Two industrial plants represent balanced three-phase loads. The plants receive their power from a
balanced three-phase source with a line voltage of 4.6 kV rms. Plant 1 is rated at 300 kVA, 0.8 pf lagging
and plant 2 is rated at 350 kVA, 0.84 pf lagging. Determine the magnitude of the line current.