0% found this document useful (0 votes)
39 views4 pages

02 LCF Datasheet en

Uploaded by

elektrocentar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views4 pages

02 LCF Datasheet en

Uploaded by

elektrocentar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

LCF

Electronic FanCoil Thermostat (flush mounting)


(from Firmware 1.7.3)

Datasheet
Subject to technical alteration
Issue date: 09.02.2022 • A121

» APPLICATION
The fan coil room thermostat has been designed for individual control
of temperature in commercial, industrial and residential buildings. It is
tailored for two-pipe and four-pipe fan coil with two-wire electric valves.
With its flush mounted modern design the device combines digital
technology with a large LCD display and additional buttons, which
enables the 2-point-single room controller to be used intuitively.

» SECURITY ADVICE – CAUTION


The installation and assembly of electrical equipment should only be performed by authorized personnel.

The product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not
be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result
in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating
equipment.

CAUTION! Risk of electric shock due to live components within the enclosure,
especially devices with mains voltage supply (usually between 90..265 V).

Please comply with


• Local laws, health & safety regulations, technical standards and regulations
• Condition of the device at the time of installation, to ensure safe installation
• This data sheet and installation manual

» NOTES ON DISPOSAL
As a component of a large-scale fixed installation, Thermokon products are intended to be used permanently as
part of a building or a structure at a pre-defined and dedicated location, hence the Waste Electrical and Electronic
Act (WEEE) is not applicable. However, most of the products may contain valuable materials that should be
recycled and not disposed of as domestic waste. Please note the relevant regulations for local disposal.

» MOUNTING ADVISE ROOM SENSORS


The Accuracy of the room sensors are influenced by the technical specifications as well as the positioning and the installation type.

During Assembly:
• Seal mounting box (if present).
• Installation type, air draught, heat source, radiation heat or direct sunlight can affect the measurement.
• Bulding material specific properties of the installation place (brick-, concrete-, partition wall, cavity wall, …) can affect the measurement.
(e.g.: Concrete accepts room temperature variation slower than cavity walls)

Assembly not recommendet in…


• Air draught (e.g.: close to windows / doors / fans …)
• Near heating sources,
• Direct sunlight
• Niches / between furniture / …

» PRODUCT TESTING AND CERTIFICATION

Declaration of conformity
The declaration of conformity of the products can be found on our website https://www.thermokon.de/

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.de · [email protected]
LCF_Datasheet_en.docx © 2022
Page 2 / 4 Issue Date: 09.02.2022

» TECHNICAL DATA
Measuring values temperature

Output switch contact 5x contact NO (2x heating & cooling, 3x fan stages, 2-point-controller), 250 V ~ max. load 3 A
fan stages switchover pause 0,5 s

Power supply 90..265 V ~

Power consumption max. 0,9 W

Measuring range temp +1..+50 °C

Accuracy temperature ±1 K (typ. a 21 °C)

Inputs input for change-over sensor NTC10k, (optional)

Display LCD 35,5x48,5 mm, white background lighting

Enclosure ABS, pure white, scratch resistant acrylic glass

Protection IP20 according to EN 60529

Cable entry rear entry

Connection electrical terminal block, max. 1,5 mm²

Ambient condition -10..+50 °C, max. 85% rH non-condensing

Mounting flush mounted in standard EU box (Ø=60 mm)

» TERMINAL CONNECTION PLAN

Wiring diagram for 2-pipe fan coil: with external sensor:

Wiring diagram for 4-pipe fan coil

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.de · [email protected]
LCF_Datasheet_en.docx © 2022
Issue Date: 09.02.2022 Page 3 / 4

» MOUNTING ADVICES

For Installing or repairing, please make sure the power is disconnected.


Insert the screw driver in the plastic teeth of thermostat. Clockwise rotation of
the screwdriver will separate front cover from base plate. Please follow the
wiring diagram to connect the wires.
Fix the thermostat base plate to the wall through the four screw holes with
distance between axes of 60 mm.
Fasten base plate and front cover. Do not press the panel in order to protect
LCD.

» CONFIGURATION
The firmware version is located on a label inside the device.
Display Panel

By pressing the MODE Button for more than 3 seconds, the parameter interface will appear.

After parameter selection / setting,


don’t press any button for 3
seconds to save the settings.

No. Name of parameter Parameter definition Default


1 Temp. correction Range ±10 °C 0
2 Key-lock 0 - unlocked 1 - lock on/off 2 - lock Mode 0
3 - lock fan speed 4 - lock temp setting 5 - lock all the keystrokes
3 not used
4 Temp. upper limit Range: +1..+50 °C 30 °C
5 Temp. lower limit Range: +1..+50 °C 16 °C
6 LCD backlight 0 - without backlight 1 - with backlight 1
7 Fan chain setting 0 – Independent (AUTO OFF) 0
(Fan Mode AUTO) 1 – Dependent (AUTO ON)
8 Fan coil selective 2 - 2-pipe system 4 - 4-pipe system 2
9 Polarity Outputs 0 - Valve de-energized closed 1 - Valve de-energized open 0
10 FAN-OFF-Delay (if parameter 7 = 1) 0
the fan continues running for x seconds after the valve has closed
0..99 (switch-off delay in seconds)

All parameters are stored within an EEPROM ensuring no data loss if the Thermostat is powered off.
Hysteresis: 1 K + 1 minute switching delay

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.de · [email protected]
LCF_Datasheet_en.docx © 2022
Page 4 / 4 Issue Date: 09.02.2022

» COMMISSIONING
Pressing the “▲” and “▼” key at the same time for more than 3 s, the units °C or °F can be selected. Temperature display range is 0..+50 °C or
+32..+99 °F. Factory default is °C.
Select 2-pipe or 4-pipe systems (Parameter 8). In both modes the control sequences Cooling – Ventilating – Heating can be selected.
Using Parameter No.1. the temperature offset can be adjusted. This feature should be used if the temperature at the mounting place of the Room
Thermostat is not accurate to the average room temperature.
Key lock selection (Parameter 2), LCD backlight (Parameter 6) and set point ranges (Parameter 4 and 5) can be set by parameters. Under Fan
operation “INDEPENDENT” (parameter 7) the fan will always run according the selected or automatic selected fan stage; under Fan operation
“DEPENDENT” the fan will be tuned off in case the valve is closed. If the valve is open, the fan will run according the selected or automatic selected
fan stage. When the fan stages are changed, the fan remains in a no-current switcheover pause (0.5 s).

Handling
By pressing “▲” or “▼” button the room temperature set point can be adjusted between +16..+30 °C (+60..+86 °F). See also parameter 4/5.
If an external temperature sensor is used in 2-pipe system to measure the temperature in the pipes, no change of mode is possible via MODE
button. The system recognizes automatically, whether current mode is cooling or heating. When temperature is <=19 °C cooling is active, when
the temperature is >=30 °C heating is active. The other mode is not available. A time delay between cooling/heating mode changes is implemented
to ensure safe operation and ensures eco-friendly operation. When using a 4-pipe system no sensor is necessary. Both functions (heating and
cooling) are available. The function can be selected via MODE button.
If no external sensor is used, the functions (heating-ventilation-cooling) can be selected using MODE button. In heating mode the valve will be
opened, if temperature is below set point, in cooling mode it will be opened, if the temperature is above set point.
If the NTC room temperature sensor is out of range, thermostat will switch off the fan and close the valve, fault code “E01” will be shown.

Fan Stage selection


Cooling or Heating mode fan stage options: Low -> Med -> Hi -> Auto
Ventilation mode fan stage options: Low -> Med -> Hi

Auto mode:

» DIMENSIONS (MM)

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 · fax: -400 · www.thermokon.de · [email protected]
LCF_Datasheet_en.docx © 2022

You might also like