Modbus Mapping A029X159 I2 200909
Modbus Mapping A029X159 I2 200909
Controller
PCC 1301
PowerCommand 1.1
PowerCommand 1.2
PowerCommand 2.2
PowerCommand 2.3
PowerCommand 3.3
i
THIS PAGE LEFT INTENTIONALLY BLANK
ii
Safety Precautions
SAVE THESE INSTRUCTIONS − This manual contains important instructions that should be followed during
installation and maintenance of the generator set and batteries.
Before operating the generator set (genset), read the Operator’s Manual and become familiar with it and
the equipment. Safe and efficient operation can be achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure to follow fundamental rules and precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the op-
erator, service personnel, or the equipment.
DANGER This symbol warns of immediate hazards which will result in severe personal injury or
death.
WARNING This symbol refers to a hazard or unsafe practice which can result in severe personal in-
jury or death.
CAUTION This symbol refers to a hazard or unsafe practice which can result in personal injury or
product or property damage.
iii
• Before starting work on the generator set, disconnect battery charger from its AC source, then disconnect
starting batteries, negative (−) cable first. In lean-burn natural gas (LBNG) gensets, also make sure the
starter’s air supply line is disconnected or completely vented until the generator set is ready to start. This
will prevent accidental starting.
• Make sure that fasteners on the generator set are secure. Tighten supports and clamps, keep guards
in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become caught in moving parts.
• If adjustment must be made while the unit is running, use extreme caution around hot manifolds, moving
parts, etc.
DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire,
explosion, severe personal injury and death. Do not operate a genset where a flammable vapor environment
can be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to block
the air intake and stop the engine. The owners and operators of the genset are solely responsible for operating
the genset safely. Contact your authorized Cummins Power Generation distributor for more information.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
• Remove electric power before removing protective shields or touching electrical equipment. Use rubber
insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical
equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when
handling electrical equipment. Do not wear jewelry. Jewelry can short out electrical contacts and cause
shock or burning.
• Use extreme caution when working on electrical components. High voltages can cause injury or death.
DO NOT tamper with interlocks.
• Follow all applicable state and local electrical codes. Have all electrical installations performed by a quali-
fied licensed electrician. Tag and lock open switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL SYSTEM. Haz-
ardous voltages can flow from the generator set into the utility line. This creates a potential for electrocu-
tion or property damage. Connect only through an approved isolation switch or an approved paralleling
device.
MEDIUM VOLTAGE GENERATOR SETS (601V to 15kV)
• Medium voltage acts differently than low voltage. Special equipment and training is required to work on
or around medium voltage equipment. Operation and maintenance must be done only by persons trained
and qualified to work on such devices. Improper use or procedures will result in severe personal injury
or death.
• Do not work on energized equipment. Unauthorized personnel must not be permitted near energized
equipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even af-
ter the equipment is disconnected from the power source. Plan the time for maintenance with authorized
personnel so that the equipment can be de-energized and safely grounded.
GENERAL SAFETY PRECAUTIONS
• Coolants under pressure have a higher boiling point than water. DO NOT open a radiator or heat ex-
changer pressure cap while the engine is running. To prevent severe scalding, let engine cool down be-
fore removing coolant pressure cap. Turn cap slowly, and do not open it fully until the pressure has been
relieved.
• Used engine oils have been identified by some state or federal agencies as causing cancer or reproduc-
tive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or contact
used oil.
iv
• Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible materials such
as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires,
live electrical equipment. (ref. NFPA No. 10).
• Make sure that rags or combustible material are not left on or near the generator set.
• Make sure generator set is mounted in a manner to prevent combustible materials from accumulating
under or near the unit.
• Remove all unnecessary grease and oil from the unit. Accumulated grease and oil can cause overheating
and engine damage which present a potential fire hazard.
• Keep the generator set and the surrounding area clean and free from obstructions. Remove any debris
from the set and keep the floor clean and dry.
• Do not work on this equipment when mentally or physically fatigued, or after consuming any alcohol or
drug that makes the operation of equipment unsafe.
• Substances in exhaust gases have been identified by some state or federal agencies as causing cancer
or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
• Do not store any flammable liquids, such as fuel, cleaners, oil, etc., near the generator set. A fire or explo-
sion could result.
• Wear hearing protection when near an operating generator set.
• To prevent serious burns, avoid contact with hot metal parts such as radiator system, turbo charger sys-
tem and exhaust system.
v
THIS PAGE LEFT INTENTIONALLY BLANK
vi
1. PCC 1301/PowerCommand 1.x Modbus Register Map
The genset controller contains data that can be read Modbus Serial Line Implementation Guide v1.0,
by a remote device communicating via Modbus both available at www.modbus.org.
RTU protocol on a two−wire RS485 master/slave
Multi−Drop Network Mode Pins:
multi−drop bus. In this arrangement the remote de-
vice is the master and the genset controller is the • Hi (+) TB2-3
slave. • Lo (−) TB2-4
• Shield TB2-1
For more information about the Modbus protocol, Note: If an address or bit is not listed in this table it is
refer to Modbus Application Protocol v1.1a and not used.
Addr. Description Read / Write Scale Units Type Notes
40004 Save adjustments Read and − − Unsigned 0=No action
Write integer 1=Save adjustments
Save adjustments saves to
non volatile memory all the
write parameters listed in
this table
40010 Genset control run/off/ Read − Switch Unsigned 0=off
auto switch position position integer 1=Run/Manual
2=Auto
40011 Genset operating Read − Operating Unsigned 0=Stopped
state state integer 1=Start Pending
2=Warm−up at Idle
3=Running
4=Cool down at Rated
5=Cool down at Idle
40012 Fault Code Read − Event code Unsigned This register contains the
integer fault code number of current-
ly active fault. See service
manual for list of supported
fault codes.
40013 Fault Type Read − Fault type Unsigned This register contains the
integer fault type of currently active
fault 0=Normal
1=Warning
2=Derate
3=Shutdown with Cool down
4=Shutdown
40016 NFPA 110 fault regis- Read − bitmap See section 4.
ter
40017 Extended Annunci- Read − bitmap See section 4.
ation fault register
40018 Alternator output volt- Read 1.0 AC Volts Unsigned
age line to neutral (a integer
phase)
40019 Alternator output volt- Read 1.0 AC Volts Unsigned
age line to neutral (b integer
phase)
1
Addr. Description Read / Write Scale Units Type Notes
40020 Alternator output volt- Read 1.0 AC Volts Unsigned
age line to neutral (c integer
phase)
40022 Alternator output volt- Read 1.0 AC Volts Unsigned
age line to line (a to b integer
phase)
40023 Alternator output volt- Read 1.0 AC Volts Unsigned
age line to line (b to c integer
phase)
40024 Alternator output volt- Read 1.0 AC Volts Unsigned
age line to line (c to a integer
phase)
40025 Alternator output vol- Read 1.0 AC Volts Unsigned
tage (used for voltage integer
regulation)
40026 Alternator output cur- Read 0.1 AC Amps Unsigned
rent (phase a) integer
40027 Alternator output cur- Read 0.1 AC Amps Unsigned
rent (phase b) integer
40028 Alternator output cur- Read 0.1 AC Amps Unsigned
rent (phase c) integer
40029 Alternator output aver- Read 0.1 AC Amps Unsigned
age current integer
40040 Alternator output volt− Read 0.1 kVA Unsigned
amperes (phase a) integer
40041 Alternator output volt− Read 0.1 kVA Unsigned
amperes (phase b) integer
40042 Alternator output volt− Read 0.1 kVA Unsigned
amperes (phase c) integer
40043 Alternator output volt− Read 0.1 kVA Unsigned
amperes (total) integer
40044 Alternator frequency Read 0.1 Hz Unsigned
integer
40058 Alternator output cur- Read 0.1 % of nominal Unsigned
rent (phase a) integer
40059 Alternator output cur- Read 0.1 % of nominal Unsigned
rent (phase a) integer
40060 Alternator output cur- Read 0.1 % of nominal Unsigned
rent (phase c) integer
40061 Control battery volt- Read 0.1 DC Volts Unsigned
age integer
40062 Engine oil pressure Read 1.0 kPa Unsigned
integer
40064 Engine coolant tem- Read 0.1 Degrees Cel- Unsigned
perature sius integer
40068 Engine speed Read 0.1 RPM Unsigned
integer
40069 Number of engine Read 1.0 Number of Unsigned
starts starts integer
40070 Engine runtime (high Read 1.0 Sec Unsigned
byte) integer
2
Addr. Description Read / Write Scale Units Type Notes
40071 Engine Runtime (Low Read 1.0 Sec Unsigned
byte) integer
40300 Genset start stop con- Read and Unsigned 0 − Stop
trol via Modbus Write integer 1− Start
40302 Genset E−stop switch Read and Unsigned 0 − Estop not active
via Modbus Write integer 1 − Estop active
43000 Nominal alternator Read and 1.0 AC Volts Unsigned
voltage setting Write integer
43001 Nominal alternator fre- Read and Hz Unsigned 0 = 60
quency setting Write integer 1 = 50
43002 Alternator phase set- Read and # of phases Unsigned 0=1
ting Write integer 1 =3
43003 Alternator connection Read and Alternator Unsigned 1=Wye
setting Write integer
43004 Glow plug driver fea- Read and Feature en- Unsigned 0 = No
ture enable Write abled integer 1 = Yes
43005 Battery charging alter- Read and Feature en- Unsigned 0 = No
nator fault enable Write abled integer 1 = Yes
43006 Remote start time Read and 1.0 Sec Unsigned
delay Write integer
43007 Remote stop time Read and 1.0 Sec Unsigned
delay Write integer
43008 Engine starting − Read and 1.0 Number of at- Unsigned
cycle crank attempts Write tempts integer
setting
43009 Engine starting − Read and 1.0 Sec Unsigned
cycle crank time set- Write integer
ting
43010 Engine starting − Read and 1.0 Sec Unsigned
cycle crank rest time Write integer
setting
43011 Fault bypass (battle Read and Feature en- Unsigned 0 =Inactive
short) feature enable Write abled integer 1 = Active
43012 Fault bypass (battle Read and Switch as- Unsigned 0= None
short) switch input as- Write signment integer 1=Customer Input 1
signment 2=Customer Input 2
3=Operator Panel
43013 Automatic voltage Read and Feature en- Unsigned 0 = No
regulator Enable Write abled integer 1 = Yes
43014 Automatic voltage Read and 0.1 Hz Unsigned
regulator volts per Write integer
hertz roll off knee set-
ting
43015 Automatic voltage Read and 0.1 %V/Hz Unsigned
regulator volts per Write integer
hertz roll off slope
setting
43016 Automatic voltage Read and 1.0 % Unsigned
regulator gain setting Write integer
3
Addr. Description Read / Write Scale Units Type Notes
43017 Automatic voltage Read and 1.0 1.0 Unsigned
regulator integral set- Write integer
ting
43018 Automatic voltage Read and 1.0 1.0 Unsigned
regulator derivative Write integer
setting
43019 Electronic governing Read and 1.0 1.0 Unsigned 0 = No
enable Write integer 1 = Yes
43020 Electronic governing Read and 0.1 1.0 Unsigned
initial duty cycle set- Write integer
ting
43021 Electronic governing Read and 0.1 Sec Unsigned
initial duty cycle time Write integer
43022 Electronic governing Read and 0.1 % Unsigned
start ramp duty cycle Write integer
setting
43023 Electronic governing Read and 0.1 % Unsigned
maximum duty cycle Write integer
setting
43024 Electronic governing Read and 1.0 % Unsigned
gain setting Write integer
43025 Electronic governing Read and 1.0 % Unsigned
integral setting Write integer
43026 Electronic governing Read and 1.0 % Unsigned
derivative setting Write integer
43027 Electronic governing Read and 0.1 % Unsigned
crank exit fuel duty Write integer
cycle setting
43028 Electronic governing Read and 1.0 % Unsigned
dither factor setting Write integer
43029 Electronic governing Read and 0.01 Sec Unsigned
start ramp time setting Write integer
43030 Electronic governing Read and 1.0 RPM Unsigned
enable engine speed Write integer
43031 Electronic governing Read and 1.0 % Unsigned
minimum duty cycle Write integer
setting
43032 Electronic governing Read and 1.0 % Unsigned
maximum duty cycle Write integer
setting
43033 Model number char- Read and Character
acter #1 Write
43034 Model number char- Read and Character
acter #2 Write
43035 Model number char- Read and Character
acter #3 Write
43036 Model number char- Read and Character
acter #4 Write
43037 Model number char- Read and Character
acter #5 Write
4
Addr. Description Read / Write Scale Units Type Notes
43038 Model number char- Read and Character
acter #6 Write
43039 Model number char- Read and Character
acter #7 Write
43040 Model number char- Read and Character
acter #8 Write
43041 Model number char- Read and Character
acter #9 Write
43042 Model number char- Read and Character
acter #10 Write
43043 Model number char- Read and Character
acter #11 Write
43044 Model number char- Read and Character
acter #12 Write
43045 Model number char- Read and Character
acter #13 Write
43046 Model number char- Read and Character
acter #14 Write
43047 Model number char- Read and Character
acter #15 Write
43048 Model number char- Read and Character
acter #16 Write
43049 Serial number charac- Read and Character
ter #1 Write
43050 Serial number charac- Read and Character
ter #2 Write
43051 Serial number charac- Read and Character
ter #3 Write
43052 Serial number charac- Read and Character
ter #4 Write
43053 Serial number charac- Read and Character
ter #5 Write
43054 Serial number charac- Read and Character
ter #6 Write
43055 Serial number charac- Read and Character
ter #7 Write
43056 Serial number charac- Read and Character
ter #8 Write
43057 Serial number charac- Read and Character
ter #9 Write
43058 Serial number charac- Read and Character
ter #10 Write
43059 Serial number charac- Read and Character
ter #11 Write
43060 Serial number charac- Read and Character
ter #12 Write
43061 Serial number charac- Read and Character
ter #13 Write
43062 Serial number charac- Read and Character
ter #14 Write
5
Addr. Description Read / Write Scale Units Type Notes
43063 Serial number charac- Read and Character
ter #15 Write
43064 Serial number charac- Read and Character
ter #16 Write
43065 Configurable input #1 Read and Input type Unsigned 0 = Event
type Write integer 1 = Warning
2 = Shutdown
43066 Configurable input #2 Read and Input type Unsigned 0 = Event
type Write integer 1 = Warning
2 = Shutdown
43067 Configurable output Read and 1.0 Event code Unsigned
#1 event code number Write integer
43068 Configurable output Read and 1.0 Event code Unsigned
#2 fault event number Write integer
43069 60 Hz alternator out- Read and 1.0 % Unsigned
put voltage adjust % Write integer
43070 50 Hz alternator out- Read and 0.1 % Unsigned
put voltage adjust % Write integer
43071 Alternator frequency Read and 0.1 0.1 Unsigned
adjustment % Write integer
43072 60 Hz line 1 to neutral Read and 0.0001 % Unsigned
metering voltage cal- Write integer
ibration
43073 60 Hz line 2 to neutral Read and 0.0001 % Unsigned
metering voltage cal- Write integer
ibration
43075 50 Hz line 1 to neutral Read and 0.0001 % Unsigned
metering voltage cal- Write integer
ibration
43076 50 Hz line 2 to neutral Read and 0.0001 % Unsigned
metering voltage cal- Write integer
ibration
43077 50 Hz line 3 to neutral Read and 0.0001 % Unsigned
metering voltage cal- Write integer
ibration
43078 60 Hz line 1 metering Read and 0.001 % Unsigned
current calibration Write integer
43079 60 Hz line 2 metering Read and 0.001 % Unsigned
current calibration Write integer
43080 60 Hz line 3 metering Read and 0.001 % Unsigned
current calibration Write integer
43081 50 Hz line 1 metering Read and 0.001 % Unsigned
current calibration Write integer
43082 50 Hz line 2 metering Read and 0.001 % Unsigned
current calibration Write integer
43083 50 Hz line 3 metering Read and 0.001 % Unsigned
current calibration Write integer
43084 Annunciator configur- Read and Input type Unsigned 0 = Event
able input #1 type Write integer 1 = Warning
2 = Shutdown
6
Addr. Description Read / Write Scale Units Type Notes
43085 Annunciator configur- Read and Input type Unsigned 0 = Event
able input #2 type Write integer 1 = Warning
2 = Shutdown
43086 Annunciator configur- Read and Input type Unsigned 0 = Event
able input #3 type Write integer 1 = Warning
2 = Shutdown
43087 Annunciator configur- Read and 1.0 Event code Unsigned
able output #1 event Write integer
code number
43088 Annunciator configur- Read and 1.0 Event code Unsigned
able output #2 event Write integer
code number
43089 Annunciator configur- Read and 1.0 Event code Unsigned
able output #3 event Write integer
code number
43090 Annunciator configur- Read and 1.0 Event code Unsigned
able output #4 event Write integer
code number
7
THIS PAGE LEFT INTENTIONALLY BLANK
8
2. PowerCommand 2.x/3.x Modbus Register Map
Note: If an address or bit is not listed in this table it is not used.
Addr. Name Parameter Access Description Control
40010 GC / Start/ Control Read Current position of the genset switch panel Off−Run−Auto PC 2.x, PC
Stop Con- Switch Only switch as seen by the genset control. Modbus mapping shall 3.x
trol Position be in both addresses 40580 and 40010.
For Modbus Only: 0: Off 1: Auto 2: Manual
0: Off
1: Manual
2: Auto
40011 GC / Start/ Genset Read Current genset operating mode. Modbus mapping shall be PC 2.x, PC
Stop Con- Run Se- Only in both addresses 43500 and 40011 3.x
trol quence 0: Off
State 1: Time Delay to Start
2: Warmup at Idle
3: Rated Freq and Voltage
4: Cooldown / Stop Delay
5: Cooldown at Idle
40013 Modbus / Modbus Read This register always returns the value 0. This is not associat- PC 2.x, PC
Modbus register Only ed with any logical. It is made same as 1302 to make it com- 3.x
40013 patible with iWatch.
0: None
1: Warning
2: Shutdown
40012 Modbus / Most Re- Read Multiplier: 1 Unit: Fault This Modbus Register dis- PC 2.x, PC
Modbus cent Fault Only Code plays most recent Fault or 3.x
or Warning Warning. It is not mapped
with any logical.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40014 ACM / Genset % Read Multiplier: Unit: % Monitors the total genset PC 2.x, PC
Genset Standby Only 0.01 standby KW percentage out- 3.x
Current Total kW put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: S
40016 PCCNet / NFPA 110 Read Multiplier: 1 Unit: 32−bit number to represent PC 2.x, PC
Universal Logical Only the status of the NFPA 110 3.x
Annuncia- Status logical. See section 4.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
9
Addr. Name Parameter Access Description Control
40017 PCCNet / NFPA 110 Read Multiplier: 1 Unit: 32−bit number to represent PC 2.x, PC
Universal Logical Only the status of the NFPA 110 3.x
Annuncia- Status logical. See section 4.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40018 ACM / Genset Read Multiplier: 1 Unit: Vac Genset L1N voltage PC 2.x, PC
Voltage L1N Volt- Only 3.x
age Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40019 ACM / Genset Read Multiplier: 1 Unit: Vac Genset L2N voltage PC 2.x, PC
Voltage L2N Volt- Only 3.x
age Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40020 ACM / Genset Read Multiplier: 1 Unit: Vac Genset L3N voltage PC 2.x, PC
Voltage L3N Volt- Only 3.x
age Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40021 ACM / Genset LN Read Multiplier: 1 Unit: Vac Genset Line to Neutral aver- PC 2.x, PC
Voltage Average Only age voltage 3.x
Voltage Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40022 ACM / Genset Read Multiplier: 1 Unit: Vac Genset L1L2 voltage PC 2.x, PC
Voltage L1L2 Volt- Only 3.x
age Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40023 ACM / Genset Read Multiplier: 1 Unit: Vac Genset L2L3 voltage PC 2.x, PC
Voltage L2L3 Volt- Only 3.x
age Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40024 ACM / Genset Read Multiplier: 1 Unit: Vac Genset L3L1 voltage PC 2.x, PC
Voltage L3L1 Volt- Only 3.x
age Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
10
Addr. Name Parameter Access Description Control
40025 ACM / Genset LL Read Multiplier: 1 Unit: Vac Genset Line to Line average PC 2.x, PC
Voltage Average Only voltage 3.x
Voltage Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40026 ACM / Genset L1 Read Multiplier: 1 Unit: Amps Monitors the genset L1 cur- PC 2.x, PC
Current Current Only rent value. 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40027 ACM / Genset L2 Read Multiplier: 1 Unit: Amps Genset L2 current PC 2.x, PC
Current Current Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40028 ACM / Genset L3 Read Multiplier: 1 Unit: Amps Genset L3 current PC 2.x, PC
Current Current Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40029 ACM / Genset Av- Read Multiplier: 1 Unit: Amps Genset average current PC 2.x, PC
Current erage Cur- Only 3.x
rent Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40030 ACM / Genset Read Multiplier: 1 Unit: Amps Genset neutral current PC 3.x
Current Neutral Only Offset: 0 Lower Limit:
Current Size (bits): Upper Limit:
16
Sign: U
40031 ACM / Genset L1 Read Multiplier: 1 Unit: kW Genset L1 kW PC 2.x, PC
Power kW Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40032 ACM / Genset L2 Read Multiplier: 1 Unit: kW Genset L2 kW PC 2.x, PC
Power kW Only 3.x
Offset: 0 Lower Limit: −32768
Size (bits): Upper Limit: 32762
16
Sign: S
11
Addr. Name Parameter Access Description Control
40033 ACM / Genset L3 Read Multiplier: 1 Unit: kW Genset L3 kW PC 2.x, PC
Power kW Only 3.x
Offset: 0 Lower Limit: −32768
Size (bits): Upper Limit: 32762
16
Sign: S
40034 ACM / Genset To- Read Multiplier: 1 Unit: kW Genset total kW PC 2.x, PC
Power tal kW Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40035 ACM / Genset L1 Read Multiplier: 1 Unit: kVAR Genset L1 KVAR PC 2.x, PC
Power kVAR Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40036 ACM / Genset L2 Read Multiplier: 1 Unit: kVAR Genset L2 Kvar PC 2.x, PC
Power kVAR Only 3.x
Offset: 0 Lower Limit: −32768
Size (bits): Upper Limit: 32762
16
Sign: S
40037 ACM / Genset L3 Read Multiplier: 1 Unit: kVAR Genset L3 Kvar PC 2.x, PC
Power kVAR Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40038 ACM / Genset To- Read Multiplier: 1 Unit: kVAR Genset total kVAR PC 2.x, PC
Power tal kVAR Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40039 ACM / Genset To- Read Multiplier: Unit: PF Genset total power factor PC 2.x, PC
Power tal Power Only 0.01 (L1+L2+L3) 3.x
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
40040 ACM / Genset L1 Read Multiplier: 1 Unit: kVA Genset L1 kVA PC 2.x, PC
Power kVA Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
12
Addr. Name Parameter Access Description Control
40041 ACM / Genset L2 Read Multiplier: 1 Unit: kVA Genset L2 kVA PC 2.x, PC
Power kVA Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40042 ACM / Genset L3 Read Multiplier: 1 Unit: kVA Genset L3 kVA PC 2.x, PC
Power kVA Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40043 ACM / Genset To- Read Multiplier: 1 Unit: kVA Genset total kVA PC 2.x, PC
Power tal kVA Only 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40044 PCCNet / Genset Read Multiplier: Unit: Hz Genset Frequency OP PC 2.x, PC
Operator Frequency Only 0.01 3.x
Panel OP Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40046 ACM / En- Genset To- Read Multiplier: 1 Unit: kWh Genset total negative kWh PC 2.x, PC
ergy tal Nega- Only accumulation 3.x
tive kWh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40047 ACM / En- Genset To- Read Multiplier: 1 Unit: kWh Genset total negative kWh PC 2.x, PC
ergy tal Nega- Only accumulation 3.x
tive kWh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40048 ACM / En- Genset To- Read Multiplier: 1 Unit: kWh Genset total positive kWh PC 2.x, PC
ergy tal Positive Only accumulation 3.x
kWh Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967290
32
Sign: U
40049 ACM / En- Genset To- Read Multiplier: 1 Unit: kWh Genset total positive kWh PC 2.x, PC
ergy tal Positive Only accumulation 3.x
kWh Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967290
32
Sign: U
13
Addr. Name Parameter Access Description Control
40050 ACM / En- Genset To- Read Multiplier: 1 Unit: kWh Genset total net kWh accu- PC 2.x, PC
ergy tal Net Only mulation 3.x
kWh Offset: 0 Lower Limit: −2147483648
Size (bits): Upper Limit: 2147483643
32
Sign: S
40051 ACM / En- Genset To- Read Multiplier: 1 Unit: kWh Genset total net kWh accu- PC 2.x, PC
ergy tal Net Only mulation 3.x
kWh Offset: 0 Lower Limit: −2147483648
Size (bits): Upper Limit: 2147483643
32
Sign: S
40052 ACM / En- Genset To- Read Multiplier: 1 Unit: kVARh Genset total negative kVARh PC 2.x, PC
ergy tal Nega- Only accumulation 3.x
tive kVARh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40053 ACM / En- Genset To- Read Multiplier: 1 Unit: kVARh Genset total negative kVARh PC 2.x, PC
ergy tal Nega- Only accumulation 3.x
tive kVARh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40054 ACM / En- Genset To- Read Multiplier: 1 Unit: kVARh Genset total positive kVARh PC 2.x, PC
ergy tal Positive Only accumulation 3.x
kVARh Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967290
32
Sign: U
40055 ACM / En- Genset To- Read Multiplier: 1 Unit: kVARh Genset total positive kVARh PC 2.x, PC
ergy tal Positive Only accumulation 3.x
kVARh Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967290
32
Sign: U
40056 ACM / En- Genset To- Read Multiplier: 1 Unit: kVARh Genset total net kVARh ac- PC 2.x, PC
ergy tal Net Only cumulation 3.x
kVARh Offset: 0 Lower Limit: −2147483648
Size (bits): Upper Limit: 2147483643
32
Sign: S
40057 ACM / En- Genset To- Read Multiplier: 1 Unit: kVARh Genset total net kVARh ac- PC 2.x, PC
ergy tal Net Only cumulation 3.x
kVARh Offset: 0 Lower Limit: −2147483648
Size (bits): Upper Limit: 2147483643
32
Sign: S
14
Addr. Name Parameter Access Description Control
40058 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L1 current percentage out- 3.x
Current L1 Current put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
40059 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L2 current percentage out- 3.x
Current L2 Current put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
40060 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L3 current percentage out- 3.x
Current L3 Current put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
40061 ASI / Ana- Battery Read Multiplier: Unit: Vdc Battery voltage value−−−−−> PC 2.x, PC
log Inputs Voltage Only 0.001 For Modbus use only multi- 3.x
plier/units = 0.1 Volts
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 39
16
Sign: U
40062 CAN / Oil Pres- Read Multiplier: Unit: psi Monitor point for the Oil PC 2.x, PC
CAN Input sure Only 0.1 Pressure 3.x
Messages Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 145
16
Sign: U
40063 CAN / Oil Tem- Read Multiplier: Unit: degF Monitor point for the Oil PC 2.x, PC
CAN Input perature Only 0.1 Temperature 3.x
Messages Offset: 0 Lower Limit: −40
Size (bits): Upper Limit: 410
16
Sign: S
40064 CAN / Coolant Read Multiplier: Unit: degF Monitor point for the Coolant PC 2.x, PC
CAN Input Tempera- Only 0.1 Temperature 3.x
Messages ture Offset: 0 Lower Limit: −40
Size (bits): Upper Limit: 260
16
Sign: S
15
Addr. Name Parameter Access Description Control
40065 CAN / Intake Read Multiplier: Unit: degF To monitor Intake Manifold PC 2.x, PC
CAN Input Manifold Only 0.1 Temperature. This parame- 3.x
Messages Tempera- ter represents ”Intake Man-
ture ifold Temperature 1”.
Offset: 0 Lower Limit: −40
Size (bits): Upper Limit: 410
16
Sign: S
40066 CAN / Fuel Tem- Read Multiplier: Unit: degF Monitor point for the Fuel PC 2.x, PC
CAN Input perature Only 0.1 Temperature 3.x
Messages Offset: 0 Lower Limit: −40
Size (bits): Upper Limit: 410
16
Sign: S
40067 CAN / Fuel Rate Read Multiplier: Unit: gal/hr Monitor point for the Fuel PC 2.x, PC
CAN Input Only 0.05 Rate 3.x
Messages Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 845
16
Sign: U
40068 CAN / Average Read Multiplier: Unit: rpm Monitor point for the Aver- PC 2.x, PC
CAN Input Engine Only 0.125 age Engine Speed 3.x
Messages Speed Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4096
16
Sign: U
40069 PCCNet / Total Start Read/ Multiplier: 1 Unit: Total number of start at- PC 2.x, PC
Operator Attempts Write tempts. 3.x
Panel OP Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
40070 CAN / Engine Read Multiplier: Unit: hours Total engine run time PC 2.x, PC
CAN Input Running Only 0.05 3.x
Messages Time Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40071 CAN / Engine Read Multiplier: Unit: hours Total engine run time PC 2.x, PC
CAN Input Running Only 0.05 3.x
Messages Time Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40072 CAN / Total Fuel Read Multiplier: Unit: gallons Total fuel consumption since PC 2.x, PC
CAN Input Consump- Only 0.1 start of engine. 3.x
Messages tion Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
16
Addr. Name Parameter Access Description Control
40073 CAN / Total Fuel Read Multiplier: Unit: gallons Total fuel consumption since PC 2.x, PC
CAN Input Consump- Only 0.1 start of engine. 3.x
Messages tion Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40074 DR / Data Total Num- Read/ Multiplier: 1 Unit: Total number of genset runs. PC 2.x, PC
Recording ber of Write 3.x
Runs Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967295
32
Sign: U
40075 DR / Data Total Num- Read/ Multiplier: 1 Unit: Total number of genset runs. PC 2.x, PC
Recording ber of Write 3.x
Runs Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967295
32
Sign: U
40076 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40077 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40078 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40079 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
17
Addr. Name Parameter Access Description Control
40080 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40081 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40082 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40083 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40084 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40085 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40086 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
18
Addr. Name Parameter Access Description Control
40087 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40088 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40089 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40090 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40091 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40092 DR / Data Runs Re- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording set Time Write cord of the last time the Run 3.x
Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40096 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
19
Addr. Name Parameter Access Description Control
40097 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40098 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40099 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40100 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40101 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40102 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40103 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
20
Addr. Name Parameter Access Description Control
40104 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40105 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40106 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40107 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40108 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40109 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40110 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
21
Addr. Name Parameter Access Description Control
40111 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40112 DR / Data Start At- Read/ Multiplier: 1 Unit: Real Time Clock stamp re- PC 2.x, PC
Recording tempts Re- Write cord of the last time the Start 3.x
set Time Attempts were reset.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
144
Sign: C
40118 ACM / Utility L1N Read Multiplier: 1 Unit: Vac Utility L1N voltage PC 3.x
Voltage Voltage Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40119 ACM / Utility L2N Read Multiplier: 1 Unit: Vac Utility L2N voltage PC 3.x
Voltage Voltage Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40120 ACM / Utility L3N Read Multiplier: 1 Unit: Vac Utility L3N voltage PC 3.x
Voltage Voltage Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40121 ACM / Utility LN Read Multiplier: 1 Unit: Vac Utility Line to Neutral aver- PC 3.x
Voltage Average Only age voltage
Voltage Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40122 ACM / Utility L1L2 Read Multiplier: 1 Unit: Vac Utility L1L2 voltage PC 3.x
Voltage Voltage Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40123 ACM / Utility L2L3 Read Multiplier: 1 Unit: Vac Utility L2L3 voltage PC 3.x
Voltage Voltage Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40124 ACM / Utility L3L1 Read Multiplier: 1 Unit: Vac Utility L3L1 voltage PC 3.x
Voltage Voltage Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
22
Addr. Name Parameter Access Description Control
40125 ACM / Utility LL Read Multiplier: 1 Unit: Vac Utility Line to Line average PC 3.x
Voltage Average Only voltage
Voltage Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40126 ACM / Utility L1 Read Multiplier: 1 Unit: Amps Utility L1 current PC 3.x
Current Current Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40127 ACM / Utility L2 Read Multiplier: 1 Unit: Amps Utility L2 current PC 3.x
Current Current Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40128 ACM / Utility L3 Read Multiplier: 1 Unit: Amps Utility L3 current PC 3.x
Current Current Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40129 ACM / Utility Av- Read Multiplier: 1 Unit: Amps Utility average current PC 3.x
Current erage Cur- Only Offset: 0 Lower Limit:
rent Size (bits): Upper Limit:
16
Sign: U
40131 ACM / Utility L1 Read Multiplier: 1 Unit: kW Utility L1 kW PC 3.x
Power kW Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40132 ACM / Utility L2 Read Multiplier: 1 Unit: kW Utility L2 kW PC 3.x
Power kW Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40133 ACM / Utility L3 Read Multiplier: 1 Unit: kW Utility L3 kW PC 3.x
Power kW Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40134 ACM / Utility Total Read Multiplier: 1 Unit: kW Utility total kW PC 3.x
Power kW Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40135 ACM / Utility L1 Read Multiplier: 1 Unit: kVAR Utility L1 Kvar PC 3.x
Power kVAR Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
23
Addr. Name Parameter Access Description Control
40136 ACM / Utility L2 Read Multiplier: 1 Unit: kVAR Utility L2 Kvar PC 3.x
Power kVAR Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40137 ACM / Utility L3 Read Multiplier: 1 Unit: kVAR Utility L3 Kvar PC 3.x
Power kVAR Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40138 ACM / Utility Total Read Multiplier: 1 Unit: kVAR Utility total kVAR PC 3.x
Power kVAR Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40139 ACM / Utility Total Read Multiplier: Unit: PF Utility total power factor PC 3.x
Power Power Only 0.01
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
40140 ACM / Utility L1 Read Multiplier: 1 Unit: kVA Utility L1 kVA PC 3.x
Power kVA Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40141 ACM / Utility L2 Read Multiplier: 1 Unit: kVA Utility L2 kVA PC 3.x
Power kVA Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40142 ACM / Utility L3 Read Multiplier: 1 Unit: kVA Utility L3 kVA PC 3.x
Power kVA Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40143 ACM / Utility Total Read Multiplier: 1 Unit: kVA Utility total kVA PC 3.x
Power kVA Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40144 ACM / Fre- Utility Fre- Read Multiplier: Unit: Hz Utility line frequency PC 3.x
quency quency Only 0.001
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40145 ACM / Fre- Utility Fre- Read Multiplier: Unit: Hz Utility line frequency PC 3.x
quency quency Only 0.001
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
24
Addr. Name Parameter Access Description Control
40146 ACM / En- Utility Total Read Multiplier: 1 Unit: kWh Utility total negative kWh ac- PC 3.x
ergy Negative Only cumulation
kWh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40147 ACM / En- Utility Total Read Multiplier: 1 Unit: kWh Utility total negative kWh ac- PC 3.x
ergy Negative Only cumulation
kWh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40148 ACM / En- Utility Total Read Multiplier: 1 Unit: kWh Utility total positive kWh ac- PC 3.x
ergy Positive Only cumulation
kWh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40149 ACM / En- Utility Total Read Multiplier: 1 Unit: kWh Utility total positive kWh ac- PC 3.x
ergy Positive Only cumulation
kWh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40150 ACM / En- Utility Total Read Multiplier: 1 Unit: kWh Utility total net kWh accu- PC 3.x
ergy Net kWh Only mulation
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: S
40151 ACM / En- Utility Total Read Multiplier: 1 Unit: kWh Utility total net kWh accu- PC 3.x
ergy Net kWh Only mulation
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: S
40152 ACM / En- Utility Total Read Multiplier: 1 Unit: kVARh Utility total negative kVARh PC 3.x
ergy Negative Only accumulation
kVARh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40153 ACM / En- Utility Total Read Multiplier: 1 Unit: kVARh Utility total negative kVARh PC 3.x
ergy Negative Only accumulation
kVARh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
25
Addr. Name Parameter Access Description Control
40154 ACM / En- Utility Total Read Multiplier: 1 Unit: kVARh Utility total positive kVARh PC 3.x
ergy Positive Only accumulation
kVARh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40155 ACM / En- Utility Total Read Multiplier: 1 Unit: kVARh Utility total positive kVARh PC 3.x
ergy Positive Only accumulation
kVARh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40156 ACM / En- Utility Total Read Multiplier: 1 Unit: kVARh Utility total net kVARh accu- PC 3.x
ergy Net kVARh Only mulation
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: S
40157 ACM / En- Utility Total Read Multiplier: 1 Unit: kVARh Utility total net kVARh accu- PC 3.x
ergy Net kVARh Only mulation
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: S
40158 ACM / Genset Read Multiplier: 1 Unit: Vac Genset Bus L1N voltage PC 3.x
Voltage Bus L1N Only Offset: 0 Lower Limit:
Voltage Size (bits): Upper Limit:
16
Sign: U
40159 ACM / Genset Read Multiplier: 1 Unit: Vac Genset Bus L2N voltage PC 3.x
Voltage Bus L2N Only Offset: 0 Lower Limit:
Voltage Size (bits): Upper Limit:
16
Sign: U
40160 ACM / Genset Read Multiplier: 1 Unit: Vac Genset Bus L3N voltage PC 3.x
Voltage Bus L3N Only Offset: 0 Lower Limit:
Voltage Size (bits): Upper Limit:
16
Sign: U
40161 ACM / Genset Read Multiplier: 1 Unit: Vac Genset Bus Line to Neutral PC 3.x
Voltage Bus LN Only average voltage
Average Offset: 0 Lower Limit:
Voltage Size (bits): Upper Limit:
16
Sign: U
40162 ACM / Genset Read Multiplier: 1 Unit: Vac Genset Bus L1L2 voltage PC 3.x
Voltage Bus L1L2 Only Offset: 0 Lower Limit:
Voltage Size (bits): Upper Limit:
16
Sign: U
26
Addr. Name Parameter Access Description Control
40163 ACM / Genset Read Multiplier: 1 Unit: Vac Genset Bus L2L3 voltage PC 3.x
Voltage Bus L2L3 Only Offset: 0 Lower Limit:
Voltage Size (bits): Upper Limit:
16
Sign: U
40164 ACM / Genset Read Multiplier: 1 Unit: Vac Genset Bus L3L1 voltage PC 3.x
Voltage Bus L3L1 Only Offset: 0 Lower Limit:
Voltage Size (bits): Upper Limit:
16
Sign: U
40165 ACM / Genset Read Multiplier: 1 Unit: Vac Genset Bus Line to Line av- PC 3.x
Voltage Bus LL Av- Only erage voltage
erage Volt- Offset: 0 Lower Limit:
age Size (bits): Upper Limit:
16
Sign: U
40166 ACM / Genset Read Multiplier: 1 Unit: Amps Genset Bus L1 current PC 3.x
Current Bus L1 Only Offset: 0 Lower Limit: 0
Current Size (bits): Upper Limit: 65530
16
Sign: U
40167 ACM / Genset Read Multiplier: 1 Unit: Amps Genset Bus L2 current PC 3.x
Current Bus L2 Only Offset: 0 Lower Limit:
Current Size (bits): Upper Limit:
16
Sign: U
40168 ACM / Genset Read Multiplier: 1 Unit: Amps Genset Bus L3 current PC 3.x
Current Bus L3 Only Offset: 0 Lower Limit:
Current Size (bits): Upper Limit:
16
Sign: U
40169 ACM / Genset Read Multiplier: 1 Unit: Amps Genset Bus Average current PC 3.x
Current Bus Aver- Only Offset: 0 Lower Limit:
age Cur- Size (bits): Upper Limit:
rent 16
Sign: U
40171 ACM / Genset Read Multiplier: 1 Unit: kW Genset Bus L1 kW PC 3.x
Power Bus L1 kW Only Offset: 0 Lower Limit: −32768
Size (bits): Upper Limit: 32762
16
Sign: S
40172 ACM / Genset Read Multiplier: 1 Unit: kW Genset Bus L2 kW PC 3.x
Power Bus L2 kW Only Offset: 0 Lower Limit: −32768
Size (bits): Upper Limit: 32762
16
Sign: S
40173 ACM / Genset Read Multiplier: 1 Unit: kW Genset Bus L3 kW PC 3.x
Power Bus L3 kW Only Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
27
Addr. Name Parameter Access Description Control
40174 ACM / Genset Read Multiplier: 1 Unit: kW Genset Bus total kW PC 3.x
Power Bus Total Only Offset: 0 Lower Limit:
kW Size (bits): Upper Limit:
16
Sign: S
40175 ACM / Genset Read Multiplier: 1 Unit: kVAR Genset bus L1 Kvar PC 3.x
Power Bus L1 Only Offset: 0 Lower Limit: −32678
kVAR Size (bits): Upper Limit: 32672
16
Sign: S
40176 ACM / Genset Read Multiplier: 1 Unit: kVAR Genset bus L2 Kvar PC 3.x
Power Bus L2 Only Offset: 0 Lower Limit: −32768
kVAR Size (bits): Upper Limit: 32762
16
Sign: S
40177 ACM / Genset Read Multiplier: 1 Unit: kVAR Genset bus L3 Kvar PC 3.x
Power Bus L3 Only Offset: 0 Lower Limit:
kVAR Size (bits): Upper Limit:
16
Sign: S
40178 ACM / Genset Read Multiplier: 1 Unit: kVAR Genset bus total kVAR PC 3.x
Power Bus Total Only Offset: 0 Lower Limit:
kVAR Size (bits): Upper Limit:
16
Sign: S
40179 ACM / Genset Read Multiplier: Unit: PF Genset Bus Total power fac- PC 3.x
Power Bus Total Only 0.01 tor
Power Offset: 0 Lower Limit:
Factor Size (bits): 8 Upper Limit:
Sign: S
40180 ACM / Genset Read Multiplier: 1 Unit: kVA Genset Bus L1 kVA PC 3.x
Power Bus L1 Only Offset: 0 Lower Limit:
kVA Size (bits): Upper Limit:
16
Sign: U
40181 ACM / Genset Read Multiplier: 1 Unit: kVA Genset Bus L2 kVA PC 3.x
Power Bus L2 Only Offset: 0 Lower Limit:
kVA Size (bits): Upper Limit:
16
Sign: U
40182 ACM / Genset Read Multiplier: 1 Unit: kVA Genset Bus L3 kVA PC 3.x
Power Bus L3 Only Offset: 0 Lower Limit:
kVA Size (bits): Upper Limit:
16
Sign: U
40183 ACM / Genset Read Multiplier: 1 Unit: kVA Genset bus total kVA PC 3.x
Power Bus Total Only Offset: 0 Lower Limit:
kVA Size (bits): Upper Limit:
16
Sign: U
28
Addr. Name Parameter Access Description Control
40184 ACM / Fre- Genset Read Multiplier: Unit: Hz Genset bus line frequency PC 3.x
quency Bus Fre- Only 0.001
quency Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40185 ACM / Fre- Genset Read Multiplier: Unit: Hz Genset bus line frequency PC 3.x
quency Bus Fre- Only 0.001
quency Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40186 ACM / En- Genset Read Multiplier: 1 Unit: kWh Genset bus total negative PC 3.x
ergy Bus Total Only kWh accumulation
Negative Offset: 0 Lower Limit:
kWh Size (bits): Upper Limit:
32
Sign: U
40187 ACM / En- Genset Read Multiplier: 1 Unit: kWh Genset bus total negative PC 3.x
ergy Bus Total Only kWh accumulation
Negative Offset: 0 Lower Limit:
kWh Size (bits): Upper Limit:
32
Sign: U
40188 ACM / En- Genset Read Multiplier: 1 Unit: kWh Genset bus total positive PC 3.x
ergy Bus Total Only kWh accumulation
Positive Offset: 0 Lower Limit:
kWh Size (bits): Upper Limit:
32
Sign: U
40189 ACM / En- Genset Read Multiplier: 1 Unit: kWh Genset bus total positive PC 3.x
ergy Bus Total Only kWh accumulation
Positive Offset: 0 Lower Limit:
kWh Size (bits): Upper Limit:
32
Sign: U
40190 ACM / En- Genset Read Multiplier: 1 Unit: kWh Genset bus total net kWh PC 3.x
ergy Bus Total Only accumulation
Net kWh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: S
40191 ACM / En- Genset Read Multiplier: 1 Unit: kWh Genset bus total net kWh PC 3.x
ergy Bus Total Only accumulation
Net kWh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: S
29
Addr. Name Parameter Access Description Control
40192 ACM / En- Genset Read Multiplier: 1 Unit: kVARh Genset bus total negative PC 3.x
ergy Bus Total Only kVARh accumulation
Negative Offset: 0 Lower Limit:
kVARh Size (bits): Upper Limit:
32
Sign: U
40193 ACM / En- Genset Read Multiplier: 1 Unit: kVARh Genset bus total negative PC 3.x
ergy Bus Total Only kVARh accumulation
Negative Offset: 0 Lower Limit:
kVARh Size (bits): Upper Limit:
32
Sign: U
40194 ACM / En- Genset Read Multiplier: 1 Unit: kVARh Genset bus total positive PC 3.x
ergy Bus Total Only kVARh accumulation
Positive Offset: 0 Lower Limit:
kVARh Size (bits): Upper Limit:
32
Sign: U
40195 ACM / En- Genset Read Multiplier: 1 Unit: kVARh Genset bus total positive PC 3.x
ergy Bus Total Only kVARh accumulation
Positive Offset: 0 Lower Limit:
kVARh Size (bits): Upper Limit:
32
Sign: U
40196 ACM / En- Genset Read Multiplier: 1 Unit: kVARh Genset Bus total net kVARh PC 3.x
ergy Bus Total Only accumulation
Net kVARh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: S
40197 ACM / En- Genset Read Multiplier: 1 Unit: kVARh Genset Bus total net kVARh PC 3.x
ergy Bus Total Only accumulation
Net kVARh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: S
40198 ACM / Ground Read Multiplier: Unit: amps Ground current PC 3.x
Current Current Only 0.1
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40199 ACM / Genset Read Multiplier: Unit: % Genset Negative Sequence PC 3.x
Current Negative Only 0.01 Current as Percent of Stand-
Sequence by Current Rating
Current % Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
30
Addr. Name Parameter Access Description Control
40207 ASI / Ana- Battery Read Multiplier: Unit: Vdc The Battery Charger Alterna- PC 2.x, PC
log Inputs Charger Only 0.001 tor Flash Voltage after all 3.x
Alternator scaling and validity checks.
Flash Volt- Offset: 0 Lower Limit: 0
age Size (bits): Upper Limit: 35
16
Sign: U
40201 ASI / Ana- Coolant Read/ Either Onan or Cummins sensor. Modbus Access: Read PC 2.x, PC
log Inputs/ Tempera- Write Only 3.x
Outputs ture Send- 0: PGBU
er Type 1: EBU
40210 ASI / Ana- External Read Multiplier: Unit: % Monitor point for the external PC 2.x, PC
log Inputs Speed Only 0.01 speed bias input. 3.x
Bias Input Offset: 0 Lower Limit: −100
Size (bits): Upper Limit: 100
16
Sign: S
40211 ASI / Ana- External Read Multiplier: Unit: % Monitor point for the external PC 2.x, PC
log Inputs Voltage Only 0.01 voltage bias input. 3.x
Bias Input Offset: 0 Lower Limit: −100
Size (bits): Upper Limit: 100
16
Sign: S
40214 ASI / Ana- kVAR Load Read Multiplier: Unit: % EU scaled value for the PC 3.x
log Inputs Setpoint Only 0.01 kVAR load setpoint
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit:
16
Sign: S
40217 ASI / Ana- kVAR Load Read Multiplier: Unit: % EU Scaled value for the PC 3.x
log Inputs Share Lev- Only 0.01 kVAR load share level ana-
el log input
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40219 ASI / Ana- kW Load Read Multiplier: Unit: % EU scaled value for the kW PC 3.x
log Inputs Setpoint Only 0.01 load setpoint
Offset: 0 Lower Limit: −25.01
Size (bits): Upper Limit: 125.01
16
Sign: S
40222 ASI / Ana- kW Load Read Multiplier: Unit: % EU Scaled value for the kW PC 3.x
log Inputs Share Lev- Only 0.01 load share level analog input
el Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
31
Addr. Name Parameter Access Description Control
40224 ASO / KVAR Read Multiplier: Unit: uA uA signal being injected into PC 3.x
Analog Load Only 0.1 a 10K ohm resistor network
Outputs Share Out- Offset: 0 Lower Limit:
put Predic- Size (bits): Upper Limit:
tor 16
Sign: S
40225 ASO / KW Load Read Multiplier: Unit: uA uA signal being injected into PC 3.x
Analog Share Out- Only 0.1 a 10K ohm resistor network
Outputs put Predic- Offset: 0 Lower Limit:
tor Size (bits): Upper Limit:
16
Sign: S
40226 ASO / Speed Read Multiplier: Unit: Vdc Configurable analog output PC 3.x
Analog Bias Out- Only 0.01 voltage output value (pre-
Outputs put / Confi- dicted)
gurable Offset: 0 Lower Limit:
Analog
Size (bits): Upper Limit:
output #1
16
Output
Predictor Sign: S
40227 ASO / Voltage Read Multiplier: Unit: Vdc Configurable analog output PC 3.x
Analog Bias Out- Only 0.01 voltage output value (pre-
Outputs put / Confi- dicted)
gurable Offset: 0 Lower Limit:
Analog
Size (bits): Upper Limit:
output #2
16
Output
Predictor Sign: S
40228 CAN / CAN Amber Read Engine Control System indicates a warning condition. PC 2.x, PC
Input Mes- Warning Only 0: Inactive 3.x
sages Lamp Sta-
tus 1: Active
40229 CAN / Barometric Read Multiplier: Unit: psi Monitor point for the Baro- PC 2.x, PC
CAN Input Absolute Only 0.1 metric Absolute Pressure. 3.x
Messages Pressure Displayed as ”Ambient Pres-
sure” in the HMI.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 37
16
Sign: U
40230 CAN / Boost Read Multiplier: Unit: psi Monitor point for the Boost PC 2.x, PC
CAN Input Pressure Only 0.1 Absolute Pressure 3.x
Messages Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 148
16
Sign: U
40231 CAN / CAN CAN Datal- Read Indicates the status of the CAN datalink PC 2.x, PC
Datalink ink Status Only 0: Inactive 3.x
1: Active
2: Failed
32
Addr. Name Parameter Access Description Control
40232 CAN / Crankcase Read Multiplier: Unit: psi Monitor point for the Crank- PC 2.x, PC
CAN Input Pressure Only 0.1 case Pressure. 3.x
Messages Offset: 0 Lower Limit: −35.67
Size (bits): Upper Limit: 38
16
Sign: S
40235 CAN / ECM Der- Read Request made by the ECS for a reduction in load PC 2.x, PC
CAN Input ate Re- Only 0: No Derate Request 3.x
Messages quest 1: Derate Request
2: Error
3: Don’t Care
40236 CAN / Engine Ap- Read Monitor point for the output of the Engine application type. PC 2.x, PC
40237 CAN Input plication Only Either ECM (CAN) or Hydro−Mechanical. 3.x
Messages Type 0: ECM
1: Hydro−Mechanical
ECS engine state indication
1: Ventilation
2: Start
3: Run
4: Normal Shutdown
5: Emergency Shutdown
6: Error
7: Don’t Care
40242 CAN / Aftercooler Read Multiplier: Unit: degF Monitor point for the After- PC 2.x, PC
CAN Input Tempera- Only 0.1 cooler Temperature. 3.x
Messages ture Offset: 0 Lower Limit: −40
Size (bits): Upper Limit: 410
16
Sign: S
40254 CAN / Fuel Sup- Read Multiplier: Unit: psi Monitor point for the Fuel PC 2.x, PC
CAN Input ply Pres- Only 0.1 Supply Pressure. Displayed 3.x
Messages sure as ”Fuel Supply Pressure” in
the HMI.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 145
16
Sign: U
40257 CAN / Intake Read Multiplier: Unit: degF Monitor point for the Intake PC 2.x, PC
CAN Input Manifold 4 Only 0.1 Manifold 4 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −40
ture Size (bits): Upper Limit: 410
16
Sign: S
40258 CAN / Fuel Outlet Read Multiplier: Unit: psi Monitor point for the Fuel PC 2.x, PC
CAN Input Pressure Only 0.1 Outlet Pressure Pressure. 3.x
Messages Displayed as ”Fuel Rail
Pressure” in the HMI.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 36404
32
Sign: U
33
Addr. Name Parameter Access Description Control
40259 CAN / Fuel Outlet Read Multiplier: Unit: psi Monitor point for the Fuel PC 2.x, PC
CAN Input Pressure Only 0.1 Outlet Pressure Pressure. 3.x
Messages Displayed as ”Fuel Rail
Pressure” in the HMI.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 36404
32
Sign: U
40260 CAN / Intake Read Multiplier: Unit: degF Monitor point for the Intake PC 2.x, PC
CAN Input Manifold 2 Only 0.1 Manifold 2 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −40
ture Size (bits): Upper Limit: 410
16
Sign: S
40261 CAN / Intake Read Multiplier: Unit: degF Monitor point for the Intake PC 2.x, PC
CAN Input Manifold 3 Only 0.1 Manifold 3 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −40
ture Size (bits): Upper Limit: 410
16
Sign: S
40262 CAN / Keyswitch Read Driver command that controls the output for the keyswitch PC 2.x, PC
CAN Out- Command Only 0: Inactive 3.x
put Mes-
sages 1: Active
40263 CAN / Normal Read Request made by the ECS for a normal shutdown with cool- PC 2.x, PC
CAN Input Shutdown Only down 3.x
Messages Request 0: No Shutdown Request
1: Normal Shutdown Request
2: Error
3: Don’t Care
40264 CAN / Percent Read Multiplier: 1 Unit: % Monitor point for the percent PC 2.x, PC
CAN Input Engine Only engine torque output and the 3.x
Messages Torque/ governor percent duty cycle
Duty Cycle output when used with the
HM ECM
Offset: 0 Lower Limit: −125
Size (bits): Upper Limit: 125
16
Sign: S
40276 CAN / Post−Filter Read Multiplier: Unit: psi Monitor point for the Post− PC 2.x, PC
CAN Input Oil Pres- Only 0.1 Filter Oil Pressure 3.x
Messages sure Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 145
16
Sign: U
40277 CAN / Pre−Filter Read Multiplier: Unit: psi Monitor point for the Pre−Fil- PC 2.x, PC
CAN Input Oil Pres- Only 0.1 ter Oil Pressure 3.x
Messages sure Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 145
16
Sign: U
34
Addr. Name Parameter Access Description Control
40278 DSI / Dis- Configur- Read Configurable Input #14 input software state status. Gives PC 2.x, PC
crete In- able Input Only software Inactive/Active state 3.x
puts #14 Switch 0: Inactive
1: Active
40279 CAN / Turbochar- Read Multiplier: 1 Unit: rpm Monitor point for the Turbo- PC 2.x, PC
CAN Input ger 1 Only charger 1 Speed 3.x
Messages Speed Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 257000
32
Sign: U
40280 CAN / Turbochar- Read Multiplier: 1 Unit: rpm Monitor point for the Turbo- PC 2.x, PC
CAN Input ger 1 Only charger 1 Speed 3.x
Messages Speed Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 257000
32
Sign: U
40281 CAN / Turbochar- Read Multiplier: Unit: psi Monitor point for the Turbo- PC 2.x, PC
CAN Input ger 2 Only 0.1 charger 2 Boost Pressure 3.x
Messages Boost Offset: 0 Lower Limit: 0
Pressure Size (bits): Upper Limit: 1160
16
Sign: U
40282 CAN / Water in Read Water in Fuel Indication PC 2.x, PC
CAN Input Fuel Indi- Only 0: No 3.x
Messages cator 1: Yes
40283 CM / Con- Controller Read The controller mode PC 2.x, PC
troller Mode Only 0: Off 3.x
Modes 1: Ready
3: Starting
4: Idle
5: Rated
6: Stop Normal
7: Stop Emergency
8: Factory Test
9: Wait to Power Down
40285 CM / Con- Power Read Multiplier: 1 Unit: sec- Timer to count down the time PC 2.x, PC
troller Down Only onds before the control goes to 3.x
Modes Mode Tim- sleep
er Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 600
16
Sign: U
40286 CM / Con- Setup Read Multiplier: 1 Unit: Sec- Time spent in Setup Mode. PC 2.x, PC
troller Mode Tim- Only onds 3.x
Modes er Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
40287 CM / Con- Tool Read The control output to the common wake−up line to wake up PC 2.x, PC
troller Wake−up Only other devices 3.x
Modes Command 0: Inactive
1: Active
35
Addr. Name Parameter Access Description Control
40289 DR / Exer- Active Read Indicates the currently active scheduler program or excep- PC 2.x, PC
cise Schedule Only tion. 3.x
Scheduler 0: None
1: Program 1
2: Program 2
3: Program 3
4: Program 4
5: Program 5
6: Program 6
7: Program 7
8: Program 8
9: Program 9
10: Program 10
11: Program 11
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
40290 DR / Data Controller Read/ Multiplier: 1 Unit: Sec- Controller ON time in sec- PC 2.x, PC
Recording On Time Write onds onds. Upper limit is 136 3.x
years.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967291
32
Sign: U
40291 DR / Data Controller Read/ Multiplier: 1 Unit: Sec- Controller ON time in sec- PC 2.x, PC
Recording On Time Write onds onds. Upper limit is 136 3.x
years.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967291
32
Sign: U
40298 DR / Data Runs Read/ Multiplier: 1 Unit: Number of runs since the PC 2.x, PC
Recording Since Re- Write last reset. Upper limit is 2^32 3.x
set − 1.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967290
32
Sign: U
40299 DR / Data Runs Read/ Multiplier: 1 Unit: Number of runs since the PC 2.x, PC
Recording Since Re- Write last reset. Upper limit is 2^32 3.x
set − 1.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967290
32
Sign: U
36
Addr. Name Parameter Access Description Control
40300 Modbus / Remote Read/ Modbus Remote Start PC 2.x, PC
Modbus Start Write 0: Inactive 3.x
Switch
(Modbus) 1: Active
40301 Modbus / Fault Reset Read/ Modbus fault reset. PC 2.x, PC
Modbus (Modbus) Write 0: Inactive 3.x
1: Active
40320 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40321 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40322 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40323 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40324 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
37
Addr. Name Parameter Access Description Control
40325 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40326 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40327 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40328 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40329 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40330 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
38
Addr. Name Parameter Access Description Control
40331 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40332 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40333 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40334 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40335 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40336 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
39
Addr. Name Parameter Access Description Control
40337 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40338 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40339 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No1 Write ter string for use by the oper-
puts Fault Text ator panel when this fault be-
comes active
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40340 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40341 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40342 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40
Addr. Name Parameter Access Description Control
40343 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40344 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40345 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40346 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40347 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40348 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
41
Addr. Name Parameter Access Description Control
40349 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40350 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40351 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40352 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40353 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40354 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
42
Addr. Name Parameter Access Description Control
40355 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40356 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40357 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40358 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40359 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No2 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40360 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43
Addr. Name Parameter Access Description Control
40361 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40362 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40363 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40364 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40365 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40366 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
44
Addr. Name Parameter Access Description Control
40367 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40368 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40369 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40370 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40371 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40372 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
45
Addr. Name Parameter Access Description Control
40373 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40374 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40375 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40376 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40377 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40378 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46
Addr. Name Parameter Access Description Control
40379 DSI / Dis- Start Inhib- Read/ Multiplier: 1 Unit: Trim to define the 20 charac- PC 3.x
crete In- it No3 Write ter string for use by the Op-
puts Fault Text erator panel when this fault
becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40400 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
1 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40401 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
2 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40402 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
3 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40403 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
4 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40404 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
5 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40405 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
6 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40406 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
7 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
47
Addr. Name Parameter Access Description Control
40407 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
8 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40408 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
9 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40409 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
10 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40410 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
11 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40411 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
12 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40412 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
13 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40413 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
14 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40414 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
15 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
48
Addr. Name Parameter Access Description Control
40415 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
16 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40416 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
17 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40417 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
18 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40418 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
19 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40419 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
20 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40420 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
21 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40421 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
22 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
40422 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
23 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: S
49
Addr. Name Parameter Access Description Control
40430 Modbus / Event Sta- Read Multiplier: 1 Unit: 16 bit fault bitmap for Modus PC 2.x, PC
Modbus tus Bitmap Only interface. 3.x
1 Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
40431 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 1 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40432 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 2 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40433 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 3 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40434 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 4 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40435 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 5 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40436 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 6 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40437 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 7 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
50
Addr. Name Parameter Access Description Control
40438 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 8 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40439 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 9 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40440 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 10 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40441 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 11 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40442 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 12 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40443 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 13 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40444 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 14 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40445 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 15 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
51
Addr. Name Parameter Access Description Control
40446 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 16 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40447 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 17 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40448 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 18 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40449 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 19 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40450 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 20 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40451 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 21 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40452 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 22 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40453 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 23 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
52
Addr. Name Parameter Access Description Control
40454 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 24 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40455 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 25 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40456 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 26 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40457 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 27 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40458 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 28 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40459 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 29 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40460 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 30 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40461 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 31 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
53
Addr. Name Parameter Access Description Control
40462 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 32 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40463 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 33 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40464 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 34 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40465 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 35 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40466 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 36 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40467 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 37 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40468 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 38 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40469 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 39 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
54
Addr. Name Parameter Access Description Control
40470 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 40 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40471 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 41 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40472 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 42 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40473 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 43 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40474 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 44 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40475 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 45 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40476 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 46 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40477 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 47 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
55
Addr. Name Parameter Access Description Control
40478 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 48 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40479 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 49 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40480 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 50 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40481 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 51 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40482 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 52 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40483 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 53 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40484 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 54 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40485 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 55 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
56
Addr. Name Parameter Access Description Control
40486 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 56 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40487 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 57 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40488 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 58 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40489 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 59 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40490 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 60 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40491 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 61 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40492 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 62 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40493 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 63 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
57
Addr. Name Parameter Access Description Control
40494 Modbus / Fault Sta- Read Multiplier: 1 Unit: 16 bit Gas fault bitmap for PC 3.x
Modbus tus Gas Only Modus interface.
Bitmap 64 Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
40500 DSI / Dis- Low Fuel Read Low Fuel input software state status. Gives software Inac- PC 2.x, PC
crete In- Switch Only tive/Active state 3.x
puts 0: Inactive
1: Active
40501 DSI / Dis- Low Fuel/ Read This is the status of the Configurable Input #6. PC 2.x, PC
crete In- Configur- Only 0: Inactive 3.x
puts able Input
#6 Switch 1: Active
40502 DSI / Safety Read 0: Inactive PC 3.x
Wire Loop Only 1: Active
40503 DSI / Dis- Differential Read Differential fault trip monitor point. PC 3.x
crete In- Fault Trip Only 0: Inactive
puts 1: Active
40504 DSI / Dis- Master Read This is the status of the Master First Start A input. PC 3.x
crete In- First Start Only 0: Inactive
puts Input A 1: Active
40505 DSI / Dis- Fire Trip Read Fire trip monitor point. PC 3.x
crete In- Only 0: Inactive
puts 1: Active
40506 DSI / Dis- Master Read Masterless Load Demand Enable Switch function output PC 3.x
crete In- First Start Only status. Gives software Inactive/Active state
puts Input B 0: Inactive
Switch 1: Active
40507 DSI / Dis- Masterless Read Masterless Load Demand Enable Switch function output PC 3.x
crete In- Load De- Only status. Gives software Inactive/Active state
puts mand En- 0: Inactive
able
Switch 1: Active
40508 DSI / Dis- Predictive Read Predictive Load Enable Switch function output status. PC 3.x
crete In- Load En- Only Gives software Inactive/Active state
puts able 0: Inactive
Switch 1: Active
40509 DSI / Dis- PTC Mode Read PTC Mode Switch function output status. Gives software PC 3.x
crete In- Switch Only Inactive/Active state
puts 0: Inactive
1: Active
40510 DSI / Dis- Extended Read This is the status of the Configurable Input #32. PC 3.x
crete In- Parallel/ Only
puts Configur- 0: Inactive
able Input
1: Active
#32 Switch
40511 DSI / Dis- Ramp Read Ramp Load/Unload input software state status. PC 3.x
crete In- Load/Un- Only 0: Load
puts load
Switch 1: Unload
58
Addr. Name Parameter Access Description Control
40512 DSI / Dis- Remote E− Read Remote E−stop input software state status. Gives soft- PC 2.x, PC
crete In- stop Switch Only ware Inactive/Active state 3.x
puts 0: Inactive
1: Active
40513 DSI / Dis- Remote Read Remote Start input software state status. Gives software PC 2.x, PC
crete In- Start Only Inactive/Active state 3.x
puts Switch 0: Inactive
1: Active
40514 DSI / Dis- Retransfer Read Retransfer Inhibit input software state status. Gives soft- PC 3.x
crete In- Inhibit Only ware Inactive/Active state
puts Switch 0: Inactive
1: Active
40515 DSI / Dis- Retransfer Read This is the status of the Configurable Input #21. PC 3.x
crete In- Inhibit/ Only
puts Configur- 0: Inactive
able Input 1: Active
#21 Switch
40516 DSI / Dis- Rupture Read Rupture Basin input software state status. Gives software PC 2.x, PC
crete In- Basin Only Inactive/Active state 3.x
puts Switch 0: Inactive
1: Active
40517 DSI / Dis- Rupture Read This is the status of the Configurable Input #12. PC 2.x, PC
crete In- Basin/Con- Only 3.x
puts figurable 0: Inactive
Input #12 1: Active
Switch
40518 DSI / Dis- Speed Read Monitors the Speed Droop Enable Switch function; Inac- PC 2.x, PC
crete In- Droop En- Only tive or Active state. 3.x
puts able 0: Inactive
Switch 1: Active
40519 DSI / Dis- Start Type Read Start Type input software state status. Gives software In- PC 2.x, PC
crete In- Switch Only active/Active state 3.x
puts 0: Inactive
1: Active
40520 DSI / Dis- Sync En- Read Sync Enable input software state status. Gives software PC 3.x
crete In- able Only Inactive/Active state
puts Switch 0: Inactive
1: Active
40521 DSI / Dis- Sync En- Read This is the status of the Configurable Input #30. PC 3.x
crete In- able/Confi- Only
puts gurable In- 0: Inactive
put #30
1: Active
Switch
40522 DSI / Dis- Tool Read Tool Wake−up input software state status. Gives software PC 2.x, PC
crete In- Wake−up Only Inactive/Active state 3.x
puts Switch 0: Inactive
1: Active
40523 DSI / Dis- Transfer Read Transfer Inhibit input software state status. Gives software PC 3.x
crete In- Inhibit Only Inactive/Active state
puts Switch 0: Inactive
1: Active
59
Addr. Name Parameter Access Description Control
40524 DSI / Dis- Transfer Read This is the status of the Configurable Input #20. PC 3.x
crete In- Inhibit/ Only
puts Configur- 0: Inactive
able Input
1: Active
#20 Switch
40525 DSI / Dis- Utility CB Read This is the status of the Configurable Input #25. PC 3.x
crete In- Inhibit/ Only
puts Configur- 0: Inactive
able Input 1: Active
#25 Switch
40526 DSI / Dis- Utility CB Read This is the status of the Configurable Input #23. PC 3.x
crete In- Pos B/ Only
puts Configur- 0: Inactive
able Input
1: Active
#23 Switch
40527 DSI / Dis- Utility CB Read This is the status of the Configurable Input #24. PC 3.x
crete In- Tripped/ Only
puts Configur- 0: Inactive
able Input 1: Active
#24 Switch
40528 DSI / Dis- Utility Read This is the status of the Configurable Input #29. PC 3.x
crete In- Single Only
puts Mode 0: Inactive
Verify/Con-
figurable
Input #29 1: Active
Switch
40529 DSI / Dis- Utility CB Read Utility CB Inhibit input software state status. Gives soft- PC 3.x
crete In- Inhibit Only ware Inactive/Active state
puts Switch 0: Inactive
1: Active
40530 DSI / Dis- Utility CB Read Utility CB Pos A input software state status. Gives soft- PC 3.x
crete In- Pos A Only ware Inactive/Active state
puts Switch 0: Inactive
1: Active
40531 DSI / Dis- Utility CB Read Utility CB Pos B input software state status. Gives software PC 3.x
crete In- Pos B Only Inactive/Active state
puts Switch 0: Inactive
1: Active
40532 DSI / Dis- Utility CB Read Utility CB Tripped input software state status. Gives soft- PC 3.x
crete In- Tripped Only ware Inactive/Active state
puts Switch 0: Inactive
1: Active
40533 DSI / Dis- Utility Read Utility Single Mode Verify input software state status. PC 3.x
crete In- Single Only Gives software Inactive/Active state
puts Mode 0: Inactive
Verify
Switch 1: Active
60
Addr. Name Parameter Access Description Control
40534 DSI / Dis- Voltage Read Voltage Droop Enable Switch function output status. Gives PC 2.x, PC
crete In- Droop En- Only software Inactive/Active state. 3.x
puts able 0: Inactive
Switch 1: Active
40535 DSO / Dis- Configur- Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- able Out- Only 0: Inactive 3.x
puts put #1 Sta-
tus 1: Active
40536 DSO / Dis- Configur- Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- able Out- Only 0: Inactive 3.x
puts put #2 Sta-
tus 1: Active
40537 DSO / Dis- Configur- Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- able Out- Only 0: Inactive
puts put #20
Status 1: Active
40538 DSO / Dis- Configur- Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- able Out- Only 0: Inactive
puts put #21
Status 1: Active
40539 DSO / Dis- Configur- Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- able Out- Only 0: Inactive
puts put #22
Status 1: Active
40540 DSO / Dis- Configur- Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- able Out- Only 0: Inactive 3.x
puts put #3 Sta-
tus 1: Active
40541 DSO / Dis- Configur- Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- able Out- Only 0: Inactive 3.x
puts put #4 Sta-
tus 1: Active
40542 DSO / Dis- Delayed Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- Off / Confi- Only 0: Inactive 3.x
puts gurable
Output #10 1: Active
40543 DSO / Dis- Fuel Shut- Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- off Status Only 0: Inactive 3.x
puts 1: Active
40545 DSO / Dis- Genset CB Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- Open Sta- Only 0: Inactive
puts tus 1: Active
40546 DSO / Dis- Hold Pow- Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- er On Driv- Only 0: Inactive 3.x
puts er Status 1: Active
40547 DSO / Dis- Keyswitch Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- Status Only 0: Inactive 3.x
puts 1: Active
61
Addr. Name Parameter Access Description Control
40548 DSO / Dis- KW/KVAR Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- Load Only
puts Share 0: Inactive
Relay Sta-
1: Active
tus
40549 DSO / Dis- Load Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- Dump / Only 3.x
puts Configur- 0: Inactive
able Out-
put #11 1: Active
Status
40550 DSO / Dis- Local Sta- Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- tus / Confi- Only 3.x
puts gurable 0: Inactive
Output #7
1: Active
Status
40551 DSO / Dis- Master Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- First Start Only 0: Inactive
puts Output
Status 1: Active
40552 DSO / Dis- Oil Priming Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- Pump / Only 3.x
puts Configur- 0: Inactive
able Out-
put #6 Sta- 1: Active
tus
40553 DSO / Dis- Ready To Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- Load /Con- Only 3.x
puts figurable 0: Inactive
Output #5
1: Active
Status
40554 DSO / Dis- Run Relay Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- #1 Status Only 0: Inactive 3.x
puts 1: Active
40555 DSO / Dis- Run Relay Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- #2 Status Only 0: Inactive 3.x
puts 1: Active
40556 DSO / Dis- Speed/ Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- Voltage Only 0: Inactive
puts Bias Relay
Status 1: Active
40557 DSO / Dis- Starter Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- Status Only 0: Inactive 3.x
puts 1: Active
40558 DSO / Dis- Tool Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- Wake−up Only 0: Inactive 3.x
puts Driver Sta-
tus 1: Active
40559 DSO / Dis- Utility CB Read Indicates if the output_s status is Inactive or Active PC 2.x, PC
crete Out- Close Sta- Only 0: Inactive 3.x
puts tus 1: Active
62
Addr. Name Parameter Access Description Control
40560 DSO / Dis- Utility CB Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- Open Sta- Only 0: Inactive
puts tus 1: Active
40561 EH / Event Common Read The status of the Common Alarm Fault PC 2.x, PC
Handler Alarm Only 0: Inactive 3.x
Fault Sta-
tus 1: Active
40562 EH / Event Common Read The status of the common shutdown command PC 2.x, PC
Handler Shutdown Only 0: Inactive 3.x
Command 1: Active
40563 EH / Event Common Read The status of the Common Shutdown Event PC 2.x, PC
Handler Shutdown Only 0: Inactive 3.x
Event Sta-
tus 1: Active
40564 EH / Event Common Read The status of the common shutdown w/Cooldown command PC 3.x
Handler Shutdown Only
w/Cool- 0: Inactive
down
1: Active
Command
40565 EH / Event Common Read The status of the Common Warning Event PC 2.x, PC
Handler Warning Only 0: Inactive 3.x
Event Sta-
tus 1: Active
40566 EH / Event Delayed Read Monitor point for the Delayed shutdown flag. PC 2.x, PC
Handler Shutdown Only 0: Inactive 3.x
Flag 1: Active
40567 EH / Event Delayed Read Multiplier: Unit: sec- Monitor point for the Delayed PC 2.x, PC
Handler Shutdown Only 0.1 onds shutdown timer. 3.x
Timer Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 3
16
Sign: U
40568 EH / Event Derate Re- Read Multiplier: 1 Unit: % The requested % derate PC 2.x, PC
Handler quest Only from the derate request logic 3.x
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 100
Sign: U
40569 EH / Event Fault Read The status of the Fault Detection Reset logic PC 2.x, PC
Handler Detection Only 0: Inactive 3.x
Reset 1: Active
40570 EH / Event Fault Reset Read One shot due to fault reset switch being active. PC 2.x, PC
Handler Command Only 0: Inactive 3.x
1: Active
40571 EH / Event Remote Read Becomes active when a remote fault reset signal has been PC 2.x, PC
Handler Shutdown Only initiated. 3.x
Fault Re- 0: Inactive
set Signal 1: Active
40572 EH / Event Shutdown Read The status of the Shutdown Fault reset logic. PC 2.x, PC
Handler Fault Reset Only 0: Inactive 3.x
1: Active
63
Addr. Name Parameter Access Description Control
40573 EH / Event Battle Read Monitor point indicating the enabled/disabled status of the PC 2.x, PC
Handler Short Flag Only battle short function 3.x
0: Not Auto
1: Auto
40574 GC / Start/ Auto Com- Read The output of the Auto Command OR logic PC 2.x, PC
Stop Con- mand Only 0: Not Auto 3.x
trol 1: Auto
40575 GC / Start/ Auto Com- Read Multiplier: 1 Unit: Bitmask to show the inputs PC 2.x, PC
Stop Con- mand In- Only to the Command output 3.x
trol puts which are currently on
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
40576 GC / Auto- AVR Regu- Read The operational mode of the AVR as a voltage or a current PC 2.x, PC
matic Volt- lation Only regulator 3.x
age Regu- Mode 0: Voltage
lator 1: Current
40577 GC / Base Fre- Read Multiplier: Unit: Hz Provides a point to monitor PC 2.x, PC
Speed quency Only 0.001 the base frequency 3.x
Reference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40578 GC / Base Fre- Read Multiplier: Unit: Hz Provides a point to monitor PC 2.x, PC
Speed quency Only 0.001 the base frequency 3.x
Reference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
40579 GC / Battery Read Multiplier: Unit: sec- Time spent while the charger PC 2.x, PC
Charging Charging Only 0.1 onds is sensed as failed 3.x
Alternator Fault Inte- Offset: 0 Lower Limit: 0
Protection grator Size (bits): Upper Limit: 300
16
Sign: U
40581 GC / Con- Controlled Read Indicates status of the controlled shutdown logic PC 3.x
trolled Shutdown Only 0: Inactive
Shutdown Status 1: Pending
Control 2: Shutdown
40582 GC / Pre- Crank Al- Read Monitor Point indicates if Cranking is Allowed by the Prelube PC 2.x, PC
lube lowed Only State Machine 3.x
0: False
1: True
40583 GC / Dead Bat- Read Multiplier: 1 Unit: Tracks the number of crank PC 2.x, PC
Cranking tery Pre- Only attempts in order to limit the 3.x
Control vention attempts when the battery is
Counter so low that the control resets
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 250
Sign: U
64
Addr. Name Parameter Access Description Control
40584 GC / Out- Delayed Read The status of the delayed run command off logic. PC 2.x, PC
puts Off Com- Only 0: Inactive 3.x
mand 1: Active
40585 GC / Start/ Emergen- Read The output of the Emergency Remote Start logic PC 2.x, PC
Stop Con- cy Remote Only 0: Stop 3.x
trol Start 1: Start
40586 GC / Auto- Excitation Read Shows the enable status of the excitation enabled = regula- PC 2.x, PC
matic Volt- State Only tor on. 3.x
age Regu- 0: Disabled
lator 1: Enabled
40587 GC / Start/ Exercise Read The output of the Exercise Command OR logic PC 2.x, PC
Stop Con- Command Only 0: Inactive 3.x
trol 1: Active
40588 GC / Start/ Exercise Read Multiplier: 1 Unit: Bitmask to show the inputs PC 2.x, PC
Stop Con- Command Only to the Command output 3.x
trol Inputs which are currently on
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 250
Sign: U
40589 GC / Start/ Exercise Read Multiplier: Unit: hours Time remaining until exer- PC 2.x, PC
Stop Con- Time Re- Only 0.1 cise stop sequence begins 3.x
trol maining Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 25
16
Sign: U
40590 GC / Start/ Extended Read The output of the Extended Parallel Switch Command OR PC 3.x
Stop Con- Parallel Only logic
trol Switch 0: Stop
Command 1: Start
40591 GC / Start/ Extended Read Multiplier: 1 Unit: Bitmask to show the inputs PC 3.x
Stop Con- Parallel Only to the Command output
trol Switch which are currently on
Command Offset: 0 Lower Limit:
Inputs Size (bits): 8 Upper Limit:
Sign: U
40592 EH / Event Battle Read Indicates status of battle short inputs PC 2.x, PC
Handler Short Com- Only 0: Inactive 3.x
mand 1: Active
40593 EH / Event Shutdown Read Indicates whether or not the genset will ignore non−critical PC 2.x, PC
Handler Fault Over- Only shutdown faults 3.x
ride 0: Inactive
1: Active
40595 GC / Final Fre- Read Multiplier: Unit: Hz The frequency scaled ver- PC 2.x, PC
Speed quency Only 0.001 sion of the final speed refer- 3.x
Reference Reference ence
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 100
32
Sign: U
65
Addr. Name Parameter Access Description Control
40596 GC / Final Fre- Read Multiplier: Unit: Hz The frequency scaled ver- PC 2.x, PC
Speed quency Only 0.001 sion of the final speed refer- 3.x
Reference Reference ence
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 100
32
Sign: U
40598 GC / Out- Fuel Shut- Read The result of the FSO driver output command logic PC 2.x, PC
puts off Com- Only 0: Inactive 3.x
mand 1: Active
40599 GC / Start/ Genset Read Genset run / stop states PC 2.x, PC
Stop Con- Run Com- Only 0: Emergency Stop 3.x
trol mand 1: Stop
2: Load Demand Stop
3: Run
40600 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40601 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40602 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40603 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
66
Addr. Name Parameter Access Description Control
40604 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40605 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40606 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40607 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40608 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40609 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
67
Addr. Name Parameter Access Description Control
40610 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40611 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40612 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40613 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40614 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40615 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #1 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
68
Addr. Name Parameter Access Description Control
40620 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40621 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40622 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40623 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40624 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40625 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
69
Addr. Name Parameter Access Description Control
40626 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40627 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40628 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40629 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40630 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40631 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
70
Addr. Name Parameter Access Description Control
40632 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40633 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40634 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40635 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #2 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40640 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40641 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
71
Addr. Name Parameter Access Description Control
40642 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40643 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40644 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40645 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40646 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40647 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
72
Addr. Name Parameter Access Description Control
40648 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40649 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40650 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40651 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40652 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40653 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
73
Addr. Name Parameter Access Description Control
40654 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40655 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #13 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40660 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40661 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40662 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40663 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
74
Addr. Name Parameter Access Description Control
40664 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40665 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40666 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40667 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40668 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40669 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
75
Addr. Name Parameter Access Description Control
40670 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40671 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40672 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40673 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40674 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
40675 DSI / Dis- Configur- Read/ Multiplier: 1 Unit: Trim to define the 16 charac- PC 2.x, PC
crete In- able Input Write ter string for use by the Op- 3.x
puts #14 Fault erator panel when this fault
Text becomes active.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
136
Sign: C
76
Addr. Name Parameter Access Description Control
40800 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40801 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40802 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40803 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40804 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40805 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
77
Addr. Name Parameter Access Description Control
40806 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40807 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40808 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40809 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40810 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40811 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
78
Addr. Name Parameter Access Description Control
40812 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40813 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40814 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40815 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40816 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40817 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
79
Addr. Name Parameter Access Description Control
40818 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40819 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40820 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40821 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40822 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40823 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
80
Addr. Name Parameter Access Description Control
40824 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40825 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40826 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40827 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40828 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40829 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
81
Addr. Name Parameter Access Description Control
40830 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40831 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40832 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40833 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40834 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40835 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
82
Addr. Name Parameter Access Description Control
40836 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40837 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40838 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40839 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40840 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40841 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
83
Addr. Name Parameter Access Description Control
40842 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40843 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40844 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40845 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40846 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40847 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40848 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
84
Addr. Name Parameter Access Description Control
40849 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40850 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40851 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40852 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40853 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40854 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40855 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
85
Addr. Name Parameter Access Description Control
40856 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40857 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40858 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40859 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40860 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40861 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40862 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
86
Addr. Name Parameter Access Description Control
40863 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40864 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40865 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40866 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40867 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40868 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40869 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
87
Addr. Name Parameter Access Description Control
40870 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40871 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40872 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40873 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40874 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40875 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40876 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
88
Addr. Name Parameter Access Description Control
40877 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40878 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40879 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40880 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40881 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40882 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40883 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
89
Addr. Name Parameter Access Description Control
40884 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40885 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40886 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40887 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40888 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40889 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40890 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
90
Addr. Name Parameter Access Description Control
40891 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40892 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40893 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40894 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40895 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40896 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40897 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
91
Addr. Name Parameter Access Description Control
40898 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40899 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40900 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40901 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40902 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40903 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40904 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
92
Addr. Name Parameter Access Description Control
40905 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40906 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40907 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40908 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40909 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40910 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40911 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
93
Addr. Name Parameter Access Description Control
40912 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40913 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40914 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40915 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40916 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40917 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40918 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
94
Addr. Name Parameter Access Description Control
40919 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
0 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40920 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40921 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40922 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40923 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40924 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40925 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
95
Addr. Name Parameter Access Description Control
40926 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40927 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40928 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40929 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40930 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40931 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40932 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
96
Addr. Name Parameter Access Description Control
40933 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40934 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40935 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40936 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40937 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40938 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40939 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 9 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
97
Addr. Name Parameter Access Description Control
40940 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40941 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40942 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40943 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40944 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40945 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40946 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
98
Addr. Name Parameter Access Description Control
40947 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40948 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40949 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40950 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40951 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40952 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40953 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
99
Addr. Name Parameter Access Description Control
40954 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40955 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40956 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40957 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40958 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40959 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 10 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40960 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
100
Addr. Name Parameter Access Description Control
40961 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40962 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40963 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40964 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40965 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40966 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40967 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
101
Addr. Name Parameter Access Description Control
40968 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40969 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40970 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40971 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40972 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40973 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40974 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
102
Addr. Name Parameter Access Description Control
40975 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40976 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40977 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40978 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40979 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 11 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40980 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40981 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
103
Addr. Name Parameter Access Description Control
40982 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40983 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40984 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40985 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40986 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40987 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40988 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
104
Addr. Name Parameter Access Description Control
40989 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40990 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40991 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40992 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40993 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40994 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40995 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
105
Addr. Name Parameter Access Description Control
40996 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40997 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40998 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
40999 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Fault 12 Write string to enter the configur- 3.x
1 Exp. Text able fault text for this fault.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43000 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L1 current percentage 3.x
Current L1 Current output.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
43001 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L2 current percentage 3.x
Current L2 Current output.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
43002 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L1 KVA percentage out- 3.x
Current L1 kVA put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
106
Addr. Name Parameter Access Description Control
43003 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L3 current percentage 3.x
Current L3 Current output.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
43004 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L2 KVA percentage out- 3.x
Current L2 kVA put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
43005 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L3 KVA percentage out- 3.x
Current L3 kVA put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
43006 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L1 KW percentage out- 3.x
Current L1 kW put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: S
43007 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L2 KW percentage out- 3.x
Current L2 kW put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: S
43008 ACM / Genset % Read Multiplier: Unit: % Monitors the genset applica- PC 2.x, PC
Genset Application Only 0.1 tion L3 KW percentage out- 3.x
Current L3 kW put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: S
43009 ACM / Genset % Read Multiplier: Unit: % Monitors the total genset ap- PC 2.x, PC
Genset Application Only 0.1 plication KVA percentage 3.x
Current Total kVA output.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
107
Addr. Name Parameter Access Description Control
43010 ACM / Genset % Read Multiplier: Unit: % Monitors the total genset ap- PC 2.x, PC
Genset Application Only 0.1 plication KW percentage out- 3.x
Current Total kW put.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: S
43011 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L1 KVA percentage output. 3.x
Current L1 kVA Offset: 0 Lower Limit:
and Power Size (bits): Upper Limit:
−% 16
Sign: U
43012 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L3 KVA percentage output. 3.x
Current L3 kVA Offset: 0 Lower Limit:
and Power Size (bits): Upper Limit:
−% 16
Sign: U
43013 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L2 KVA percentage output. 3.x
Current L2 kVA Offset: 0 Lower Limit:
and Power Size (bits): Upper Limit:
−% 16
Sign: U
43014 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L1 KW percentage output. 3.x
Current L1 kW Offset: 0 Lower Limit:
and Power Size (bits): Upper Limit:
−% 16
Sign: S
43015 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L2 KW percentage output. 3.x
Current L2 kW Offset: 0 Lower Limit:
and Power Size (bits): Upper Limit:
−% 16
Sign: S
43016 ACM / Genset % Read Multiplier: Unit: % Monitors the genset standby PC 2.x, PC
Genset Standby Only 0.1 L3 KW percentage output. 3.x
Current L3 kW Offset: 0 Lower Limit:
and Power Size (bits): Upper Limit:
−% 16
Sign: S
43017 ACM / Genset % Read Multiplier: Unit: % Monitors the total genset PC 2.x, PC
Genset Standby Only 0.1 standby KVA percentage 3.x
Current Total kVA output.
and Power Offset: 0 Lower Limit:
−% Size (bits): Upper Limit:
16
Sign: U
108
Addr. Name Parameter Access Description Control
43018 ACM / Genset Read Multiplier: Unit: kVA The genset KVA rating. PC 2.x, PC
Genset Application Only 0.1 3.x
Ratings kVA rating Offset: 0 Lower Limit:
Scalars Size (bits): Upper Limit:
16
Sign: U
43019 ACM / Genset Read Multiplier: Unit: kW The genset KW rating. PC 2.x, PC
Genset Application Only 0.1 3.x
Ratings kW rating Offset: 0 Lower Limit:
Scalars Size (bits): Upper Limit:
16
Sign: U
43020 ACM / Genset Read Multiplier: 1 Unit: Amps The value of the genset ap- PC 2.x, PC
Genset Application Only plication nominal current. 3.x
Ratings Nominal Displayed as ”Genset Ap-
Scalars Current plication Rated Current” in
HMI
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43021 ACM / Genset Av- Read Multiplier: Unit: % Genset average voltage per- PC 2.x, PC
Voltage erage Volt- Only 0.01 centage. 3.x
age% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43030 ACM / Genset L1 Read Multiplier: Unit: PF Genset L1 power factor PC 2.x, PC
Power Power Only 0.01 3.x
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43031 ACM / Genset Read Multiplier: Unit: De- Genset L1L2 voltage phase PC 2.x, PC
Phase L1L2 Only 0.01 grees angle 3.x
Phase Dif- Offset: 0 Lower Limit:
ference Size (bits): Upper Limit:
16
Sign: U
43032 ACM / Genset Read Multiplier: Unit: % Genset L1L2 voltage% PC 2.x, PC
Voltage L1L2 Volt- Only 0.01 3.x
age% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43033 ACM / Genset Read Multiplier: Unit: % Genset L1N voltage% PC 2.x, PC
Voltage L1N Volt- Only 0.01 3.x
age% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
109
Addr. Name Parameter Access Description Control
43044 ACM / Genset L2 Read Multiplier: Unit: PF Genset L2 power factor PC 2.x, PC
Power Power Only 0.01 3.x
Factor Offset: 0 Lower Limit: −1.28
Size (bits): 8 Upper Limit: 1.27
Sign: S
43045 ACM / Genset Read Multiplier: Unit: De- Genset L2L3 voltage phase PC 2.x, PC
Phase L2L3 Only 0.01 grees angle 3.x
Phase Dif- Offset: 0 Lower Limit: 0
ference Size (bits): Upper Limit: 655.3
16
Sign: U
43046 ACM / Genset Read Multiplier: Unit: % Genset L2L3 voltage% PC 2.x, PC
Voltage L2L3 Volt- Only 0.01 3.x
age% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43047 ACM / Genset Read Multiplier: Unit: % Genset L2N voltage% PC 2.x, PC
Voltage L2N Volt- Only 0.01 3.x
age% Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 655.3
16
Sign: U
43058 ACM / Genset L3 Read Multiplier: Unit: PF Genset L3 power factor PC 2.x, PC
Power Power Only 0.01 3.x
Factor Offset: 0 Lower Limit: −1.28
Size (bits): 8 Upper Limit: 1.22
Sign: S
43059 ACM / Genset Read Multiplier: Unit: De- Genset L3L1 voltage phase PC 2.x, PC
Phase L3L1 Only 0.01 grees angle 3.x
Phase Dif- Offset: 0 Lower Limit: 0
ference Size (bits): Upper Limit: 655.3
16
Sign: U
43060 ACM / Genset Read Multiplier: Unit: % Genset L3L1 voltage% PC 2.x, PC
Voltage L3L1 Volt- Only 0.01 3.x
age% Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 655.3
16
Sign: U
43061 ACM / Genset Read Multiplier: Unit: % Genset L3N voltage% PC 2.x, PC
Voltage L3N Volt- Only 0.01 3.x
age% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43062 ACM / Genset Read Multiplier: Unit: kVA KVA rating for the genset in PC 2.x, PC
Genset Standby Only 0.1 Standby configuration. 3.x
Ratings kVA rating Offset: 0 Lower Limit:
Scalars Size (bits): Upper Limit:
16
Sign: U
110
Addr. Name Parameter Access Description Control
43063 ACM / Genset Read Multiplier: Unit: kW KW rating for the genset in PC 2.x, PC
Genset Standby Only 0.1 Standby configuration. 3.x
Ratings kW rating Offset: 0 Lower Limit:
Scalars Size (bits): Upper Limit:
16
Sign: U
43064 ACM / Genset Read Multiplier: 1 Unit: Amps The value of the genset PC 2.x, PC
Genset Standby Only standby nominal current. 3.x
Ratings Nominal Displayed as ”Genset Stand-
Scalars Current by Rated Current” in HMI
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43065 ACM / En- Genset To- Read Multiplier: 1 Unit: kVAh Genset total kVAh accumula- PC 2.x, PC
ergy tal kVAh Only tion 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
43066 ACM / En- Genset To- Read Multiplier: 1 Unit: kVAh Genset total kVAh accumula- PC 2.x, PC
ergy tal kVAh Only tion 3.x
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
43067 ACM / Genset To- Read Multiplier: Unit: % Total KVAR’s per Standby PC 2.x, PC
Genset tal kVARs Only 0.01 KVA. 3.x
Current per Stand- Offset: 0 Lower Limit:
and Power by kVA Size (bits): Upper Limit:
−% 16
Sign: S
43100 ACM / Genset Read Multiplier: Unit: % Genset Bus average volt- PC 3.x
Voltage Bus Aver- Only 0.01 age%
age Volt- Offset: 0 Lower Limit:
age% Size (bits): Upper Limit:
16
Sign: U
43111 ACM / Genset Read Multiplier: Unit: PF Genset Bus L1 power factor PC 3.x
Power Bus L1 Only 0.01
Power Offset: 0 Lower Limit: −1.28
Factor Size (bits): 8 Upper Limit: 1.22
Sign: S
43112 ACM / Genset Read Multiplier: Unit: De- Genset bus L1L2 voltage PC 3.x
Phase Bus L1L2 Only 0.01 grees phase angle
Phase Dif- Offset: 0 Lower Limit:
ference Size (bits): Upper Limit:
16
Sign: U
111
Addr. Name Parameter Access Description Control
43113 ACM / Genset Read Multiplier: Unit: % Genset Bus L1L2 voltage% PC 3.x
Voltage Bus L1L2 Only 0.01
Voltage% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43114 ACM / Genset Read Multiplier: Unit: % Genset Bus L1N voltage% PC 3.x
Voltage Bus L1N Only 0.01
Voltage% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43125 ACM / Genset Read Multiplier: Unit: PF Genset Bus L2 power factor PC 3.x
Power Bus L2 Only 0.01
Power Offset: 0 Lower Limit:
Factor Size (bits): 8 Upper Limit:
Sign: S
43126 ACM / Genset Read Multiplier: Unit: De- Genset bus L2L3 voltage PC 3.x
Phase Bus L2L3 Only 0.01 grees phase angle
Phase Dif- Offset: 0 Lower Limit:
ference Size (bits): Upper Limit:
16
Sign: U
43127 ACM / Genset Read Multiplier: Unit: % Genset Bus L2L3 voltage% PC 3.x
Voltage Bus L2L3 Only 0.01
Voltage% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43128 ACM / Genset Read Multiplier: Unit: % Genset Bus L2N voltage% PC 3.x
Voltage Bus L2N Only 0.01
Voltage% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43139 ACM / Genset Read Multiplier: Unit: PF Genset Bus L3 power factor PC 3.x
Power Bus L3 Only 0.01
Power Offset: 0 Lower Limit: −1.28
Factor Size (bits): 8 Upper Limit: 1.22
Sign: S
43140 ACM / Genset Read Multiplier: Unit: De- Genset bus L3L1 voltage PC 3.x
Phase Bus L3L1 Only 0.01 grees phase angle
Phase Dif- Offset: 0 Lower Limit:
ference Size (bits): Upper Limit:
16
Sign: U
43141 ACM / Genset Read Multiplier: Unit: % Genset Bus L3L1 voltage% PC 3.x
Voltage Bus L3L1 Only 0.01
Voltage% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
112
Addr. Name Parameter Access Description Control
43142 ACM / Genset Read Multiplier: Unit: % Genset Bus L3N voltage% PC 3.x
Voltage Bus L3N Only 0.01
Voltage% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43143 ACM / En- Genset Read Multiplier: 1 Unit: kVAh Genset bus total kVAh accu- PC 3.x
ergy Bus Total Only mulation
kVAh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
43144 ACM / En- Genset Read Multiplier: 1 Unit: kVAh Genset bus total kVAh accu- PC 3.x
ergy Bus Total Only mulation
kVAh Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
43145 ACM / Sync Read Multiplier: Unit: deg Other meter to genset meter PC 3.x
Phase Phase Dif- Only 0.01 L1 voltage phase angle
ference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43146 ACM / Ap- Paralleling Read/ Determines what the function of the Other Meter is. PC 3.x
plication Application Write 0: None
Configura- 1: Utility
tion 2: Genset Bus
43147 ACM / System Read Multiplier: 1 Unit: kVA Sum of genset bus and utility PC 3.x
Power Total kVA Only bus kVA
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43148 ACM / System Read Multiplier: 1 Unit: kVAR Sum of genset bus and utility PC 3.x
Power Total kVAR Only bus kVAR
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43149 ACM / System Read Multiplier: 1 Unit: kW Sum of genset bus and utility PC 3.x
Power Total kW Only bus kW
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43150 ACM / System Read Multiplier: Unit: PF System total power factor PC 3.x
Power Total Pow- Only 0.01 (totalized value of utility bus
er Factor plus genset bus)
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
113
Addr. Name Parameter Access Description Control
43151 ACM / Utility Av- Read Multiplier: Unit: % Utility average voltage% PC 3.x
Voltage erage Volt- Only 0.01
age% Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43162 ACM / Utility L1 Read Multiplier: Unit: PF Utility L1 power factor PC 3.x
Power Power Only 0.01
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43163 ACM / Utility L1L2 Read Multiplier: Unit: De- Utility L1L2 voltage phase PC 3.x
Phase Phase Dif- Only 0.01 grees angle
ference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43164 ACM / Utility L1L2 Read Multiplier: Unit: % Utility L1L2 voltage% PC 3.x
Voltage Voltage% Only 0.01
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43165 ACM / Utility L1N Read Multiplier: Unit: % Utility L1N voltage% PC 3.x
Voltage Voltage% Only 0.01
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43176 ACM / Utility L2 Read Multiplier: Unit: PF Utility L2 power factor PC 3.x
Power Power Only 0.01
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43177 ACM / Utility L2L3 Read Multiplier: Unit: De- Utility L2L3 voltage phase PC 3.x
Phase Phase Dif- Only 0.01 grees angle
ference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43178 ACM / Utility L2L3 Read Multiplier: Unit: % Utility L2L3 voltage% PC 3.x
Voltage Voltage% Only 0.01
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43179 ACM / Utility L2N Read Multiplier: Unit: % Utility L2N voltage% PC 3.x
Voltage Voltage% Only 0.01
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
114
Addr. Name Parameter Access Description Control
43190 ACM / Utility L3 Read Multiplier: Unit: PF Utility L3 power factor PC 3.x
Power Power Only 0.01
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43191 ACM / Utility L3L1 Read Multiplier: Unit: De- Utility L3L1 voltage phase PC 3.x
Phase Phase Dif- Only 0.01 grees angle
ference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43192 ACM / Utility L3L1 Read Multiplier: Unit: % Utility L3L1 voltage% PC 3.x
Voltage Voltage% Only 0.01
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43193 ACM / Utility L3N Read Multiplier: Unit: % Utility L3N voltage% PC 3.x
Voltage Voltage% Only 0.01
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43194 ACM / En- Utility Total Read Multiplier: 1 Unit: kVAh Utility total kVAh accumula- PC 3.x
ergy kVAh Only tion
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
43195 ACM / En- Utility Total Read Multiplier: 1 Unit: kVAh Utility total kVAh accumula- PC 3.x
ergy kVAh Only tion
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
43200 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43201 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
115
Addr. Name Parameter Access Description Control
43202 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43203 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43204 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43205 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43206 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43207 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43208 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43209 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
116
Addr. Name Parameter Access Description Control
43210 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43211 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43212 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43213 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43214 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43215 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43216 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43217 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
117
Addr. Name Parameter Access Description Control
43218 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43219 DR / Data Genset Read/ Multiplier: 1 Unit: Number identifying the mod- PC 2.x, PC
Recording Model Write el of this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43220 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43221 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43222 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43223 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43224 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43225 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
118
Addr. Name Parameter Access Description Control
43226 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43227 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43228 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43229 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43230 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43231 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43232 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43233 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
119
Addr. Name Parameter Access Description Control
43234 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43235 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43236 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43237 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43238 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43239 DR / Data Genset Read/ Multiplier: 1 Unit: Serial number of identifying PC 2.x, PC
Recording Serial Write this genset. 3.x
Number Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43240 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43241 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
120
Addr. Name Parameter Access Description Control
43242 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43243 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43244 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43245 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43246 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43247 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43248 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
121
Addr. Name Parameter Access Description Control
43249 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43250 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43251 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43252 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43253 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43254 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43255 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
122
Addr. Name Parameter Access Description Control
43256 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43257 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43258 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43259 DR / Data Alternator Read/ Multiplier: 1 Unit: Number identifying this gen- PC 2.x, PC
Recording Model Write sets alternator model num- 3.x
Number ber.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43260 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43261 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43262 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
123
Addr. Name Parameter Access Description Control
43263 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43264 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43265 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43266 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43267 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43268 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43269 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
124
Addr. Name Parameter Access Description Control
43270 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43271 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43272 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43273 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43274 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43275 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43276 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
125
Addr. Name Parameter Access Description Control
43277 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43278 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43279 DR / Data Alternator Read/ Multiplier: 1 Unit: Unique number identifying PC 2.x, PC
Recording Serial Write this gensets alternator serial 3.x
Number number.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43280 DSI / Dis- Coolant Read Coolant Level input software state status. Gives software In- PC 2.x, PC
crete In- Level Only active/Active state 3.x
puts Switch 0: Inactive
1: Active
43281 DSI / Dis- Coolant Read This is the status of the Configurable Input #5. PC 2.x, PC
crete In- Level/Con- Only 3.x
puts figurable 0: Inactive
Input #5
1: Active
Switch
43283 DSI / Dis- Fault Reset Read Fault Reset input software state status. Gives software Inac- PC 2.x, PC
crete In- Switch Only tive/Active state 3.x
puts 0: Inactive
1: Active
43284 DSI / Dis- Fault Re- Read This is the status of the Configurable Input #10. PC 2.x, PC
crete In- set/Confi- Only 3.x
puts gurable In- 0: Inactive
put #10 1: Active
Switch
43285 DSI / Dis- Genset CB Read This is the status of the Configurable Input #28. PC 3.x
crete In- Inhibit/ Only
puts Configur- 0: Inactive
able Input 1: Active
#28 Switch
43286 DSI / Dis- Genset CB Read This is the status of the Configurable Input #26. PC 3.x
crete In- Pos B/ Only
puts Configur- 0: Inactive
able Input
1: Active
#26 Switch
126
Addr. Name Parameter Access Description Control
43287 DSI / Dis- Genset CB Read This is the status of the Configurable Input #27. PC 3.x
crete In- Tripped/ Only
puts Configur- 0: Inactive
able Input
1: Active
#27 Switch
43288 DSI / Dis- Genset CB Read Genset CB Inhibit input software state status. Gives soft- PC 3.x
crete In- Inhibit Only ware Inactive/Active state
puts Switch 0: Inactive
1: Active
43289 DSI / Dis- Genset CB Read Genset CB Pos A input software state status. Gives software PC 3.x
crete In- Pos A Only Inactive/Active state
puts Switch 0: Inactive
1: Active
43290 DSI / Dis- Genset CB Read Genset CB Pos B input software state status. Gives software PC 3.x
crete In- Pos B Only Inactive/Active state
puts Switch 0: Inactive
1: Active
43291 DSI / Dis- Genset CB Read Genset CB Tripped input software state status. Gives soft- PC 3.x
crete In- Tripped Only ware Inactive/Active state
puts Switch 0: Inactive
1: Active
43292 DSI / Dis- Ground Read Ground Fault Switch function output status. Gives software PC 2.x, PC
crete In- Fault Only Inactive/Active state 3.x
puts Switch 0: Inactive
1: Active
43293 DSI / Dis- High Alt Read High Alt Temp Switch function output status. Gives software PC 2.x, PC
crete In- Temp Only Inactive/Active state 3.x
puts Switch 0: Inactive
1: Active
43295 DSI / Dis- Load De- Read This is the status of the Configurable Input #31. PC 3.x
crete In- mand Stop/ Only
puts Configur- 0: Inactive
able Input 1: Active
#31 Switch
43296 DSI / Dis- Local E− Read Monitors the E−Stop switch. PC 2.x, PC
crete In- stop Switch Only 0: Inactive 3.x
puts 1: Active
43297 DSI / Dis- Low Cool- Read Low Coolant #2 Switch function output status. Gives soft- PC 2.x, PC
crete In- ant #2 Only ware Inactive/Active state 3.x
puts Switch 0: Inactive
1: Active
43298 DSI / Dis- Low Fuel In Read Low Fuel In Day Tank Switch function output status. Gives PC 2.x, PC
crete In- Day Tank Only software Inactive/Active state 3.x
puts Switch 0: Inactive
1: Active
43299 DSI / Dis- Low Fuel Read Low Fuel In Day Tank Switch function output status. Gives PC 2.x, PC
crete In- In Day Only software Inactive/Active state 3.x
puts Tank 0: Inactive
Switch 1: Active
127
Addr. Name Parameter Access Description Control
43300 ACM / Ap- Genset Read/ Delta or Wye for Utility connection PC 3.x
plication Bus Delta/ Write 0: Delta
Configura- Wye Con-
tion nection 1: Wye
43301 ACM / Genset Read/ Multiplier: 1 Unit: Vac Genset Bus nominal voltage PC 3.x
Voltage Bus Nomi- Write Offset: 0 Lower Limit: 110
nal Voltage Size (bits): Upper Limit: 45000
16
Sign: U
43302 ACM / Ap- Genset Read/ Delta or Wye for Genset connection PC 2.x, PC
plication Delta/Wye Write 0: Delta 3.x
Configura- Connec-
tion tion 1: Wye
43303 ACM / Genset Read/ Multiplier: 1 Unit: Vac Genset nominal line−line PC 2.x, PC
Voltage Nominal Write voltage 3.x
Voltage Offset: 0 Lower Limit: 110
Size (bits): Upper Limit: 45000
16
Sign: U
43304 ACM / Ap- Single/3 Read/ Setup mode interlocked. Genset’s single phase/3 phase PC 2.x, PC
plication Phase Write metering setup configuration. 3.x
Configura- Connec- 0: Single Phase
tion tion 1: Three Phase
43306 ACM / Ap- Utility Del- Read/ Delta or Wye for Utility connection PC 3.x
plication ta/Wye Write 0: Delta
Configura- Connec-
tion tion 1: Wye
43307 ACM / Utility Read/ Multiplier: 1 Unit: Vac Utility nominal voltage PC 3.x
Voltage Nominal Write Offset: 0 Lower Limit: 110
Voltage Size (bits): Upper Limit: 45000
16
Sign: U
43309 AP / Fre- Overfre- Read/ Enables overfrequency diagnostic witness test. PC 2.x, PC
quency quency En- Write 0: Disabled 3.x
Protection able 1: Enabled
43310 AP / Power Overload Read/ Multiplier: 1 Unit: sec- The time delay until an over- PC 2.x, PC
Flow Moni- Warning Write onds load condition is reported as 3.x
tor Set Time a fault
Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 120
Sign: U
43311 AP / Power Overload Read/ Multiplier: Unit: % Sets the Overload Warning PC 2.x, PC
Flow Moni- Warning Write 0.01 fault trip threshold as per- 3.x
tor Threshold centage of genset applica-
tion kW rating.
Offset: 0 Lower Limit: 80
Size (bits): Upper Limit: 140
16
Sign: U
128
Addr. Name Parameter Access Description Control
43338 CAN / CAN Fail- Read/ Multiplier: 1 Unit: Sets the maximum number PC 2.x, PC
CAN ure Retries Write of CAN communication re- 3.x
Datalink tries
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 10
Sign: U
43340 CM / Con- Max Setup Read/ Multiplier: 1 Unit: Sec- Max time allowed in Setup PC 2.x, PC
troller Mode Time Write onds Mode. 3.x
Modes Offset: 0 Lower Limit: 30
Size (bits): Upper Limit: 3600
16
Sign: U
43341 CM / Con- Power Read/ Trim to enable sleep mode PC 2.x, PC
troller Down Write 0: Disable 3.x
Modes Mode En-
able 1: Enable
43342 CM / Con- Power Read/ Multiplier: 1 Unit: sec- Timer setting for the Power PC 2.x, PC
troller Down Write onds Down delay feature 3.x
Modes Mode Time Offset: 0 Lower Limit: 0
Delay Size (bits): Upper Limit: 600
16
Sign: U
43343 CM / Con- Setup Read/ Volatile to allow entry into Setup Mode PC 2.x, PC
troller Mode En- Write 0: Disable 3.x
Modes able 1: Enable
43344 DR / Real Clock Date Read/ Multiplier: 1 Unit: Use to set or read the cur- PC 2.x, PC
Time Clock Write rent date. 3.x
Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 31
Sign: U
43345 DR / Real Clock Hour Read/ Multiplier: 1 Unit: Use to set or read the cur- PC 2.x, PC
Time Clock Write rent hour. 3.x
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 23
Sign: U
43346 DR / Real Clock Min- Read/ Multiplier: 1 Unit: Use to set or read the cur- PC 2.x, PC
Time Clock ute Write rent minute. 3.x
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 59
Sign: U
43347 DR / Real Clock Read/ Use to set the real time clock and save settings.
Time Clock Mode Write 0: Normal PC 2.x, PC
1: Set Clock 3.x
2: Save Clock
43348 DR / Real Clock Read/ Multiplier: 1 Unit: Use to set or read the cur- PC 2.x, PC
Time Clock Month Write rent month. 3.x
Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 12
Sign: U
129
Addr. Name Parameter Access Description Control
43349 DR / Real Clock Sec- Read/ Multiplier: 1 Unit: Use to set or read the cur- PC 2.x, PC
Time Clock ond Write rent second. 3.x
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 59
Sign: U
43350 DR / Real Clock Year Read/ Multiplier: 1 Unit: Use to set or read the cur- PC 2.x, PC
Time Clock Write rent year. 3.x
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 99
Sign: U
43351 DR / Real Daylight Read/ Multiplier: 1 Unit: Use to set the hour of the PC 2.x, PC
Time Clock Savings Write day when daylight savings 3.x
End Hour time ends.
Offset: 0 Lower Limit: 2
Size (bits): 8 Upper Limit: 19
Sign: U
43352 DR / Real Daylight Read/ Multiplier: 1 Unit: Use to set the month when PC 2.x, PC
Time Clock Savings Write daylight savings time ends. 3.x
End Month Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 12
Sign: U
43353 DR / Real Daylight Read/ Use to set the week of the month when daylight savings time PC 2.x, PC
Time Clock Savings Write ends. 3.x
End Week 0: First Occurrence
Occur- 1: Second Occurrence
rence in 2: Third Occurrence
Month 3: Fourth Occurrence
4: Last Occurrence
43354 DR / Real Daylight Read/ Use to set the day of the week when daylight savings time PC 2.x, PC
Time Clock Savings Write starts. 3.x
Start Day 0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43355 DR / Real Daylight Read/ Multiplier: 1 Unit: Use to set the hour of the PC 2.x, PC
Time Clock Savings Write day when daylight savings 3.x
Start Hour time starts.
Offset: 0 Lower Limit: 2
Size (bits): 8 Upper Limit: 19
Sign: U
43356 DR / Real Daylight Read/ Multiplier: 1 Unit: Use to set the month when PC 2.x, PC
Time Clock Savings Write daylight savings time starts. 3.x
Start Offset: 0 Lower Limit: 1
Month Size (bits): 8 Upper Limit: 12
Sign: U
130
Addr. Name Parameter Access Description Control
43357 DR / Real Daylight Read/ Use to set the week of the month when daylight savings time PC 2.x, PC
Time Clock Savings Write starts. 3.x
Start Week 0: First Occurrence
Occur- 1: Second Occurrence
rence in 2: Third Occurrence
Month 3: Fourth Occurrence
4: Last Occurrence
43358 DR / Real Daylight Read/ Multiplier: 1 Unit: Min- Use to set the amount of PC 2.x, PC
Time Clock Savings Write utes daylight savings time adjust- 3.x
Time Ad- ment applied.
justment Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 120
Sign: U
43359 DR / Real Daylight Read/ Use to enable the daylight savings time feature. PC 2.x, PC
Time Clock Savings Write 0: Disabled 3.x
Time En-
able 1: Enabled
43360 DR / Exer- Exercise Read/ Enables the exercise scheduler. PC 2.x, PC
cise Scheduler Write 0: Disabled 3.x
Scheduler Enable 1: Enabled
43361 DR / Data Reset Fuel Read/ The reset trip fuel consumption command. PC 2.x, PC
Recording Consump- Write 0: Inactive 3.x
tion 1: Active
43362 DR / Data Reset Read/ The reset runs command. PC 2.x, PC
Recording Runs Write 0: Inactive 3.x
1: Active
43363 DR / Data Reset Start Read/ The reset start attempts command. PC 2.x, PC
Recording Attempts Write 0: Inactive 3.x
1: Active
43364 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to select an exception PC 2.x, PC
cise Exception Write to adjust. 3.x
Scheduler Select Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 6
Sign: U
43365 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the date for PC 2.x, PC
cise Exception Write the selected exception. 3.x
Scheduler x Date Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 31
Sign: U
43366 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the length in PC 2.x, PC
cise Exception Write days for the selected excep- 3.x
Scheduler x Duration tion.
Days Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 44
Sign: U
43367 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the length in PC 2.x, PC
cise Exception Write hours for the selected ex- 3.x
Scheduler x Duration ception.
Hours Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 23
Sign: U
131
Addr. Name Parameter Access Description Control
43368 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the length in PC 2.x, PC
cise Exception Write minutes for the selected ex- 3.x
Scheduler x Duration ception.
Minutes Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 59
Sign: U
43369 DR / Exer- Scheduler Read/ Used to enable or disable the selected exception. PC 2.x, PC
cise Exception Write 0: Disable 3.x
Scheduler x Enable 1: Enable
43370 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the starting PC 2.x, PC
cise Exception Write hour for the selected excep- 3.x
Scheduler x Hour tion.
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 23
Sign: U
43371 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the starting PC 2.x, PC
cise Exception Write minute for the selected ex- 3.x
Scheduler x Minute ception.
Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 59
Sign: U
43372 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the starting PC 2.x, PC
cise Exception Write month for the selected ex- 3.x
Scheduler x Month ception.
Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 12
Sign: U
43373 DR / Exer- Scheduler Read/ Used to adjust the repeat interval for the selected exception. PC 2.x, PC
cise Exception Write 0: Once Only 3.x
Scheduler x Repeat 1: Every Year
43374 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to select a program to PC 2.x, PC
cise Program Write adjust. 3.x
Scheduler Select Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 12
Sign: U
43375 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the length in PC 2.x, PC
cise Program x Write hours for the selected pro- 3.x
Scheduler Duration gram.
Hours Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 23
Sign: U
43376 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the length in PC 2.x, PC
cise Program x Write minutes for the selected pro- 3.x
Scheduler Duration gram.
Minutes Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 59
Sign: U
43377 DR / Exer- Scheduler Read/ Used to enable or disable the selected program. PC 2.x, PC
cise Program x Write 0: Disable 3.x
Scheduler Enable 1: Enable
132
Addr. Name Parameter Access Description Control
43378 DR / Exer- Scheduler Read/ Used to adjust the repeat interval for the selected program. PC 2.x, PC
cise Program x Write 0: Once 3.x
Scheduler Repeat In- 1: Every Week
terval 2: Every 2 Weeks
3: Every 3 Weeks
4: Every 4 Weeks
5: Every 5 Weeks
6: First Week of Month
7: Second Week of Month
8: Third Week of Month
9: Fourth Week of Month
10: Last Week of Month
43379 DR / Exer- Scheduler Read/ Used to adjust the run mode for the selected program. PC 2.x, PC
cise Program x Write 0: No Load 3.x
Scheduler Run Mode 1: With Load
2: Extended Parallel
43380 DR / Exer- Scheduler Read/ Used to adjust the start day of the week for the selected pro- PC 2.x, PC
cise Program x Write gram. 3.x
Scheduler Start Day 0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43381 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the start hour PC 2.x, PC
cise Program x Write for the selected program. 3.x
Scheduler Start Hour Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 23
Sign: U
43382 DR / Exer- Scheduler Read/ Multiplier: 1 Unit: Used to adjust the start min- PC 2.x, PC
cise Program x Write ute for the selected program. 3.x
Scheduler Start Min- Offset: 0 Lower Limit: 0
ute Size (bits): 8 Upper Limit: 59
Sign: U
43383 DR / Real Daylight Read/ Use to set the day of the week when daylight savings time PC 2.x, PC
Time Clock Savings Write ends. 3.x
End Day 0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43501 GC / Start/ Genset Read Source or type of current genset run (if running) or previous PC 2.x, PC
Stop Con- Run Type Only genset run (if stopped) 3.x
trol 0: Emergency Remote Start
1: Non Emergency Remote Start
2: Load Demand Start
3: Manual Run
4: Exercise
133
Addr. Name Parameter Access Description Control
43502 GC / Start/ Idle Rated Read The output command of the Idle/Rated Logic PC 2.x, PC
Stop Con- Command Only 0: Idle 3.x
trol 1: Rated
43503 GC / Start/ Idle Re- Read Indicates a request to go to manual idle. Manual idle allowed PC 2.x, PC
Stop Con- quest Only if breaker is open or not controlled 3.x
trol 0: False
1: True
43506 GC / Over- Load Read Monitors the software command to the load dump driver out- PC 2.x, PC
load Dump Only put 3.x
Protection Command 0: Inactive
1: Active
43507 GC / Over- Load Read Monitors the state of the load dump overload detection algo- PC 2.x, PC
load Dump Only rithm 3.x
Protection Overload 0: Inactive
Condition 1: Active
43508 GC / Over- Load Read The state of the load dump underfrequency detection algo- PC 2.x, PC
load Dump Un- Only rithm 3.x
Protection derfre- 0: Inactive
quency
Condition 1: Active
43509 GC / Bat- Low Bat- Read Multiplier: Unit: Vdc The low battery voltage PC 2.x, PC
tery tery Volt- Only 0.1 threshold when the genset is 3.x
Protection age Run- in rated mode
ning Offset: 0 Lower Limit: 12
Threshold Size (bits): Upper Limit: 28
16
Sign: U
43510 GC / Bat- Low Bat- Read Multiplier: Unit: Vdc The low battery voltage PC 2.x, PC
tery tery Volt- Only 0.1 threshold when the genset is 3.x
Protection age not in rated mode
Stopped Offset: 0 Lower Limit: 11
Threshold Size (bits): Upper Limit: 26
16
Sign: U
43511 GC / Bat- Low Bat- Read Multiplier: Unit: Vdc The selection of the running PC 2.x, PC
tery tery Volt- Only 0.1 or stopped threshold 3.x
Protection age Offset: 0 Lower Limit: 11
Threshold Size (bits): Upper Limit: 28
16
Sign: U
43512 GC / Start/ Manual Read The output of the Manual Command OR logic PC 2.x, PC
Stop Con- Command Only 0: Not Manual 3.x
trol 1: Manual
43513 GC / Start/ Manual Read Multiplier: 1 Unit: Bitmask to show the inputs PC 2.x, PC
Stop Con- Command Only to the Command output 3.x
trol Inputs which are currently on
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
134
Addr. Name Parameter Access Description Control
43515 GC / Pre- Oil Priming Read The Prelube Driver Command. PC 2.x, PC
lube Pump Only 0: Inactive 3.x
Command 1: Active
43516 GC / Pre- Prelube Read Set to a required mode based on the type of starting require- PC 2.x, PC
lube Mode Only ment 3.x
0: Crank After Prelube
1: Crank With Prelube
2: Prelube Only
43517 GC / Pre- Prelube Read The monitor point for the prelube state. PC 2.x, PC
lube State Only 0: Complete 3.x
1: Armed
2: Prelube Output ON
3: Prelube Output OFF
4: Enable Crank
43518 GC / Start/ PTC Gen- Read Current mode for the genset operation part of the PTC func- PC 3.x
Stop Con- set Operat- Only tion
trol ing Mode 0: Off
1: Manual
2: Normal
3: Normal Override
4: Test
5: Exercise
6: Utility Fail
7: Extended Parallel
43519 GC / Start/ PTC Mode Read The output of the PTC Mode Switch Command OR logic PC 3.x
Stop Con- Switch Only 0: Inactive
trol Command 1: Active
43520 GC / Start/ PTC Mode Read Multiplier: 1 Unit: Bitmask to show the inputs PC 3.x
Stop Con- Switch Only to the Command output
trol Command which are currently on.
Inputs Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
43521 GC / Start/ PTC Status Read Indicates what the current state is of PTC control action PC 3.x
Stop Con- Only 0: Off/ Not Enabled
trol 1: Manual Mode
2: Normal Utility
3: Retransfer
4: Retransfer Override
5: Emergency Test
6: Normal Test
7: Exercise
8: Utility Failure
9: Extended Parallel
135
Addr. Name Parameter Access Description Control
43522 GC / Start/ PTC Read operation mode for the breaker pair portion of the PTC func- PC 3.x
Stop Con- Transfer Only tion
trol Pair Oper- 0: Off
ating Mode 1: Manual
2: Normal
3: Normal Override
4: Test
5: Exercise
6: Utility Fail
7: Extended Parallel
43523 GC / Out- Ready to Read The state that the Ready to Load Driver output is being com- PC 2.x, PC
puts Load Com- Only manded to 3.x
mand 0: Inactive
1: Active
43524 GC / Start/ Remote Read The output of the Remote Start Command OR logic PC 2.x, PC
Stop Con- Start Com- Only 0: Stop 3.x
trol mand 1: Start
43525 GC / Start/ Remote Read Multiplier: 1 Unit: Bitmask to show the inputs PC 2.x, PC
Stop Con- Start Com- Only to the Command output 3.x
trol mand In- which are currently on
puts Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
43526 GC / Start/ Remote Read Status of remote start and load demand stop inputs PC 2.x, PC
Stop Con- Start State Only 0: Off 3.x
trol 1: Remote Start
2: Load Demand Stop
3: Load Demand Start
43527 GC / Auto- RMS Reg- Read Multiplier: Unit: % The RMS voltage (or cur- PC 2.x, PC
matic Volt- ulation Er- Only 0.01 rent) error at the AVR 3.x
age Regu- ror Offset: 0 Lower Limit: −100
lator Size (bits): Upper Limit: 100
16
Sign: S
43528 GC / Start/ Run Com- Read The signal that is commanding a change to the run mode PC 2.x, PC
Stop Con- mand Only 0: Off 3.x
trol 1: Run
43529 GC / Start/ Run Relay Read 0: Inactive PC 2.x, PC
Stop Con- Command Only 3.x
1: Active
trol
43530 GC / Out- Speed and Read Monitor point for the command which closes the on−board PC 3.x
puts Voltage Only relay enabling the voltage and speed bias outputs.
Bias Relay 0: Inactive
Command 1: Active
43531 GC / Speed Read Multiplier: Unit: % Indicates amount of speed PC 3.x
Speed Bias Com- Only 0.01 bias offset GCS is com-
Reference mand manding to ECS governor or
external governor
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit:
16
Sign: S
136
Addr. Name Parameter Access Description Control
43533 GC / Start/ Start Read Multiplier: 1 Unit: sec- Time remaining until start is PC 2.x, PC
Stop Con- Count- Only onds initiated 3.x
trol down Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 300
16
Sign: U
43534 GC / Start Dis- Read Monitor point for the Start Disconnect logic. True = genset PC 2.x, PC
Cranking connect Only sensed above start disconnect speed. 3.x
Control Logic 0: False
1: True
43536 GC / Start/ Start Type Read The output of the Start Type Command OR logic PC 2.x, PC
Stop Con- Command Only 0: Emergency 3.x
trol 1: Non Emergency
43537 GC / Start/ Start Type Read Multiplier: 1 Unit: Bitmask to show the inputs PC 2.x, PC
Stop Con- Command Only to the Command output 3.x
trol Inputs which are currently on
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
43538 GC / Starter Read The state the Starter Command output from the cranking al- PC 2.x, PC
Cranking Command Only gorithm is being commanded to 3.x
Control 0: Inactive
1: Active
43539 GC / Start/ Stop Read Multiplier: 1 Unit: sec- Time remaining until genset PC 2.x, PC
Stop Con- Count- Only onds stops 3.x
trol down Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 5000
16
Sign: U
43540 GC / Start/ Switch Read Status of run and exercise commands from display panel PC 2.x, PC
Stop Con- Panel Run Only 0: None 3.x
trol Request 1: Manual
2: Exercise
43542 GC / Volt- Target Read Multiplier: Unit: % The target voltage without PC 2.x, PC
age Set- Voltage Only 0.01 ramping and torque match 3.x
point voltage rolloff effects
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 150
16
Sign: U
43543 GC / Start/ Time At No Read Multiplier: 1 Unit: sec- Amount of time the genset PC 2.x, PC
Stop Con- Load Only onds has run at no load 3.x
trol Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 600
16
Sign: U
43544 GC / Start/ Time at Read Multiplier: 1 Unit: sec- Amount of time spend in PC 2.x, PC
Stop Con- Rated Only onds Rated Cooldown 3.x
trol Cooldown Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 5000
16
Sign: U
137
Addr. Name Parameter Access Description Control
43546 GC / Auto- Voltage Read Multiplier: Unit: % Indicates amount of voltage PC 3.x
matic Volt- Bias Com- Only 0.01 bias offset GCS is com-
age Regu- mand manding to an external regu-
lator lator
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit:
16
Sign: S
43547 GC / Volt- Voltage Read Multiplier: Unit: % The voltage setpoint com- PC 2.x, PC
age Set- Setpoint Only 0.01 mand 3.x
point Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 150
16
Sign: U
43550 GC / Bat- Weak Bat- Read Multiplier: Unit: Vdc Monitor point for the weak PC 2.x, PC
tery tery Only 0.1 battery voltage threshold 3.x
Protection Threshold Offset: 0 Lower Limit: 6
Size (bits): Upper Limit: 16
16
Sign: U
43551 GC / Bat- Weak Bat- Read/ Multiplier: 1 Unit: sec- The time delay until a weak PC 2.x, PC
tery tery Volt- Write onds battery condition is reported 3.x
Protection age Set as a fault
Time Offset: 0 Lower Limit: 1
Size (bits): Upper Limit: 5
16
Sign: U
43552 PARCTL / Paralleling Read Multiplier: Unit: % voltage offset to voltage reg- PC 2.x, PC
Metering Voltage Only 0.01 ulator for paralleling function 3.x
and Refer- Ref Offset Offset: 0 Lower Limit:
ence Size (bits): Upper Limit:
Selection 16
Sign: S
43553 PARCTL / Synchro- Read indicates whether synchronizer is on or off PC 3.x
Synchro- nizer Sta- Only 0: Synchronizer Off
nizer tus 1: Synchronizer On
43554 PARST / Active Read Multiplier: Unit: sec- countdown value of the ac- PC 3.x
PTC Tim- Transition Only 0.1 onds tive transition timer
ers Timer Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43555 PARST / Active Read indicates the active transition type for PTC PC 3.x
PTC Tim- Transition Only 0: None
ers Type 1: Programmed Transition
2: Transfer
3: Retransfer
4: Max Parallel
138
Addr. Name Parameter Access Description Control
43556 PARST / Arbitration Read indicates current arbitration state PC 3.x
First Start State Only 0: Off
1: Arbitrate0
2: Winner
3: Arbitrate1
4: Sleep
43557 PARST / Arbitration Read Multiplier: 1 Unit: msec arbitration loop countdown PC 3.x
First Start Timer Only timer
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43558 PARST / ES State Read internal paralleling status variable PC 3.x
Paralleling Only 0: Standby
Control 1: Dead Bus
Mode 2: Synchronize
3: Load Share
4: Load Govern
43559 PARST / First Start Read indicates status of the first start system PC 3.x
First Start State Only 0: First Start Not Allowed
1: First Start Requested
2: First Start Permitted
43560 PARST / Genset CB Read genset cb close command status PC 3.x
Circuit Close Only 0: Inactive
Breaker Command 1: Active
43561 PARST / Genset CB Read status of gen fail to close lockout function PC 3.x
Circuit Fail To Only 0: Inactive
Breaker Close
Lockout 1: Active
43562 PARST / Genset CB Read indicates genset breaker position PC 3.x
Circuit Position Only 0: Open
Breaker Status 1: Closed
2: Not Available
43563 PARST / Genset Read indicates status of the genset source PC 3.x
PTC Availability Only 0: Not Available
Source Status 1: Available
Availability 2: Unknown
43564 PARST / Bus Status Read indicates status of the bus PC 3.x
Dead Bus Only 0: Unavailable
Close 1: Dead
2: Live
43565 PARST / Genset CB Read genset cb inhibit command PC 3.x
Circuit Inhibit Only 0: Inactive
Breaker Command 1: Active
43566 PARST / Genset CB Read genset cb tripped command PC 3.x
Circuit Tripped Only 0: Inactive
Breaker Command 1: Active
43567 PARST / Genset Read indicates genset breaker position based on current PC 3.x
Circuit Current Only
Breaker Based 0: Unknown
Breaker
1: Closed
Position
139
Addr. Name Parameter Access Description Control
43568 PARST / Genset Read Multiplier: Unit: Hz indicates the lower drop−out PC 3.x
PTC Sen- Frequency Only 0.1 threshold in Hz for genset
sors Lower frequency sensor
Drop−Out Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43569 PARST / Genset Read Multiplier: Unit: Hz indicates the lower pick−up PC 3.x
PTC Sen- Frequency Only 0.1 threshold in Hz for genset
sors Lower frequency sensor
Pick−Up Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43570 PARST / Genset Read indicates genset frequency sensor status PC 3.x
PTC Sen- Frequency Only 0: Unknown
sors Sensor 1: Picked Up
Status 2: Dropped Out
43571 PARST / Genset Read Multiplier: Unit: Hz indicates the upper drop−out PC 3.x
PTC Sen- Frequency Only 0.1 threshold in Hz for genset
sors Upper frequency sensor
Drop−Out Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43572 PARST / Genset Read Multiplier: Unit: Hz indicates the upper pick−up PC 3.x
PTC Sen- Frequency Only 0.1 threshold in Hz for genset
sors Upper frequency sensor
Pick−Up Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43573 PARST / Genset Read indicates genset loss of phase sensor status PC 3.x
PTC Sen- Loss of Only 0: Unknown
sors Phase
1: Picked Up
Sensor
Status 2: Dropped Out
43574 PARST / Genset Read Multiplier: 1 Unit: Vac indicates the drop−out PC 3.x
PTC Sen- Overvol- Only threshold in volts for genset
sors tage Drop− overvoltage sensor
Out Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43575 PARST / Genset Read Multiplier: 1 Unit: Vac indicates the pick−up thresh- PC 3.x
PTC Sen- Overvol- Only old in volts for genset over-
sors tage Pick− voltage sensor
Up Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
140
Addr. Name Parameter Access Description Control
43576 PARST / Genset Read indicates genset overvoltage sensor status PC 3.x
PTC Sen- Overvol- Only 0: Unknown
sors tage Sen- 1: Picked Up
sor Status 2: Dropped Out
43577 PARST / Genset Read indicates genset phase rotation sensor status PC 3.x
PTC Sen- Phase Only 0: Unknown
sors Rotation
1: Picked Up
Sensor
Status 2: Dropped Out
43578 PARST / Genset Read Multiplier: 1 Unit: Vac indicates the drop−out PC 3.x
PTC Sen- Undervol- Only threshold in volts for genset
sors tage Drop− undervoltage sensor
Out Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43579 PARST / Genset Read Multiplier: 1 Unit: Vac indicates the pick−up thresh- PC 3.x
PTC Sen- Undervol- Only old in volts for genset under-
sors tage Pick− voltage sensor
Up Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43580 PARST / Genset Read indicates genset undervoltage sensor status PC 3.x
PTC Sen- Undervol- Only 0: Unknown
sors tage Sen- 1: Picked Up
sor Status 2: Dropped Out
43581 PARST / Master Read status of the first start output command PC 3.x
First Start First Start Only 0: Inactive
Output
Command 1: Active
43582 PARST / Maximum Read Multiplier: Unit: sec- countdown value of the max- PC 3.x
PTC Tim- Parallel Only 0.1 onds imum parallel timer
ers Timer Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43583 PARST / Maximum Read indicates status of the maximum parallel timer PC 3.x
PTC Tim- Parallel Only 0: Not Timing
ers Timer Sta- 1: Timing
tus 2: Expired
43584 PARST / Paralleling Read indicates which speed control algorithm is in effect PC 2.x, PC
Paralleling Speed Only 0: Isochronous 3.x
Control Control 1: Droop
Mode Mode 2: Synchronize
3: Load Share
4: Load Govern
141
Addr. Name Parameter Access Description Control
43585 PARST / Paralleling Read indicates which voltage control algorithm is in effect PC 2.x, PC
Paralleling Voltage Only 0: Isochronous 3.x
Control Control 1: Droop
Mode Mode 2: Synchronize
3: Load Share
4: Load Govern
43586 PARST / Pro- Read Multiplier: Unit: sec- countdown value of the pro- PC 3.x
PTC Tim- grammed Only 0.1 onds grammed transition timer
ers Transition Offset: 0 Lower Limit:
Timer Size (bits): Upper Limit:
16
Sign: U
43587 PARST / Pro- Read indicates status of the programmed transition timer PC 3.x
PTC Tim- grammed Only 0: Not Timing
ers Transition
1: Timing
Timer Sta-
tus 2: Expired
43588 PARST / PTC En- Read indicates if PTC functions are running PC 3.x
PTC En- able Status Only 0: Disable
ables 1: Enable
43589 PARST / PTC Oper- Read indicates the transition type currently in effect PC 3.x
PTC State ating Tran- Only 0: Open Transition
Machine sition Type 1: Hard Closed Transition
2: Soft Closed Transition
43590 PARST / PTC State Read indicates the connected state of the Power Transfer Control PC 3.x
PTC State Only 0: PTC Not Enabled
Machine 1: No Source Connected
2: Utility Connected
3: Genset Connected
4: Paralleled
43591 PARST / Retransfer Read Multiplier: Unit: sec- countdown value of the re- PC 3.x
PTC Tim- Timer Only 0.1 onds transfer timer
ers Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43592 PARST / Retransfer Read indicates status of the retransfer timer PC 3.x
PTC Tim- Timer Sta- Only 0: Not Timing
ers tus 1: Timing
2: Expired
43593 PARST / Speed Read command value of speed droop enable PC 2.x, PC
Paralleling Droop En- Only 0: Inactive 3.x
Control able Com-
Mode mand 1: Active
43594 PARST / Speed Read indicates whether or not speed droop is in effect PC 2.x, PC
Paralleling Droop Sta- Only 0: Droop Disabled 3.x
Control tus
Mode 1: Droop Enabled
142
Addr. Name Parameter Access Description Control
43595 PARST / Transfer Read Multiplier: Unit: sec- countdown value of the PC 3.x
PTC Tim- Timer Only 0.1 onds transfer timer
ers Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43596 PARST / Transfer Read indicates status of the transfer timer PC 3.x
PTC Tim- Timer Sta- Only 0: Not Timing
ers tus 1: Timing
2: Expired
43597 PARST / Utility CB Read utility cb close command status PC 3.x
Circuit Close Only 0: Inactive
Breaker Command 1: Active
43598 PARST / Utility CB Read utility cb open command status PC 3.x
Circuit Open Only 0: Inactive
Breaker Command 1: Active
43599 PARST / Utility CB Read indicates utility breaker position PC 3.x
Circuit Position Only 0: Open
Breaker Status 1: Closed
2: Not Available
43600 PARCTL / Load Gov- Read/ Use to select how genset kW output will be controlled when PC 3.x
Load Gov- ern kW Write paralleled to utility.
ern Method 0: Genset kW
1: Genset kW w/Utility Constraint
2: Utility kW
43608 DSO / Dis- Configur- Read/ Multiplier: 1 Unit: The event code for this out- PC 2.x, PC
crete Out- able Out- Write put. 3.x
puts put #1 Offset: 0 Lower Limit: 0
Event Size (bits): Upper Limit: 65530
Code 16
Sign: U
43610 DSO / Dis- Configur- Read/ Multiplier: 1 Unit: The event code for this out- PC 2.x, PC
crete Out- able Out- Write put. 3.x
puts put #2 Offset: 0 Lower Limit: 0
Event Size (bits): Upper Limit: 65530
Code 16
Sign: U
43613 DSO / Dis- Configur- Read/ Multiplier: 1 Unit: The event code for this out- PC 3.x
crete Out- able Out- Write put.
puts put #20 Offset: 0 Lower Limit: 0
Event Size (bits): Upper Limit: 65530
Code 16
Sign: U
43616 DSO / Dis- Configur- Read/ Multiplier: 1 Unit: The event code for this out- PC 3.x
crete Out- able Out- Write put.
puts put #21 Offset: 0 Lower Limit: 0
Event Size (bits): Upper Limit: 65530
Code 16
Sign: U
143
Addr. Name Parameter Access Description Control
43619 DSO / Dis- Configur- Read/ Multiplier: 1 Unit: The event code for this out- PC 3.x
crete Out- able Out- Write put.
puts put #22 Offset: 0 Lower Limit: 0
Event Size (bits): Upper Limit: 65530
Code 16
Sign: U
43622 DSO / Dis- Configur- Read/ Multiplier: 1 Unit: The event code for this out- PC 2.x, PC
crete Out- able Out- Write put. 3.x
puts put #3 Offset: 0 Lower Limit: 0
Event Size (bits): Upper Limit: 65530
Code 16
Sign: U
43625 DSO / Dis- Configur- Read/ Multiplier: 1 Unit: The event code for this out- PC 2.x, PC
crete Out- able Out- Write put. 3.x
puts put #4 Offset: 0 Lower Limit: 0
Event Size (bits): Upper Limit: 65530
Code 16
Sign: U
43641 EH / Event Delayed Read/ Enables the Delayed Shutdown feature. PC 2.x, PC
Handler Shutdown Write 0: Disabled 3.x
Enable 1: Enabled
43642 EH / Event Delayed Read/ Multiplier: Unit: sec- Sets the shutdown fault PC 2.x, PC
Handler Shutdown Write 0.1 onds delayed time delay for the 3.x
Time Delayed Shutdown feature.
Delay Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 3
16
Sign: U
43643 EH / Event Remote Read/ Trim to enable Remote Fault Reset. Can only reset ”Warn- PC 2.x, PC
Handler Fault Reset Write ing” Faults 3.x
Enabled 0: Disable
1: Enable
43644 EH / Fault Fail To Read/ Multiplier: 1 Unit: sec- Trim to set the time for a PC 2.x, PC
Handling Shutdown Write onds shutdown fault to be active 3.x
Delay and the genset not shutting
down before the Fail to Shut-
down fault occurs.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 30
16
Sign: U
43645 EP / Low LCL Detec- Read/ Sets low coolant level fault response to None Warning or PC 2.x, PC
Coolant tion Re- Write Shutdown. 3.x
Level sponse 0: None
1: Warning
2: Shutdown
43646 EP / Low LCT Warn- Read/ Multiplier: 1 Unit: Min- Sets time to clear the low PC 2.x, PC
Coolant ing Clear Write utes coolant temp fault. 3.x
Temp Time Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 30
Sign: U
144
Addr. Name Parameter Access Description Control
43647 EP / Low LCT Warn- Read/ Multiplier: 1 Unit: Min- Sets time to set the low cool- PC 2.x, PC
Coolant ing Set Write utes ant temp fault. 3.x
Temp Time Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 30
Sign: U
43648 EP / Low LCT Warn- Read/ Multiplier: 1 Unit: degF Sets threshold for the low PC 2.x, PC
Coolant ing Write coolant temp fault warning. 3.x
Temp Threshold Offset: 0 Lower Limit: −20
Size (bits): Upper Limit: 100
16
Sign: S
43649 GC / Volt- V/Hz Knee Read/ Multiplier: Unit: Hz The voltage will roll off (de- PC 2.x, PC
age Set- Frequency Write 0.1 crease) proportionally to the 3.x
point V/Hz setup once the fre-
quency drops below the set
point in the V/Hz Knee Fre-
quency. This allows the gen-
set to recover faster when
the frequency drops.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43650 GC / Volt- V/Hz Rol- Read/ Multiplier: Unit: % / Hz The amount of voltage roll PC 2.x, PC
age Set- loff Slope Write 0.1 off when the frequency is be- 3.x
point low the knee frequency
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43651 GC / Bat- 12 V High Read/ Multiplier: Unit: Vdc Sets 12V high battery volt- PC 2.x, PC
tery Battery Write 0.1 age fault threshold. 3.x
Protection Voltage Offset: 0 Lower Limit: 14
Threshold Size (bits): Upper Limit: 17
16
Sign: U
43652 GC / Bat- 12 V Low Read/ Multiplier: Unit: Vdc Sets 12V low battery voltage PC 2.x, PC
tery Battery Write 0.1 fault threshold for genset op- 3.x
Protection Voltage eration while in rated mode
Running Offset: 0 Lower Limit: 12
Threshold Size (bits): Upper Limit: 16
16
Sign: U
43653 GC / Bat- 12 V Low Read/ Multiplier: Unit: Vdc Sets 12V low battery voltage PC 2.x, PC
tery Battery Write 0.1 fault threshold for genset op- 3.x
Protection Voltage eration in all modes except
Stopped rated
Threshold Offset: 0 Lower Limit: 11
Size (bits): Upper Limit: 13
16
Sign: U
145
Addr. Name Parameter Access Description Control
43654 GC / Bat- 12 V Weak Read/ Multiplier: Unit: Vdc Sets 12V weak battery volt- PC 2.x, PC
tery Battery Write 0.1 age fault threshold 3.x
Protection Voltage Offset: 0 Lower Limit: 6
Threshold Size (bits): Upper Limit: 10
16
Sign: U
43655 GC / Bat- 24 V High Read/ Multiplier: Unit: Vdc Sets 24V high battery volt- PC 2.x, PC
tery Battery Write 0.1 age fault threshold 3.x
Protection Voltage Offset: 0 Lower Limit: 28
Threshold Size (bits): Upper Limit: 34
16
Sign: U
43656 GC / Bat- 24 V Low Read/ Multiplier: Unit: Vdc Sets 24V low battery voltage PC 2.x, PC
tery Battery Write 0.1 fault threshold for genset op- 3.x
Protection Voltage eration while in rated mode
Running Offset: 0 Lower Limit: 24
Threshold Size (bits): Upper Limit: 28
16
Sign: U
43657 GC / Bat- 24 V Low Read/ Multiplier: Unit: Vdc Sets 24V low battery voltage PC 2.x, PC
tery Battery Write 0.1 fault threshold for genset op- 3.x
Protection Voltage eration in all modes except
Stopped rated
Threshold Offset: 0 Lower Limit: 22
Size (bits): Upper Limit: 26
16
Sign: U
43658 GC / Bat- 24 V Weak Read/ Multiplier: Unit: Vdc Sets 24V weak battery volt- PC 2.x, PC
tery Battery Write 0.1 age fault threshold 3.x
Protection Voltage Offset: 0 Lower Limit: 12
Threshold Size (bits): Upper Limit: 16
16
Sign: U
43659 GC / Adjustable Read/ Multiplier: Unit: rpm/Hz Sets the rpm/Hz conversion PC 2.x, PC
Speed Freq/ Write 0.01 factor when the Freq to 3.x
Reference Speed Speed Gain Select trim is
Gain set to this trim
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 240
16
Sign: U
43660 GC / Speed Alternate Read/ Sets the genset nominal frequency. PC 2.x, PC
Reference Frequency Write 0: 50 Hz 3.x
Switch 1: 60 Hz
43661 GC / Auto- AVR Gain Read/ Multiplier: Unit: A trim that allows the user to PC 2.x, PC
matic Volt- Adjust Write 0.01 modify the overall gains of 3.x
age Regu- Trim the AVR.
lator Offset: 0 Lower Limit: 0.05
Size (bits): Upper Limit: 10
16
Sign: U
146
Addr. Name Parameter Access Description Control
43662 GC / Charging Read/ Multiplier: Unit: sec- Sets the time delay for the PC 2.x, PC
Charging Alternator Write 0.1 onds charging alt failure fault 3.x
Alternator Fault Time Offset: 0 Lower Limit: 2
Protection Delay Size (bits): Upper Limit: 300
16
Sign: U
43663 GC / Continu- Read/ Multiplier: 1 Unit: sec- Sets the maximum amount PC 2.x, PC
Cranking ous Crank Write onds of time to engage the starter 3.x
Control Engage when using the continuous
Time cranking method
Offset: 0 Lower Limit: 40
Size (bits): Upper Limit: 100
16
Sign: U
43664 GC / Con- Controlled Read/ Multiplier: 1 Unit: sec- Delay allowed for a shut- PC 3.x
trolled Shutdown Write onds down with cooldown fault
Shutdown Advance prior to shutting down the
Control Notice genset
Delay Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 300
16
Sign: U
43665 GC / Crank At- Read/ Multiplier: 1 Unit: Sets the maximum number PC 2.x, PC
Cranking tempts Write of times to engage the start- 3.x
Control er when attempting to start
engine using the cycle
cranking method
Offset: 0 Lower Limit: 1
Size (bits): Upper Limit: 7
16
Sign: U
43666 GC / Cycle / Read/ Selects whether to use continuous cranking or cycle crank- PC 2.x, PC
Cranking Cont Crank Write ing when attempting to start engine 3.x
Control Select 0: Cycle
1: Continuous
43667 GC / Cycle Read/ Multiplier: 1 Unit: sec- Sets the maximum amount PC 2.x, PC
Cranking Crank En- Write onds of time to engage the starter 3.x
Control gage Time during a single crank attempt
when using the cycle crank-
ing method
Offset: 0 Lower Limit: 2
Size (bits): Upper Limit: 20
16
Sign: U
43668 GC / Cycle Read/ Multiplier: 1 Unit: sec- Sets the amount of time to PC 2.x, PC
Cranking Crank Write onds wait between crank attempts 3.x
Control Rest Time Offset: 0 Lower Limit: 7
Size (bits): Upper Limit: 40
16
Sign: U
147
Addr. Name Parameter Access Description Control
43669 GC / Out- Delayed Read/ Multiplier: Unit: sec- Time delay between when PC 2.x, PC
puts Off FSO Write 0.1 onds the Delayed Off Command 3.x
Relay turns off and Run Command
Time turns off
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 120
16
Sign: U
43670 GC / Volt- External Read/ Multiplier: Unit: Hz Sets the knee frequency for PC 2.x, PC
age Set- AVR Knee Write 0.1 the fixed knee freq logic. 3.x
point Frequency Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43671 GC / Volt- External Read/ Enables the external bias (speed and voltage commands) to PC 3.x
age Set- Bias Com- Write the hardware outputs.
point mands En- 0: Disabled
able 1: Enabled
43672 GC / Frequency Read/ Multiplier: Unit: Hz A method of adding in a fre- PC 2.x, PC
Speed Adjust Write 0.01 quency offset to the base 3.x
Reference frequency subject to high
and low limit calibrations
Offset: 0 Lower Limit: −6
Size (bits): Upper Limit: 6
16
Sign: S
43673 GC / Start/ Genset Read/ Multiplier: Unit: hours Sets the total exercise time PC 2.x, PC
Stop Con- Exercise Write 0.1 not including warmup at idle 3.x
trol Time or idle cooldown time
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 25
16
Sign: U
43674 GC / Gov- Governor Read/ Multiplier: Unit: A trim that allows the user to PC 2.x, PC
ernor Gain Ad- Write 0.01 modify the overall gain of the 3.x
just governor
Offset: 0 Lower Limit: 0.05
Size (bits): Upper Limit: 10
16
Sign: U
43675 GC / Bat- High Bat- Read/ Multiplier: 1 Unit: sec- The time delay until a high PC 2.x, PC
tery tery Volt- Write onds battery voltage condition is 3.x
Protection age Set reported as a fault.
Time Offset: 0 Lower Limit: 2
Size (bits): Upper Limit: 60
16
Sign: U
148
Addr. Name Parameter Access Description Control
43676 GC / Bat- High Bat- Read Multiplier: Unit: Vdc The high battery voltage PC 2.x, PC
tery tery Volt- Only 0.1 threshold 3.x
Protection age Offset: 0 Lower Limit: 14
Threshold Size (bits): Upper Limit: 34
16
Sign: U
43677 GC / Start/ Idle Cool- Read/ Multiplier: Unit: min- Sets time to run at idle be- PC 2.x, PC
Stop Con- down Time Write 0.25 utes fore shutting down genset on 3.x
trol normal stops
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 60
16
Sign: U
43678 GC / Idle Speed Read/ Multiplier: 1 Unit: rpm Sets the speed at which the PC 2.x, PC
Speed Write engine will idle subject to 3.x
Reference high and low limit calibra-
tions
Offset: 0 Lower Limit: 700
Size (bits): Upper Limit: 1100
16
Sign: U
43679 GC / Idle to Read/ Multiplier: Unit: sec- The time over which the PC 2.x, PC
Speed Rated Write 0.1 onds speed reference is to ramp 3.x
Reference Ramp from idle speed to rated
Time speed
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 30
16
Sign: U
43680 GC / Start/ Idle War- Read/ Multiplier: 1 Unit: degF Coolant temperature thresh- PC 2.x, PC
Stop Con- mup Cool- Write old to end idle warmup time 3.x
trol ant Temp Offset: 0 Lower Limit: −40
Size (bits): Upper Limit: 300
16
Sign: S
43681 GC / Start/ Idle War- Read/ Multiplier: 1 Unit: sec- Sets maximum idle warmup PC 2.x, PC
Stop Con- mup Time Write onds time. Warmup time may be 3.x
trol less if coolant temperature
exceeds threshold
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 3600
16
Sign: U
43682 GC / Over- Load Read/ Enables the load dump output as a function of the overload PC 2.x, PC
load Dump Ac- Write and underfrequency conditions 3.x
Protection tivation 0: Overload
Method 1: Underfrequency
2: Overload or Underfrequency
3: Disabled
149
Addr. Name Parameter Access Description Control
43683 GC / Over- Load Read/ Multiplier: 1 Unit: sec- The time delay until the load PC 2.x, PC
load Dump Write onds dump overload condition is 3.x
Protection Overload set active
Set Time Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 120
16
Sign: U
43684 GC / Over- Load Read/ Multiplier: 1 Unit: % The load dump overload PC 2.x, PC
load Dump Write threshold as a percentage of 3.x
Protection Overload the genset application rating
Threshold Offset: 0 Lower Limit: 80
Size (bits): Upper Limit: 140
16
Sign: U
43685 GC / Over- Load Read/ Multiplier: 1 Unit: Hz The frequency amount which PC 2.x, PC
load Dump Un- Write the load dump underfre- 3.x
Protection derfre- quency threshold is below
quency the final frequency reference
Offset Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: S
43686 GC / Over- Load Read/ Multiplier: 1 Unit: sec- The time delay until the load PC 2.x, PC
load Dump Un- Write onds dump underfrequency condi- 3.x
Protection derfre- tion is set active
quency Offset: 0 Lower Limit: 0
Set Time Size (bits): Upper Limit: 20
16
Sign: U
43687 GC / Over- Load Read Multiplier: Unit: Hz The frequency trip threshold PC 2.x, PC
load Dump Un- Only 0.1 for the load dump underfre- 3.x
Protection derfre- quency condition
quency Offset: 0 Lower Limit: 0
Threshold Size (bits): Upper Limit: 90
16
Sign: U
43688 GC / Bat- Low Bat- Read/ Multiplier: 1 Unit: sec- The time delay until a low PC 2.x, PC
tery tery Volt- Write onds battery voltage condition is 3.x
Protection age Set reported as a fault
Time Offset: 0 Lower Limit: 2
Size (bits): Upper Limit: 60
16
Sign: U
43689 GC / Out- Low Fuel Read/ Multiplier: 1 Unit: sec- Low Fuel in Day Tank Fault PC 2.x, PC
puts in Day Write onds time delay from switch input. 3.x
Tank Time Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 20
16
Sign: U
150
Addr. Name Parameter Access Description Control
43690 GC / Out- Low Fuel Read/ Multiplier: 1 Unit: sec- A trim that sets the delay PC 2.x, PC
puts Set/Clear Write onds time for generating the inac- 3.x
Time tive and active faults.
Offset: 0 Lower Limit: 2
Size (bits): Upper Limit: 60
16
Sign: U
43691 GC / Start/ Manual Read/ Use to command idle speed or to bypass idle warmup during PC 2.x, PC
Stop Con- Warmup Write a manual run 3.x
trol Bypass 0: Normal
1: Bypass Warmup
43692 GC / Start/ Max Idle Read/ Multiplier: Unit: min- Sets the fault time for the PC 2.x, PC
Stop Con- Time Write 0.1 utes Too Long in Idle fault. 3.x
trol Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 20
16
Sign: U
43693 GC / Bat- Nominal Read/ Selects the genset_s nominal battery operating voltage PC 2.x, PC
tery Battery Write 0: 12V 3.x
Protection Voltage 1: 24V
43694 GC / Pre- Prelube Read/ Enables Or Disables the cyclic mode of prelube operation PC 2.x, PC
lube Cycle En- Write 0: Disabled 3.x
able 1: Enabled
43695 GC / Pre- Prelube Read/ Multiplier: Unit: hours Sets the period of the Pre- PC 2.x, PC
lube Cycle Time Write 0.1 lube Cycle Iteration 3.x
Offset: 0 Lower Limit: 1
Size (bits): Upper Limit: 1000
16
Sign: U
43696 GC / Pre- Prelube Read/ Selects whether the Prelube function is enabled or disabled. PC 2.x, PC
lube Function Write This is Setup mode interlocked 3.x
Enable 0: Disabled
1: Enabled
43697 GC / Pre- Prelube Oil Read/ Multiplier: Unit: psig The oil pressure value which PC 2.x, PC
lube Pressure Write 0.1 when reached the prelube 3.x
Threshold driver will turn off
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43698 GC / Pre- Prelube Read/ Multiplier: Unit: sec- Sets the maximum time for PC 2.x, PC
lube Timeout Write 0.1 onds which the Prelube Driver will 3.x
Period Remain ON
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 30
16
Sign: U
151
Addr. Name Parameter Access Description Control
43699 GC / Rated to Read/ Multiplier: Unit: sec- The time over which the PC 2.x, PC
Speed Idle Ramp Write 0.1 onds speed reference is to ramp 3.x
Reference Time from rated speed to idle
speed
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 30
16
Sign: U
43700 PARST / Utility Read indicates status of the utility source PC 3.x
PTC Availability Only 0: Not Available
Source Status 1: Available
Availability 2: Unknown
43701 PARST / Utility CB Read utility cb inhibit command PC 3.x
Circuit Inhibit Only 0: Inactive
Breaker Command 1: Active
43702 PARST / Utility CB Read utility cb tripped command PC 3.x
Circuit Tripped Only 0: Inactive
Breaker Command 1: Active
43703 PARST / Utility Cur- Read indicates utility breaker position based on current PC 3.x
Circuit rent Based Only 0: Unknown
Breaker Breaker
Position 1: Closed
43704 PARST / Utility Fre- Read Multiplier: Unit: Hz indicates the lower drop−out PC 3.x
PTC Sen- quency Only 0.1 threshold in Hz for utility fre-
sors Lower quency sensor
Drop−Out Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43705 PARST / Utility Fre- Read Multiplier: Unit: Hz indicates the lower pick−up PC 3.x
PTC Sen- quency Only 0.1 threshold in Hz for utility fre-
sors Lower quency sensor
Pick−Up Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43706 PARST / Utility Fre- Read indicates utility frequency sensor status PC 3.x
PTC Sen- quency Only 0: Unknown
sors Sensor 1: Picked Up
Status 2: Dropped Out
43707 PARST / Utility Fre- Read Multiplier: Unit: Hz indicates the upper drop−out PC 3.x
PTC Sen- quency Only 0.1 threshold in Hz for utility fre-
sors Upper quency sensor
Drop−Out Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
152
Addr. Name Parameter Access Description Control
43708 PARST / Utility Fre- Read Multiplier: Unit: Hz indicates the upper pick−up PC 3.x
PTC Sen- quency Only 0.1 threshold in Hz for utility fre-
sors Upper quency sensor
Pick−Up Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43709 PARST / Utility Loss Read indicates utility loss of phase sensor status PC 3.x
PTC Sen- of Phase Only 0: Unknown
sors Sensor 1: Picked Up
Status 2: Dropped Out
43710 PARST / Utility Read Multiplier: 1 Unit: Vac indicates the drop−out PC 3.x
PTC Sen- Overvol- Only threshold in volts for utility
sors tage Drop− overvoltage sensor
Out Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43711 PARST / Utility Read Multiplier: 1 Unit: Vac indicates the pick−up thresh- PC 3.x
PTC Sen- Overvol- Only old in volts for utility overvol-
sors tage Pick− tage sensor
Up Offset: 0 Lower Limit:
Threshold Size (bits): Upper Limit:
16
Sign: U
43712 PARST / Utility Read indicates utility overvoltage sensor status PC 3.x
PTC Sen- Overvol- Only 0: Unknown
sors tage Sen- 1: Picked Up
sor Status 2: Dropped Out
43713 PARST / Utility Read indicates utility phase rotation sensor status PC 3.x
PTC Sen- Phase Only 0: Unknown
sors Rotation
1: Picked Up
Sensor
Status 2: Dropped Out
43714 PARST / Utility Un- Read Multiplier: 1 Unit: Vac indicates the drop−out PC 3.x
PTC Sen- dervoltage Only threshold in volts for utility
sors Drop−Out undervoltage sensor
Threshold Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43715 PARST / Utility Un- Read Multiplier: 1 Unit: Vac indicates the pick−up thresh- PC 3.x
PTC Sen- dervoltage Only old in volts for utility under-
sors Pick−Up voltage sensor
Threshold Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
153
Addr. Name Parameter Access Description Control
43716 PARST / Utility Un- Read indicates utility undervoltage sensor status PC 3.x
PTC Sen- dervoltage Only 0: Unknown
sors Sensor 1: Picked Up
Status 2: Dropped Out
43717 PARST / Voltage Read Command value of voltage droop enable PC 2.x, PC
Paralleling Droop En- Only 0: Inactive 3.x
Control able Com-
Mode mand 1: Active
43718 PARST / Voltage Read indicates whether or not voltage droop is in effect PC 2.x, PC
Paralleling Droop Sta- Only 0: Droop Disabled 3.x
Control tus
Mode 1: Droop Enabled
43719 PCCNet / Alternator Read Multiplier: 1 Unit: degF Monitor point for the Alterna- PC 2.x, PC
I/O Module Tempera- Only tor Temp 1 input from the 3.x
0 Main ture 1 Aux 101 I/O Module.
Board (Aux101) Offset: 0 Lower Limit: −32767
Size (bits): Upper Limit: 32762
16
Sign: S
43720 PCCNet / Alternator Read Multiplier: 1 Unit: degF Monitor point for the Alterna- PC 2.x, PC
I/O Module Tempera- Only tor Temp 2 input from the 3.x
0 Main ture 2 Aux 101 I/O Module.
Board (Aux101) Offset: 0 Lower Limit: −32767
Size (bits): Upper Limit: 32762
16
Sign: S
43721 PCCNet / Alternator Read Multiplier: 1 Unit: degF Monitor point for the Alterna- PC 2.x, PC
I/O Module Tempera- Only tor Temp 3 input from the 3.x
0 Main ture 3 Aux 101 I/O Module.
Board (Aux101) Offset: 0 Lower Limit: −32767
Size (bits): Upper Limit: 32762
16
Sign: S
43722 PCCNet / Ambient Read Multiplier: 1 Unit: degF Monitor point for the Ambient PC 2.x, PC
I/O Module Tempera- Only Temp input from the Aux 101 3.x
0 Main ture I/O Module.
Board (Aux101) Offset: 0 Lower Limit: −32767
Size (bits): Upper Limit: 32762
16
Sign: S
43723 PCCNet / Aux101 0 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 0 analog input 1 in Volts 3.x
0 Main put 1 Volt- Offset: 0 Lower Limit: −500
Board age Size (bits): Upper Limit: 500
16
Sign: S
154
Addr. Name Parameter Access Description Control
43724 PCCNet / Aux101 0 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 0 analog input 2 in Volts 3.x
0 Main put 2 Volt- Offset: 0 Lower Limit: −500
Board age Size (bits): Upper Limit: 500
16
Sign: S
43725 PCCNet / Aux101 0 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 0 analog input 3 in Volts 3.x
0 Main put 3 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43726 PCCNet / Aux101 0 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 0 analog input 4 in Volts 3.x
0 Main put 4 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43727 PCCNet / Aux101 0 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 0 analog input 5 in Volts 3.x
0 Main put 5 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43728 PCCNet / Aux101 0 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 0 analog input 6 in Volts 3.x
0 Main put 6 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43729 PCCNet / Aux101 0 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 0 analog input 7 in Volts 3.x
0 Main put 7 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43730 PCCNet / Aux101 0 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 0 analog input 8 in Volts 3.x
0 Main put 8 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43731 PCCNet / Aux101 1 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 1 analog input 1 in Volts 3.x
1 Main put 1 Volt- Offset: 0 Lower Limit: −500
Board age Size (bits): Upper Limit: 500
16
Sign: S
155
Addr. Name Parameter Access Description Control
43732 PCCNet / Aux101 1 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 1 analog input 2 in Volts 3.x
1 Main put 2 Volt- Offset: 0 Lower Limit: −500
Board age Size (bits): Upper Limit: 500
16
Sign: S
43733 PCCNet / Aux101 1 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 1 analog input 3 in Volts 3.x
1 Main put 3 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43734 PCCNet / Aux101 1 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 1 analog input 4 in Volts 3.x
1 Main put 4 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43735 PCCNet / Aux101 1 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 1 analog input 5 in Volts 3.x
1 Main put 5 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43736 PCCNet / Aux101 1 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 1 analog input 6 in Volts 3.x
1 Main put 6 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43737 PCCNet / Aux101 1 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 1 analog input 7 in Volts 3.x
1 Main put 7 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43738 PCCNet / Aux101 1 Read Multiplier: Unit: Vdc Monitor point for the module PC 2.x, PC
I/O Module Analog In- Only 0.01 1 analog input 8 in Volts 3.x
1 Main put 8 Volt- Offset: 0 Lower Limit:
Board age Size (bits): Upper Limit:
16
Sign: S
43739 PCCNet / Battery Read Monitor point for the battery charger failure input from the PC 2.x, PC
Universal Charger Only PCCNet Annunciator. 3.x
Annuncia- AC Failure 0: Inactive
tor (HMI113) 1: Active
156
Addr. Name Parameter Access Description Control
43740 PCCNet / Drive End Read Multiplier: 1 Unit: degF Monitor point for the Drive PC 2.x, PC
I/O Module Bearing Only End Bearing Temp input 3.x
0 Main Tempera- from the I/O Module.
Board ture Offset: 0 Lower Limit: −32767
(Aux101) Size (bits): Upper Limit: 32762
16
Sign: S
43741 PCCNet / Exhaust Read Multiplier: 1 Unit: degF Monitor point for the Exhaust PC 2.x, PC
I/O Module Stack Only Stack Temp1 input from the 3.x
0 Main Tempera- I/O Module.
Board ture 1 Offset: 0 Lower Limit: −32767
(Aux101) Size (bits): Upper Limit: 32762
16
Sign: S
43742 PCCNet / Exhaust Read Multiplier: 1 Unit: degF Monitor point for the Exhaust PC 2.x, PC
I/O Module Stack Only Stack Temp2 input from the 3.x
0 Main Tempera- I/O Module.
Board ture 2 Offset: 0 Lower Limit: −32768
(Aux101) Size (bits): Upper Limit: 32762
16
Sign: S
43743 PCCNet / External Read Multiplier: Unit: % Monitor point for the Speed PC 2.x, PC
I/O Module Speed Only 0.01 Bias input from the I/O Mod- 3.x
0 Main Bias Input ule.
Board (PCCNet) Offset: 0 Lower Limit: −100
Size (bits): Upper Limit: 100
16
Sign: U
43744 PCCNet / External Read Multiplier: Unit: % Monitor point for the Voltage PC 2.x, PC
I/O Module Voltage Only 0.01 Bias input from the I/O Mod- 3.x
0 Main Bias Input ule.
Board (PCCNet) Offset: 0 Lower Limit: −100
Size (bits): Upper Limit: 100
16
Sign: U
43745 PCCNet / Fuel Level Read Multiplier: Unit: % Monitor point for the % fuel PC 2.x, PC
I/O Module % Only 0.1 level input from the I/O Mod- 3.x
0 Main (PCCNet) ule.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43746 PCCNet / Fuel Level Read Multiplier: 1 Unit: Monitor point for the fuel le- PC 2.x, PC
I/O Module (PCCNet) Only vel (in gallons) input from the 3.x
0 Main I/O Module.
Board Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
157
Addr. Name Parameter Access Description Control
43747 PCCNet / HMI113 Read Monitor point for input #1 from the Annunciator. PC 2.x, PC
Universal Fault 1 Sta- Only 0: Inactive 3.x
Annuncia- tus
tor 1: Active
43748 PCCNet / HMI113 Read Monitor point for input #2 from the Annunciator. PC 2.x, PC
Universal Fault 2 Sta- Only 0: Inactive 3.x
Annuncia- tus
tor 1: Active
43749 PCCNet / HMI113 Read Monitor point for the input #3 from the Annunciator. PC 2.x, PC
Universal Fault 3 Sta- Only 0: Inactive 3.x
Annuncia- tus
tor 1: Active
43750 PCCNet / Intake Read Multiplier: 1 Unit: degF Monitor point for the Intake PC 2.x, PC
I/O Module Manifold Only Manifold Temp 1 input from 3.x
0 Main Tempera- the I/O Module.
Board ture 1 Offset: 0 Lower Limit: −32768
(Aux101) Size (bits): Upper Limit: 32762
16
Sign: S
43751 PCCNet / Low Cool- Read Monitor point for the Low Coolant Level input from the PC 2.x, PC
Universal ant Level Only PCCNet Annunciator. 3.x
Annuncia- (HMI113) 0: Inactive
tor 1: Active
43752 PCCNet / Low Fuel Read Monitor point for the Low Fuel Level input from the PCCNet PC 2.x, PC
Universal Level Only Annunciator. 3.x
Annuncia- (HMI113) 0: Inactive
tor 1: Active
43755 PCCNet / Non−Drive Read Multiplier: 1 Unit: degF Monitor point for the Non− PC 2.x, PC
I/O Module End Bear- Only Drive End Bearing Temp in- 3.x
0 Main ing Tem- put from the I/O Module.
Board perature Offset: 0 Lower Limit: −65534
(Aux101) Size (bits): Upper Limit: 65535
16
Sign: S
43756 PCCNet / Number of Read Multiplier: 1 Unit: Used to monitor the amount PC 2.x, PC
Monitoring Connected Only of connected Bargraph mod- 3.x
and Diag- Bargraph ules.
nostics Modules Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 255
Sign: U
43757 PCCNet / Oil Tem- Read Multiplier: 1 Unit: degF Monitor point for the Oil PC 2.x, PC
I/O Module perature Only Temp input from the I/O 3.x
0 Main (Aux101) Module.
Board Offset: 0 Lower Limit: −65534
Size (bits): Upper Limit: 65535
16
Sign: S
158
Addr. Name Parameter Access Description Control
43758 Modbus / Modbus Read Multiplier: 1 Unit: Modbus bus message count PC 2.x, PC
Modbus Bus Mes- Only 3.x
sage Offset: 0 Lower Limit:
Count Size (bits): Upper Limit:
16
Sign: U
43759 Modbus / Modbus Read Multiplier: 1 Unit: Modbus CRC errors count PC 2.x, PC
Modbus CRC Er- Only 3.x
rors Count Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43760 Modbus / Modbus Read Multiplier: 1 Unit: Modbus exception count PC 2.x, PC
Modbus Exception Only 3.x
Count Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
43761 Modbus / Modbus Read Multiplier: 1 Unit: Modbus no response count PC 2.x, PC
Modbus No Re- Only 3.x
sponse Offset: 0 Lower Limit:
Count Size (bits): Upper Limit:
16
Sign: U
43762 Modbus / Modbus Read Multiplier: 1 Unit: Modbus slave message PC 2.x, PC
Modbus Slave Only count 3.x
Message Offset: 0 Lower Limit:
Count Size (bits): Upper Limit:
16
Sign: U
43763 PARCTL / Frequency Read Multiplier: Unit: Hz frequency match error value PC 3.x
Synchro- Match Er- Only 0.001 used by frequency match PI
nizer ror loop
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43764 PARCTL / Frequency Read Multiplier: Unit: Hz offset to the frequency PC 3.x
Synchro- Match Off- Only 0.001 match error calculation
nizer set Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43765 PARCTL / Load Read indicates a load dump is desired due to load exceeding der- PC 2.x, PC
Derate Dump Re- Only ate level. 3.x
quest 0: Inactive
1: Active
159
Addr. Name Parameter Access Description Control
43766 PARCTL / Load Gov- Read indicates status of load govern kVAR ramping control PC 3.x
Load Gov- ern kVAR Only 0: Not Applicable
ern Ramp 1: Ramp Load
State 2: Track Target
3: Ramp Unload
4: Ramp Unload Complete
43767 PARCTL / Load Gov- Read Multiplier: Unit: % indicates the final target set- PC 3.x
Load Gov- ern kVAR Only 0.01 point for genset kVAR output
ern Target when paralleled to utility
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43768 PARCTL / Load Gov- Read indicates status of load govern kW ramping control PC 3.x
Load Gov- ern kW Only 0: Not Applicable
ern Ramp 1: Ramp Load
State 2: Track Target
3: Ramp Unload
4: Ramp Unload Complete
43769 PARCTL / Load Gov- Read Multiplier: Unit: % indicates the final target set- PC 3.x
Load Gov- ern kW Only 0.01 point for genset kW output
ern Target when paralleled to utility
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43770 PARCTL / Permissive Read indicates when permissive sync check conditions have been PC 3.x
Synchro- Close Al- Only met
nizer lowed 0: Not Allowed
1: Allowed
43772 PARCTL / Permissive Read Multiplier: Unit: deg phase error signal for the PC 3.x
Synchro- Phase Only 0.01 permissive sync check algo-
nizer Match Er- rithm
ror Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43773 PARCTL / Phase Read Multiplier: Unit: deg phase error signal for the PC 3.x
Synchro- Match Er- Only 0.01 synchronizer control algo-
nizer ror rithm
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
43774 PARCTL / Ramp Read indicates overall status of ramp load unload inputs PC 3.x
Load Load/Un- Only 0: Load
Share load Com-
mand 1: Unload
43775 PARCTL / Utility Un- Read indicates unloaded status of the utility source PC 3.x
Load Gov- loaded Sta- Only 0: Not Available
ern tus 1: Not Unloaded
2: Unloaded
160
Addr. Name Parameter Access Description Control
43776 DSO / Dis- Genset CB Read Indicates if the output_s status is Inactive or Active PC 3.x
crete Out- Close Sta- Only 0: Inactive
puts tus 1: Active
43777 DSI / Dis- Start Type/ Read This is the status of the Configurable Input #11. PC 2.x, PC
crete In- Configur- Only 0: Inactive 3.x
puts able Input
#11 Switch 1: Active
43778 DR / Exer- Scheduler Read Indicates the current run command coming from the sched- PC 2.x, PC
cise Run Com- Only uler. 3.x
Scheduler mand 0: Off
1: No Load
2: With Load
3: Extended Parallel
43789 DSI / Dis- Backup Read This is the status of the Configurable Input #33. PC 3.x
crete In- Start Dis- Only
puts connect/ 0: Inactive
Configur-
able Input 1: Active
#33 Switch
43790 DSI / Dis- Backup Read Status of the Backup Start Disconnect Switch Input PC 3.x
crete In- Start Dis- Only 0: Inactive
puts connect
Switch 1: Active
43791 DSI / Dis- Battery Read Battery Charger Failed Switch function output status; gives PC 2.x, PC
crete In- Charger Only software Inactive/Active state 3.x
puts Failed 0: Inactive
Switch 1: Active
43785 DR / Data Start At- Read/ Multiplier: 1 Unit: Number of start attempts PC 2.x, PC
Recording tempts Write since the last reset. 3.x
Since Re- Offset: 0 Lower Limit: 0
set Size (bits): Upper Limit: 4294967290
32
Sign: U
43786 DR / Data Start At- Read/ Multiplier: 1 Unit: Number of start attempts PC 2.x, PC
Recording tempts Write since the last reset. 3.x
Since Re- Offset: 0 Lower Limit: 0
set Size (bits): Upper Limit: 4294967290
32
Sign: U
43787 DR / Data Total Start Read/ Multiplier: 1 Unit: Total number of start at- PC 2.x, PC
Recording Attempts Write tempts. 3.x
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967295
32
Sign: U
43788 DR / Data Total Start Read/ Multiplier: 1 Unit: Total number of start at- PC 2.x, PC
Recording Attempts Write tempts. 3.x
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4294967295
32
Sign: U
161
Addr. Name Parameter Access Description Control
43792 DSI / Dis- Battle Read Battle Short Switch function output status (Active or Inac- PC 2.x, PC
crete In- Short Only tive). 3.x
puts Switch 0: Inactive
1: Active
43793 DSI / Dis- Configur- Read Configurable Input #1 input software state status. Gives soft- PC 2.x, PC
crete In- able Input Only ware Inactive/Active state 3.x
puts #1 Switch 0: Inactive
1: Active
43794 DSI / Dis- Configur- Read Configurable Input #2 input software state status. Gives soft- PC 2.x, PC
crete In- able Input Only ware Inactive/Active state 3.x
puts #2 Switch 0: Inactive
1: Active
43795 DSI / Dis- Configur- Read Configurable Input #13 input software state status. Gives PC 2.x, PC
crete In- able Input Only software Inactive/Active state 3.x
puts #13 Switch 0: Inactive
1: Active
43796 PARST / Genset CB Read genset cb open command status PC 3.x
Circuit Open Only 0: Inactive
Breaker Command 1: Active
43797 PCCNet / Number of Read Multiplier: 1 Unit: Used to monitor the amount PC 2.x, PC
Monitoring Connected Only of connected Battery Char- 3.x
and Diag- Battery gers.
nostics Chargers Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 255
Sign: U
43800 GC / Start/ Rated Read/ Multiplier: 1 Unit: sec- Minimum time to spend at PC 2.x, PC
Stop Con- Cooldown Write onds rated speed less than 10% 3.x
trol Time load before normal shut-
down is allowed
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 600
16
Sign: U
43801 GC / Start/ Rated to Read/ Multiplier: Unit: sec- Sets the delay time for tran- PC 2.x, PC
Stop Con- Idle Transi- Write 0.1 onds sitioning from Rated to Idle 3.x
trol tion Delay speed. 0 seconds = feature
is disabled.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43802 GC / Out- Rupture Read/ Multiplier: Unit: sec- Rupture Basin fault time PC 2.x, PC
puts Basin Time Write 0.1 onds delay 3.x
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 20
16
Sign: U
162
Addr. Name Parameter Access Description Control
43803 GC / Start/ Start Time Read/ Multiplier: 1 Unit: sec- Sets the time to wait from re- PC 2.x, PC
Stop Con- Delay Write onds ceiving a valid remote start 3.x
trol signal until starting the gen-
set
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 300
16
Sign: U
43804 GC / Starting to Read/ Multiplier: Unit: sec- The time over which the PC 2.x, PC
Speed Rated Write 0.1 onds speed reference is to ramp 3.x
Reference Ramp from starting speed to rated
Time speed
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 30
16
Sign: U
43805 GC / Start/ Time Read/ Multiplier: 1 Unit: sec- Sets time to run at rated PC 2.x, PC
Stop Con- Delay to Write onds speed before going to cool- 3.x
trol Stop down at idle. Does not apply
to manual runs
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 600
16
Sign: U
43806 GC / Volt- Voltage Read/ Multiplier: Unit: % A trim that allows the user to PC 2.x, PC
age Set- Adjust Write 0.01 add/subtract an offset to the 3.x
point nominal voltage when calcu-
lating the voltage setpoint
Offset: 0 Lower Limit: −5
Size (bits): Upper Limit: 5
16
Sign: S
43807 GC / Volt- Voltage Read/ Multiplier: Unit: sec- The time period over which PC 2.x, PC
age Set- Ramp Write 0.01 onds the voltage setpoint com- 3.x
point Time mand should rise from 0% to
the target voltage
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 5
16
Sign: U
43810 Modbus / Battle Read/ Trim to enable Battle Short via Modbus. PC 2.x, PC
Modbus Short Write 0: Inactive 3.x
Switch
(Modbus) 1: Active
43811 Modbus / Exercise Read/ Modbus exercise switch PC 2.x, PC
Modbus Switch Write 0: Inactive 3.x
(Modbus) 1: Active
43813 Modbus / Extended Read/ Modbus extended parallel switch PC 2.x, PC
Modbus Parallel Write 0: Inactive 3.x
Switch
(Modbus) 1: Active
163
Addr. Name Parameter Access Description Control
43814 Modbus / PTC Mode Read/ Modbus PTC Mode switch PC 3.x
Modbus Switch Write 0: Inactive
(Modbus) 1: Active
43815 Modbus / Start Type Read/ Modbus start type switch PC 2.x, PC
Modbus (Modbus) Write 0: Emergency 3.x
1: Non Emergency
43816 PARCTL / Sync Dis- Read/ use to turn off synchronizer for testing purposes PC 3.x
Synchro- able Write 0: Inactive
nizer 1: Active
43817 PARST / Genset CB Read/ genset cb inhibit from Modbus PC 3.x
Circuit Inhibit Write 0: Inactive
Breaker Switch
(Modbus) 1: Active
43818 PARST / Isolated Read/ Sets the speed control method for isolated bus paralleling. PC 2.x, PC
Paralleling Bus Speed Write Parameter is also known as Load Share Speed Droop Con- 3.x
Control Control trol Method
Mode Method 0: Constant
1: Droop
43819 PARST / Isolated Read/ Sets the voltage control method for isolated bus paralleling. PC 2.x, PC
Paralleling Bus Volt- Write 0: Constant 3.x
Control age Con-
Mode trol Method 1: Droop
43820 PARST / Maximum Read/ Multiplier: Unit: sec- Sets the maximum time that PC 3.x
PTC Tim- Parallel Ti- Write 0.1 onds the genset can remain paral-
ers me leled to the utility during
(TDMP) closed transition transfers.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 1800
16
Sign: U
43821 PARST / Pro- Read/ Multiplier: Unit: sec- Sets the time delay from PC 3.x
PTC Tim- grammed Write 0.1 onds when one source opens until
ers Transition the other closes during open
Delay transition transfers.
(TDPT) Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 60
16
Sign: U
43822 PARST / Retransfer Read/ Multiplier: Unit: sec- Sets the amount of time that PC 3.x
PTC Tim- Delay Write 0.1 onds the utility source must be
ers (TDEN) available before the control
will retransfer to that source.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 1800
16
Sign: U
43823 PARST / Synchro- Read/ Sets the speed control method for synchronizing. PC 3.x
Paralleling nizer Write 0: Phase Match
Control Speed
1: Slip Frequency
Mode Control
Method 2: External
164
Addr. Name Parameter Access Description Control
43824 PARST / Synchro- Read/ Sets the voltage control method for synchronizing. PC 3.x
Paralleling nizer Volt- Write 0: Voltage Match
Control age Con-
Mode trol Method 1: External
43825 PARST / Transfer Read/ Multiplier: Unit: sec- Sets the amount of time that PC 3.x
PTC Tim- Delay Write 0.1 onds the genset source must be
ers (TDNE) available before the control
will transfer to that source.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 120
16
Sign: U
43826 PARST / Transition Read/ Sets the load transfer transition type for use when Genset PC 3.x
PTC State Type Write Application Type = Power Transfer Control.
Machine 0: Open Transition
1: Hard Closed Transition
2: Soft Closed Transition
43827 PARST / Retransfer Read/ retransfer inhibit switch input status from Modbus PC 3.x
PTC Inhib- Inhibit Write 0: Inactive
its Switch
(Modbus) 1: Active
43828 PARST / Utility CB Read/ utility cb inhibit from Modbus PC 3.x
Circuit Inhibit Write 0: Inactive
Breaker Switch
(Modbus) 1: Active
43829 PARST / Utility Par- Read/ Sets the speed control method for utility paralleling. PC 3.x
Paralleling allel Speed Write 0: Load Govern
Control Control
Mode Method 1: Droop
43830 PARST / Utility Par- Read/ Sets the voltage control method for utility paralleling. PC 3.x
Paralleling allel Volt- Write 0: Load Govern
Control age Con- 1: Droop
Mode trol Method 2: Load Govern with Droop Feed Forward
43831 PCCNet / Aux101 Read/ Selects the genset reaction to a loss of a Device 0 I/O Mod- PC 2.x, PC
I/O Module Device 0 Write ule as critical (Shutdown) or non−critical (Warning). 3.x
0 Main PCCNet
Board Failure Re- 0: Critical Device Response
sponse 1: Non−Critical Device Response
Type
43832 PCCNet / Aux101 Read/ Selects the genset reaction to a loss of a Device 1 I/O Mod- PC 2.x, PC
I/O Module Device 1 Write ule as critical (Shutdown) or non−critical (Warning). 3.x
1 Main PCCNet
Board Failure Re- 0: Critical Device Response
sponse 1: Non−Critical Device Response
Type
43834 PCCNet / HMI113 Read/ Selects the genset reaction to a loss of an Annunciator as PC 2.x, PC
Universal Annuncia- Write critical or non−critical. Selecting Critical will cause a shut- 3.x
Annuncia- tor PCCNet down when the Annunciator looses communication.
tor Failure Re- 0: Critical Device Response
sponse
Type 1: Non−Critical Device Response
165
Addr. Name Parameter Access Description Control
43835 PCCNet / HMI1xx Read/ Selects the genset reaction to a loss of an HMI1xx Operator PC 2.x, PC
Operator PCCNet Write Panel as critical or non−critical. A critical response will shut- 3.x
Panel Failure Re- down the genset when PCCNet communication is lost.
sponse 0: Critical Device Response
Type 1: Non−Critical Device Response
43836 PCCNet / HMI220 Read/ Selects the genset reaction to a loss of an HMI220 Operator PC 2.x, PC
Operator PCCNet Write Panel as critical or non−critical.. A critical response will shut- 3.x
Panel Failure Re- down the genset when PCCNet communication is lost.
sponse 0: Critical Device Response
Type 1: Non−Critical Device Response
43837 PCCNet / HMI320 Read/ Selects the genset reaction to a loss of an HMI320 Operator PC 2.x, PC
Operator PCCNet Write Panel as critical or non−critical.. A critical response will shut- 3.x
Panel Failure Re- down the genset when PCCNet communication is lost.
sponse 0: Critical Device Response
Type 1: Non−Critical Device Response
43838 PCCNet / HMI4xx Read/ Selects the genset reaction to a loss of an HMI4xx Operator PC 2.x, PC
Operator PCCNet Write Panel as critical or non−critical.. A critical response will shut- 3.x
Panel Failure Re- down the genset when PCCNet communication is lost.
sponse 0: Critical Device Response
Type 1: Non−Critical Device Response
43839 PCCNet / PCCNet Read/ Multiplier: 1 Unit: sec- Selects the time allowed for PC 2.x, PC
Monitoring Device Write onds arbitration to occur before a 3.x
and Diag- Failure PCCNet failure fault is gen-
nostics Time erated.
Delay Offset: 0 Lower Limit: 0
Size (bits): 8 Upper Limit: 250
Sign: U
43840 PARST / Test With Read/ Use to choose whether a test is with load or without load. PC 3.x
PTC En- Load En- Write 0: Disabled
ables able 1: Enabled
43841 PARST / Transfer Read/ transfer inhibit switch input status from Modbus PC 3.x
PTC Inhib- Inhibit Write 0: Inactive
its Switch
(Modbus) 1: Active
43845 Modbus / Modbus Read/ Multiplier: 1 Unit: sec- Time delay before the con- PC 2.x, PC
Modbus Failure Write onds trol activates the Modus fail- 3.x
Time ure fault after the master is
Delay sensed as no longer pres-
ent.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43846 Modbus / Modbus Read/ When set to Reset Commands will reset the Modus control PC 2.x, PC
Modbus Commu- Write logics to an inactive state when Modbus communications 3.x
nications are lost
Lost Re- 0: Do Nothing
sponse
Method 1: Reset Commands
166
Addr. Name Parameter Access Description Control
43847 Modbus / Modbus Read/ Resets all Modus counters including J14 if applicable. PC 2.x, PC
Modbus Clear Write 0: Do Nothing 3.x
Counters 1: Clear Counters
43848 PARCTL / Controlled Read/ Multiplier: 1 Unit: sec- maximum ramp unload time PC 3.x
Load Gov- Shutdown Write onds during a shutdown with cool-
ern Max Ramp down
Unload Offset: 0 Lower Limit: 0
Time Size (bits): Upper Limit: 300
16
Sign: U
43849 PARCTL / Genset Read/ Multiplier: 1 Unit: kVAR Sets the genset load govern PC 3.x
Load Gov- kVAR Set- Write kVAR base load internal op-
ern point erating setpoint in units of
kVAR. Requires that Load
Govern kVAR Setpoint
Source = Internal and Load
Govern kVAR Method =
Genset kVAR.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 20000
16
Sign: S
43850 PARCTL / Genset Read/ Multiplier: Unit: % Sets the genset load govern PC 3.x
Load Gov- kVAR Set- Write 0.01 kVAR base load internal op-
ern point Per- erating setpoint in % of
cent standby kVA rating. Requires
that Load Govern kVAR Set-
point Source = Internal and
Load Govern kVAR Method
= Genset kVAR.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 60
16
Sign: S
43851 PARCTL / Genset kW Read/ Multiplier: 1 Unit: kW Sets the genset load govern PC 3.x
Load Gov- Setpoint Write kW base load internal oper-
ern ating setpoint in units of kW.
Requires that Load Govern
kW Setpoint Source = Inter-
nal and Load Govern kW
Method = Genset kW.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 20000
16
Sign: S
167
Addr. Name Parameter Access Description Control
43852 PARCTL / Genset kW Read/ Multiplier: Unit: % Sets the genset load govern PC 3.x
Load Gov- Setpoint Write 0.01 kW base load internal oper-
ern Percent ating setpoint in % of stand-
by rating. Requires that Load
Govern kW Setpoint Source
= Internal and Load Govern
kW Method = Genset kW.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 100
16
Sign: S
43853 PARCTL / Genset Read/ Multiplier: Unit: PF Sets the load govern set- PC 3.x
Load Gov- Power Write 0.01 point for genset power factor
ern Factor Set- control. Requires that Load
point Govern kVAR Setpoint
Source = Internal and Load
Govern kVAR Method =
Genset Power Factor.
Offset: 0 Lower Limit: 0.7
Size (bits): 8 Upper Limit: 1
Sign: S
43854 PARCTL / Load De- Read/ Modbus input for activating load demand stop on the genset PC 3.x
Load De- mand Stop Write 0: Inactive
mand (Modbus) 1: Active
43855 PARCTL / Load Gov- Read/ Use to select how genset kVAR output will be controlled PC 3.x
Load Gov- ern kVAR Write when paralleled to utility.
ern Method 0: Genset kVAR
1: Genset Power Factor
2: Utility kVAR
3: Utility Power Factor
43856 PARCTL / Load Gov- Read/ Multiplier: 1 Unit: sec- Sets load govern kVAR ramp PC 3.x
Load Gov- ern kVAR Write onds load rate = Genset Standby
ern Ramp kVA * 0.6/ this time.
Load Time Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 900
16
Sign: U
43857 PARCTL / Load Gov- Read/ Multiplier: 1 Unit: sec- Sets load govern kVAR ramp PC 3.x
Load Gov- ern kVAR Write onds unload rate = Genset Stand-
ern Ramp Un- by KVA * 0.6/ this time.
load Time Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 900
16
Sign: U
43859 PARCTL / Load Gov- Read/ Multiplier: 1 Unit: sec- Sets load govern kW ramp PC 3.x
Load Gov- ern kW Write onds load rate = Genset Standby
ern Ramp kW rating/ this time.
Load Time Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 900
16
Sign: U
168
Addr. Name Parameter Access Description Control
43860 PARCTL / Load Gov- Read/ Multiplier: 1 Unit: sec- Sets load govern kW ramp PC 3.x
Load Gov- ern kW Write onds unload rate = Genset Stand-
ern Ramp Un- by kW rating/ this time.
load Time Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 900
16
Sign: U
43861 PARCTL / Ramp Read/ use to control ramp load and unload via Modbus PC 3.x
Load Load/Un- Write 0: Load
Share load (Mod-
bus) 1: Unload
43862 PARCTL / Slip Fre- Read/ Multiplier: Unit: Hz Sets the synchronizer slip PC 3.x
Synchro- quency Write 0.001 frequency. Requires that
nizer Sync Speed Control Method
= Slip Frequency.
Offset: 0 Lower Limit: −3
Size (bits): Upper Limit: 3
16
Sign: S
43863 PARCTL / Utility Read/ Multiplier: 1 Unit: kVAR Sets the utility kVAR peak PC 3.x
Load Gov- kVAR Set- Write shave internal operating set-
ern point point in units of kVAR. Re-
quires that Load Govern
kVAR Setpoint Source = In-
ternal and Load Govern
kVAR Method = Utility kVAR
Offset: 0 Lower Limit: −20000
Size (bits): Upper Limit: 20000
16
Sign: S
43864 PARCTL / Utility Read/ Multiplier: Unit: % Sets the utility kVAR peak PC 3.x
Load Gov- kVAR Set- Write 0.01 shave internal operating set-
ern point Per- point in % of genset standby
cent kVA rating. Requires that
Load Govern kVAR Setpoint
Source = Internal and Load
Govern kVAR Method = Util-
ity kVAR.
Offset: 0 Lower Limit: −320
Size (bits): Upper Limit: 320
16
Sign: S
169
Addr. Name Parameter Access Description Control
43865 PARCTL / Utility kW Read/ Multiplier: 1 Unit: kW Sets the utility kW minimum PC 3.x
Load Gov- Constraint Write load level for constrained
ern base load mode of opera-
tion. Requires that Load
Govern kW Setpoint Source
= Internal and Load Govern
kW Method = Genset kW w/
Utility Constraint.
Offset: 0 Lower Limit: −20000
Size (bits): Upper Limit: 20000
16
Sign: S
43866 PARCTL / Utility kW Read/ Multiplier: Unit: % Sets utility kW minimum load PC 3.x
Load Gov- Constraint Write 0.01 level for constrained base
ern Percent load mode in % of genset
standby rating. Requires that
Load Govern kW Setpoint
Source = Internal and Load
Govern kW Method = Gen-
set kW w/Utility Constraint.
Offset: 0 Lower Limit: −320
Size (bits): Upper Limit: 320
16
Sign: S
43867 PARCTL / Utility kW Read/ Multiplier: 1 Unit: kW Sets the utility kW peak PC 3.x
Load Gov- Setpoint Write shave internal operating set-
ern point in units of kW. Re-
quires that Load Govern kW
Setpoint Source = Internal
and Load Govern kW Meth-
od = Utility kW.
Offset: 0 Lower Limit: −20000
Size (bits): Upper Limit: 20000
16
Sign: S
43868 PARCTL / Utility kW Read/ Multiplier: Unit: % Sets the utility kW peak PC 3.x
Load Gov- Setpoint Write 0.01 shave internal operating set-
ern Percent point in % of genset standby
rating. Requires that Load
Govern kW Setpoint Source
= Internal and Load Govern
kW Method = Utility kW.
Offset: 0 Lower Limit: −320
Size (bits): Upper Limit: 320
16
Sign: S
170
Addr. Name Parameter Access Description Control
43869 PARCTL / Utility Pow- Read/ Multiplier: Unit: PF Sets the internal setpoint for PC 3.x
Load Gov- er Factor Write 0.01 utility power factor control
ern Setpoint mode when paralleled to util-
ity. Requires that Load Gov-
ern kVAR Setpoint Source =
Internal and Load Govern
kVAR Method = Utility Power
Factor.
Offset: 0 Lower Limit: 0.7
Size (bits): 8 Upper Limit: 1
Sign: S
43870 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 2 Write entry of the fault/event code 3.x
0 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43871 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 4 Write entry of the fault/event code 3.x
0 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43872 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 5 Write entry of the fault/event code 3.x
0 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43873 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 6 Write entry of the fault/event code 3.x
0 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43874 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 7 Write entry of the fault/event code 3.x
0 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
171
Addr. Name Parameter Access Description Control
43875 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 1 Write entry of the fault/event code 3.x
1 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43876 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 2 Write entry of the fault/event code 3.x
1 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43877 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 3 Write entry of the fault/event code 3.x
1 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43878 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 4 Write entry of the fault/event code 3.x
1 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43879 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 5 Write entry of the fault/event code 3.x
1 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43880 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 6 Write entry of the fault/event code 3.x
1 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
172
Addr. Name Parameter Access Description Control
43881 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 7 Write entry of the fault/event code 3.x
1 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43882 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 8 Write entry of the fault/event code 3.x
1 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43883 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 10 Write entry of the fault/event code 3.x
0 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43884 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 11 Write entry of the fault/event code 3.x
0 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43885 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 12 Write entry of the fault/event code 3.x
0 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43886 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 13 Write entry of the fault/event code 3.x
0 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
173
Addr. Name Parameter Access Description Control
43887 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 14 Write entry of the fault/event code 3.x
0 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43888 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 15 Write entry of the fault/event code 3.x
0 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43889 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 16 Write entry of the fault/event code 3.x
0 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43890 PCCNet / Aux102 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 9 Write entry of the fault/event code 3.x
0 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43891 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 10 Write entry of the fault/event code 3.x
1 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43892 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 11 Write entry of the fault/event code 3.x
1 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
174
Addr. Name Parameter Access Description Control
43893 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 12 Write entry of the fault/event code 3.x
1 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43894 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 13 Write entry of the fault/event code 3.x
1 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43895 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 14 Write entry of the fault/event code 3.x
1 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43896 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 15 Write entry of the fault/event code 3.x
1 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43897 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 16 Write entry of the fault/event code 3.x
1 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43898 PCCNet / Aux102 1 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 9 Write entry of the fault/event code 3.x
1 Exp. Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
175
Addr. Name Parameter Access Description Control
43900 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
Universal Output 1 Write entry of the fault/event code 3.x
Annuncia- Fault/ which will turn the output
tor Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43901 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
Universal Output 2 Write entry of the fault/event code 3.x
Annuncia- Fault/ which will turn the output
tor Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43902 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
Universal Output 3 Write entry of the fault/event code 3.x
Annuncia- Fault/ which will turn the output
tor Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43903 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
Universal Output 4 Write entry of the fault/event code 3.x
Annuncia- Fault/ which will turn the output
tor Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43906 PARST / Speed Read/ speed droop enable switch input status from Modbus PC 2.x, PC
Paralleling
Droop En- Write 0: Inactive 3.x
Control able Switch
Mode (Modbus) 1: Active
43907 PARST / Voltage Read/ Voltage droop enable switch input status from Modbus PC 2.x, PC
Paralleling
Droop En- Write 0: Inactive 3.x
Control able Switch
Mode (Modbus) 1: Active
43908 PARST / Genset CB Read/ genset cb tripped from Modbus PC 3.x
Circuit Tripped Write 0: Inactive
Breaker Switch
(Modbus) 1: Active
43909 PARST / Utility CB Read/ utility cb tripped switch input from Modbus PC 3.x
Circuit Tripped Write 0: Inactive
Breaker Switch
(Modbus) 1: Active
43910 PC Tool / Save Trims Read/ The save trims command. PC 2.x, PC
Non−View- Write 0: Do Nothing 3.x
able 1: Save Trims
176
Addr. Name Parameter Access Description Control
43911 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 3 Write entry of the fault/event code 3.x
0 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43912 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 1 Write entry of the fault/event code 3.x
0 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65530
16
Sign: U
43913 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Parameter to allow for the PC 2.x, PC
I/O Module Output 8 Write entry of the fault/event code 3.x
0 Main Fault/ which will turn the output
Board Event relay on and off.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
43915 GC / Start/ Extended Read/ use to enable the extended paralleling mode of PTC PC 3.x
Stop Con- Parallel Write 0: Disabled
trol Enable 1: Enabled
43916 GC / Volt- V/Hz Knee Read/ Multiplier: Unit: Hz The voltage will roll off (de- PC 2.x, PC
age Set- Frequency Write 0.1 crease) proportionally to the 3.x
point 50Hz V/Hz setup once the fre-
quency drops below the set
point in the V/Hz Knee Fre-
quency. This allows the gen-
set to recover faster when
the frequency drops. This is
for 50Hz frequency.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
177
Addr. Name Parameter Access Description Control
43917 GC / Volt- V/Hz Knee Read/ Multiplier: Unit: Hz The voltage will roll off (de- PC 2.x, PC
age Set- Frequency Write 0.1 crease) proportionally to the 3.x
point 60Hz V/Hz setup once the fre-
quency drops below the set
point in the V/Hz Knee Fre-
quency. This allows the gen-
set to recover faster when
the frequency drops. This is
for 60Hz frequency.
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43918 GC / Volt- V/Hz Rol- Read/ Multiplier: Unit: % / Hz The amount of voltage roll PC 2.x, PC
age Set- loff Slope Write 0.1 off when the frequency is be- 3.x
point 50Hz low the knee frequency
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43919 GC / Volt- V/Hz Rol- Read/ Multiplier: Unit: % / Hz The amount of voltage roll PC 2.x, PC
age Set- loff Slope Write 0.1 off when the frequency is be- 3.x
point 60Hz low the knee frequency
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 10
16
Sign: U
43920 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43921 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43922 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43923 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
178
Addr. Name Parameter Access Description Control
43924 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43925 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43926 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43927 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43928 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43929 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43930 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43931 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
179
Addr. Name Parameter Access Description Control
43932 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43933 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43934 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43935 ACM / Ap- Genset Read/ Multiplier: 1 Unit: Name for the genset source. PC 2.x, PC
plication Source Write 3.x
Configura- Name Offset: 0 Lower Limit:
tion Size (bits): Upper Limit:
136
Sign: C
43936 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43937 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43938 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43939 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43940 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
180
Addr. Name Parameter Access Description Control
43941 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43942 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43943 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43944 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43945 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43946 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43947 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43948 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43949 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43950 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
181
Addr. Name Parameter Access Description Control
43951 ACM / Ap- Utility Read/ Multiplier: 1 Unit: Name for the Utility source PC 3.x
plication Source Write Offset: 0 Lower Limit:
Configura- Name Size (bits): Upper Limit:
tion 136
Sign: C
43952 GC / Speed/ Read/ Multiplier: Unit: sec- Sets the delay time for gen- PC 2.x, PC
Speed Frequency Write 0.1 onds erating the Speed/Frequen- 3.x
Reference Delay cy mismatch fault
Offset: 0 Lower Limit: 0.5
Size (bits): Upper Limit: 10
16
Sign: U
43953 GC / Speed/ Read/ Multiplier: Unit: Hz Sets the threshold for gener- PC 2.x, PC
Speed Frequency Write 0.1 ating the Speed/Frequency 3.x
Reference Threshold mismatch fault
Offset: 0 Lower Limit: 0.5
Size (bits): Upper Limit: 20
16
Sign: U
43954 PARCTL / Sync En- Read/ Modbus input for enabling the synchronizer PC 3.x
Synchro- able (Mod- Write 0: Inactive
nizer bus) 1: Active
43955 GC / Start/ Genset Idle Read/ Enables or Disable idling of genset with external governor. PC 2.x, PC
Stop Con- Enable Write 0: Disabled 3.x
trol 1: Enabled
43956 PARCTL / Permissive Read Multiplier: Unit: Hz frequency match error value PC 3.x
Synchro- Frequency Only 0.001 used by permissive sync
nizer Match Er- check
ror Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
43957 PARCTL / Permissive Read Multiplier: Unit: Hz frequency match error value PC 3.x
Synchro- Frequency Only 0.001 used by permissive sync
nizer Match Er- check
ror Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
43958 PARCTL / Sync En- Read indicates overall status of sync enable inputs PC 3.x
Synchro- able Com- Only 0: Inactive
nizer mand 1: Active
43959 PARCTL / Utility Un- Read/ Multiplier: 1 Unit: kW Sets threshold at which util- PC 3.x
Load Gov- loaded Write ity source is considered as
ern Level unloaded.
Offset: 0 Lower Limit: −32768
Size (bits): Upper Limit: 32767
16
Sign: S
182
Addr. Name Parameter Access Description Control
43960 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43961 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43962 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43963 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43964 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43965 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43966 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
183
Addr. Name Parameter Access Description Control
43967 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43968 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43969 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43970 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43971 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43972 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43973 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
184
Addr. Name Parameter Access Description Control
43974 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43975 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43976 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43977 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43978 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43979 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 1 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43980 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
185
Addr. Name Parameter Access Description Control
43981 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43982 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43983 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43984 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43985 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43986 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43987 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
186
Addr. Name Parameter Access Description Control
43988 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43989 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43990 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43991 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43992 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43993 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43994 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
187
Addr. Name Parameter Access Description Control
43995 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43996 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43997 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43998 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
43999 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 2 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
45999 CAN / CAN Unrecog- Read Indicates whether or not all pairs in current DM1 are recog- PC 2.x, PC
Datalink nized SPN/ Only nized 3.x
FMI Status 0: All Pairs Recognized
1: Pair Not Recognized
46000 ACM / Genset Read Genset phase rotation PC 2.x, PC
Phase Phase Only 0: L1−L2−L3 3.x
Rotation 1: L1−L3−L2
2: Not Available
46001 ACM / Utility Read Utility phase rotation PC 3.x
Phase Phase Only 0: L1−L2−L3
Rotation 1: L1−L3−L2
2: Not Available
46002 ACM / Genset Read Genset bus phase rotation PC 3.x
Phase Bus Phase Only 0: L1−L2−L3
Rotation 1: L1−L3−L2
2: Not Available
188
Addr. Name Parameter Access Description Control
46003 GC / Base Read Multiplier: Unit: rpm Provides a point to monitor PC 2.x, PC
Speed Speed Only 0.0625 the base speed 3.x
Reference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
46004 GC / Base Read Multiplier: Unit: rpm Provides a point to monitor PC 2.x, PC
Speed Speed Only 0.0625 the base speed 3.x
Reference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
46005 GC / Final Read Multiplier: Unit: rpm Provides a point to monitor PC 2.x, PC
Speed Speed Only 0.0625 the final speed reference 3.x
Reference Reference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
46006 GC / Final Read Multiplier: Unit: rpm Provides a point to monitor PC 2.x, PC
Speed Speed Only 0.0625 the final speed reference 3.x
Reference Reference Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
46008 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 1 Only 0.1 Port 1 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −459
ture Size (bits): Upper Limit: 3155
16
Sign: S
46009 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 2 Only 0.1 Port 2 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46010 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 3 Only 0.1 Port 3 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46011 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 4 Only 0.1 Port 4 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
189
Addr. Name Parameter Access Description Control
46012 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 5 Only 0.1 Port 5 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46013 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 6 Only 0.1 Port 6 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46014 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 7 Only 0.1 Port 7 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46015 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 8 Only 0.1 Port 8 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46016 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 9 Only 0.1 Port 9 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46017 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 10 Only 0.1 Port 10 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46018 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 11 Only 0.1 Port 11 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46019 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 12 Only 0.1 Port 12 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
190
Addr. Name Parameter Access Description Control
46020 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 13 Only 0.1 Port 13 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46021 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 14 Only 0.1 Port 14 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46022 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 15 Only 0.1 Port 15 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46023 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 16 Only 0.1 Port 16 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46024 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 17 Only 0.1 Port 17 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46025 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 18 Only 0.1 Port 18 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46026 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 19 Only 0.1 Port 19 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46027 CAN / Exhaust Read Multiplier: Unit: degF Monitor point for the Exhaust PC 2.x, PC
CAN Input Port 20 Only 0.1 Port 20 Temperature 3.x
Messages Tempera- Offset: 0 Lower Limit: −460
ture Size (bits): Upper Limit: 3155
16
Sign: S
46028 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 1 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 1 Size (bits): 8 Upper Limit:
Messages Sign: U
191
Addr. Name Parameter Access Description Control
46029 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 2 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 2 Size (bits): 8 Upper Limit:
Messages Sign: U
46030 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 3 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 3 Size (bits): 8 Upper Limit:
Messages Sign: U
46031 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 4 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 4 Size (bits): 8 Upper Limit:
Messages Sign: U
46032 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 5 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 5 Size (bits): 8 Upper Limit:
Messages Sign: U
46033 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 6 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 6 Size (bits): 8 Upper Limit:
Messages Sign: U
46034 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 7 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 7 Size (bits): 8 Upper Limit:
Messages Sign: U
46035 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 8 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 8 Size (bits): 8 Upper Limit:
Messages Sign: U
46036 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 9 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 9 Size (bits): 8 Upper Limit:
Messages Sign: U
46037 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 10 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 10 Size (bits): 8 Upper Limit:
Messages Sign: U
46038 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 11 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 11 Size (bits): 8 Upper Limit:
Messages Sign: U
46039 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 12 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 12 Size (bits): 8 Upper Limit:
Messages Sign: U
46040 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 13 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 13 Size (bits): 8 Upper Limit:
Messages Sign: U
192
Addr. Name Parameter Access Description Control
46041 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 14 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 14 Size (bits): 8 Upper Limit:
Messages Sign: U
46042 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 15 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 15 Size (bits): 8 Upper Limit:
Messages Sign: U
46043 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 16 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 16 Size (bits): 8 Upper Limit:
Messages Sign: U
46044 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 17 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 17 Size (bits): 8 Upper Limit:
Messages Sign: U
46045 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 18 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 18 Size (bits): 8 Upper Limit:
Messages Sign: U
46046 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 19 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 19 Size (bits): 8 Upper Limit:
Messages Sign: U
46047 CAN_LBN Knock Read Multiplier: 1 Unit: % Knock Level for cylinder 20 PC 3.x
G / CAN Level Cyl- Only Offset: 0 Lower Limit:
Gas Input inder 20 Size (bits): 8 Upper Limit:
Messages Sign: U
46048 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 1
Gas Input 1 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46049 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 2
Gas Input 2 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46050 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 3
Gas Input 3 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
193
Addr. Name Parameter Access Description Control
46051 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 4
Gas Input 4 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46052 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 5
Gas Input 5 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46053 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 6
Gas Input 6 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46054 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 7
Gas Input 7 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46055 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 8
Gas Input 8 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46056 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 9
Gas Input 9 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46057 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 10
Gas Input 10 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46058 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 11
Gas Input 11 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
194
Addr. Name Parameter Access Description Control
46059 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 12
Gas Input 12 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46060 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 13
Gas Input 13 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46061 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 14
Gas Input 14 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46062 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 15
Gas Input 15 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46063 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 16
Gas Input 16 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46064 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 17
Gas Input 17 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46065 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 18
Gas Input 18 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46066 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 19
Gas Input 19 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
195
Addr. Name Parameter Access Description Control
46067 CAN_LBN Knock Read Multiplier: 1 Unit: Knock count value for Cylin- PC 3.x
G / CAN Count Cyl Only der 20
Gas Input 20 Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65530
16
Sign: U
46068 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 1 Only 0.1 grees inder 1
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46069 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 2 Only 0.1 grees inder 2
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46070 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 3 Only 0.1 grees inder 3
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46071 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 4 Only 0.1 grees inder 4
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46072 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 5 Only 0.1 grees inder 5
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46073 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 6 Only 0.1 grees inder 6
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46074 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 7 Only 0.1 grees inder 7
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
196
Addr. Name Parameter Access Description Control
46075 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 8 Only 0.1 grees inder 8
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46076 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 9 Only 0.1 grees inder 9
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46077 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 10 Only 0.1 grees inder 10
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46078 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 11 Only 0.1 grees inder 11
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46079 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 12 Only 0.1 grees inder 12
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46080 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 13 Only 0.1 grees inder 13
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46081 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 14 Only 0.1 grees inder 14
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46082 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 15 Only 0.1 grees inder 15
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
197
Addr. Name Parameter Access Description Control
46083 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 16 Only 0.1 grees inder 16
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46084 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 17 Only 0.1 grees inder 17
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46085 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 18 Only 0.1 grees inder 18
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46086 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 19 Only 0.1 grees inder 19
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46087 CAN_LBN Spark Tim- Read Multiplier: Unit: De- Spark timing degrees for cyl- PC 3.x
G / CAN ing Cyl 20 Only 0.1 grees inder 20
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46088 CAN_LBN Internal Read Multiplier: Unit: degF Temperature of the engine PC 3.x
G / CAN SSM558 1 Only 0.1 electronic control unit
Gas Input Tempera- SSM558 1
Messages ture Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
46089 CAN_LBN Internal Read Multiplier: Unit: degF Temperature of the engine PC 3.x
G / CAN SSM558 2 Only 0.1 electronic control unit
Gas Input Tempera- SSM558 2
Messages ture Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
46090 CAN_LBN Internal Read Multiplier: Unit: degF Temperature of the engine PC 3.x
G / CAN MCM700 Only 0.1 electronic control unit
Gas Input Tempera- MCM700
Messages ture Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: S
198
Addr. Name Parameter Access Description Control
46091 CAN_LBN Derate Au- Read Derate authorization request from customer. PC 3.x
G / CAN thorization Only 0: NO
Gas Input 1: YES
Messages 2: Reserved
3: N/A
46092 CAN_LBN Start Sys- Read Start system status monitor point. PC 3.x
G / CAN tem Status Only 0: Not Tripped
Gas Input 1: Tripped
Messages 2: Reserved
3: N/A
46093 CAN_LBN Ventilator Read Vent Fan status monitor point. PC 3.x
G / CAN Fan Status Only 0: OFF
Gas Input 1: ON
Messages 2: TRIPPED
3: N/A
46094 CAN_LBN Louvres Read Louvres Closed monitor point. PC 3.x
G / CAN Status Only 0: Open
Gas Input 1: Closed
Messages 2: Reserved
3: N/A
46095 CAN_LBN Radiator Read Radiator Fan status monitor point. PC 3.x
G / CAN Fan Status Only 0: OFF
Gas Input 1: ON
Messages 2: TRIPPED
3: N/A
46096 CAN_LBN GIB Isola- Read GIB Isolator Open monitor point. PC 3.x
G / CAN tor Open Only 0: Close
Gas Input (Aux101) 1: Open
Messages 2: Reserved
3: N/A
46097 AD_LBNG Alternator Read Alternator Heater status monitor point. PC 3.x
/ LBNG Heater Sta- Only 0: OFF
Auxiliary tus 1: ON
Devices 2: TRIPPED
3: N/A
46099 CAN_LBN Gearbox Read Gearbox Oil Pressure monitor point. PC 3.x
G / CAN Oil Pres- Only 0: No
Gas Input sure
Messages (Aux101) 1: Yes
46100 CAN_LBN Gearbox Read Gearbox Oil Temperature monitor point. PC 3.x
G / CAN Oil Tem- Only 0: No
Gas Input perature
Messages (Aux101) 1: Yes
46101 CAN_LBN Start Inhib- Read Start Inhibit No1 monitor point. PC 3.x
G / CAN it No1 Only 0: Inactive
Gas Input (Aux101) 1: Active
Messages 2: Reserved
3: N/A
46102 CAN_LBN Start Inhib- Read Start Inhibit No2 monitor point. PC 3.x
G / CAN it No2 Only 0: Inactive
Gas Input (Aux101) 1: Active
Messages 2: Reserved
3: N/A
199
Addr. Name Parameter Access Description Control
46103 CAN_LBN Start Inhib- Read Start Inhibit No3 monitor point. PC 3.x
G / CAN it No3 Only 0: Inactive
Gas Input (Aux101) 1: Active
Messages 2: Reserved
3: N/A
46104 CAN_LBN DC PSU Read Engine PSU Not Available monitor point. PC 3.x
G / CAN Unavaila- Only 0: No
Gas Input ble
Messages (Aux101) 1: Yes
46105 CAN_LBN Ventilator Read Ventilator Fan Trip monitor point. PC 3.x
G / CAN Fan Trip Only 0: No
Gas Input (Aux101)
Messages 1: Yes
46106 CAN_LBN Aux101−3 Read Multiplier: Unit: Software version of the firm- PC 3.x
G / CAN Software Only 0.01 ware for the Aux101−3
Gas Input Version Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46107 CAN_LBN Aux101−4 Read Multiplier: Unit: Software version of the firm- PC 3.x
G/ Software Only 0.01 ware for the Aux101−4
Version Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46108 CAN_LBN Aux101−5 Read Multiplier: Unit: Software version of the firm- PC 3.x
G/ Software Only 0.01 ware for the Aux101−5
Version Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46109 CAN_LBN Engine Read Indicate current state or mode of operation by the engine PC 3.x
G / CAN Operating Only 0: Engine Stopped
Gas Input State 1: Pre−Start
Messages 2: Starting
3: Warm−Up
4: Running
5: Cool−Down
6: Engine Stopping
7: Post−Run
46110 CAN_LBN Fuel Pump Read Fuel pump state PC 3.x
G / CAN Control Only 0: Inactive
Gas Input Status
Messages 1: Active
46111 CAN_LBN Time Re- Read Multiplier: 1 Unit: sec- Indicate time remaining in PC 3.x
G / CAN maining in Only onds the current engine state
Gas Input Engine Offset: 0 Lower Limit:
Messages Operating Size (bits): Upper Limit:
State 16
Sign: U
200
Addr. Name Parameter Access Description Control
46112 CAN_LBN Fuel Shut- Read Fuel shutoff valve status PC 3.x
G / CAN off Vent Only 0: Closed
Gas Input Valve sta-
Messages tus 1: Open
46113 CAN_LBN Down- Read The result of the FSO driver output command logic for fuel PC 3.x
G / CAN stream Only shutoff valve 1
Gas Input Valve 0: Closed
Messages Command 1: Open
Status 2: Reserved
3: N/A
46114 CAN_LBN Upstream Read The result of the FSO driver output command logic for fuel PC 3.x
G / CAN Valve Only shutoff valve 2
Gas Input Command 0: Closed
Messages Status 1: Open
2: Reserved
3: N/A
46115 CAN_LBN VPS Status Read Control setting for fuel shutoff valve proving system test PC 3.x
G / CAN Only 0: Not Tested
Gas Input 1: Pass
Messages 2: Reserved
3: FAIL
46116 CAN_LBN Gas Sup- Read Multiplier: Unit: psi Gage Pressure of gas sup- PC 3.x
G / CAN ply Pres- Only 0.1 ply to fuel metering device.
Gas Input sure Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46117 CAN_LBN Engine Oil Read Engine Oil pre heater command status PC 3.x
G / CAN PreHeater Only 0: OFF
Gas Input Ctrl Status 1: ON
Messages 2: Reserved
3: N/A
46118 CAN_LBN Engine Read Control setting for cutting power to various devices when the PC 3.x
G / CAN Power Only engine is not in use
Gas Input Conserva- 0: OFF
Messages tion Ctrl
Status 1: ON
201
Addr. Name Parameter Access Description Control
46122 CAN_LBN Emergen- Read Active when the engine control request an emergency shut- PC 3.x
G / CAN cy Shut- Only down (immediate shutdown)
Gas Input down Re- 0: Inactive
Messages quest 1: Active
46123 CAN_LBN Engine Read Multiplier: Unit: Per- Derate request in percent PC 3.x
G / CAN Derate Re- Only 0.4 cent made by the engine control
Gas Input quest Offset: 0 Lower Limit:
Messages Size (bits): 8 Upper Limit:
Sign: U
46124 CAN / Coolant Read Multiplier: Unit: psi Monitor point for the Coolant PC 2.x, PC
CAN Input Pressure Only 0.1 Pressure. 3.x
Messages Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 145
16
Sign: U
46125 CAN_LBN Coolant 2 Read Multiplier: Unit: psi Monitor point for the Coolant PC 3.x
G / CAN Pressure Only 0.1 2 Pressure.
Gas Input Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 145
16
Sign: U
46127 CAN_LBN Coolant 2 Read Multiplier: Unit: degF Monitor point for the Coolant PC 3.x
G / CAN Tempera- Only 0.1 2 Temperature
Gas Input ture Offset: 0 Lower Limit: −40
Messages Size (bits): Upper Limit: 260
16
Sign: S
46128 CAN_LBN Compres- Read Multiplier: Unit: % Engine turbocharger com- PC 3.x
G / CAN sor Bypass Only 0.1 pressor bypass actuator
Gas Input Position position
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46129 CAN_LBN Engine Oil Read Multiplier: Unit: psi Engine oil pressure at the PC 3.x
G / CAN Filter Out- Only 0.1 outlet of the filter
Gas Input let Pres- Offset: 0 Lower Limit:
Messages sure Size (bits): Upper Limit:
16
Sign: U
46130 CAN_LBN Oil Priming Read Status for the priming pump (ON or OFF) PC 3.x
G / CAN Pump Con- Only 0: OFF
Gas Input trol Status 1: ON
Messages 2: Reserved
3: N/A
46131 CAN_LBN Oil Priming Read Status of the engine before start (Pre−Lubed or Not) PC 3.x
G / CAN State Only 0: Low
Gas Input 1: Optimum
Messages 2: Reserved
3: N/A
202
Addr. Name Parameter Access Description Control
46132 CAN_LBN Oil Pre− Read Status of the engine oil before start (Pre−Heated or Not) PC 3.x
G / CAN Heated Only 0: Heated
Gas Input State 1: Cold
Messages 2: Not Available
46133 CAN_LBN Coolant Read Status of the engine coolant before start (Pre−Heated or PC 3.x
G / CAN Pre− Only Not)
Gas Input Heated 0: Heated
Messages State 1: Cold
2: Not Available
46134 CAN_LBN Ventilation Read Engine Ventilation Status (Vented or Not) PC 3.x
G / CAN Status Only 0: Vented
Gas Input 1: Not Vented
Messages 2: Ventilation Delay
3: Currently Venting
4: Not Able To Determine
5: Not Available
46135 CAN_LBN Intake Read Multiplier: Unit: psi Intake Manifold Pressure 1 PC 3.x
G / CAN Manifold Only 0.1
Gas Input Pressure 1 Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46136 CAN_LBN Compres- Read Multiplier: Unit: kPa Absolute Pressure at the PC 3.x
G / CAN sor Outlet Only 0.1 outlet of the compressor.
Gas Input Pressure Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46137 CAN_LBN Turbochar- Read Multiplier: Unit: psi Monitor point for the Turbo- PC 3.x
G / CAN ger 1 Only 0.1 charger 1 Boost Pressure
Gas Input Boost Offset: 0 Lower Limit: 0
Messages Pressure Size (bits): Upper Limit: 1160
16
Sign: U
46138 CAN_LBN Genset Read Multiplier: Unit: Hz Average Genset AC frequen- PC 3.x
G / CAN Avg AC Only 0.1 cy
Gas Input Frequency Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46139 CAN_LBN Fuel Valve Read Multiplier: Unit: psi Absolute Pressure of Gas on PC 3.x
G / CAN 1 Inlet Ab- Only 0.1 the inlet side of the first sys-
Gas Input solute tem control valve
Messages Pressure Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
203
Addr. Name Parameter Access Description Control
46140 CAN_LBN Fuel Valve Read Multiplier: Unit: psi Absolute Pressure of Gas on PC 3.x
G / CAN 1 Outlet Only 0.1 the outlet side of the first
Gas Input Absolute system control valve
Messages Pressure Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46141 CAN_LBN Fuel Valve Read Multiplier: Unit: % PC 3.x
G / CAN 1 Position Only 0.1
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46142 CAN_LBN Fuel Valve Read Multiplier: Unit: psi Absolute Pressure of Gas on PC 3.x
G / CAN 2 Inlet Ab- Only 0.1 the inlet side of the second
Gas Input solute system control valve
Messages Pressure Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46143 CAN_LBN Fuel Valve Read Multiplier: Unit: psi Absolute Pressure of Gas on PC 3.x
G / CAN 2 Outlet Only 0.1 the outlet side of the second
Gas Input Absolute system control valve
Messages Pressure Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46144 CAN_LBN Fuel Valve Read Multiplier: Unit: % PC 3.x
G / CAN 2 Position Only 0.1
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46145 CAN_LBN Gas Mass Read Multiplier: Unit: Gas Mass Flow value of the PC 3.x
G / CAN Flow Only 0.1 Pounds per engine.
Gas Input hour
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
46146 CAN_LBN Gas Mass Read Multiplier: Unit: Gas Mass Flow value of the PC 3.x
G / CAN Flow Only 0.1 Pounds per engine.
Gas Input hour
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
204
Addr. Name Parameter Access Description Control
46147 CAN_LBN Throttle 1 Read Multiplier: Unit: % Position of the throttle 1. PC 3.x
G / CAN Position Only 0.1
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46148 CAN_LBN Throttle 2 Read Multiplier: Unit: % Position of the throttle 2. PC 3.x
G / CAN Position Only 0.1
Gas Input Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46149 CAN_LBN Raw Value Read Multiplier: 1 Unit: Count Raw Value for the DE RTD PC 3.x
G / CAN DE RTD Only Bearing from the Aux101
Gas Input Bearing Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46150 CAN_LBN Raw Value Read Multiplier: 1 Unit: Count Raw Value Alternator RTD PC 3.x
G / CAN Alternator Only L1 from Aux101 (10 bits raw
Gas Input RTD L1 data)
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46151 CAN_LBN Raw Value Read Multiplier: 1 Unit: Count Raw Value Alternator RTD PC 3.x
G / CAN Alternator Only L2 from Aux101 (10 bits raw
Gas Input RTD L2 data)
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46152 CAN_LBN Raw Value Read Multiplier: 1 Unit: Count Raw Value Alternator RTD PC 3.x
G / CAN Alternator Only L3 from Aux101 (10 bits raw
Gas Input RTD L3 data)
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46153 CAN_LBN Raw Value Read Multiplier: 1 Unit: Count Raw Value NDE RTD Bear- PC 3.x
G / CAN NDE RTD Only ing from Aux101 (10 bits raw
Gas Input Bearing data)
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46154 CAN_LBN LBNG Key- Read Driver command that controls the output for the keyswitch PC 3.x
G / CAN switch Only 0: Inactive
Gas Input Command
Messages 1: Active
205
Addr. Name Parameter Access Description Control
46155 CAN_LBN MCM700 Read Multiplier: Unit: Vdc Engine Control Module Bat- PC 3.x
G / CAN Battery Only 0.1 tery Voltage.
Gas Input Voltage Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65535
16
Sign: U
46156 CAN_LBN MCM700 Read Multiplier: Unit: Vdc Engine Control Module Iso- PC 3.x
G / CAN Isolated Only 0.1 lated Battery Voltage.
Gas Input Battery Offset: 0 Lower Limit:
Messages Voltage Size (bits): Upper Limit:
16
Sign: U
46157 CAN_LBN CM700 Read Multiplier: Unit: Vdc Engine Control Module PC 3.x
G / CAN Sensor Only 0.1 CM700 Sensor Voltage A
Gas Input Voltage A Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46158 CAN_LBN CM700 Read Multiplier: Unit: Vdc Engine Control Module PC 3.x
G / CAN Sensor Only 0.1 CM700 Sensor Voltage B
Gas Input Voltage B Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46159 CAN_LBN CM700 Read Multiplier: Unit: Vdc Engine Control Module PC 3.x
G / CAN Sensor Only 0.1 CM700 Sensor Voltage C
Gas Input Voltage C Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46160 CAN_LBN SSM558 1 Read Multiplier: Unit: Vdc SSM558 1 Engine Control PC 3.x
G / CAN Battery Only 0.1 Module Battery Voltage.
Gas Input Voltage Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65535
16
Sign: U
46161 CAN_LBN SSM558 1 Read Multiplier: Unit: Vdc SSM558 1 Engine Control PC 3.x
G / CAN Isolated Only 0.1 Module Isolated Battery Volt-
Gas Input Battery age.
Messages Voltage Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
46162 CAN_LBN SSM558 2 Read Multiplier: Unit: Vdc SSM558 2 Engine Control PC 3.x
G / CAN Battery Only 0.1 Module Battery Voltage.
Gas Input Voltage Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 65535
16
Sign: U
206
Addr. Name Parameter Access Description Control
46163 CAN_LBN SSM558 2 Read Multiplier: Unit: Vdc SSM558 2 Engine Control PC 3.x
G / CAN Isolated Only 0.1 Module Isolated Battery Volt-
Gas Input Battery age.
Messages Voltage Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
46164 CAN_LBN Intake Read Multiplier: Unit: psi Intake Manifold Pressure 2 PC 3.x
G / CAN Manifold Only 0.1
Gas Input Pressure 2 Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46165 CAN_LBN Intake Read Multiplier: Unit: degF Monitor point for the Intake PC 3.x
G / CAN Manifold Only 0.1 Manifold Temperature 2
Gas Input Tempera- Offset: 0 Lower Limit: −40
Messages ture 2 Size (bits): Upper Limit: 410
16
Sign: S
46166 CAN_LBN Exhaust Read Multiplier: Unit: psi Monitor point for exhaust PC 3.x
G / CAN Back Pres- Only 0.1 back pressure value
Gas Input sure Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: U
46168 CAN_LBN Air Filter Read Multiplier: Unit: psi Monitor point for air filter dif- PC 3.x
G / CAN Differential Only 0.1 ferential pressure value
Gas Input Pressure Offset: 0 Lower Limit:
Messages Size (bits): Upper Limit:
16
Sign: S
46170 CAN_LBN Gas Mass Read Multiplier: Unit: Gas Mass Flow 2 value of PC 3.x
G / CAN Flow 2 Only 0.1 Pounds per the engine.
Gas Input hour
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
46171 CAN_LBN Gas Mass Read Multiplier: Unit: Gas Mass Flow 2 value of PC 3.x
G / CAN Flow 2 Only 0.1 Pounds per the engine.
Gas Input hour
Messages Offset: 0 Lower Limit:
Size (bits): Upper Limit:
32
Sign: U
46272 CAN_LBN Engine Read Multiplier: Unit: degF Temperature of the engine PC 3.x
G / CAN ECM Inter- Only 0.1 electronic control unit
Gas Input nal Tem- Offset: 0 Lower Limit:
Messages perature Size (bits): Upper Limit:
16
Sign: S
207
Addr. Name Parameter Access Description Control
46175 AD_LBNG Gearbox Read Occurs when Gearbox Low Oil Pressure switch becomes PC 3.x
/ Gearbox Oil Pres- Only active.
sure Low 0: Inactive
1: Active
46176 AD_LBNG Gearbox Read/ Enables gearbox protection. PC 3.x
/ Gearbox Present Write 0: No
1: Yes
46180 AD_LBNG E−Stops Read Monitors the E−Stops switches. PC 3.x
/ Discrete disen- Only 0: Inactive
Inputs gaged 1: Active
46182 AD_LBNG Radiator Read Radiator fan control command PC 3.x
/ LBNG Fan control Only 0: Inactive
Auxiliary
Devices 1: Active
46183 AD_LBNG Ventilator Read/ Vent fan control mode limited or continuous PC 3.x
/ LBNG Fan mode Write 0: Limited
Auxiliary
Devices 1: Continuous
46288 CAN_LBN DE/NDE Read/ Gives reference point for engine cylinder numbering PC 3.x
G / CAN Cylinder Write 0: Drive End
Gas Input Viewpoint 1: Non−Drive End
Messages Reference 2: Reserved
3: N/A
46289 CAN_LBN Start Sys- Read Start system trip monitor point. PC 3.x
G / CAN tem Trip Only 0: Not Tripped
Gas Input (Aux 101) 1: Tripped
Messages 2: Reserved
3: N/A
46290 CAN_LBN Louvres Read Louvres Closed monitor point. PC 3.x
G / CAN Closed Only 0: Open
Gas Input (Aux 101) 1: Closed
Messages 2: Reserved
3: N/A
46291 CAN_LBN Radiator Read Radiator Fan Trip monitor point. PC 3.x
G / CAN Fan Trip Only 0: Not Tripped
Gas Input (Aux 101) 1: Tripped
Messages 2: Reserved
3: N/A
208
Addr. Name Parameter Access Description Control
46300 CAN_LBN LBNG Read/ Switch to enable or disable the gas specific features and pa- PC 3.x
G / Control- Genset En- Write rameters
ler Modes able 0: Disable
1: Enable
46301 CAN_LBN Aux101−3 Read/ Enable the processing for Aux101−3 messages PC 3.x
G / CAN Enable Write 0: Disable
Gas Input
Messages 1: Enable
46302 CAN_LBN Aux101−4 Read/ Enable the processing for Aux101−4 messages PC 3.x
G / CAN Enable Write 0: Disable
Gas Input
Messages 1: Enable
46303 CAN_LBN Aux101−5 Read/ Enable the processing for Aux101−5 messages PC 3.x
G / CAN Enable Write 0: Disable
Gas Input
Messages 1: Enable
46304 CAN_LBN Aux101−6 Read/ Enable the processing for Aux101−6 messages PC 3.x
G / CAN Enable Write 0: Disable
Gas Input
Messages 1: Enable
46308 CAN_LBN Aux101−3 Read/ Multiplier: 1 Unit: Input Port configuration bye PC 3.x
G / CAN Input Port Write for the Aux101−3
Gas Input Config Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 255
16
Sign: U
46309 CAN_LBN Aux101−4 Read/ Multiplier: 1 Unit: Input Port configuration bye PC 3.x
G / CAN Input Port Write for the Aux101−4
Gas Input Config Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 255
16
Sign: U
46310 CAN_LBN Aux101−5 Read/ Multiplier: 1 Unit: Input Port configuration bye PC 3.x
G / CAN Input Port Write for the Aux101−5
Gas Input Config
Messages
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 255
16
Sign: U
46311 CAN_LBN Aux101−3 Read/ Multiplier: 1 Unit: Digital Input Port configura- PC 3.x
G / CAN DI Active Write tion active High or active low
Gas Input High/Low for the Aux101−3
Messages Selection
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 255
16
Sign: U
46312 CAN_LBN Aux101−4 Read/ Multiplier: 1 Unit: Digital Input Port configura- PC 3.x
G / CAN DI Active Write tion active High or active low
Gas Input High/Low for the Aux101−4
Messages Selection
209
Addr. Name Parameter Access Description Control
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 255
16
Sign: U
46313 CAN_LBN Aux101−5 Read/ Multiplier: 1 Unit: Digital Input Port configura- PC 3.x
G / CAN DI Active Write tion active High or active low
Gas Input High/Low for the Aux101−5
Messages Selection
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 255
16
Sign: U
46314 CAN_LBN Aux101−3 Read/ Multiplier: 1 Unit: Discrete Input configuration PC 3.x
G / CAN DI Config Write bit mask for the Aux101−3
Gas Input Mask
Messages
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 255
16
Sign: U
46315 CAN_LBN Aux101−4 Read/ Multiplier: 1 Unit: Discrete Input configuration PC 3.x
G / CAN DI Config Write bit mask for the Aux101−4
Gas Input Mask
Messages
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 255
16
Sign: U
46316 CAN_LBN Aux101−5 Read/ Multiplier: 1 Unit: Discrete Input configuration PC 3.x
G / CAN DI Config Write bit mask for the Aux101−5
Gas Input Mask
Messages
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 255
16
Sign: U
46317 CAN_LBN Rated Oil Read/ Multiplier: Unit: degF Oil temperature threshold for PC 3.x
G / CAN Tempera- Write 0.015625 the engine to be able to run
Gas Input ture at rated speed
Messages Threshold
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 60
16
Sign: S
46318 CAN_LBN Alternator Read/ Multiplier: Unit: % Alternator efficiency PC 3.x
G / CAN Efficiency Write 0.0025
Gas Input Offset: 0 Lower Limit: 0
Messages Size (bits): Upper Limit: 1
16
Sign: U
210
Addr. Name Parameter Access Description Control
46323 CAN_LBN Vehicle Read/ A trim that enables the Vehicle Electrical Power 2 message PC 3.x
G / CAN Electrical Write
Gas Input Power 2 0: Disabled
Messages PGN65165
1: Enabled
Enable
46326 CAN_LBN Gaseous Read/ A trim that enables the Gaseous Fuel Pressure message PC 3.x
G / CAN Fuel Pres- Write
Gas Input sure 0: Disabled
Messages PGN65163 1: Enabled
Enable
46327 CAN_LBN Fuel Infor- Read/ A trim that enables the Fuel Information 3 − Gaseous mes- PC 3.x
G / CAN mation 3 − Write sage
Gas Input Gaseous 0: Disabled
Messages PGN64930
Enable 1: Enabled
46328 CAN_LBN Fuel Infor- Read/ A trim that enables the Fuel Information 2 − Gaseous mes- PC 3.x
G / CAN mation 2 − Write sage
Gas Input Gaseous 0: Disabled
Messages PGN65153
Enable 1: Enabled
46332 CAN_LBN Inlet/Ex- Read/ A trim that enables the Inlet/Exhaust Conditions message PC 3.x
G / CAN haust Con- Write
Gas Input ditions 0: Disabled
Messages PGN65270
1: Enabled
Enable
46333 CAN_LBN Knock Read/ A trim that enables Knock Count 1 message PC 3.x
G / CAN Count 1 Write 0: Disabled
Gas Input PGN65336
Messages Enable 1: Enabled
46334 CAN_LBN Knock Read/ A trim that enables Knock Count 2 message PC 3.x
G / CAN Count 2 Write 0: Disabled
Gas Input PGN65337
Messages Enable 1: Enabled
46335 CAN_LBN Knock Read/ A trim that enables Knock Count 3 message PC 3.x
G / CAN Count 3 Write 0: Disabled
Gas Input PGN65338
Messages Enable 1: Enabled
46336 CAN_LBN Knock Read/ A trim that enables Knock Count 4 message PC 3.x
G / CAN Count 4 Write 0: Disabled
Gas Input PGN65339
Messages Enable 1: Enabled
46337 CAN_LBN Knock Read/ A trim that enables Knock Count 5 message PC 3.x
G / CAN Count 5 Write 0: Disabled
Gas Input PGN65340
Messages Enable 1: Enabled
46338 CAN_LBN Ignition Read/ A trim that enables the Ignition Timing 1 message PC 3.x
G / CAN Timing 1 Write 0: Disabled
Gas Input PGN65154
Messages Enable 1: Enabled
211
Addr. Name Parameter Access Description Control
46339 CAN_LBN Ignition Read/ A trim that enables the Ignition Timing 2 message PC 3.x
G / CAN Timing 2 Write 0: Disabled
Gas Input PGN65155
Messages Enable 1: Enabled
46340 CAN_LBN Ignition Read/ A trim that enables the Ignition Timing 3 message PC 3.x
G / CAN Timing 3 Write 0: Disabled
Gas Input PGN65156
Messages Enable 1: Enabled
46341 CAN_LBN Ignition Read/ A trim that enables the Ignition Timing 4 message PC 3.x
G / CAN Timing 4 Write 0: Disabled
Gas Input PGN65157
Messages Enable 1: Enabled
46342 CAN_LBN Ignition Read/ A trim that enables the Ignition Timing 5 message PC 3.x
G / CAN Timing 5 Write 0: Disabled
Gas Input PGN65158
Messages Enable 1: Enabled
46346 CAN_LBN Cylinder Read/ Parameter to define on which end is the numbering of the PC 3.x
G / CAN Identifica- Write cylinder starting on the HMI (NDE or DE)
Gas Input tion Start- 0: Drive End
Messages ing Point 1: Non Drive End
2: N/A
46348 GC / Target Read Multiplier: Unit: rpm The speed reference func- PC 2.x, PC
Speed Speed Only 0.0625 tion desired speed before 3.x
Reference ramping
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4000
32
Sign: U
46349 GC / Target Read Multiplier: Unit: rpm The speed reference func- PC 2.x, PC
Speed Speed Only 0.0625 tion desired speed before 3.x
Reference ramping
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 4000
32
Sign: U
46367 Modbus / Modbus Read Multiplier: 1 Unit: The number of Modus mes- PC 3.x
Modbus Bus Mes- Only sages with no response for
sage J14 port only
Count Offset: 0 Lower Limit:
(J14) Size (bits): Upper Limit:
16
Sign: U
46366 Modbus / Modbus Read/ Sets the Modus number of stop bits for this node Limited to 1 PC 3.x
Modbus Stop Bits Write bit if parity = Odd or Even
(J14) 0: 01
1: 02
212
Addr. Name Parameter Access Description Control
46368 Modbus / Modbus Read Multiplier: 1 Unit: The number of Modus CRC PC 3.x
Modbus CRC Error Only errors for J14 only.
Count Offset: 0 Lower Limit:
(J14) Size (bits): Upper Limit:
16
Sign: U
46369 Modbus / Modbus Read Multiplier: 1 Unit: Modbus exception count for PC 3.x
Modbus Exception Only J14 only.
Count Offset: 0 Lower Limit:
(J14) Size (bits): Upper Limit:
16
Sign: U
46370 Modbus / Modbus Read Multiplier: 1 Unit: Modbus no response count PC 3.x
Modbus No Re- Only for J14 only.
sponse Offset: 0 Lower Limit:
Count Size (bits): Upper Limit:
(J14) 16
Sign: U
46371 Modbus / Modbus Read Multiplier: 1 Unit: The number of Modbus PC 3.x
Modbus Slave Only slave messages for J14 only.
Message Offset: 0 Lower Limit:
Count Size (bits): Upper Limit:
(J14) 16
Sign: U
46372 Modbus / Modbus Read/ Multiplier: 1 Unit: Sets the Modus address for PC 3.x
Modbus Node Ad- Write this node for J14 only.
dress Offset: 0 Lower Limit: 1
(J14) Size (bits): 8 Upper Limit: 247
Sign: U
46373 Modbus / Modbus Read/ Sets the baud rate for Modus communications for J14 only. PC 3.x
Modbus Baud Rate Write 1.66666666
(J14) 3.375
6.75
3: 19200
46374 Modbus / Modbus Read/ Sets the Modus parity for this node for J14 only. PC 3.x
Modbus Parity (J14) Write 0: Even
1: Odd
2: None
46376 Modbus / Modbus Read/ Sets the Modus baud rate. PC 2.x, PC
Modbus Baud Rate Write 0: 2400 Baud 3.x
1: 4800 Baud
2: 9600 Baud
3: 19200 Baud
4: 38400 Baud
46377 Modbus / Modbus Read/ Sets the Modus parity for this node PC 2.x, PC
Modbus Parity Write 0: Even 3.x
1: Odd
2: None
46378 Modbus / Modbus Read/ Multiplier: 1 Unit: Sets the Modus address for PC 2.x, PC
Modbus Node Ad- Write this node 3.x
dress Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 247
Sign: U
213
Addr. Name Parameter Access Description Control
46379 Modbus / Modbus Read/ Sets the Modus number of stop bits for this node Limited to 1 PC 2.x, PC
Modbus Stop Bits Write bit if parity = Odd or Even 3.x
0: 01
1: 02
46380 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46381 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46382 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46383 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46384 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46385 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
214
Addr. Name Parameter Access Description Control
46386 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46387 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46388 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46389 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46390 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46391 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46392 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
215
Addr. Name Parameter Access Description Control
46393 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46394 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46395 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46396 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46397 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46398 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46399 PCCNet / HMI113 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
Universal Fault 3 Write string to enter the configur- 3.x
Annuncia- Text able fault text for this fault.
tor Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
216
Addr. Name Parameter Access Description Control
46561 PCCNet / Operator Read Multiplier: 1 Unit: 16−bit number to represent PC 3.x
Operator Panel Sta- Only the status of operator panel
Panel tus indications.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
16
Sign: U
46600 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46601 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46602 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46603 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46604 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
217
Addr. Name Parameter Access Description Control
46605 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46606 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46607 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46608 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46609 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46610 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
218
Addr. Name Parameter Access Description Control
46611 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46612 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46613 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46614 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46615 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46616 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
219
Addr. Name Parameter Access Description Control
46617 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46618 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46619 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46620 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46621 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46622 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
220
Addr. Name Parameter Access Description Control
46623 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46624 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46625 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46626 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46627 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46628 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
221
Addr. Name Parameter Access Description Control
46629 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46630 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46631 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46632 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46633 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46634 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
222
Addr. Name Parameter Access Description Control
46635 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46636 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46637 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46638 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46639 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46640 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
223
Addr. Name Parameter Access Description Control
46641 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46642 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46643 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46644 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46645 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46646 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
224
Addr. Name Parameter Access Description Control
46647 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46648 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46649 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46650 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46651 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46652 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
225
Addr. Name Parameter Access Description Control
46653 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46654 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46655 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46656 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46657 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46658 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
226
Addr. Name Parameter Access Description Control
46659 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 1 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46660 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46661 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46662 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46663 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46664 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
227
Addr. Name Parameter Access Description Control
46665 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46666 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46667 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46668 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46669 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46670 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
228
Addr. Name Parameter Access Description Control
46671 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46672 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46673 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46674 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46675 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46676 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
229
Addr. Name Parameter Access Description Control
46677 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46678 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46679 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 2 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46800 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46801 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46802 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
230
Addr. Name Parameter Access Description Control
46803 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46804 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46805 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46806 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46807 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46808 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
231
Addr. Name Parameter Access Description Control
46809 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46810 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46811 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46812 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46813 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46814 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
232
Addr. Name Parameter Access Description Control
46815 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46816 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46817 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46818 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46819 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46820 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
233
Addr. Name Parameter Access Description Control
46821 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46822 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46823 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46824 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46825 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46826 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
234
Addr. Name Parameter Access Description Control
46827 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46828 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46829 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46830 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46831 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46832 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
235
Addr. Name Parameter Access Description Control
46833 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46834 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46835 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46836 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46837 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46838 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
236
Addr. Name Parameter Access Description Control
46839 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46840 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46841 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46842 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46843 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46844 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
237
Addr. Name Parameter Access Description Control
46845 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46846 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46847 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46848 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46849 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46850 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
238
Addr. Name Parameter Access Description Control
46851 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46852 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46853 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46854 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46855 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46856 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
239
Addr. Name Parameter Access Description Control
46857 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46858 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46859 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46860 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46861 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46862 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
240
Addr. Name Parameter Access Description Control
46863 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46864 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46865 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46866 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46867 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46868 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
241
Addr. Name Parameter Access Description Control
46869 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46870 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46871 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46872 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46873 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46874 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
242
Addr. Name Parameter Access Description Control
46875 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46876 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46877 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46878 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46879 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46880 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
243
Addr. Name Parameter Access Description Control
46881 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46882 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46883 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46884 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46885 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46886 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
244
Addr. Name Parameter Access Description Control
46887 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46888 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46889 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46890 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46891 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46892 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
245
Addr. Name Parameter Access Description Control
46893 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46894 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46895 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46896 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46897 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46898 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
246
Addr. Name Parameter Access Description Control
46899 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 3 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46900 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46901 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46902 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46903 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46904 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
247
Addr. Name Parameter Access Description Control
46905 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46906 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46907 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46908 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46909 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46910 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
248
Addr. Name Parameter Access Description Control
46911 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46912 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46913 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46914 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46915 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46916 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
249
Addr. Name Parameter Access Description Control
46917 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46918 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46919 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 4 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46920 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46921 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46922 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
250
Addr. Name Parameter Access Description Control
46923 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46924 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46925 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46926 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46927 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46928 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
251
Addr. Name Parameter Access Description Control
46929 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46930 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46931 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46932 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46933 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46934 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
252
Addr. Name Parameter Access Description Control
46935 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46936 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46937 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46938 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46939 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 5 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46940 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
253
Addr. Name Parameter Access Description Control
46941 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46942 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46943 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46944 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46945 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46946 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
254
Addr. Name Parameter Access Description Control
46947 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46948 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46949 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46950 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46951 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46952 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
255
Addr. Name Parameter Access Description Control
46953 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46954 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46955 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46956 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46957 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46958 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
256
Addr. Name Parameter Access Description Control
46959 PCCNet / Aux101 1 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 6 Write field to allow for the entry of 3.x
1 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46960 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46961 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46962 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46963 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46964 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
257
Addr. Name Parameter Access Description Control
46965 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46966 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46967 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46968 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46969 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46970 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
258
Addr. Name Parameter Access Description Control
46971 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46972 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46973 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46974 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46975 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46976 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
259
Addr. Name Parameter Access Description Control
46977 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46978 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46979 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 7 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46980 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46981 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46982 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
260
Addr. Name Parameter Access Description Control
46983 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46984 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46985 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46986 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46987 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46988 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
261
Addr. Name Parameter Access Description Control
46989 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46990 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46991 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46992 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46993 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46994 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
262
Addr. Name Parameter Access Description Control
46995 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46996 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46997 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46998 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
46999 PCCNet / Aux101 0 Read/ Multiplier: 1 Unit: Twenty (20) character text PC 2.x, PC
I/O Module Input 8 Write field to allow for the entry of 3.x
0 Main Fault Text the displayed configurable
Board fault text.
Offset: 0 Lower Limit:
Size (bits): Upper Limit:
168
Sign: C
47001 GC / Gov- Electronic Read/ Disable for mechanical governed genset. MODBUS Access: PC 2.x, PC
ernor Governor Write Ready Only 3.x
Enable 0: Disable
1: Enable
47002 GC / Gov- GK1 Read/ Multiplier: 1 Unit: The governor 60Hz K1 gain PC 2.x, PC
ernor (60Hz) Write adjust. MODBUS Access: 3.x
Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
263
Addr. Name Parameter Access Description Control
47003 GC / Gov- GK2 Read/ Multiplier: 1 Unit: The governor 60Hz integral PC 2.x, PC
ernor (60Hz) Write gain adjust. MODBUS Ac- 3.x
cess: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
47004 GC / Gov- GK3 Read/ Multiplier: 1 Unit: The governor 60Hz K3 gain PC 2.x, PC
ernor (60Hz) Write adjust. MODBUS Access: 3.x
Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 32768
16
Sign: U
47005 GC / Gov- Governor Read/ Multiplier: Unit: The governor 60Hz damping PC 2.x, PC
ernor Damping Write 1.52587890 adjust. MODBUS Access: 3.x
Effect 625E−05 Read Only
(60Hz) Offset: 0 Lower Limit: 0.6
Size (bits): Upper Limit: 0.95
16
Sign: U
47006 GC / Gov- GK1 Read/ Multiplier: 1 Unit: The governor 50Hz K1 gain PC 2.x, PC
ernor (50Hz) Write adjust. MODBUS Access: 3.x
Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
47007 GC / Gov- GK2 Read/ Multiplier: 1 Unit: The governor 50Hz integral PC 2.x, PC
ernor (50Hz) Write gain adjust. MODBUS Ac- 3.x
cess: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
47008 GC / Gov- GK3 Read/ Multiplier: 1 Unit: The governor 50Hz K3 gain PC 2.x, PC
ernor (50Hz) Write adjust. MODBUS Access: 3.x
Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 32768
16
Sign: U
47009 GC / Gov- Governor Read/ Multiplier: Unit: The governor 50Hz damping PC 2.x, PC
ernor Damping Write 1.52587890 adjust. MODBUS Access: 3.x
Effect 625E−05 Read Only
(50Hz) Offset: 0 Lower Limit: 0.6
Size (bits): Upper Limit: 0.95
16
Sign: U
264
Addr. Name Parameter Access Description Control
47010 GC / Gov- GK1 (Idle) Read/ Multiplier: 1 Unit: This trim is used to adjust PC 2.x, PC
ernor Write gk1 in idle mode. MODBUS 3.x
Access: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
47011 GC / Gov- GK2 (Idle) Read/ Multiplier: 1 Unit: This trim is used to adjust PC 2.x, PC
ernor Write gk2 in idle mode. MODBUS 3.x
Access: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
47012 GC / Gov- GK3 (Idle) Read/ Multiplier: 1 Unit: This trim is used to adjust PC 2.x, PC
ernor Write gk3 in idle mode. MODBUS 3.x
Access: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 32768
16
Sign: U
47013 GC / Gov- Gov Read/ Multiplier: Unit: The governor damping ad- PC 2.x, PC
ernor Damping Write 1.52587890 just for idle rating. MODBUS 3.x
Effect 625E−05 Access: Read Only
(Idle) Offset: 0 Lower Limit: 0.6
Size (bits): Upper Limit: 0.95
16
Sign: U
47014 GC / Gov- Gain Win- Read/ Either enables or disables Gain Windowing feature. MOD- PC 2.x, PC
ernor dowing En- Write BUS Access: Read Only 3.x
able 0: Disable
1: Enable
47015 GC / Gov- GK1 Low Read/ Multiplier: 1 Unit: The governor 50Hz K1 low PC 2.x, PC
ernor (50Hz) Write gain adjust. MODBUS Ac- 3.x
cess: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
47016 GC / Gov- GK1 Low Read/ Multiplier: 1 Unit: The governor 60Hz K1 low PC 2.x, PC
ernor (60Hz) Write gain adjust. MODBUS Ac- 3.x
cess: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
265
Addr. Name Parameter Access Description Control
47017 GC / Gov- GK1 High Read/ Multiplier: 1 Unit: The governor 50Hz K1 high PC 2.x, PC
ernor (50Hz) Write gain adjust. MODBUS Ac- 3.x
cess: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
47018 GC / Gov- GK1 High Read/ Multiplier: 1 Unit: The governor 60Hz K1 high PC 2.x, PC
ernor (60Hz) Write gain adjust. MODBUS Ac- 3.x
cess: Read Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 65535
16
Sign: U
47019 GC / Gov- Governor Read/ Multiplier: 1 Unit: The speed error higher limit. PC 2.x, PC
ernor Speed Write MODBUS Access: Read 3.x
Delta High Only
Offset: 0 Lower Limit: 50
Size (bits): Upper Limit: 1000
16
Sign: U
47020 GC / Gov- Governor Read/ Multiplier: 1 Unit: The speed error lower limit. PC 2.x, PC
ernor Speed Write MODBUS Access: Read 3.x
Delta Low Only
Offset: 0 Lower Limit: 50
Size (bits): Upper Limit: 1000
16
Sign: U
47021 ASI / Ana- Intake Read/ Either Onan or Cummins sensor. MODBUS Access: Read PC 2.x, PC
log Inputs/ Manifold Write Only 3.x
Outputs Tempera- 0: PGBU
ture Send-
er Type 1: EBU
47022 ASI / Ana- Intake Read/ Intake Manifold Temp Sensor available or not. MODBUS Ac- PC 2.x, PC
log Inputs/ Manifold Write cess: Read Only 3.x
Outputs Tempera- 0: Disable
ture Sen-
sor Enable 1: Enable
47023 ASI / Ana- Oil Tem- Read/ Either Onan or Cummins sensor. PC 2.x, PC
log Inputs/ perature Write 0: PGBU 3.x
Outputs Sender
Type 1: EBU
47024 ASI / Ana- Oil Tem- Read/ High Oil Temperature Sensor available or not. PC 2.x, PC
log Inputs/ perature Write 0: Disable 3.x
Outputs Sensor En-
able 1: Enable
266
Addr. Name Parameter Access Description Control
47025 GC / Auto- AVR PWM Read Multiplier: Unit: % The AVR PWM software PC 2.x, PC
matic Volt- Command Only 0.01 command. Linear relation- 3.x
age Regu- ship between counts and %
lator duty cycle with 10000
counts=100% duty cycle.
MODBUS Access: Read
Only
Offset: 0 Lower Limit: 0
Size (bits): Upper Limit: 100
16
Sign: U
267
THIS PAGE LEFT INTENTIONALLY BLANK
268
3. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps
Note: If an address or bit is not listed in this table it is not used.
Addr. Bit # Name Fault Event Name Response Control
Code
40400 0 Fault Status Bit- 115 Engine Magnetic Crankshaft Speed/ Shutdown PC 2.x, PC
map 1 Position 3.x
40400 1 Fault Status Bit- 122 Intake Manifold 1 Pressure: Vtg Above Warning PC 2.x, PC
map 1 Normal 3.x
40400 2 Fault Status Bit- 123 Intake Manifold 1 Pressure: Vtg Below Warning PC 2.x, PC
map 1 Normal 3.x
40400 3 Fault Status Bit- 124 Intake Manifold 1 Pressure: Moderate- Warning PC 2.x, PC
map 1 ly Severe 3.x
40400 4 Fault Status Bit- 135 Engine Oil Rifle Pressure 1: Vtg Above Warning PC 2.x, PC
map 1 Normal 3.x
40400 5 Fault Status Bit- 141 Engine Oil Rifle Pressure 1: Vtg Below Warning PC 2.x, PC
map 1 Normal 3.x
40400 6 Fault Status Bit- 143 Engine Oil Rifle Pressure −Moderately Warning PC 2.x, PC
map 1 Severe 3.x
40400 7 Fault Status Bit- 144 Engine Coolant Temp 1: Vtg Above Warning PC 2.x, PC
map 1 Normal 3.x
40400 8 Fault Status Bit- 145 Engine Coolant Temp 1: Vtg Below Warning PC 2.x, PC
map 1 Normal 3.x
40400 9 Fault Status Bit- 146 Engine Coolant Temp: Moderately Derate PC 2.x, PC
map 1 Above Normal 3.x
40400 10 Fault Status Bit- 151 Engine Coolant Temp: Severely Above Shutdown PC 2.x, PC
map 1 Normal 3.x
40400 11 Fault Status Bit- 153 Intake Manifold 1 Temp: Vtg Above Warning PC 2.x, PC
map 1 Normal 3.x
40400 12 Fault Status Bit- 154 Intake Manifold 1 Temp: Vtg Below Warning PC 2.x, PC
map 1 Normal 3.x
40400 13 Fault Status Bit- 155 Intake Manifold 1 Temp: Severely Shutdown PC 2.x, PC
map 1 Above Normal 3.x
40400 14 Fault Status Bit- 187 Sensor Supply 2: Vtg Below Normal Warning PC 2.x, PC
map 1 3.x
40400 15 Fault Status Bit- 195 Coolant Level Sensor 1: Vtg Above Warning PC 2.x, PC
map 1 Normal 3.x
40401 0 Fault Status Bit- 196 Coolant Level Sensor 1: Vtg Below Warning PC 2.x, PC
map 2 Normal 3.x
40401 1 Fault Status Bit- 197 Coolant Level: Below Normal − Moder- Warning PC 2.x, PC
map 2 ately Severe 3.x
40401 2 Fault Status Bit- 212 Engine Oil Temp Sensor 1: Vtg Above Warning PC 2.x, PC
map 2 Normal 3.x
40401 3 Fault Status Bit- 213 Engine Oil Temp Sensor 1: Vtg below Warning PC 2.x, PC
map 2 Normal 3.x
40401 4 Fault Status Bit- 214 Engine Oil Temp: Above Normal − Shutdown PC 2.x, PC
map 2 Most severe 3.x
40401 5 Fault Status Bit- 221 Barometric Pressure: Vtg Above Nor- Warning PC 2.x, PC
map 2 mal 3.x
40401 6 Fault Status Bit- 222 Barometric Pressure Sensor: Vtg Be- Warning PC 2.x, PC
map 2 low Normal 3.x
40401 7 Fault Status Bit- 223 Eng Oil Burn Valve Solenoid: Vtg Be- Warning PC 2.x, PC
map 2 low Normal 3.x
269
Addr. Bit # Name Fault Event Name Response Control
Code
40401 8 Fault Status Bit- 224 Engine Oil Burn Valve Solenoid: Vtg Warning PC 2.x, PC
map 2 Above Normal 3.x
40401 9 Fault Status Bit- 227 Sensor Supply 2: Vtg Above Normal Warning PC 2.x, PC
map 2 3.x
40401 10 Fault Status Bit- 228 Coolant Pressure: Below Normal− Shutdown PC 2.x, PC
map 2 Most Severe 3.x
40401 11 Fault Status Bit- 231 Coolant Pressure Sensor: Vtg Above Warning PC 2.x, PC
map 2 Normal 3.x
40401 12 Fault Status Bit- 232 Coolant Pressure Sensor: Vtg Below Warning PC 2.x, PC
map 2 Normal 3.x
40401 13 Fault Status Bit- 234 Engine Crankshaft Speed/Posn: Shutdown PC 2.x, PC
map 2 Above Normal 3.x
40401 14 Fault Status Bit- 235 Coolant Level: Below Normal−Most Shutdown PC 2.x, PC
map 2 Severe 3.x
40401 15 Fault Status Bit- 238 Sensor Supply 3: Vtg Below Normal Warning PC 2.x, PC
map 2 3.x
40402 0 Fault Status Bit- 239 Voltage Supply C High Error Warning PC 2.x, PC
map 3 3.x
40402 1 Fault Status Bit- 245 Radiator Fan Control Driver Low Error Warning PC 2.x, PC
map 3 3.x
40402 2 Fault Status Bit- 261 Engine Fuel Temp: Above Normal− Warning PC 2.x, PC
map 3 Moderately Severe 3.x
40402 3 Fault Status Bit- 263 Engine Fuel Temp Sensor 1: Vtg Warning PC 2.x, PC
map 3 Above Normal 3.x
40402 4 Fault Status Bit- 265 Engine Fuel Temp Sensor 1: Vtg Be- Warning PC 2.x, PC
map 3 low Normal 3.x
40402 5 Fault Status Bit- 266 Engine Fuel Temp: Above Normal− Shutdown PC 2.x, PC
map 3 Most severe 3.x
40402 6 Fault Status Bit- 271 Fuel Pump Pressurizing Assembly 1: Warning PC 2.x, PC
map 3 Vtg Below Normal 3.x
40402 7 Fault Status Bit- 272 Fuel Pump Pressurizing Assembly 1: Warning PC 2.x, PC
map 3 Vtg Above Normal 3.x
40402 8 Fault Status Bit- 281 APC_DIESEL_CYL_PRS_IMBAL_ER- Warning PC 2.x, PC
map 3 ROR 3.x
40402 9 Fault Status Bit- 285 SAE J1939 Muxing PGN Timeout: Ab- Warning PC 2.x, PC
map 3 normal Update Rate 3.x
40402 10 Fault Status Bit- 286 SAE J1939 Muxing Config: Out of Cal- Warning PC 2.x, PC
map 3 ibration 3.x
40402 13 Fault Status Bit- 295 AMBIENT_AIR_PRESS_KEYON_ER- Warning PC 2.x, PC
map 3 ROR 3.x
40402 14 Fault Status Bit- 319 RTC PWR Intr: Data Erratic Intermit- Warning PC 2.x, PC
map 3 tent or Wrong 3.x
40402 15 Fault Status Bit- 322 Injector Solenoid Driver Cylinder 1: Warning PC 2.x, PC
map 3 UnderCurrent 3.x
40403 0 Fault Status Bit- 323 Injector Solenoid Driver Cylinder 5: Warning PC 2.x, PC
map 4 UnderCurrent 3.x
40403 1 Fault Status Bit- 324 Injector Solenoid Driver Cylinder 3: Warning PC 2.x, PC
map 4 UnderCurrent 3.x
40403 2 Fault Status Bit- 325 Injector Solenoid Driver Cylinder 6: Warning PC 2.x, PC
map 4 UnderCurrent 3.x
270
Addr. Bit # Name Fault Event Name Response Control
Code
40403 3 Fault Status Bit- 331 Injector Solenoid Driver Cylinder 2: Warning PC 2.x, PC
map 4 UnderCurrent 3.x
40403 4 Fault Status Bit- 332 Injector Solenoid Driver Cylinder 4: Warning PC 2.x, PC
map 4 UnderCurrent 3.x
40403 6 Fault Status Bit- 342 Electronic Calibration Code: Out of Shutdown PC 2.x, PC
map 4 Calibration 3.x
40403 7 Fault Status Bit- 343 Eng Ctrl: internal h/w failure−Bad De- Warning PC 2.x, PC
map 4 vice/Component 3.x
40403 8 Fault Status Bit- 351 Injector Power Supply: Bad Device/ Warning PC 2.x, PC
map 4 Component 3.x
40403 9 Fault Status Bit- 352 Sensor Supply 1: Vtg Below Normal Warning PC 2.x, PC
map 4 3.x
40403 10 Fault Status Bit- 359 Fail To Start Fault Shutdown PC 2.x, PC
map 4 3.x
40403 11 Fault Status Bit- 386 Sensor Supply 1: Vtg Above Normal Warning PC 2.x, PC
map 4 3.x
40403 12 Fault Status Bit- 415 Eng Oil Rifle Pressure: Below Normal− Shutdown PC 2.x, PC
map 4 Most Severe 3.x
40403 13 Fault Status Bit- 418 Water in Fuel Indicator: Above Nor- Warning PC 2.x, PC
map 4 mal−Least Severe 3.x
40403 14 Fault Status Bit- 421 Eng Oil Temp: Above Normal−Moder- Warning PC 2.x, PC
map 4 ately Severe 3.x
40403 15 Fault Status Bit- 422 COOLANT_LEVEL_READING_IN- Warning PC 2.x, PC
map 4 CORRECT 3.x
40404 0 Fault Status Bit- 425 OIL_TEMPERA- Warning PC 2.x, PC
map 5 TURE_IN_RANGE_ERROR 3.x
40404 1 Fault Status Bit- 426 J1939 Datalink: Data Erratic/Intermit- NONE PC 2.x, PC
map 5 tent/Wrong 3.x
40404 2 Fault Status Bit- 427 CAN Datalink Degraded Warning PC 2.x, PC
map 5 3.x
40404 3 Fault Status Bit- 435 OIL_PRESSURE_SWITCH_ERROR Warning PC 2.x, PC
map 5 3.x
40404 4 Fault Status Bit- 441 Low Battery Voltage Warning PC 2.x, PC
map 5 3.x
40404 5 Fault Status Bit- 442 High Battery Voltage Warning PC 2.x, PC
map 5 3.x
40404 6 Fault Status Bit- 449 Injector Metering Rail 1 Pressure: Shutdown PC 2.x, PC
map 5 Above Normal 3.x
40404 7 Fault Status Bit- 451 Injector Metering Rail 1 Pressure: Vtg Warning PC 2.x, PC
map 5 Above Normal 3.x
40404 8 Fault Status Bit- 452 Injector Metering Rail 1 Pressure: Vtg Warning PC 2.x, PC
map 5 Below Normal 3.x
40404 9 Fault Status Bit- 488 Intake Manifold 1 Temp: Above Nor- Derate PC 2.x, PC
map 5 mal−Moderate 3.x
40404 10 Fault Status Bit- 546 Fuel Delivery Pressure: Vtg Above Warning PC 2.x, PC
map 5 Normal 3.x
40404 11 Fault Status Bit- 547 Fuel Delivery Pressure: Vtg Below Warning PC 2.x, PC
map 5 Normal 3.x
40404 12 Fault Status Bit- 553 APC_DIESEL_HIGH_PRS_ERROR Warning PC 2.x, PC
map 5 3.x
271
Addr. Bit # Name Fault Event Name Response Control
Code
40404 13 Fault Status Bit- 554 APC_DIESEL_PRS_SIR_ERROR Warning PC 2.x, PC
map 5 3.x
40404 14 Fault Status Bit- 556 Crankcase Pressure: Above Normal− Shutdown PC 2.x, PC
map 5 Most Severe 3.x
40404 15 Fault Status Bit- 559 Injector Metering Rail 1 Pressure: Be- Warning PC 2.x, PC
map 5 low Normal 3.x
40405 1 Fault Status Bit- 611 Engine Shut Down Hot Condition Ex- Warning PC 2.x, PC
map 6 ists 3.x
40405 3 Fault Status Bit- 689 Eng Crankshaft Speed/Pos Warning Warning PC 2.x, PC
map 6 3.x
40405 4 Fault Status Bit- 731 Eng Speed: Cam/Crankshaft Misalign- Warning PC 2.x, PC
map 6 ment 3.x
40405 7 Fault Status Bit- 1117 Power Lost With Ignition On Warning PC 2.x, PC
map 6 3.x
40405 8 Fault Status Bit- 1122 Rated to Idle Transition NONE PC 2.x, PC
map 6 3.x
40405 9 Fault Status Bit- 1124 Delayed Shutdown Fault Warning PC 2.x, PC
map 6 3.x
40405 10 Fault Status Bit- 1131 Battle Short Mode Active Warning PC 2.x, PC
map 6 3.x
40405 11 Fault Status Bit- 1132 Controlled Shutdown In Process Warning PC 3.x
map 6
40405 13 Fault Status Bit- 1243 Engine Derate Derate PC 2.x, PC
map 6 3.x
40405 14 Fault Status Bit- 1244 Engine Normal Shutdown Shutdown PC 2.x, PC
map 6 w/Cool- 3.x
down
40405 15 Fault Status Bit- 1245 Engine Shutdown Shutdown PC 2.x, PC
map 6 3.x
40406 0 Fault Status Bit- 1246 Unrecognized Engine Fault Warning PC 2.x, PC
map 7 3.x
40406 1 Fault Status Bit- 1247 Engine Shutdown _ Unannounced Shutdown PC 2.x, PC
map 7 3.x
40406 2 Fault Status Bit- 1248 Engine Warning Warning PC 3.x
map 7
40406 3 Fault Status Bit- 1256 Ctrl Module ID Input State Warning Er- Warning PC 2.x, PC
map 7 ror 3.x
40406 4 Fault Status Bit- 1257 Ctrl Module ID I/P State shutdown Er- Shutdown PC 2.x, PC
map 7 ror 3.x
40406 5 Fault Status Bit- 1322 kW Load Setpoint OOR High Warning PC 3.x
map 7
40406 6 Fault Status Bit- 1323 kW Load Setpoint OOR Low Warning PC 3.x
map 7
40406 7 Fault Status Bit- 1324 kVAR Load Setpoint OOR High Warning PC 3.x
map 7
40406 8 Fault Status Bit- 1325 kVAR Load Setpoint OOR Low Warning PC 3.x
map 7
40406 9 Fault Status Bit- 1336 Cooldown Completed Fault Shutdown PC 2.x, PC
map 7 3.x
272
Addr. Bit # Name Fault Event Name Response Control
Code
40406 10 Fault Status Bit- 1357 Eng Oil Lvl Remote Reservoir: Below Warning PC 2.x, PC
map 7 Normal 3.x
40407 0 Fault Status Bit- 1376 Eng Camshaft Speed/Pos Warning Warning PC 2.x, PC
map 8 3.x
40407 1 Fault Status Bit- 3611 Custom Overcurrent Fault Warning PC 3.x
map 8
40407 2 Fault Status Bit- 3513 Negative Sequence Overcurrent Warning PC 3.x
map 8
40407 3 Fault Status Bit- 1416 Fail to Shutdown Warning PC 2.x, PC
map 8 3.x
40407 4 Fault Status Bit- 1417 Power Down Failure Warning PC 2.x, PC
map 8 3.x
40407 5 Fault Status Bit- 1433 Local E−Stop Shutdown PC 2.x, PC
map 8 3.x
40407 6 Fault Status Bit- 1434 Remote E−Stop Shutdown PC 2.x, PC
map 8 3.x
40407 7 Fault Status Bit- 1435 Low Coolant Temperature Warning PC 2.x, PC
map 8 3.x
40407 8 Fault Status Bit- 1438 Fail To Crank Fault Shutdown PC 2.x, PC
map 8 3.x
40407 9 Fault Status Bit- 1439 Low Fuel in Day Tank Warning PC 2.x, PC
map 8 3.x
40407 10 Fault Status Bit- 1441 Low Fuel Level Warning PC 2.x, PC
map 8 3.x
40407 11 Fault Status Bit- 1442 Weak Battery Warning PC 2.x, PC
map 8 3.x
40407 12 Fault Status Bit- 1443 Dead Battery Shutdown PC 2.x, PC
map 8 3.x
40407 13 Fault Status Bit- 1444 Overload Warning PC 2.x, PC
map 8 3.x
40407 14 Fault Status Bit- 1445 Short Circuit Shutdown PC 2.x, PC
map 8 3.x
40407 15 Fault Status Bit- 1446 High AC Voltage Shutdown PC 2.x, PC
map 8 3.x
40408 0 Fault Status Bit- 1447 Low AC Voltage Shutdown PC 2.x, PC
map 9 3.x
40408 1 Fault Status Bit- 1448 Underfrequency Shutdown PC 2.x, PC
map 9 3.x
40408 2 Fault Status Bit- 1449 Overfrequency Warning PC 2.x, PC
map 9 3.x
40408 3 Fault Status Bit- 1459 Reverse kW Shutdown PC 2.x, PC
map 9 3.x
40408 4 Fault Status Bit- 1461 Loss of Field Shutdown PC 2.x, PC
map 9 3.x
40408 5 Fault Status Bit- 1463 Not In Auto NONE PC 2.x, PC
map 9 3.x
40408 6 Fault Status Bit- 1464 Load Dump Warning PC 2.x, PC
map 9 3.x
40408 7 Fault Status Bit- 1465 Ready To Load NONE PC 2.x, PC
map 9 3.x
273
Addr. Bit # Name Fault Event Name Response Control
Code
40408 8 Fault Status Bit- 1469 Speed/Frequency Mismatch Fault Warning PC 2.x, PC
map 9 3.x
40408 9 Fault Status Bit- 1471 High Current Warning Warning PC 2.x, PC
map 9 3.x
40408 10 Fault Status Bit- 1472 Overcurrent Shutdown Shutdown PC 2.x, PC
map 9 3.x
40408 11 Fault Status Bit- 1483 Common Alarm None PC 2.x, PC
map 9 3.x
40408 12 Fault Status Bit- 1548 Injector Solenoid Driver Cylinder 7: Warning PC 2.x, PC
map 9 UnderCurrent 3.x
40408 13 Fault Status Bit- 1549 Injector Solenoid Driver Cylinder 8: Warning PC 2.x, PC
map 9 UnderCurrent 3.x
40408 14 Fault Status Bit- 1551 Injector Solenoid Driver Cylinder 10: Warning PC 2.x, PC
map 9 UnderCurrent 3.x
40408 15 Fault Status Bit- 1552 Injector Solenoid Driver Cylinder 11: Warning PC 2.x, PC
map 9 UnderCurrent 3.x
40409 0 Fault Status Bit- 1553 Injector Solenoid Driver Cylinder 12: Warning PC 2.x, PC
map 10 UnderCurrent 3.x
40409 1 Fault Status Bit- 1554 Injector Solenoid Driver Cylinder 13: Warning PC 2.x, PC
map 10 UnderCurrent 3.x
40409 2 Fault Status Bit- 1555 Injector Solenoid Driver Cylinder 14: Warning PC 2.x, PC
map 10 UnderCurrent 3.x
40409 3 Fault Status Bit- 1556 Injector Solenoid Driver Cylinder 15: Warning PC 2.x, PC
map 10 UnderCurrent 3.x
40409 4 Fault Status Bit- 1557 Injector Solenoid Driver Cylinder 16: Warning PC 2.x, PC
map 10 UnderCurrent 3.x
40409 7 Fault Status Bit- 1622 Injector Solenoid Driver Cylinder 9: Warning PC 2.x, PC
map 10 UnderCurrent 3.x
40409 8 Fault Status Bit- 1689 Real Time Clock Power Interrupt Fault Warning PC 2.x, PC
map 10 3.x
40409 9 Fault Status Bit- 1695 SENSOR_SUPPLY_5_VOLT- Warning PC 2.x, PC
map 10 AGE_HIGH_ERROR 3.x
40409 10 Fault Status Bit- 1696 SENSOR_SUPPLY_5_VOLT- Warning PC 2.x, PC
map 10 AGE_LOW_ERROR 3.x
40409 11 Fault Status Bit- 1843 Crankcase Pressure: Vtg Above Nor- Warning PC 2.x, PC
map 10 mal 3.x
40409 12 Fault Status Bit- 1844 Crankcase Pressure: Vtg Below Nor- Warning PC 2.x, PC
map 10 mal 3.x
40409 13 Fault Status Bit- 1845 Water in Fuel Indicator: Vtg Above Warning PC 2.x, PC
map 10 Normal 3.x
40409 14 Fault Status Bit- 1846 Water in Fuel Indicator: Vtg Below Warning PC 2.x, PC
map 10 Normal 3.x
40409 15 Fault Status Bit- 1847 Eng Coolant Temp − Shutdown w/Cool Shutdown PC 2.x, PC
map 10 w/Cool- 3.x
down
40410 0 Fault Status Bit- 1852 Water in Fuel Indicator: Above Nor- Warning PC 2.x, PC
map 11 mal−Moderate 3.x
40410 1 Fault Status Bit- 1853 HMI113 Fault 1 NONE PC 2.x, PC
map 11 3.x
274
Addr. Bit # Name Fault Event Name Response Control
Code
40410 2 Fault Status Bit- 1854 HMI113 Fault 2 NONE PC 2.x, PC
map 11 3.x
40410 3 Fault Status Bit- 1855 HMI113 Fault 3 NONE PC 2.x, PC
map 11 3.x
40410 5 Fault Status Bit- 1891 Eng Oil Change Interval Warning PC 2.x, PC
map 11 3.x
40410 6 Fault Status Bit- 1893 J39_EGR_VALVE_COMM_TIME- Warning PC 2.x, PC
map 11 OUT_ERROR 3.x
40410 7 Fault Status Bit- 1894 J39_VGT_COMM_TIMEOUT_ERROR Warning PC 2.x, PC
map 11 3.x
40410 8 Fault Status Bit- 1896 EGR_DL_VALVE_STUCK_ERROR Warning PC 2.x, PC
map 11 3.x
40410 9 Fault Status Bit- 1899 EGR_DELTA_P_IR_LOW_ERROR Warning PC 2.x, PC
map 11 3.x
40410 11 Fault Status Bit- 1912 Utility Loss Of Phase Warning PC 3.x
map 11
40410 12 Fault Status Bit- 1913 Genset Loss Of Phase Warning PC 3.x
map 11
40410 13 Fault Status Bit- 1914 Utility Phase Rotation Warning PC 3.x
map 11
40410 14 Fault Status Bit- 1915 Genset Phase Rotation Warning PC 3.x
map 11
40410 15 Fault Status Bit- 1916 Sync Check OK NONE PC 3.x
map 11
40411 0 Fault Status Bit- 1917 High Fuel Level Warning PC 2.x, PC
map 12 3.x
40411 1 Fault Status Bit- 1918 Very Low Fuel Level Shutdown PC 2.x, PC
map 12 3.x
40411 2 Fault Status Bit- 1933 EGR_DL_VOLTAGE_HIGH_ERROR Warning PC 2.x, PC
map 12 3.x
40411 3 Fault Status Bit- 1934 EGR_DL_VOLTAGE_LOW_ERROR Warning PC 2.x, PC
map 12 3.x
40411 4 Fault Status Bit- 1935 EGR_DL_COMMAND_SOURCE_ER- Warning PC 2.x, PC
map 12 ROR 3.x
40411 5 Fault Status Bit- 1942 BEYOND_THD_AZ_ERROR Warning PC 2.x, PC
map 12 3.x
40411 6 Fault Status Bit- 1943 CBR_DENSITY_DERATE_ER- NONE PC 2.x, PC
map 12 ROR_ID 3.x
40411 7 Fault Status Bit- 1944 HMI113 Output Configuration Fault Warning PC 2.x, PC
map 12 3.x
40411 8 Fault Status Bit- 1961 EGR_DL_EDU_TMPTR_HIGH_ER- Warning PC 2.x, PC
map 12 ROR 3.x
40411 9 Fault Status Bit- 1974 CRANKCASE_PRES- Warning PC 2.x, PC
map 12 SURE_LEAST_SEV_HIGH 3.x
40411 10 Fault Status Bit- 1992 Eng Crankshaft Speed/Posn: Above Shutdown PC 2.x, PC
map 12 Normal 3.x
40411 11 Fault Status Bit- 1999 Maximum Parallel Time Warning PC 3.x
map 12
40411 12 Fault Status Bit- 2185 Sensor Supply 4: Vtg Above Normal Warning PC 2.x, PC
map 12 3.x
275
Addr. Bit # Name Fault Event Name Response Control
Code
40411 13 Fault Status Bit- 2186 Sensor Supply 4: Vtg Below Normal Warning PC 2.x, PC
map 12 3.x
40411 14 Fault Status Bit- 2215 Fuel Pump Delivery Pressure: Below Warning PC 2.x, PC
map 12 Normal 3.x
40411 15 Fault Status Bit- 2249 APC_DIESEL_LOW2_PRS_ERROR Warning PC 2.x, PC
map 12 3.x
40412 0 Fault Status Bit- 2261 Fuel Pump Delivery Pressure: Above Warning PC 2.x, PC
map 13 Normal 3.x
40412 1 Fault Status Bit- 2262 Fuel Pump Delivery−Below Normal Warning PC 2.x, PC
map 13 3.x
40412 2 Fault Status Bit- 2265 Electric Lift Pump for Eng Fuel: Vtg Warning PC 2.x, PC
map 13 Above Normal 3.x
40412 3 Fault Status Bit- 2266 Electric Lift Pump for Eng Fuel: Vtg Warning PC 2.x, PC
map 13 Below Normal 3.x
40412 4 Fault Status Bit- 2292 APC_DIESEL_FLOW_HIGH_ERROR Warning PC 2.x, PC
map 13 3.x
40412 5 Fault Status Bit- 2293 APC_DIESEL_FLOW_LOW_ERROR Warning PC 2.x, PC
map 13 3.x
40412 6 Fault Status Bit- 2311 Electronic Fuel Injection Control Valve Warning PC 2.x, PC
map 13 3.x
40412 7 Fault Status Bit- 2328 Utility Available NONE PC 3.x
map 13
40412 8 Fault Status Bit- 2331 Utility Undervoltage Warning PC 3.x
map 13
40412 9 Fault Status Bit- 2332 Utility Connected NONE PC 3.x
map 13
40412 10 Fault Status Bit- 2333 Genset Connected NONE PC 3.x
map 13
40412 11 Fault Status Bit- 2335 Excitation/Loss of AC Voltage Sensing Shutdown PC 2.x, PC
map 13 3.x
40412 12 Fault Status Bit- 2336 Checksum Fault Shutdown PC 2.x, PC
map 13 3.x
40412 13 Fault Status Bit- 2342 Too Long in Idle Warning PC 2.x, PC
map 13 3.x
40412 14 Fault Status Bit- 2358 Utility Overvoltage Warning PC 3.x
map 13
40412 15 Fault Status Bit- 2377 Fan Control: Vtg Above Normal Warning PC 2.x, PC
map 13 3.x
40413 0 Fault Status Bit- 2396 Utility Breaker Fail To Close Warning PC 3.x
map 14
40413 1 Fault Status Bit- 2397 Utility Breaker Fail To Open Warning PC 3.x
map 14
40413 2 Fault Status Bit- 3226 Base Load NONE PC 3.x
map 14
40413 3 Fault Status Bit- 3227 Peak Shave NONE PC 3.x
map 14
40413 4 Fault Status Bit- 2555 GHC_LOW_VOLTAGE_ERROR_1 Warning PC 2.x, PC
map 14 3.x
40413 5 Fault Status Bit- 2556 GHC_HIGH_VOLTAGE_ERROR_1 Warning PC 2.x, PC
map 14 3.x
276
Addr. Bit # Name Fault Event Name Response Control
Code
40413 6 Fault Status Bit- 2678 Charging Alternator Failure Fault Warning PC 2.x, PC
map 14 3.x
40413 7 Fault Status Bit- 2965 Genset Available NONE PC 3.x
map 14
40413 8 Fault Status Bit- 2971 Test/Exercise is Active Fault NONE PC 2.x, PC
map 14 3.x
40413 9 Fault Status Bit- 2972 Field Overload Shutdown PC 2.x, PC
map 14 3.x
40413 10 Fault Status Bit- 2973 CHARGE_PRESS_IR_ERROR Warning PC 2.x, PC
map 14 3.x
40413 11 Fault Status Bit- 2943 Manual Switch Configuration Fault Warning PC 2.x, PC
map 14 3.x
40413 12 Fault Status Bit- 2944 Auto Switch Configuration Fault Warning PC 2.x, PC
map 14 3.x
40413 13 Fault Status Bit- 2914 Genset AC Meter Failed Shutdown PC 2.x, PC
map 14 3.x
40413 14 Fault Status Bit- 2915 Genset Bus AC Meter Failed Warning PC 3.x
map 14
40413 15 Fault Status Bit- 2916 Utility AC Meter Failed Warning PC 3.x
map 14
40414 0 Fault Status Bit- 2814 Genset CT Ratio Too Small Shutdown PC 2.x, PC
map 15 3.x
40414 1 Fault Status Bit- 2815 Genset CT Ratio Too Large Warning PC 2.x, PC
map 15 3.x
40414 2 Fault Status Bit- 2816 Genset PT Ratio Too Small Shutdown PC 2.x, PC
map 15 3.x
40414 3 Fault Status Bit- 2817 Genset PT Ratio Too Large Warning PC 2.x, PC
map 15 3.x
40414 4 Fault Status Bit- 2818 Genset Bus PT Ratio Too Small Shutdown PC 3.x
map 15
40414 5 Fault Status Bit- 2819 Genset Bus PT Ratio Too Large Warning PC 3.x
map 15
40414 6 Fault Status Bit- 2821 Utility PT Ratio Too Small Shutdown PC 3.x
map 15
40414 7 Fault Status Bit- 2822 Utility PT Ratio Too Large Warning PC 3.x
map 15
40414 8 Fault Status Bit- 2619 Aux101 0 Input 1 Fault Warning PC 2.x, PC
map 15 3.x
40414 9 Fault Status Bit- 2621 Aux101 0 Input 2 Fault Warning PC 2.x, PC
map 15 3.x
40414 10 Fault Status Bit- 2622 Aux101 0 Input 3 Fault Warning PC 2.x, PC
map 15 3.x
40414 11 Fault Status Bit- 2623 Aux101 0 Input 4 Fault Warning PC 2.x, PC
map 15 3.x
40414 12 Fault Status Bit- 2624 Aux101 0 Input 5 Fault Warning PC 2.x, PC
map 15 3.x
40414 13 Fault Status Bit- 2625 Aux101 0 Input 6 Fault Warning PC 2.x, PC
map 15 3.x
40414 14 Fault Status Bit- 2626 Aux101 0 Input 7 Fault Warning PC 2.x, PC
map 15 3.x
277
Addr. Bit # Name Fault Event Name Response Control
Code
40414 15 Fault Status Bit- 2627 Aux101 0 Input 8 Fault Warning PC 2.x, PC
map 15 3.x
40415 0 Fault Status Bit- 2882 Aux101 1 Input 1 Fault Warning PC 2.x, PC
map 16 3.x
40415 1 Fault Status Bit- 2883 Aux101 1 Input 2 Fault Warning PC 2.x, PC
map 16 3.x
40415 2 Fault Status Bit- 2884 Aux101 1 Input 3 Fault Warning PC 2.x, PC
map 16 3.x
40415 3 Fault Status Bit- 2885 Aux101 1 Input 4 Fault Warning PC 2.x, PC
map 16 3.x
40415 4 Fault Status Bit- 2886 Aux101 1 Input 5 Fault Warning PC 2.x, PC
map 16 3.x
40415 5 Fault Status Bit- 2887 Aux101 1 Input 6 Fault Warning PC 2.x, PC
map 16 3.x
40415 6 Fault Status Bit- 2888 Aux101 1 Input 7 Fault Warning PC 2.x, PC
map 16 3.x
40415 7 Fault Status Bit- 2889 Aux101 1 Input 8 Fault Warning PC 2.x, PC
map 16 3.x
40415 8 Fault Status Bit- 2628 Aux102 0 Expansion Input 9 Fault Warning PC 2.x, PC
map 16 3.x
40415 9 Fault Status Bit- 2629 Aux102 0 Expansion Input 10 Fault Warning PC 2.x, PC
map 16 3.x
40415 10 Fault Status Bit- 2631 Aux102 0 Expansion Input 11 Fault Warning PC 2.x, PC
map 16 3.x
40415 11 Fault Status Bit- 2632 Aux102 0 Expansion Input 12 Fault Warning PC 2.x, PC
map 16 3.x
40415 12 Fault Status Bit- 2891 Aux102 1 Expansion Input 9 Fault Warning PC 2.x, PC
map 16 3.x
40415 13 Fault Status Bit- 2892 Aux102 1 Expansion Input 10 Fault Warning PC 2.x, PC
map 16 3.x
40415 14 Fault Status Bit- 2893 Aux102 1 Expansion Input 11 Fault Warning PC 2.x, PC
map 16 3.x
40415 15 Fault Status Bit- 2894 Aux102 1 Expansion Input 12 Fault Warning PC 2.x, PC
map 16 3.x
40416 0 Fault Status Bit- 2895 PCCnet Device Failed Warning Warning PC 2.x, PC
map 17 3.x
40416 1 Fault Status Bit- 2896 PCCnet Device Failed Shutdown Shutdown PC 2.x, PC
map 17 3.x
40416 2 Fault Status Bit- 2917 Genset Bus Voltage OOR Warning Warning PC 3.x
map 17
40416 3 Fault Status Bit- 2918 Utility Voltage OOR Warning Warning PC 3.x
map 17
40416 4 Fault Status Bit- 2919 Utility Current OOR Warning Warning PC 3.x
map 17
40416 5 Fault Status Bit- 2921 Genset Bus Current OOR Warning Warning PC 3.x
map 17
40416 6 Fault Status Bit- 2922 Genset Neutral Current OOR Warning Warning PC 3.x
map 17
40416 7 Fault Status Bit- 2923 Genset Bus kW OOR Warning Warning PC 3.x
map 17
278
Addr. Bit # Name Fault Event Name Response Control
Code
40416 8 Fault Status Bit- 2924 Genset Bus kVAR OOR Warning Warning PC 3.x
map 17
40416 9 Fault Status Bit- 2925 Genset Bus kVA OOR Warning Warning PC 3.x
map 17
40416 10 Fault Status Bit- 2926 Utility kW OOR Warning Warning PC 3.x
map 17
40416 11 Fault Status Bit- 2927 Utility kVAR OOR Warning Warning PC 3.x
map 17
40416 12 Fault Status Bit- 2928 Utility kVA OOR Warning Warning PC 3.x
map 17
40416 13 Fault Status Bit- 3599 Ground Current OOR Warning Warning PC 3.x
map 17
40416 14 Fault Status Bit- 2931 AUX101 Device ID Fault Shutdown PC 2.x, PC
map 17 3.x
40416 15 Fault Status Bit- 2779 Utility Unloaded Event NONE PC 3.x
map 17
40417 3 Fault Status Bit- 2932 AUX101 Oil Temp OOR Hi Warning PC 2.x, PC
map 18 3.x
40417 4 Fault Status Bit- 2933 AUX101 Oil Temp OOR Low Warning PC 2.x, PC
map 18 3.x
40417 5 Fault Status Bit- 2657 Exhaust Stack Temp 1 OOR High Warning PC 2.x, PC
map 18 3.x
40417 6 Fault Status Bit- 2947 Exhaust Stack Temp 1 OOR Low Warning PC 2.x, PC
map 18 3.x
40417 7 Fault Status Bit- 2949 High Exhaust Stack Temperature 1 Warning PC 2.x, PC
map 18 3.x
40417 8 Fault Status Bit- 2653 Exhaust Stack Temp 2 OOR High Warning PC 2.x, PC
map 18 3.x
40417 9 Fault Status Bit- 2946 Exhaust Stack Temp 2 OOR Low Warning PC 2.x, PC
map 18 3.x
40417 10 Fault Status Bit- 2948 High Exhaust Stack Temperature 2 Warning PC 2.x, PC
map 18 3.x
40417 11 Fault Status Bit- 2934 Ambient Temp OOR High Warning PC 2.x, PC
map 18 3.x
40417 12 Fault Status Bit- 2935 Ambient Temp OOR Low Warning PC 2.x, PC
map 18 3.x
40417 13 Fault Status Bit- 2936 Fuel Level OOR High Warning PC 2.x, PC
map 18 3.x
40417 14 Fault Status Bit- 2937 Fuel Level OOR Low Warning PC 2.x, PC
map 18 3.x
40417 15 Fault Status Bit- 2951 Alternator Temp 1 OOR High Warning PC 2.x, PC
map 18 3.x
40418 0 Fault Status Bit- 2952 Alternator Temp 1 OOR Low Warning PC 2.x, PC
map 19 3.x
40418 1 Fault Status Bit- 2953 High Alternator Temp 1 Warning PC 2.x, PC
map 19 3.x
40418 2 Fault Status Bit- 2954 Alternator Temp 2 OOR High Warning PC 2.x, PC
map 19 3.x
40418 3 Fault Status Bit- 2955 Alternator Temp 2 OOR Low Warning PC 2.x, PC
map 19 3.x
279
Addr. Bit # Name Fault Event Name Response Control
Code
40418 4 Fault Status Bit- 2956 High Alternator Temp 2 Warning PC 2.x, PC
map 19 3.x
40418 5 Fault Status Bit- 2957 Alternator Temp 3 OOR High Warning PC 2.x, PC
map 19 3.x
40418 6 Fault Status Bit- 2958 Alternator Temp 3 OOR Low Warning PC 2.x, PC
map 19 3.x
40418 7 Fault Status Bit- 2959 High Alternator Temp 3 Warning PC 2.x, PC
map 19 3.x
40418 8 Fault Status Bit- 2992 Intake Manifold Temp 1 OOR High Warning PC 2.x, PC
map 19 3.x
40418 9 Fault Status Bit- 2978 Intake Manifold Temp 1 OOR Low Warning PC 2.x, PC
map 19 3.x
40418 10 Fault Status Bit- 2981 Drive End Bearing Temp OOR High Warning PC 2.x, PC
map 19 3.x
40418 11 Fault Status Bit- 2982 Drive End Bearing Temp OOR Low Warning PC 2.x, PC
map 19 3.x
40418 12 Fault Status Bit- 2983 High Drive End Bearing Temperature Warning PC 2.x, PC
map 19 3.x
40418 13 Fault Status Bit- 2984 Non−Drive End Bearing Temp OOR Warning PC 2.x, PC
map 19 High 3.x
40418 14 Fault Status Bit- 2985 Non−Drive End Bearing Temp OOR Warning PC 2.x, PC
map 19 Low 3.x
40418 15 Fault Status Bit- 2986 High Non−Drive End Bearing Temper- Warning PC 2.x, PC
map 19 ature 3.x
40419 0 Fault Status Bit- 2945 Rupture Basin Warning PC 2.x, PC
map 20 3.x
40419 1 Fault Status Bit- 2979 High Alternator Temp Switch fault Warning PC 2.x, PC
map 20 3.x
40419 2 Fault Status Bit- 2993 Battery Charger Failed Fault Warning PC 2.x, PC
map 20 3.x
40419 3 Fault Status Bit- 2938 Earth/Ground Fault Warning PC 2.x, PC
map 20 3.x
40419 4 Fault Status Bit- 2939 Modbus Failure Fault Warning PC 2.x, PC
map 20 3.x
40419 5 Fault Status Bit- 2977 Low Coolant Level #2 Warning PC 2.x, PC
map 20 3.x
40419 6 Fault Status Bit- 1978 Speed Bias OOR High Warning PC 2.x, PC
map 20 3.x
40419 7 Fault Status Bit- 2541 Voltage Bias OOR Low Warning PC 2.x, PC
map 20 3.x
40419 8 Fault Status Bit- 2539 Voltage Bias OOR High Warning PC 2.x, PC
map 20 3.x
40419 9 Fault Status Bit- 1573 Configurable Input #1 NONE PC 2.x, PC
map 20 3.x
40419 10 Fault Status Bit- 1312 Configurable Input #2 NONE PC 2.x, PC
map 20 3.x
40419 11 Fault Status Bit- 1317 Configurable Input #13 NONE PC 2.x, PC
map 20 3.x
40419 12 Fault Status Bit- 1318 Configurable Input #14 NONE PC 2.x, PC
map 20 3.x
280
Addr. Bit # Name Fault Event Name Response Control
Code
40419 13 Fault Status Bit- 1979 Speed Bias OOR Low Warning PC 2.x, PC
map 20 3.x
40419 14 Fault Status Bit- 236 Both Engine Speed Signals Lost: Most Shutdown PC 2.x, PC
map 20 Severe Level 3.x
40419 15 Fault Status Bit- 3629 Less Severe Response−Warning Warning PC 3.x
map 20
40420 0 Fault Status Bit- 3631 Most Severe−Shutdown Shutdown PC 3.x
map 21
40430 0 Event Status Bit- 1540 Common Warning NONE PC 2.x, PC
map 1 3.x
40430 1 Event Status Bit- 1541 Common Shutdown NONE PC 2.x, PC
map 1 3.x
40431 0 Fault Status Gas 121 EPS Main Channel Lost Error Warning PC 3.x
Bitmap 1
40431 1 Fault Status Gas 136 Oil Inlet Pressure High Error Warning PC 3.x
Bitmap 1
40431 2 Fault Status Gas 137 Oil Inlet Pressure Low Error Warning PC 3.x
Bitmap 1
40431 3 Fault Status Gas 142 Oil Overpressure Error Warning PC 3.x
Bitmap 1
40431 4 Fault Status Gas 156 Intake Manifold Temp 2 OORH Warning PC 3.x
Bitmap 1
40431 5 Fault Status Gas 157 Intake Manifold Temp 2 OORL Warning PC 3.x
Bitmap 1
40431 6 Fault Status Gas 158 Intake Manifold Temp 2 High Shutdown PC 3.x
Bitmap 1
40431 7 Fault Status Gas 159 Intake Manifold 3 Temp OORH Warning PC 3.x
Bitmap 1
40431 8 Fault Status Gas 161 Intake Manifold 3 Temp OORL Warning PC 3.x
Bitmap 1
40431 9 Fault Status Gas 162 Intake Manifold 3 Temp High Shutdown PC 3.x
Bitmap 1
40431 10 Fault Status Gas 163 Intake Manifold 4 Temp OORH Warning PC 3.x
Bitmap 1
40431 11 Fault Status Gas 164 Intake Manifold 4 Temp OORL Warning PC 3.x
Bitmap 1
40431 12 Fault Status Gas 165 Intake Manifold 4 Temp High Shutdown PC 3.x
Bitmap 1
40431 13 Fault Status Gas 175 Throttle_Driver_Feedback_High_Error Shutdown PC 3.x
Bitmap 1 w/Cool-
down
40431 14 Fault Status Gas 176 Throttle_Driver_Feedback_Low_Error Shutdown PC 3.x
Bitmap 1 w/Cool-
down
40431 15 Fault Status Gas 177 Throttle_Actuator_Error Shutdown PC 3.x
Bitmap 1 w/Cool-
down
40432 0 Fault Status Gas 219 Eng Oil Level Remote Reservoir: Warning PC 2.x, PC
Bitmap 2 Least Severe Level 3.x
281
Addr. Bit # Name Fault Event Name Response Control
Code
40432 1 Fault Status Gas 233 HT Coolant Pressure Moderate Low Warning PC 2.x, PC
Bitmap 2 3.x
40432 2 Fault Status Gas 244 Red Stop Lamp Driver OORL Warning PC 3.x
Bitmap 2
40432 3 Fault Status Gas 246 Exhaust Gas Temp Sensor 1 OORH Warning PC 3.x
Bitmap 2
40432 4 Fault Status Gas 247 Exhaust Gas Temp Sensor 1 OORL Warning PC 3.x
Bitmap 2
40432 5 Fault Status Gas 248 Exhaust Gas Temp Sensor 1 High Warning PC 3.x
Bitmap 2
40432 6 Fault Status Gas 253 Oil Level Low Error Shutdown PC 3.x
Bitmap 2 w/Cool-
down
40432 7 Fault Status Gas 254 FSO NON Low Control Error Shutdown PC 2.x, PC
Bitmap 2 3.x
40432 8 Fault Status Gas 277 Fuel Control Valve Out of Adj Warning PC 3.x
Bitmap 2
40432 9 Fault Status Gas 346 Powerdown Data Lost Error Warning PC 3.x
Bitmap 2
40432 10 Fault Status Gas 354 Manifold_Absolute_Pres- Warning PC 3.x
Bitmap 2 sure_1_High_Error
40432 11 Fault Status Gas 355 Manifold_Absolute_Pres- Warning PC 3.x
Bitmap 2 sure_1_Low_Error
40432 12 Fault Status Gas 412 J1708 Link Cannot Transmit Error NONE PC 3.x
Bitmap 2
40432 13 Fault Status Gas 414 J1708 Link Not Fast Enough Error NONE PC 3.x
Bitmap 2
40432 14 Fault Status Gas 453 Gas_Mass_Flow_High_Error Warning PC 3.x
Bitmap 2
40432 15 Fault Status Gas 454 Gas_Mass_Flow_Low_Error Warning PC 3.x
Bitmap 2
40433 0 Fault Status Gas 458 Spark_Timing_B_Error Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 1 Fault Status Gas 459 Spark_Timing_A_Error Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 2 Fault Status Gas 461 Spark_Reference_B_Error Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 3 Fault Status Gas 462 Spark_Reference_A_Error Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 4 Fault Status Gas 477 Isolated Battery Voltage Low Error Warning PC 3.x
Bitmap 3
40433 5 Fault Status Gas 478 Isolated Battery Voltage High Error Warning PC 3.x
Bitmap 3
40433 6 Fault Status Gas 512 Throttle Pos 1 Feedback OOR High Warning PC 3.x
Bitmap 3
282
Addr. Bit # Name Fault Event Name Response Control
Code
40433 7 Fault Status Gas 513 Throttle Pos 1 Feedback OOR Low Warning PC 3.x
Bitmap 3
40433 8 Fault Status Gas 557 Fuel Control Valve 2 OORH Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 9 Fault Status Gas 558 Fuel Control Valve 2 OORL Warning PC 3.x
Bitmap 3
40433 10 Fault Status Gas 561 Heavy_Knock_Error_1_(A1) Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 11 Fault Status Gas 562 Heavy_Knock_Error_2_(B1) Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 12 Fault Status Gas 563 Heavy_Knock_Error_3_(A2) Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 13 Fault Status Gas 564 Heavy_Knock_Error_4_(B2) Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 14 Fault Status Gas 565 Heavy_Knock_Error_5_(A3) Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40433 15 Fault Status Gas 566 Heavy_Knock_Error_6_(B3) Shutdown PC 3.x
Bitmap 3 w/Cool-
down
40434 0 Fault Status Gas 567 Heavy_Knock_Error_7_(A4) Shutdown PC 3.x
Bitmap 4 w/Cool-
down
40434 1 Fault Status Gas 568 Heavy_Knock_Error_8_(B4) Shutdown PC 3.x
Bitmap 4 w/Cool-
down
40434 2 Fault Status Gas 569 Heavy_Knock_Error_9_(A5) Shutdown PC 3.x
Bitmap 4 w/Cool-
down
40434 3 Fault Status Gas 571 Knock Cyl 1 (A1) OORL Warning PC 3.x
Bitmap 4
40434 4 Fault Status Gas 572 Knock Cyl 2 (B1) OORL Warning PC 3.x
Bitmap 4
40434 5 Fault Status Gas 573 Knock Cyl 3 (A2) OORL Warning PC 3.x
Bitmap 4
40434 6 Fault Status Gas 574 Knock Cyl 4 (B2) OORL Warning PC 3.x
Bitmap 4
40434 7 Fault Status Gas 575 Knock Cyl 5 (A3) OORL Warning PC 3.x
Bitmap 4
40434 8 Fault Status Gas 576 Knock Cyl 6 (B3) OORL Warning PC 3.x
Bitmap 4
40434 9 Fault Status Gas 577 Knock Cyl 7 (A4) OORL Warning PC 3.x
Bitmap 4
40434 10 Fault Status Gas 578 Knock Cyl 8 (B4) OORL Warning PC 3.x
Bitmap 4
283
Addr. Bit # Name Fault Event Name Response Control
Code
40434 11 Fault Status Gas 579 Knock Cyl 9 (A5) OORL Warning PC 3.x
Bitmap 4
40434 12 Fault Status Gas 584 High Side DRV3 High Control Error Warning PC 3.x
Bitmap 4
40434 13 Fault Status Gas 585 High Side DRV3 Low Control Error Warning PC 3.x
Bitmap 4
40434 14 Fault Status Gas 591 Exhaust_Backpressure_High_Error Warning PC 3.x
Bitmap 4
40434 15 Fault Status Gas 592 Exhaust_Backpressure_Low_Error Warning PC 3.x
Bitmap 4
40435 0 Fault Status Gas 595 Turbo 1 Overspeed Warning Error Warning PC 3.x
Bitmap 5
40435 1 Fault Status Gas 618 Turbo 1 Inlet Pressure High Warning PC 3.x
Bitmap 5
40435 2 Fault Status Gas 619 Turbo 2 Inlet Press High Warning PC 3.x
Bitmap 5
40435 3 Fault Status Gas 641 Exhaust Temp 1 (A1) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
40435 4 Fault Status Gas 642 Exhaust Temp 3 (A2) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
40435 5 Fault Status Gas 643 Exhaust Temp 5 (A3) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
40435 6 Fault Status Gas 644 Exhaust Temp 7 (A4) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
40435 7 Fault Status Gas 645 Exhaust Temp 9 (A5) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
40435 8 Fault Status Gas 646 Exhaust Temp 11 (A6) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cool-
down
40435 9 Fault Status Gas 647 Exhaust Temp 13 (A7) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cool-
down
40435 10 Fault Status Gas 648 Exhaust Temp 15 (A8) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cool-
down
40435 11 Fault Status Gas 651 Exhaust Temp 17 (A9) High Serious Shutdown PC 3.x
Bitmap 5 Error w/Cool-
down
40435 12 Fault Status Gas 652 Exhaust Temp 2 (B1) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
40435 13 Fault Status Gas 653 Exhaust Temp 4 (B2) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
284
Addr. Bit # Name Fault Event Name Response Control
Code
40435 14 Fault Status Gas 654 Exhaust Temp 6 (B3) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
40435 15 Fault Status Gas 655 Exhaust Temp 8 (B4) High Serious Er- Shutdown PC 3.x
Bitmap 5 ror w/Cool-
down
40436 0 Fault Status Gas 656 Exhaust Temp 10 (B5) High Serious Shutdown PC 3.x
Bitmap 6 Error w/Cool-
down
40436 1 Fault Status Gas 657 Exhaust Temp 12 (B6) High Serious Shutdown PC 3.x
Bitmap 6 Error w/Cool-
down
40436 2 Fault Status Gas 658 Exhaust Temp 14 (B7) High Serious Shutdown PC 3.x
Bitmap 6 Error w/Cool-
down
40436 3 Fault Status Gas 671 Exhaust Gas Temp Cyl 1 (A1) OORL Warning PC 3.x
Bitmap 6
40436 4 Fault Status Gas 672 Exhaust Gas Temp Cyl 3 (A2) OORL Warning PC 3.x
Bitmap 6
40436 5 Fault Status Gas 673 Exhaust Gas Temp Cyl 5 (A3) OORL Warning PC 3.x
Bitmap 6
40436 6 Fault Status Gas 674 Exhaust Gas Temp Cyl 7 (A4) OORL Warning PC 3.x
Bitmap 6
40436 7 Fault Status Gas 675 Exhaust Gas Temp Cyl 9 (A5) OORL Warning PC 3.x
Bitmap 6
40436 8 Fault Status Gas 676 Exhaust Gas Temp Cyl 11 (A6) OORL Warning PC 3.x
Bitmap 6
40436 9 Fault Status Gas 677 Exhaust Gas Temp Cyl 13 (A7) OORL Warning PC 3.x
Bitmap 6
40436 10 Fault Status Gas 678 Exhaust Gas Temp Cyl 15 (A8) OORL Warning PC 3.x
Bitmap 6
40436 11 Fault Status Gas 683 Turbo 2 Speed Moderate High Warning PC 3.x
Bitmap 6
40436 12 Fault Status Gas 684 Turbo 2 Speed Moderate Low Warning PC 3.x
Bitmap 6
40436 13 Fault Status Gas 685 Turbo 2 Speed Incorrect Warning PC 3.x
Bitmap 6
40436 14 Fault Status Gas 686 Turbo 1 Speed Incorrect Warning PC 2.x, PC
Bitmap 6 3.x
40436 15 Fault Status Gas 687 Turbo 1 Speed Low Warning PC 3.x
Bitmap 6
40437 0 Fault Status Gas 697 ECM Internal Temperature High Error Warning PC 2.x, PC
Bitmap 7 3.x
40437 1 Fault Status Gas 698 ECM Internal Temperature Low Error Warning PC 2.x, PC
Bitmap 7 3.x
40437 2 Fault Status Gas 721 Exhaust Gas Temp 2 (B1) OORL Warning PC 3.x
Bitmap 7
40437 3 Fault Status Gas 722 Exhaust Gas Temp 4 (B2) OORL Warning PC 3.x
Bitmap 7
285
Addr. Bit # Name Fault Event Name Response Control
Code
40437 4 Fault Status Gas 723 Exhaust Gas Temp 6 (B3) OORL Warning PC 3.x
Bitmap 7
40437 5 Fault Status Gas 724 Exhaust Gas Temp 8 (B4) OORL Warning PC 3.x
Bitmap 7
40437 6 Fault Status Gas 725 Exhaust Gas Temp 10 (B5) OORL Warning PC 3.x
Bitmap 7
40437 7 Fault Status Gas 726 Exhaust Gas Temp 12 (B6) OORL Warning PC 3.x
Bitmap 7
40437 8 Fault Status Gas 727 Exhaust Gas Temp 14 (B7) OORL Warning PC 3.x
Bitmap 7
40437 9 Fault Status Gas 728 Exhaust Gas Temp 16 (B8) OORL Warning PC 3.x
Bitmap 7
40437 10 Fault Status Gas 736 Starter Air Pressure OORL Warning PC 3.x
Bitmap 7
40437 11 Fault Status Gas 737 Starter Air Pressure OORH Warning PC 3.x
Bitmap 7
40437 12 Fault Status Gas 738 Starter Air Press Underpressure Error Warning PC 3.x
Bitmap 7
40437 13 Fault Status Gas 741 Air Filter Restriction Pressure High Er- Warning PC 3.x
Bitmap 7 ror
40437 14 Fault Status Gas 742 Air Filter Restriction Pressure Low Er- Warning PC 3.x
Bitmap 7 ror
40437 15 Fault Status Gas 751 Gas_Mass_Flow_In_Range_Error Warning PC 3.x
Bitmap 7
40438 0 Fault Status Gas 752 Exhaust_Gas_Oxygen_In_Range_Er- Warning PC 3.x
Bitmap 8 ror
40438 1 Fault Status Gas 783 Intake Manifold 1 Temp Abnormal Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40438 2 Fault Status Gas 1213 COP_Overboost_Error Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40438 3 Fault Status Gas 1274 Heavy_Knock_Error_10_(B5) Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40438 4 Fault Status Gas 1281 Heavy_Knock_Error_12_(B6) Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40438 5 Fault Status Gas 1285 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 8 ror_13_(A7) w/Cool-
down
40438 6 Fault Status Gas 1286 Heavy_Knock_Error_13_(A7) Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40438 7 Fault Status Gas 1291 Heavy_Knock_Error_14_(B7) Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40438 8 Fault Status Gas 1295 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 8 ror_15_(A8) w/Cool-
down
286
Addr. Bit # Name Fault Event Name Response Control
Code
40438 9 Fault Status Gas 1296 Heavy_Knock_Error_15_(A8) Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40438 10 Fault Status Gas 1311 Heavy_Knock_Error_18_(B9) Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40438 11 Fault Status Gas 1362 Oil Filter Restriction Error Warning PC 3.x
Bitmap 8
40438 12 Fault Status Gas 1452 Genset Breaker Fail To Close Shutdown PC 3.x
Bitmap 8
40438 13 Fault Status Gas 1457 Fail To Synchronize Warning PC 3.x
Bitmap 8
40438 14 Fault Status Gas 1458 Sync Phase Rotation Mismatch Warning PC 3.x
Bitmap 8
40438 15 Fault Status Gas 1474 ECM Software mismatch Shutdown PC 3.x
Bitmap 8 w/Cool-
down
40439 0 Fault Status Gas 1521 Exhaust Gas Temp 3 (A2) OORH Warning PC 3.x
Bitmap 9
40439 1 Fault Status Gas 1522 Exhaust Gas Temp 5 (A3) OORH Warning PC 3.x
Bitmap 9
40439 2 Fault Status Gas 1523 Exhaust Gas Temp 7 (A4) OORH Warning PC 3.x
Bitmap 9
40439 3 Fault Status Gas 1524 Exhaust Gas Temp 9 (A5) OORH Warning PC 3.x
Bitmap 9
40439 4 Fault Status Gas 1525 Exhaust Gas Temp 11 (A6) OORH Warning PC 3.x
Bitmap 9
40439 5 Fault Status Gas 1526 Exhaust Gas Temp 13 (A7) OORH Warning PC 3.x
Bitmap 9
40439 6 Fault Status Gas 1527 Exhaust Gas Temp 15 (A8) OORH Warning PC 3.x
Bitmap 9
40439 7 Fault Status Gas 1528 Exhaust Gas Temp 17 (A9) OORH Warning PC 3.x
Bitmap 9
40439 8 Fault Status Gas 1529 Exhaust Gas Temp 2 (B1) OORH Warning PC 3.x
Bitmap 9
40439 9 Fault Status Gas 1531 Exhaust Gas Temp 6 (B3) OORH Warning PC 3.x
Bitmap 9
40439 10 Fault Status Gas 1532 Exhaust Gas Temp 8 (B4) OORH Warning PC 3.x
Bitmap 9
40439 11 Fault Status Gas 1533 Exhaust Gas Temp 10 (B5) OORH Warning PC 3.x
Bitmap 9
40439 12 Fault Status Gas 1534 Exhaust Gas Temp 12 (B6) OORH Warning PC 3.x
Bitmap 9
40439 13 Fault Status Gas 1535 Exhaust Gas Temp 14 (B7) OORH Warning PC 3.x
Bitmap 9
40439 14 Fault Status Gas 1536 Exhaust Gas Temp 16 (B8) OORH Warning PC 3.x
Bitmap 9
40439 15 Fault Status Gas 1537 Exhaust Gas Temp 18 (B9) OORH Warning PC 3.x
Bitmap 9
287
Addr. Bit # Name Fault Event Name Response Control
Code
40440 0 Fault Status Gas 1545 EPS Backup Channel Lost Warning PC 3.x
Bitmap 10
40440 1 Fault Status Gas 1546 EPS Main Channel Lost Warning PC 3.x
Bitmap 10
40440 2 Fault Status Gas 1579 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 10 ror_12_(B6) w/Cool-
down
40440 3 Fault Status Gas 1581 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 10 ror_14_(B7) w/Cool-
down
40440 4 Fault Status Gas 1582 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 10 ror_16_(B8) w/Cool-
down
40440 5 Fault Status Gas 1583 Heavy_Knock_Error_16_(B8) Shutdown PC 3.x
Bitmap 10 w/Cool-
down
40440 6 Fault Status Gas 1587 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 10 ror_17_(A9) w/Cool-
down
40440 7 Fault Status Gas 1588 Heavy_Knock_Error_17_(A9) Shutdown PC 3.x
Bitmap 10 w/Cool-
down
40440 8 Fault Status Gas 1593 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 10 ror_18_(B9) w/Cool-
down
40440 9 Fault Status Gas 1618 Exhaust Gas Temp Cyl 1 (A1) OORH Warning PC 3.x
Bitmap 10
40440 10 Fault Status Gas 1619 Exhaust Gas Temp Cyl 4 (B2) OORH Warning PC 3.x
Bitmap 10
40440 11 Fault Status Gas 1636 Intake Manif Press 2 OORH Warning PC 3.x
Bitmap 10
40440 12 Fault Status Gas 1637 Intake Manif Press 2 OORL Warning PC 3.x
Bitmap 10
40440 13 Fault Status Gas 1737 CAN_Throttle_Internal_Failure_Error Shutdown PC 3.x
Bitmap 10 w/Cool-
down
40440 14 Fault Status Gas 1738 CAN_Throttle_Internal_Fault_Error Warning PC 3.x
Bitmap 10
40440 15 Fault Status Gas 1739 Engine Throttle Control Condition Ex- Warning PC 3.x
Bitmap 10 ists
40441 0 Fault Status Gas 1741 CAN_Throttle_High_Temp_Warn- Warning PC 3.x
Bitmap 11 ing_Error
40441 1 Fault Status Gas 1742 CAN_Throttle_Temp_Limiting_Error Warning PC 3.x
Bitmap 11
40441 2 Fault Status Gas 1743 Throttle Ctrl 2 OOR High Shutdown PC 3.x
Bitmap 11 w/Cool-
down
40441 3 Fault Status Gas 1744 Throttle Ctrl 2 OOR Low Shutdown PC 3.x
Bitmap 11 w/Cool-
down
288
Addr. Bit # Name Fault Event Name Response Control
Code
40441 4 Fault Status Gas 1745 Throttle Ctrl 2 Incorrect Shutdown PC 3.x
Bitmap 11 w/Cool-
down
40441 5 Fault Status Gas 1746 Throttle Ctrl 2 Out of Adjustment Shutdown PC 3.x
Bitmap 11 w/Cool-
down
40441 6 Fault Status Gas 1747 Throttle Ctrl 2 Bad Device Shutdown PC 3.x
Bitmap 11 w/Cool-
down
40441 7 Fault Status Gas 1748 Throttle Ctrl 2 Root Unknown Warning PC 3.x
Bitmap 11
40441 8 Fault Status Gas 1749 Throttle Ctrl 2 Condition Exists Warning PC 3.x
Bitmap 11
40441 9 Fault Status Gas 1751 Throttle Ctrl 2 Warning High Warning PC 3.x
Bitmap 11
40441 10 Fault Status Gas 1752 Throttle Ctrl 2 Moderate High Warning PC 3.x
Bitmap 11
40441 11 Fault Status Gas 1753 Fuel Shutoff 2 OOR High Warning PC 3.x
Bitmap 11
40441 12 Fault Status Gas 1754 Fuel Tmp 2 OOR High Warning PC 3.x
Bitmap 11
40441 13 Fault Status Gas 1755 Fuel Tmp 2 OOR Low Warning PC 3.x
Bitmap 11
40441 14 Fault Status Gas 1756 Gas Flow 2 OOR High Warning PC 3.x
Bitmap 11
40441 15 Fault Status Gas 1757 Gas Flow 2 OOR Low Warning PC 3.x
Bitmap 11
40442 0 Fault Status Gas 1758 Gas Flow 2 Incorrect Data Warning PC 3.x
Bitmap 12
40442 1 Fault Status Gas 1759 FCV 2 Pos Feedback Incorrect Shutdown PC 3.x
Bitmap 12 w/Cool-
down
40442 2 Fault Status Gas 1761 FCV_Actuator_Error_1761 Shutdown PC 3.x
Bitmap 12 w/Cool-
down
40442 3 Fault Status Gas 1984 Int Man 2 Tmp Moderate High Warning PC 3.x
Bitmap 12
40442 4 Fault Status Gas 1765 FCV 2 In Pr OOR High Warning PC 3.x
Bitmap 12
40442 5 Fault Status Gas 1766 FCV 2 In Pr OOR Low Warning PC 3.x
Bitmap 12
40442 6 Fault Status Gas 1767 FCV 2 Out Pr OOR High Warning PC 3.x
Bitmap 12
40442 7 Fault Status Gas 1768 FCV 2 Out Pr OOR Low Warning PC 3.x
Bitmap 12
40442 8 Fault Status Gas 1769 E_Shutd Indication OORH Warning PC 3.x
Bitmap 12
40442 9 Fault Status Gas 1771 E_Shutd Indication OORL Warning PC 3.x
Bitmap 12
289
Addr. Bit # Name Fault Event Name Response Control
Code
40442 10 Fault Status Gas 1772 Eng Derate Request OORH Warning PC 3.x
Bitmap 12
40442 11 Fault Status Gas 1773 Eng Derate Request OORL Warning PC 3.x
Bitmap 12
40442 12 Fault Status Gas 1774 Oil Priming Pump OORH Warning PC 3.x
Bitmap 12
40442 13 Fault Status Gas 1775 Oil Priming Pump OORL Warning PC 3.x
Bitmap 12
40442 14 Fault Status Gas 3362 Power Conservation Control OORH Warning PC 3.x
Bitmap 12
40442 15 Fault Status Gas 3363 Power Conservation Control OORL Warning PC 3.x
Bitmap 12
40443 0 Fault Status Gas 1778 Engine_Heater_Control_Driv- Warning PC 3.x
Bitmap 13 er_High_Error
40443 1 Fault Status Gas 1779 Engine_Heater_Control_Driv- Warning PC 3.x
Bitmap 13 er_Low_Error
40443 2 Fault Status Gas 1781 Shutd Request OOR High Warning PC 3.x
Bitmap 13
40443 3 Fault Status Gas 1782 Shutd Request OOR Low Warning PC 3.x
Bitmap 13
40443 4 Fault Status Gas 1783 Coolant_Pump_Control_Driv- Warning PC 3.x
Bitmap 13 er_High_Error
40443 5 Fault Status Gas 1784 Coolant_Pump_Control_Driv- Warning PC 3.x
Bitmap 13 er_Low_Error
40443 6 Fault Status Gas 1785 Oil_Priming_Pump_Manual_Over- Warning PC 3.x
Bitmap 13 ride_Input_On
40443 7 Fault Status Gas 1786 Oil_Priming_Pump_Stuck_On_Error Warning PC 3.x
Bitmap 13
40443 8 Fault Status Gas 1787 Post_Lube_Oil_Priming_Error Warning PC 3.x
Bitmap 13
40443 9 Fault Status Gas 1788 Maintenance_Lube_Oil_Priming_Error Warning PC 3.x
Bitmap 13
40443 10 Fault Status Gas 1789 Pre_Start_Lube_Oil_Priming_Error Shutdown PC 3.x
Bitmap 13 w/Cool-
down
40443 11 Fault Status Gas 1791 Failure_To_Meet_Load_Speed_Error Shutdown PC 3.x
Bitmap 13 w/Cool-
down
40443 12 Fault Status Gas 1792 Idle when CB Closed Warning PC 3.x
Bitmap 13
40443 13 Fault Status Gas 1793 Speed/Posit sensor out of Adj Warning PC 3.x
Bitmap 13
40443 14 Fault Status Gas 1794 Fire Detected Shutdown PC 3.x
Bitmap 13 w/Cool-
down
40443 15 Fault Status Gas 1795 Compressor_Bypass_Posi- Warning PC 3.x
Bitmap 13 tion_High_Error
40444 0 Fault Status Gas 1796 Compressor_Bypass_Posi- Warning PC 3.x
Bitmap 14 tion_Low_Error
290
Addr. Bit # Name Fault Event Name Response Control
Code
40444 1 Fault Status Gas 1797 Compressor Bypass ctrl OORH Warning PC 3.x
Bitmap 14
40444 2 Fault Status Gas 1798 Compressor Bypass ctrl OORL Warning PC 3.x
Bitmap 14
40444 3 Fault Status Gas 1799 CB_Position_Err_Status Warning PC 3.x
Bitmap 14
40444 4 Fault Status Gas 1811 HIGH_SIDE_DRV2_High_Control_Er- Warning PC 3.x
Bitmap 14 ror (VPS)
40444 5 Fault Status Gas 1812 HIGH_SIDE_DRV2_Low_Control_Er- Warning PC 3.x
Bitmap 14 ror (VPS)
40444 6 Fault Status Gas 1813 Valve_Proving_Sys- Warning PC 3.x
Bitmap 14 tem_Test_Failed_Warning_Error
40444 7 Fault Status Gas 1814 Valve_Proving_Sys- Shutdown PC 3.x
Bitmap 14 tem_Test_Failed_Shutdown_Error w/Cool-
down
40444 8 Fault Status Gas 1815 RLY14_High_Control_Error Warning PC 3.x
Bitmap 14
40444 9 Fault Status Gas 1816 Oil PreHtr Ctrl OOR Low Warning PC 3.x
Bitmap 14
40444 10 Fault Status Gas 1817 Oil_Pre−Heater_Tripped_Error Warning PC 3.x
Bitmap 14
40444 11 Fault Status Gas 1818 Oil_Pre−Heater_Not_Warming_Error Warning PC 3.x
Bitmap 14
40444 12 Fault Status Gas 1819 Common AC Aux CB tripped Warning PC 3.x
Bitmap 14
40444 13 Fault Status Gas 1821 Min_FSO_Speed_Error Shutdown PC 3.x
Bitmap 14 w/Cool-
down
40444 14 Fault Status Gas 1822 LT Coolant Level Low Shutdown Error Shutdown PC 3.x
Bitmap 14 w/Cool-
down
40444 15 Fault Status Gas 1823 LT Coolant Level Low Warning Error Warning PC 3.x
Bitmap 14
40445 0 Fault Status Gas 1824 Idle_Rated_Trans_Oil_Temp_Low_Er- Warning PC 3.x
Bitmap 15 ror
40445 1 Fault Status Gas 1825 Dirty_Oil_Level_Error Warning PC 3.x
Bitmap 15
40445 2 Fault Status Gas 1826 ECM Software incompatible Shutdown PC 3.x
Bitmap 15 w/Cool-
down
40445 3 Fault Status Gas 1827 Fuel_Inlet_Pressure_High_Error Warning PC 3.x
Bitmap 15
40445 4 Fault Status Gas 1828 Fuel_Inlet_Pressure_Low_Error Warning PC 3.x
Bitmap 15
40445 5 Fault Status Gas 1829 Vent_Gas_Valve_Error Shutdown PC 3.x
Bitmap 15 w/Cool-
down
40445 6 Fault Status Gas 1831 Upstream_FSO_Valve_Error Shutdown PC 3.x
Bitmap 15 w/Cool-
down
291
Addr. Bit # Name Fault Event Name Response Control
Code
40445 7 Fault Status Gas 1832 Downstream_FSO_Valve_Error Shutdown PC 3.x
Bitmap 15 w/Cool-
down
40445 8 Fault Status Gas 1833 Engine_Heater_Trip_Error Warning PC 3.x
Bitmap 15
40445 9 Fault Status Gas 1834 Coolant_Pump_Trip_Error Warning PC 3.x
Bitmap 15
40445 10 Fault Status Gas 1835 Oil_Priming_Pump_Tripped_Error Warning PC 3.x
Bitmap 15
40445 11 Fault Status Gas 1836 LCP_(LT)_Low_Serious_Error Shutdown PC 3.x
Bitmap 15 w/Cool-
down
40445 12 Fault Status Gas 1837 Permanent_FS_Cam_Sync_Lost_Er- Shutdown PC 3.x
Bitmap 15 ror w/Cool-
down
40445 13 Fault Status Gas 1838 Partial_Engine_Overload_Shut- Shutdown PC 3.x
Bitmap 15 down_Error w/Cool-
down
40445 14 Fault Status Gas 1839 Fuel_Supply_Pressure_High_Error Warning PC 3.x
Bitmap 15
40445 15 Fault Status Gas 1841 Fuel_Supply_Pressure_Low_Error Warning PC 3.x
Bitmap 15
40446 0 Fault Status Gas 1842 Radiator_Fan_Trip_Error Warning PC 3.x
Bitmap 16
40446 1 Fault Status Gas 1858 Exhaust Aft Inlet O2 OOR High Warning PC 3.x
Bitmap 16
40446 2 Fault Status Gas 1859 Exhaust Aft Inlet O2 OOR Low Warning PC 3.x
Bitmap 16
40446 3 Fault Status Gas 1861 Exhaust Aft Inlet O2 Incorrect Warning PC 3.x
Bitmap 16
40446 4 Fault Status Gas 1862 Exhaust Aft Out O2 OOR High Warning PC 3.x
Bitmap 16
40446 5 Fault Status Gas 1863 Exhaust Aft Outlet O2 OOR Low Warning PC 3.x
Bitmap 16
40446 6 Fault Status Gas 1864 Exhaust Aft Outlet O2 Incorrect Warning PC 3.x
Bitmap 16
40446 7 Fault Status Gas 1985 Int Man 3 Tmp Moderate High Warning PC 3.x
Bitmap 16
40446 8 Fault Status Gas 1986 Int Man 4 Tmp Moderate High Warning PC 3.x
Bitmap 16
40446 9 Fault Status Gas 2111 Coolant_Inlet_Temperatu- Warning PC 3.x
Bitmap 16 re_(LT)_High_Error
40446 10 Fault Status Gas 2112 Coolant_Inlet_Temperatu- Warning PC 3.x
Bitmap 16 re_(LT)_Low_Error
40446 11 Fault Status Gas 2113 CIT_(LT)_High_Warning_Error Warning PC 3.x
Bitmap 16
40446 12 Fault Status Gas 2114 CIT_(LT)_High_Serious_Error Shutdown PC 3.x
Bitmap 16 w/Cool-
down
292
Addr. Bit # Name Fault Event Name Response Control
Code
40446 13 Fault Status Gas 2115 LT_Coolant_Pressure_High_Error Warning PC 3.x
Bitmap 16
40446 14 Fault Status Gas 2116 LT_Coolant_Pressure_Low_Error Warning PC 3.x
Bitmap 16
40446 15 Fault Status Gas 2117 LCP_(LT)_Low_Warning_Error Warning PC 3.x
Bitmap 16
40447 0 Fault Status Gas 2121 Exhaust_Temp_1_(A1)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 1 Fault Status Gas 2122 Exhaust_Temp_3_(A2)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 2 Fault Status Gas 2123 Exhaust_Temp_5_(A3)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 3 Fault Status Gas 2124 Exhaust_Temp_7_(A4)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 4 Fault Status Gas 2125 Exhaust_Temp_9_(A5)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 5 Fault Status Gas 2126 Exhaust_Temp_11_(A6)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 6 Fault Status Gas 2127 Exhaust_Temp_13_(A7)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 7 Fault Status Gas 2128 Exhaust_Temp_15_(A8)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 8 Fault Status Gas 2129 Exhaust_Temp_17_(A9)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 9 Fault Status Gas 2131 Exhaust_Temp_2_(B1)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 10 Fault Status Gas 2132 Exhaust_Temp_4_(B2)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 11 Fault Status Gas 2133 Exhaust_Temp_6_(B3)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 12 Fault Status Gas 2134 Exhaust_Temp_8_(B4)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 13 Fault Status Gas 2135 Exhaust_Temp_10_(B5)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 14 Fault Status Gas 2136 Exhaust_Temp_12_(B6)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40447 15 Fault Status Gas 2137 Exhaust_Temp_14_(B7)_High_Warn- Warning PC 3.x
Bitmap 17 ing_Error
40448 0 Fault Status Gas 2138 Exhaust_Temp_16_(B8)_High_Warn- Warning PC 3.x
Bitmap 18 ing_Error
40448 1 Fault Status Gas 2139 Exhaust_Temp_18_(B9)_High_Warn- Warning PC 3.x
Bitmap 18 ing_Error
40448 2 Fault Status Gas 2141 Start_Air_Pressure_High_Error Warning PC 3.x
Bitmap 18
40448 3 Fault Status Gas 2142 Start_Air_Pressure_Low_Error Warning PC 3.x
Bitmap 18
40448 4 Fault Status Gas 2143 SAP_Overpressure_Error Warning PC 3.x
Bitmap 18
293
Addr. Bit # Name Fault Event Name Response Control
Code
40448 5 Fault Status Gas 2144 Exhaust Temp 16 (B8) High Serious Shutdown PC 3.x
Bitmap 18 Error w/Cool-
down
40448 6 Fault Status Gas 2145 Exhaust Temp 18 (B9) High Serious Shutdown PC 3.x
Bitmap 18 Error w/Cool-
down
40448 7 Fault Status Gas 2146 EGT 17 (A9) OOR Low Warning PC 3.x
Bitmap 18
40448 8 Fault Status Gas 2147 EGT 18 (B9) OOR Low Warning PC 3.x
Bitmap 18
40448 9 Fault Status Gas 2154 Oil_Filter_Outlet_Pressure_High_Error Warning PC 3.x
Bitmap 18
40448 10 Fault Status Gas 2155 Oil_Filter_Outlet_Pressure_Low_Error Warning PC 3.x
Bitmap 18
40448 11 Fault Status Gas 2157 Int Man 2 Tmp Abnormal Rate Shutdown PC 3.x
Bitmap 18 w/Cool-
down
40448 12 Fault Status Gas 2158 Int Man 3 Tmp Abnormal Rate Shutdown PC 3.x
Bitmap 18 w/Cool-
down
40448 13 Fault Status Gas 2159 Int Man 4 Tmp Abnormal Rate Shutdown PC 3.x
Bitmap 18 w/Cool-
down
40448 14 Fault Status Gas 2188 Exhaust O2 OOR High Warning PC 3.x
Bitmap 18
40448 15 Fault Status Gas 2191 ST_Throttle_Press_Err_Status Warning PC 3.x
Bitmap 18
40449 0 Fault Status Gas 2192 Exhaust O2 OOR Low Warning PC 3.x
Bitmap 19
40449 1 Fault Status Gas 2217 RAM_Image_Word_Error Warning PC 3.x
Bitmap 19
40449 2 Fault Status Gas 2219 Exhaust O2 Moderate High Warning PC 3.x
Bitmap 19
40449 3 Fault Status Gas 2221 Exhaust O2 Moderate Low Warning PC 3.x
Bitmap 19
40449 4 Fault Status Gas 2281 Knock 11 (A6) Moderate High Shutdown PC 3.x
Bitmap 19 w/Cool-
down
40449 5 Fault Status Gas 2282 Knock 11 (A6) Critical High Shutdown PC 3.x
Bitmap 19 w/Cool-
down
40449 6 Fault Status Gas 2298 Fuel Shutoff 2 OOR Low Warning PC 3.x
Bitmap 19
40449 7 Fault Status Gas 2315 Red Lamp OOR High Warning PC 3.x
Bitmap 19
40449 8 Fault Status Gas 2316 Amber Lamp OOR High Warning PC 3.x
Bitmap 19
40449 9 Fault Status Gas 2317 Amber Lamp OOR Low Warning PC 3.x
Bitmap 19
294
Addr. Bit # Name Fault Event Name Response Control
Code
40449 10 Fault Status Gas 2427 Fuel_Outlet_Pressure_High_Error Warning PC 3.x
Bitmap 19
40449 11 Fault Status Gas 2428 Fuel_Outlet_Pressure_Low_Error Warning PC 3.x
Bitmap 19
40449 12 Fault Status Gas 2453 Total Real Power Circuit OORH Warning PC 3.x
Bitmap 19
40449 13 Fault Status Gas 2454 Total Real Power Circuit OORL Warning PC 3.x
Bitmap 19
40449 14 Fault Status Gas 2455 Speed_Bias_Low_Error Warning PC 3.x
Bitmap 19
40449 15 Fault Status Gas 2456 Speed_Bias_High_Error Warning PC 3.x
Bitmap 19
40450 0 Fault Status Gas 2457 Max_Total_Misfire_Error Shutdown PC 3.x
Bitmap 20 w/Cool-
down
40450 1 Fault Status Gas 2458 Cylinder_2_(B1)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 2 Fault Status Gas 2459 Cylinder_4_(B2)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 3 Fault Status Gas 2461 Cylinder_6_(B3)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 4 Fault Status Gas 2462 Cylinder_8_(B4)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 5 Fault Status Gas 2463 Cylinder_10_(B5)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 6 Fault Status Gas 2464 Cylinder_12_(B6)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 7 Fault Status Gas 2465 Cylinder_14_(B7)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 8 Fault Status Gas 2466 Cylinder_16_(B8)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 9 Fault Status Gas 2467 Cylinder_18_(B9)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 10 Fault Status Gas 2469 Cylinder_1_(A1)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 11 Fault Status Gas 2471 Cylinder_3_(A2)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 12 Fault Status Gas 2472 Cylinder_5_(A3)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 13 Fault Status Gas 2473 Cylinder_7_(A4)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 14 Fault Status Gas 2475 Cylinder_9_(A5)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40450 15 Fault Status Gas 2476 Cylinder_11_(A6)_Total_Misfire_Error Warning PC 3.x
Bitmap 20
40451 0 Fault Status Gas 2477 Cylinder_13_(A7)_Total_Misfire_Error Warning PC 3.x
Bitmap 21
40451 1 Fault Status Gas 2478 Cylinder_15_(A8)_Total_Misfire_Error Warning PC 3.x
Bitmap 21
295
Addr. Bit # Name Fault Event Name Response Control
Code
40451 2 Fault Status Gas 2479 Cylinder_17_(A9)_Total_Misfire_Error Warning PC 3.x
Bitmap 21
40451 3 Fault Status Gas 2482 Start_Before_Ready_Error Shutdown PC 3.x
Bitmap 21 w/Cool-
down
40451 4 Fault Status Gas 2483 Continuous_Starter_Failure_Error Shutdown PC 3.x
Bitmap 21 w/Cool-
down
40451 5 Fault Status Gas 2484 Exhaust Temperature 1 (A1) Abnormal Shutdown PC 3.x
Bitmap 21 Rate w/Cool-
down
40451 6 Fault Status Gas 2485 Exhaust Temperature 3 (A2) Abnormal Shutdown PC 3.x
Bitmap 21 Rate w/Cool-
down
40451 7 Fault Status Gas 2486 Exhaust Temperature 5 (A3) Abnormal Shutdown PC 3.x
Bitmap 21 Rate w/Cool-
down
40451 8 Fault Status Gas 2487 Exhaust Temperature 7 (A4) Abnormal Shutdown PC 3.x
Bitmap 21 Rate w/Cool-
down
40451 9 Fault Status Gas 2488 Exhaust Temperature 9 (A5) Abnormal Shutdown PC 3.x
Bitmap 21 Rate w/Cool-
down
40451 10 Fault Status Gas 2489 Exhaust Temperature 11 (A6) Abnor- Shutdown PC 3.x
Bitmap 21 mal Rate w/Cool-
down
40451 11 Fault Status Gas 2491 Exhaust Temperature 13 (A7) Abnor- Shutdown PC 3.x
Bitmap 21 mal Rate w/Cool-
down
40451 12 Fault Status Gas 2492 Exhaust Temperature 15 (A8) Abnor- Shutdown PC 3.x
Bitmap 21 mal Rate w/Cool-
down
40451 13 Fault Status Gas 2493 Exhaust Temperature 17 (A9) Abnor- Shutdown PC 3.x
Bitmap 21 mal Rate w/Cool-
down
40451 14 Fault Status Gas 2494 Exhaust Temperature 2 (B1) Abnormal Shutdown PC 3.x
Bitmap 21 Rate w/Cool-
down
40451 15 Fault Status Gas 2495 Exhaust Temperature 4 (B2) Abnormal Shutdown PC 3.x
Bitmap 21 Rate w/Cool-
down
40452 0 Fault Status Gas 2496 Exhaust Temperature 6 (B3) Abnormal Shutdown PC 3.x
Bitmap 22 Rate w/Cool-
down
40452 1 Fault Status Gas 2497 Exhaust Temperature 8 (B4) Abnormal Shutdown PC 3.x
Bitmap 22 Rate w/Cool-
down
40452 2 Fault Status Gas 2498 Exhaust Temperature 10 (B5) Abnor- Shutdown PC 3.x
Bitmap 22 mal Rate w/Cool-
down
296
Addr. Bit # Name Fault Event Name Response Control
Code
40452 3 Fault Status Gas 2499 Exhaust Temperature 12 (B6) Abnor- Shutdown PC 3.x
Bitmap 22 mal Rate w/Cool-
down
40452 4 Fault Status Gas 2511 Exhaust Temperature 14 (B7) Abnor- Shutdown PC 3.x
Bitmap 22 mal Rate w/Cool-
down
40452 5 Fault Status Gas 2512 Exhaust Temperature 16 (B8) Abnor- Shutdown PC 3.x
Bitmap 22 mal Rate w/Cool-
down
40452 6 Fault Status Gas 2513 Exhaust Temperature 18 (B9) Abnor- Shutdown PC 3.x
Bitmap 22 mal Rate w/Cool-
down
40452 7 Fault Status Gas 2517 Compressor_Outlet_Pres- Warning PC 3.x
Bitmap 22 sure_High_Error
40452 8 Fault Status Gas 2518 Compressor_Outlet_Pres- Warning PC 3.x
Bitmap 22 sure_Low_Error
40452 9 Fault Status Gas 2521 Bank_Id_Error Shutdown PC 3.x
Bitmap 22 w/Cool-
down
40452 10 Fault Status Gas 2522 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 22 ror_1_(A1) w/Cool-
down
40452 11 Fault Status Gas 2523 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 22 ror_2_(B1) w/Cool-
down
40452 12 Fault Status Gas 2524 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 22 ror_3_(A2) w/Cool-
down
40452 13 Fault Status Gas 2525 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 22 ror_4_(B2) w/Cool-
down
40452 14 Fault Status Gas 2526 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 22 ror_5_(A3) w/Cool-
down
40452 15 Fault Status Gas 2527 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 22 ror_6_(B3) w/Cool-
down
40453 0 Fault Status Gas 2528 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 23 ror_7_(A4) w/Cool-
down
40453 1 Fault Status Gas 2529 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 23 ror_8_(B4) w/Cool-
down
40453 2 Fault Status Gas 2531 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 23 ror_9_(A5) w/Cool-
down
40453 3 Fault Status Gas 2532 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 23 ror_10_(B5) w/Cool-
down
297
Addr. Bit # Name Fault Event Name Response Control
Code
40453 4 Fault Status Gas 2544 ECM_Overtemp_Error Shutdown PC 3.x
Bitmap 23 w/Cool-
down
40453 5 Fault Status Gas 2567 DG_Air_Compressor_Trip_Error Warning PC 3.x
Bitmap 23
40453 6 Fault Status Gas 2643 Throttle Pos 2 Feedback OOR High Warning PC 3.x
Bitmap 23
40453 7 Fault Status Gas 2644 Throttle Pos 2 Feedback OOR Low Warning PC 3.x
Bitmap 23
40453 8 Fault Status Gas 2661 At Least One ACK: Most Severe Fault Shutdown PC 2.x, PC
Bitmap 23 3.x
40453 9 Fault Status Gas 2724 Gas Supply Pr Moderate High Warning PC 3.x
Bitmap 23
40453 10 Fault Status Gas 2725 Gas Supply Pr Moderate Low Warning PC 3.x
Bitmap 23
40453 11 Fault Status Gas 2737 Exh Gas Tmp Critical High Shutdown PC 3.x
Bitmap 23 w/Cool-
down
40453 12 Fault Status Gas 2766 Bank_A_CCD_Failed_Error Shutdown PC 3.x
Bitmap 23 w/Cool-
down
40453 13 Fault Status Gas 2767 Bank_B_CCD_Failed_Error Shutdown PC 3.x
Bitmap 23 w/Cool-
down
40453 14 Fault Status Gas 2768 CAN Parent Communication Incorrect Shutdown PC 3.x
Bitmap 23 w/Cool-
down
40453 15 Fault Status Gas 2769 CAN Child Com Incorrect Shutdown PC 3.x
Bitmap 23 w/Cool-
down
40454 0 Fault Status Gas 2789 COT_Low_Error Warning PC 3.x
Bitmap 24
40454 1 Fault Status Gas 2793 COT_Low_Serious_Error Shutdown PC 3.x
Bitmap 24 w/Cool-
down
40454 2 Fault Status Gas 2794 Ign Shutd Relay OOR High Warning PC 3.x
Bitmap 24
40454 3 Fault Status Gas 2795 Ign Shutd Relay OOR Low Warning PC 3.x
Bitmap 24
40454 4 Fault Status Gas 2796 Partial_Engine_Overload_Warn- Warning PC 3.x
Bitmap 24 ing_Error
40454 5 Fault Status Gas 2797 Inlet Gas Diff Pressure OOR High Warning PC 3.x
Bitmap 24
40454 6 Fault Status Gas 2798 Inlet Gas Diff Pressure OOR Low Warning PC 3.x
Bitmap 24
40454 7 Fault Status Gas 2799 IMOP_Compressor_Outlet_Pres- Shutdown PC 3.x
Bitmap 24 ure_Delta_Error w/Cool-
down
298
Addr. Bit # Name Fault Event Name Response Control
Code
40454 8 Fault Status Gas 2811 IMOP_Compressor_Outlet_Pres- Shutdown PC 3.x
Bitmap 24 sure_Maximum_Error w/Cool-
down
40454 9 Fault Status Gas 2837 Exhaust_Temp_1_(A1)_Deviation_Er- Warning PC 3.x
Bitmap 24 ror
40454 10 Fault Status Gas 2838 Exhaust_Temp_3_(A2)_Deviation_Er- Warning PC 3.x
Bitmap 24 ror
40454 11 Fault Status Gas 2839 Exhaust_Temp_5_(A3)_Deviation_Er- Warning PC 3.x
Bitmap 24 ror
40454 12 Fault Status Gas 2841 Exhaust_Temp_7_(A4)_Deviation_Er- Warning PC 3.x
Bitmap 24 ror
40454 13 Fault Status Gas 2842 Exhaust_Temp_9_(A5)_Deviation_Er- Warning PC 3.x
Bitmap 24 ror
40454 14 Fault Status Gas 2843 Exhaust_Temp_11_(A6)_Devi- Warning PC 3.x
Bitmap 24 ation_Error
40454 15 Fault Status Gas 2844 Exhaust_Temp_13_(A7)_Devi- Warning PC 3.x
Bitmap 24 ation_Error
40455 0 Fault Status Gas 2845 Exhaust_Temp_15_(A8)_Devi- Warning PC 3.x
Bitmap 25 ation_Error
40455 1 Fault Status Gas 2846 Exhaust_Temp_17_(A9)_Devi- Warning PC 3.x
Bitmap 25 ation_Error
40455 2 Fault Status Gas 2847 Exhaust_Temp_2_(B1)_Deviation_Er- Warning PC 3.x
Bitmap 25 ror
40455 3 Fault Status Gas 2848 Exhaust_Temp_4_(B2)_Deviation_Er- Warning PC 3.x
Bitmap 25 ror
40455 4 Fault Status Gas 2849 Exhaust_Temp_6_(B3)_Deviation_Er- Warning PC 3.x
Bitmap 25 ror
40455 5 Fault Status Gas 2851 Exhaust_Temp_8_(B4)_Deviation_Er- Warning PC 3.x
Bitmap 25 ror
40455 6 Fault Status Gas 2852 Exhaust_Temp_10_(B5)_Devi- Warning PC 3.x
Bitmap 25 ation_Error
40455 7 Fault Status Gas 2853 Exhaust_Temp_12_(B6)_Devi- Warning PC 3.x
Bitmap 25 ation_Error
40455 8 Fault Status Gas 2854 Exhaust_Temp_14_(B7)_Devi- Warning PC 3.x
Bitmap 25 ation_Error
40455 9 Fault Status Gas 2855 Exhaust_Temp_16_(B8)_Devi- Warning PC 3.x
Bitmap 25 ation_Error
40455 10 Fault Status Gas 2856 Exhaust_Temp_18_(B9)_Devi- Warning PC 3.x
Bitmap 25 ation_Error
40455 11 Fault Status Gas 2857 Turbo_1_Overspeed_Critical_Error Shutdown PC 3.x
Bitmap 25 w/Cool-
down
40455 12 Fault Status Gas 2858 Turbo_2_Overspeed_Critical_Error Shutdown PC 3.x
Bitmap 25 w/Cool-
down
40455 13 Fault Status Gas 2859 Alt Heater Ctrl OOR High Warning PC 3.x
Bitmap 25
40455 14 Fault Status Gas 2861 Alt Heater Ctrl OOR Low Warning PC 3.x
Bitmap 25
299
Addr. Bit # Name Fault Event Name Response Control
Code
40455 15 Fault Status Gas 2862 Gen Alternator 1st Start Cond Exists Warning PC 3.x
Bitmap 25
40456 0 Fault Status Gas 2863 Genset to Engine Com Incorrect Shutdown PC 3.x
Bitmap 26 w/Cool-
down
40456 1 Fault Status Gas 2864 FSO_NON_High_Control_Error Shutdown PC 3.x
Bitmap 26 w/Cool-
down
40456 2 Fault Status Gas 3364 Power Conservation Control Cond Ex- Warning PC 3.x
Bitmap 26 ists
40456 3 Fault Status Gas 2866 FCV_Position_High_Error Warning PC 3.x
Bitmap 26
40456 4 Fault Status Gas 2867 FCV_Position_Low_Error Warning PC 3.x
Bitmap 26
40456 5 Fault Status Gas 2868 Engine_Heater_Over−Tempera- Warning PC 3.x
Bitmap 26 ture_Alarm_Error
40456 6 Fault Status Gas 2869 HT Cool Temp Driver OOR High Warning PC 3.x
Bitmap 26
40456 7 Fault Status Gas 2871 HT Cool Temp Driver OOR Low Warning PC 3.x
Bitmap 26
40456 8 Fault Status Gas 2872 HT Cool Temp Driver Cond Exists Warning PC 3.x
Bitmap 26
40456 9 Fault Status Gas 2873 LT Cool Temp Driver OOR High Warning PC 3.x
Bitmap 26
40456 10 Fault Status Gas 2874 LT Cool Temp Driver OOR Low Warning PC 3.x
Bitmap 26
40456 11 Fault Status Gas 2875 LT Cool Temp Driver Cond Exists Warning PC 3.x
Bitmap 26
40456 12 Fault Status Gas 2876 Comp_Surge_Shutdown_Error Shutdown PC 3.x
Bitmap 26 w/Cool-
down
40456 13 Fault Status Gas 2877 Comp_Surge_Derate_Error Warning PC 3.x
Bitmap 26
40456 14 Fault Status Gas 2994 MC68302_Error Warning PC 3.x
Bitmap 26
40456 15 Fault Status Gas 2995 Int Man Pressure 1 Critical High Shutdown PC 3.x
Bitmap 26 w/Cool-
down
40457 0 Fault Status Gas 2996 Int Man Pressure 1 Moderate High Warning PC 3.x
Bitmap 27
40457 1 Fault Status Gas 2997 Exhaust O2 Critical Low Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 2 Fault Status Gas 3111 Excessive_Mech_Vibration_1_(A1) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 3 Fault Status Gas 3112 Excessive_Mech_Vibration_2_(B1) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
300
Addr. Bit # Name Fault Event Name Response Control
Code
40457 4 Fault Status Gas 3113 Excessive_Mech_Vibration_3_(A2) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 5 Fault Status Gas 3114 Excessive_Mech_Vibration_4_(B2) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 6 Fault Status Gas 3115 Excessive_Mech_Vibration_5_(A3) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 7 Fault Status Gas 3116 Excessive_Mech_Vibration_6_(B3) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 8 Fault Status Gas 3117 Excessive_Mech_Vibration_7_(A4) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 9 Fault Status Gas 3118 Excessive_Mech_Vibration_8_(B4) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 10 Fault Status Gas 3119 Excessive_Mech_Vibration_9_(A5) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 11 Fault Status Gas 3121 Excessive_Mech_Vibration_10_(B5) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 12 Fault Status Gas 3122 Excessive_Mech_Vibration_11_(A6) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 13 Fault Status Gas 3123 Excessive_Mech_Vibration_12_(B6) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 14 Fault Status Gas 3124 Excessive_Mech_Vibration_13_(A7) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40457 15 Fault Status Gas 3125 Excessive_Mech_Vibration_14_(B7) Shutdown PC 3.x
Bitmap 27 w/Cool-
down
40458 0 Fault Status Gas 3126 Excessive_Mech_Vibration_15_(A8) Shutdown PC 3.x
Bitmap 28 w/Cool-
down
40458 1 Fault Status Gas 3127 Excessive_Mech_Vibration_16_(B8) Shutdown PC 3.x
Bitmap 28 w/Cool-
down
40458 2 Fault Status Gas 3128 Excessive_Mech_Vibration_17_(A9) Shutdown PC 3.x
Bitmap 28 w/Cool-
down
40458 3 Fault Status Gas 3129 Excessive_Mech_Vibration_18_(B9) Shutdown PC 3.x
Bitmap 28 w/Cool-
down
40458 4 Fault Status Gas 1275 Knock Cyl 10 (B5) OORL Warning PC 3.x
Bitmap 28
301
Addr. Bit # Name Fault Event Name Response Control
Code
40458 5 Fault Status Gas 1277 Knock Cyl 11 (A6) OORL Warning PC 3.x
Bitmap 28
40458 6 Fault Status Gas 1282 Knock Cyl 12 (B6) OORL Warning PC 3.x
Bitmap 28
40458 7 Fault Status Gas 1287 Knock Cyl 13 (A7) OORL Warning PC 3.x
Bitmap 28
40458 8 Fault Status Gas 1292 Knock Cyl 14 (B7) OORL Warning PC 3.x
Bitmap 28
40458 9 Fault Status Gas 1297 Knock Cyl 15 (A8) OORL Warning PC 3.x
Bitmap 28
40458 10 Fault Status Gas 1584 Knock Cyl 16 (B8) OORL Warning PC 3.x
Bitmap 28
40458 11 Fault Status Gas 1589 Knock Cyl 17 (A9) OORL Warning PC 3.x
Bitmap 28
40458 12 Fault Status Gas 1338 Knock Cyl 18 (B9) OORL Warning PC 3.x
Bitmap 28
40459 0 Fault Status Gas 189 HT Coolant Temperature Root Cause Shutdown PC 3.x
Bitmap 29 Unknown w/Cool-
down
40459 1 Fault Status Gas 229 HT Coolant Pressure Incorrect Warning PC 3.x
Bitmap 29
40459 2 Fault Status Gas 334 HT Coolant Temperature Incorrect Warning PC 3.x
Bitmap 29
40459 4 Fault Status Gas 831 Spark Plug 1 (A1) OORL Warning PC 3.x
Bitmap 29
40459 5 Fault Status Gas 832 Spark Plug 2 (B1) OORL Warning PC 3.x
Bitmap 29
40459 6 Fault Status Gas 833 Spark Plug 3 (A2) OORL Warning PC 3.x
Bitmap 29
40459 7 Fault Status Gas 834 Spark Plug 4 (B2) OORL Warning PC 3.x
Bitmap 29
40459 8 Fault Status Gas 835 Spark Plug 5 (A3) OORL Warning PC 3.x
Bitmap 29
40459 9 Fault Status Gas 836 Spark Plug 6 (B3) OORL Warning PC 3.x
Bitmap 29
40459 10 Fault Status Gas 837 Spark Plug 7 (A4) OORL Warning PC 3.x
Bitmap 29
40459 11 Fault Status Gas 838 Spark Plug 8 (B4) OORL Warning PC 3.x
Bitmap 29
40459 12 Fault Status Gas 839 Spark Plug 9 (A5) OORL Warning PC 3.x
Bitmap 29
40459 13 Fault Status Gas 841 Spark Plug 10 (B5) OORL Warning PC 3.x
Bitmap 29
40459 14 Fault Status Gas 842 Spark Plug 11 (A6) OORL Warning PC 3.x
Bitmap 29
40459 15 Fault Status Gas 843 Spark Plug 12 (B6) OORL Warning PC 3.x
Bitmap 29
40460 0 Fault Status Gas 844 Spark Plug 13 (A7) OORL Warning PC 3.x
Bitmap 30
302
Addr. Bit # Name Fault Event Name Response Control
Code
40460 1 Fault Status Gas 845 Spark Plug 14 (B7) OORL Warning PC 3.x
Bitmap 30
40460 2 Fault Status Gas 846 Spark Plug 15 (A8) OORL Warning PC 3.x
Bitmap 30
40460 3 Fault Status Gas 847 Spark Plug 16 (B8) OORL Warning PC 3.x
Bitmap 30
40460 4 Fault Status Gas 848 Spark Plug 17 (A9) OORL Warning PC 3.x
Bitmap 30
40460 5 Fault Status Gas 849 Spark Plug 18 (B9) OORL Warning PC 3.x
Bitmap 30
40460 7 Fault Status Gas 891 Spark Plug 1 (A1) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40460 8 Fault Status Gas 892 Spark Plug 2 (B1) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40460 9 Fault Status Gas 893 Spark Plug 3 (A2) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40460 10 Fault Status Gas 894 Spark Plug 4 (B2) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40460 11 Fault Status Gas 895 Spark Plug 5 (A3) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40460 12 Fault Status Gas 896 Spark Plug 6 (B3) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40460 13 Fault Status Gas 897 Spark Plug 7 (A4) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40460 14 Fault Status Gas 898 Spark Plug 8 (B4) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40460 15 Fault Status Gas 899 Spark Plug 9 (A5) Root Cause Un- Warning PC 3.x
Bitmap 30 known
40461 0 Fault Status Gas 911 Spark Plug 10 (B5) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 1 Fault Status Gas 912 Spark Plug 11 (A6) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 2 Fault Status Gas 913 Spark Plug 12 (B6) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 3 Fault Status Gas 914 Spark Plug 13 (A7) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 4 Fault Status Gas 915 Spark Plug 14 (B7) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 5 Fault Status Gas 916 Spark Plug 15 (A8) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 6 Fault Status Gas 917 Spark Plug 16 (B8) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 7 Fault Status Gas 918 Spark Plug 17 (A9) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 8 Fault Status Gas 919 Spark Plug 18 (B9) Root Cause Un- Warning PC 3.x
Bitmap 31 known
40461 10 Fault Status Gas 1276 Knock Cyl 10 (B5) OORH Warning PC 3.x
Bitmap 31
40461 11 Fault Status Gas 1278 Knock Cyl 11 (A6) OORH Warning PC 3.x
Bitmap 31
303
Addr. Bit # Name Fault Event Name Response Control
Code
40461 12 Fault Status Gas 1279 Knock 12 (B6) High Warning Warning PC 3.x
Bitmap 31
40461 13 Fault Status Gas 1283 Knock Cyl 12 (B6) OORH Warning PC 3.x
Bitmap 31
40461 14 Fault Status Gas 1284 Knock 13 (A7) High Warning Warning PC 3.x
Bitmap 31
40461 15 Fault Status Gas 1288 Knock Cyl 13 (A7) OORH Warning PC 3.x
Bitmap 31
40462 0 Fault Status Gas 1289 Knock 14 (B7) High Warning Warning PC 3.x
Bitmap 32
40462 1 Fault Status Gas 1293 Knock Cyl 14 (B7) OORH Warning PC 3.x
Bitmap 32
40462 2 Fault Status Gas 1294 Knock 15 (A8) High Warning Warning PC 3.x
Bitmap 32
40462 3 Fault Status Gas 1298 Knock Cyl 15 (A8) OORH Warning PC 3.x
Bitmap 32
40462 4 Fault Status Gas 1299 Knock 16 (B8) High Warning Warning PC 3.x
Bitmap 32
40462 6 Fault Status Gas 1339 Knock Cyl 18 (B9) OORH Warning PC 3.x
Bitmap 32
40462 7 Fault Status Gas 1352 Knock 20 (B10) High Warning Warning PC 3.x
Bitmap 32
40462 8 Fault Status Gas 1353 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 32 ror_20_(B10) w/Cool-
down
40462 9 Fault Status Gas 1354 Heavy_Knock_Error_20_(B10) Shutdown PC 3.x
Bitmap 32 w/Cool-
down
40462 10 Fault Status Gas 1355 Knock Cyl 20 (B10) OORL Warning PC 3.x
Bitmap 32
40462 11 Fault Status Gas 1356 Knock Cyl 20 (B10) OORH Warning PC 3.x
Bitmap 32
40462 12 Fault Status Gas 1572 Continuous_Light_Knock_Er- Shutdown PC 3.x
Bitmap 32 ror_19_(A10) w/Cool-
down
40462 13 Fault Status Gas 1574 Heavy_Knock_Error_19_(A10) Shutdown PC 3.x
Bitmap 32 w/Cool-
down
40462 14 Fault Status Gas 1575 Knock Cyl 19 (A10) OORL Warning PC 3.x
Bitmap 32
40462 15 Fault Status Gas 1576 Knock Cyl 19 (A10) OORH Warning PC 3.x
Bitmap 32
40463 0 Fault Status Gas 1585 Knock Cyl 16 (B8) OORH Warning PC 3.x
Bitmap 33
40463 1 Fault Status Gas 1586 Knock 17 (A9) High Warning Warning PC 3.x
Bitmap 33
40463 2 Fault Status Gas 1591 Knock Cyl 17 (A9) OORH Warning PC 3.x
Bitmap 33
40463 3 Fault Status Gas 1592 Knock 18 (B9) High Warning Warning PC 3.x
Bitmap 33
304
Addr. Bit # Name Fault Event Name Response Control
Code
40463 4 Fault Status Gas 1594 Knock 19 (A10) High Warning Warning PC 3.x
Bitmap 33
40463 6 Fault Status Gas 2193 HT Coolant Level Moderate High Warning PC 3.x
Bitmap 33
40463 7 Fault Status Gas 2231 Knock Cyl 1 (A1) OORH Warning PC 3.x
Bitmap 33
40463 8 Fault Status Gas 2232 Knock Cyl 2 (B1) OORH Warning PC 3.x
Bitmap 33
40463 9 Fault Status Gas 2233 Knock Cyl 3 (A2) OORH Warning PC 3.x
Bitmap 33
40463 10 Fault Status Gas 2234 Knock Cyl 4 (B2) OORH Warning PC 3.x
Bitmap 33
40463 11 Fault Status Gas 2235 Knock Cyl 5 (A3) OORH Warning PC 3.x
Bitmap 33
40463 12 Fault Status Gas 2236 Knock Cyl 6 (B3) OORH Warning PC 3.x
Bitmap 33
40463 13 Fault Status Gas 2237 Knock Cyl 7 (A4) OORH Warning PC 3.x
Bitmap 33
40463 14 Fault Status Gas 2238 Knock Cyl 8 (B4) OORH Warning PC 3.x
Bitmap 33
40463 15 Fault Status Gas 2239 Knock Cyl 9 (A5) OORH Warning PC 3.x
Bitmap 33
40464 0 Fault Status Gas 2279 Knock 11 (A6) High Warning Warning PC 3.x
Bitmap 34
40464 1 Fault Status Gas 2431 Knock 1 (A1) High Warning Warning PC 3.x
Bitmap 34
40464 2 Fault Status Gas 2432 Knock 2 (B1) High Warning Warning PC 3.x
Bitmap 34
40464 3 Fault Status Gas 2433 Knock 3 (A2) High Warning Warning PC 3.x
Bitmap 34
40464 4 Fault Status Gas 2434 Knock 4 (B2) High Warning Warning PC 3.x
Bitmap 34
40464 5 Fault Status Gas 2435 Knock 5 (A3) High Warning Warning PC 3.x
Bitmap 34
40464 6 Fault Status Gas 2436 Knock 6 (B3) High Warning Warning PC 3.x
Bitmap 34
40464 7 Fault Status Gas 2437 Knock 7 (A4) High Warning Warning PC 3.x
Bitmap 34
40464 8 Fault Status Gas 2438 Knock 8 (B4) High Warning Warning PC 3.x
Bitmap 34
40464 9 Fault Status Gas 2439 Knock 9 (A5) High Warning Warning PC 3.x
Bitmap 34
40464 10 Fault Status Gas 2441 Knock 10 (B5) High Warning Warning PC 3.x
Bitmap 34
40464 11 Fault Status Gas 2514 Exhaust Temperature 19 (A10) Abnor- Shutdown PC 3.x
Bitmap 34 mal Rate w/Cool-
down
40464 12 Fault Status Gas 2515 Exhaust Temperature 20 (B10) Abnor- Shutdown PC 3.x
Bitmap 34 mal Rate w/Cool-
down
305
Addr. Bit # Name Fault Event Name Response Control
Code
40464 13 Fault Status Gas 2553 Engine Oil Level Low Warning Error Warning PC 3.x
Bitmap 34
40464 14 Fault Status Gas 2568 Gas Supply Pressure Critical High Shutdown PC 3.x
Bitmap 34 w/Cool-
down
40464 15 Fault Status Gas 2569 Gas Supply Pressure Critical Low Shutdown PC 3.x
Bitmap 34 w/Cool-
down
40465 0 Fault Status Gas 2586 Spark Plug 1 (A1) High Warning NONE PC 3.x
Bitmap 35
40465 1 Fault Status Gas 2587 Spark Plug 2 (B1) High Warning NONE PC 3.x
Bitmap 35
40465 2 Fault Status Gas 2588 Spark Plug 3 (A2) High Warning NONE PC 3.x
Bitmap 35
40465 3 Fault Status Gas 2589 Spark Plug 4 (B2) High Warning NONE PC 3.x
Bitmap 35
40465 4 Fault Status Gas 2591 Spark Plug 5 (A3) High Warning NONE PC 3.x
Bitmap 35
40465 5 Fault Status Gas 2592 Spark Plug 6 (B3) High Warning NONE PC 3.x
Bitmap 35
40465 6 Fault Status Gas 2593 Spark Plug 1 (A1) Low Warning NONE PC 3.x
Bitmap 35
40465 7 Fault Status Gas 2594 Spark Plug 2 (B1) Low Warning NONE PC 3.x
Bitmap 35
40465 8 Fault Status Gas 2595 Spark Plug 3 (A2) Low Warning NONE PC 3.x
Bitmap 35
40465 9 Fault Status Gas 2596 Spark Plug 4 (B2) Low Warning NONE PC 3.x
Bitmap 35
40465 10 Fault Status Gas 2597 Spark Plug 5 (A3) Low Warning NONE PC 3.x
Bitmap 35
40465 11 Fault Status Gas 2598 Spark Plug 6 (B3) Low Warning NONE PC 3.x
Bitmap 35
40465 12 Fault Status Gas 2646 HT Coolant Temperature Condition Warning PC 3.x
Bitmap 35 Exists
40465 13 Fault Status Gas 2963 HT Coolant Temperature Warning NONE PC 2.x, PC
Bitmap 35 High 3.x
40466 0 Fault Status Gas 3262 Spark Plug 7 (A4) High Warning NONE PC 3.x
Bitmap 36
40466 1 Fault Status Gas 3263 Spark Plug 7 (A4) Low Warning NONE PC 3.x
Bitmap 36
40466 2 Fault Status Gas 3264 Spark Plug 8 (B4) High Warning NONE PC 3.x
Bitmap 36
40466 3 Fault Status Gas 3265 Spark Plug 8 (B4) Low Warning NONE PC 3.x
Bitmap 36
40466 4 Fault Status Gas 3266 Spark Plug 9 (A5) High Warning NONE PC 3.x
Bitmap 36
40466 5 Fault Status Gas 3267 Spark Plug 9 (A5) Low Warning NONE PC 3.x
Bitmap 36
40466 6 Fault Status Gas 3268 Spark Plug 10 (B5) High Warning NONE PC 3.x
Bitmap 36
306
Addr. Bit # Name Fault Event Name Response Control
Code
40466 7 Fault Status Gas 3269 Spark Plug 10 (B5) Low Warning NONE PC 3.x
Bitmap 36
40466 8 Fault Status Gas 3271 Spark Plug 11 (A6) High Warning NONE PC 3.x
Bitmap 36
40466 9 Fault Status Gas 3272 Spark Plug 11 (A6) Low Warning NONE PC 3.x
Bitmap 36
40466 10 Fault Status Gas 3273 Spark Plug 12 (B6) High Warning NONE PC 3.x
Bitmap 36
40466 11 Fault Status Gas 3274 Spark Plug 12 (B6) Low Warning NONE PC 3.x
Bitmap 36
40466 12 Fault Status Gas 3275 Spark Plug 13 (A7) High Warning NONE PC 3.x
Bitmap 36
40466 13 Fault Status Gas 3276 Spark Plug 13 (A7) Low Warning NONE PC 3.x
Bitmap 36
40466 14 Fault Status Gas 3277 Spark Plug 14 (B7) High Warning NONE PC 3.x
Bitmap 36
40466 15 Fault Status Gas 3278 Spark Plug 14 (B7) Low Warning NONE PC 3.x
Bitmap 36
40467 0 Fault Status Gas 3279 Spark Plug 15 (A8) High Warning NONE PC 3.x
Bitmap 37
40467 1 Fault Status Gas 3281 Spark Plug 15 (A8) Low Warning NONE PC 3.x
Bitmap 37
40467 2 Fault Status Gas 3282 Spark Plug 16 (B8) High Warning NONE PC 3.x
Bitmap 37
40467 3 Fault Status Gas 3283 Spark Plug 16 (B8) Low Warning NONE PC 3.x
Bitmap 37
40467 4 Fault Status Gas 3284 Spark Plug 17 (A9) High Warning NONE PC 3.x
Bitmap 37
40467 5 Fault Status Gas 3285 Spark Plug 17 (A9) Low Warning NONE PC 3.x
Bitmap 37
40467 6 Fault Status Gas 3286 Spark Plug 18 (B9) High Warning NONE PC 3.x
Bitmap 37
40467 7 Fault Status Gas 3287 Spark Plug 18 (B9) Low Warning NONE PC 3.x
Bitmap 37
40467 8 Fault Status Gas 3288 Exhaust Aft Outlet Oxygen Relay Warning PC 3.x
Bitmap 37 OORH
40467 9 Fault Status Gas 3289 Exhaust Aft Outlet Oxygen Relay Warning PC 3.x
Bitmap 37 OORL
40467 10 Fault Status Gas 3291 Exhaust Aft Inlet Oxygen Relay OORH Warning PC 3.x
Bitmap 37
40467 11 Fault Status Gas 3292 Exhaust Aft Inlet Oxygen Relay OORL Warning PC 3.x
Bitmap 37
40467 12 Fault Status Gas 3293 Exhaust Oxygen Relay OORH Warning PC 3.x
Bitmap 37
40467 13 Fault Status Gas 3294 Exhaust Oxygen Relay OORL Warning PC 3.x
Bitmap 37
40468 3 Fault Status Gas 3365 External Air Pressure Low Warning Er- Warning PC 3.x
Bitmap 38 ror
40468 4 Fault Status Gas 3384 Manifold_Absolute_Pres- Warning PC 3.x
Bitmap 38 sure_2_High_Error
307
Addr. Bit # Name Fault Event Name Response Control
Code
40468 5 Fault Status Gas 3391 Manifold_Absolute_Pres- Warning PC 3.x
Bitmap 38 sure_2_Low_Error
40468 6 Fault Status Gas 3392 Int Man Pressure 2 Critical High Shutdown PC 3.x
Bitmap 38 w/Cool-
down
40468 7 Fault Status Gas 3393 Int Man Pressure 2 Moderate High Warning PC 3.x
Bitmap 38
40468 9 Fault Status Gas 3397 Low Gearbox Oil Pressure − Condition Shutdown PC 3.x
Bitmap 38 Exists w/Cool-
down
40468 10 Fault Status Gas 3398 High Gearbox Oil Temperature − Con- Shutdown PC 3.x
Bitmap 38 dition Exists w/Cool-
down
40468 11 Fault Status Gas 3399 Differential Fault − Condition Exists Shutdown PC 3.x
Bitmap 38 w/Cool-
down
40468 12 Fault Status Gas 3411 DC Power Supply Fault − Condition Warning PC 3.x
Bitmap 38 Exists
40468 13 Fault Status Gas 3412 GIB Isolator Open Fault − Condition Warning PC 3.x
Bitmap 38 Exists
40468 14 Fault Status Gas 3413 Radiator Fan Trip Fault − Condition Warning PC 3.x
Bitmap 38 Exists
40468 15 Fault Status Gas 3414 Ventilator Fan Trip Fault − Condition Warning PC 3.x
Bitmap 38 Exists
40469 0 Fault Status Gas 3415 Louvres Closed Fault − Condition Ex- Warning PC 3.x
Bitmap 39 ists
40469 1 Fault Status Gas 3416 Start System Fault − Condition Exists Warning PC 3.x
Bitmap 39
40469 2 Fault Status Gas 3417 Alternator Heater Trip Fault − Condi- Warning PC 3.x
Bitmap 39 tion Exists
40469 4 Fault Status Gas 9971 ECM Derate Fault NONE PC 3.x
Bitmap 39
40469 5 Fault Status Gas 3479 Start−Inhibit Shutdown Fault Shutdown PC 3.x
Bitmap 39
40469 6 Fault Status Gas 3481 Start−Inhibit Warning Fault Event Warning PC 3.x
Bitmap 39
40469 7 Fault Status Gas 3483 High Alternator Temperature 1 Shut- Shutdown PC 2.x, PC
Bitmap 39 down Fault 3.x
40469 8 Fault Status Gas 3484 High Alternator Temperature 2 Shut- Shutdown PC 2.x, PC
Bitmap 39 down Fault 3.x
40469 9 Fault Status Gas 3485 High Alternator Temperature 3 Shut- Shutdown PC 2.x, PC
Bitmap 39 down Fault 3.x
40469 10 Fault Status Gas 3486 High Drive End Bearing Temperature Shutdown PC 2.x, PC
Bitmap 39 Shutdown Fault 3.x
40469 11 Fault Status Gas 3487 High Non−Drive End Bearing Temp Shutdown PC 2.x, PC
Bitmap 39 Shutdown Fault 3.x
40469 12 Fault Status Gas 3482 Off Load Running Fault Shutdown PC 3.x
Bitmap 39
40469 14 Fault Status Gas 463 Exhaust_Gas_Oxygen_High_Error Warning PC 3.x
Bitmap 39
308
Addr. Bit # Name Fault Event Name Response Control
Code
40469 15 Fault Status Gas 464 Exhaust_Gas_Oxygen_Low_Error Warning PC 3.x
Bitmap 39
40470 0 Fault Status Gas 3491 Oil Filter Restriction High Shutdown PC 3.x
Bitmap 40 w/Cool-
down
40470 1 Fault Status Gas 2313 Fuel Control Valve Error Warning PC 3.x
Bitmap 40
40470 2 Fault Status Gas 3475 Engine Electronic Fuel Valve #2 Warning PC 3.x
Bitmap 40 OORH
40470 3 Fault Status Gas 3476 Engine Electronic Fuel Valve #2 OORL Warning PC 3.x
Bitmap 40
40470 4 Fault Status Gas 2812 Throttle Control Actuator Error Shutdown PC 3.x
Bitmap 40 w/Cool-
down
40470 5 Fault Status Gas 3489 Compressor Bypass Actuator Error Warning PC 3.x
Bitmap 40
40470 6 Fault Status Gas 3458 Knock Engine Derate Warning PC 3.x
Bitmap 40
40470 7 Fault Status Gas 781 CAN Datalink Failed Shutdown PC 2.x, PC
Bitmap 40 3.x
40470 8 Fault Status Gas 3499 Throttle Actuator 2− Special Instruc- Shutdown PC 3.x
Bitmap 40 tion w/Cool-
down
40470 9 Fault Status Gas 3511 Throttle Actuator 2− Shorted High Shutdown PC 3.x
Bitmap 40 w/Cool-
down
40470 10 Fault Status Gas 3512 Throttle Actuator 2− Shorted Low Shutdown PC 3.x
Bitmap 40 w/Cool-
down
40470 11 Fault Status Gas 2752 Throttle Actuator − Shorted High Shutdown PC 3.x
Bitmap 40 w/Cool-
down
40470 12 Fault Status Gas 3514 Throttle Actuator − Shorted Low Shutdown PC 3.x
Bitmap 40 w/Cool-
down
40470 13 Fault Status Gas 3515 Throttle Actuator − Special instruction Shutdown PC 3.x
Bitmap 40 w/Cool-
down
40470 14 Fault Status Gas 3521 Throttle Actuator − Temperature low Warning PC 3.x
Bitmap 40
40470 15 Fault Status Gas 3522 Throttle Actuator 2− Temp low Warning PC 3.x
Bitmap 40
309
THIS PAGE LEFT INTENTIONALLY BLANK
310
4. NFPA 110 & Extended Annunciation Bitmap
NFPA110 bitmap (Register 40016) Extended Annunciation Bitmap (Register 40017)
BIT DESCRIPTION BIT DESCRIPTION
0 (MSB) Common Alarm 0 (MSB) Check Genset
1 Genset Supplying Load 1 Ground Fault
2 Genset Running 2 High AC Voltage
3 Not in Auto 3 Low AC Voltage
4 High Battery Voltage 4 Under Frequency
5 Low Battery Voltage 5 Overload
6 Charger AC Failure 6 Overcurrent
7 Fail to Start 7 Short Circuit
8 Low Coolant Temperature 8 Reverse KW
9 Pre-high Engine Temperature 9 Reverse KVAR
10 High Engine Temperature 10 Fail to Sync
11 Pre-low Oil Pressure 11 Fail to Close
12 Low Oil Pressure 12 Load Demand
13 Overspeed 13 Genset Circuit Breaker Tripped
14 Low Coolant Level 14 Utility Circuit Breaker Tripped
15 (LSB) Low Fuel Level 15 (LSB) Emergency Stop
311
THIS PAGE LEFT INTENTIONALLY BLANK
312
Cummins Power Generation
1400 73rd Ave. NE
Minneapolis, MN 55432 USA
Phone 1 763 574 5000
Toll-free 1 800 888 6626
Fax 1 763 574 5298
Email [email protected]
www.cumminspower.com
CumminsR, the “C” logo, and “Our energy working for you.”
are trademarks of Cummins Inc.
E2009 Cummins Power Generation, Inc. All rights reserved.