net untanking weight of:
. Core (Kg)
. Frame (Kg)
. Coil (Kg)
Page 18 of 19
kV) Ministry ofElectricity (MoE)/IRAQ
ce and Other Technical
for each rated capacity of
Specifications
Required Proposed
To be filled in
To be filled in
To be filled in
IEC 60076
Outdoor
To be filled in
To be filled in
Yes
To be filled in
11(+2 x 2.5%/-
2 x 2.5%)
0.416Y/0.24
3
50
Dyn11
ONAN
45
50
To be filled in
To be filled in
Delta
Star (Neutral
brought out)
75
28
To be filled in
+5%/-5%
2.5%
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
55
Yes
IEC 60296
To be filled in
To be filled in
Clobe or gate
valve
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in
To be filled in