ALGORITHMIC SYSTEM

MSTAY
Technical signals module

Microprocessed algorithmic addressable loop device (with short-circuit isolator).

It has two inputs to distinguish between the open or close state of a dry contact connected in series with a 10
kΩ resistor. In quiescent condition, the contact has to be open, and in anomaly condition, the contact has to be
closed. In the first input (marked with IN1), the closed contact is detected as an ALARM condition. In the second
input (marked with IN2), the closed contact is detected as FAULT warning condition. It is possible to associate both
inputs having an alarm and fault conditions information.

In the quiescent condition, the device supervises the electrical connection through a 33 kΩ resistor, which allows
indication of open electrical connection or short circuit status.

It is usually used to inform about the status of other detection systems associated to Cofem systems, like flow
sensors in the case of sprinkler installations, end of stroke for fire-resistant doors, elevators, or level of deposits, etc.

The red Led blinking indicates communication with the control panel, and if it remains lit it indicates the alarm
status. The lit green LED indicates activation of one or both inputs.

This device has an output for connection to a remote action indicator, which is activated when in case of alarm
status. The technical signals module is a loop powered device.

The device is supplied in a rectangular, heat-resistant ABS box.

The module is certified according to EN 54-18 Standard, and CE mark according to the European Regulation of
Construction Products (UE) N°305/2011.

MSTAY

BUCLE IN1 IN2 PIAL


TECHNICAL FEATURES - - - - -
+
+

+
+
+

Power Supply 24 - 35V with polarity


Standby Current 1 mA IN
LOOP
Short-Circuit Isolator Yes
OUT
Supervision voltage 7V with reverse polarity
Remote Indicator Output Yes
Activation signal Green Light
Free voltage device Free voltage device
Communication/Alarm Indicator Red Light
10K 10K
Humidity 20 - 95% RH
Temperature -10ºC +50ºC 33K 33K
Dry contact Dry contact
Size 140,5 x 73 x 48 mm
Standard EN 54-18
IP Protection IP 30

www.cofem.com