Static Lateral Procedure
Static Lateral Procedure
500 9.5
1200 6.5
1300 3.5
ΣW 3000
Required : Calculate the Design Base Shear, V
Distribute V per level (Direct Shear)
Distribute V horizontally (Direct Shear)
Structure Period
Method A
T= Ct ( hn )( 3/ 4 ) 0.0853(9.5)^3/4 = 0.4616 s (208-12)
F= 0 .07TV (208-16)
Near Source Factors
Na = 1.0
Nv = 1.0
Page 6
Ca = 0.44
Cv = 0.64
Zone 4
Z= 0.4
R= 8
Design Base Shear
Use V = 412.50 KN
Vertical Distribution of Design Base Shear(V) V= 412.50 KN
Level W(KN) h(m) Wh (KN-m) Wh/ΣWh Fx(KN)
ROOF 500 9.5 4750 0.278 114.58
3F 1200 6.5 7800 0.456 188.16
2F 1300 3.5 4550 0.266 109.76
GROUND 0
Σ 3000 17100
Wh
Fx= (V −Ft ) (208-17)
ΣWh
114.58 KN
188.16 KN
109.76 KN
No. of Columns: 4
30.56 KN
50.18 KN
29.27 KN
Frame A,B, D
Frame 1,3,4
EQ from Left
No. of Columns: 3
22.92 KN
37.63 KN
21.95 KN
Frame C
Frame 2
EQ from Right
No. of Columns: 4
30.56 KN
50.18 KN
29.27 KN
Frame A,B, D
Frame 1,3,4
EQ from Right
37.63 KN
21.95 KN
Frame C
Frame 2