CT Sizing For Differnt Types and Classes
CT Sizing For Differnt Types and Classes
Cable burden can be calculated the following way: VAcable = k × L/S, where:
k = 0.44 for 5 A secondary, = 0.0176 for 1 A secondary
L = total feed/return length of cable (m)
S = cross sectional area of copper cable (mm2)
** in these example we did not consider the Internal resistance of the CT winding . Or let it be negligable
A metering class indicates the accuracy of the CT secondary current at 5 to 125% of rated primary current.
Above this level, the CT starts to saturate and the secondary current is clipped
to protect the inputs of a connected metering instrument.
General metering CT would use a metering class CL 0.5 – 1.0
Revenue metering CT would use a metering class CL 0.2 – 0.5
Protection class CT
A protection class CT provides a linear transformation of the primary to secondary current at high overload levels.
This characteristic makes them suitable for use with overcurrent protection relays.
A relay trip setting is normally 10~15 times the maximum load current and this level should fall on the linear part
of the CT secondary current curve. If a CT saturates before the relay trip level is reached,
the fault will remain undetected, leading to equipment damage and serious danger to personnel.
The most commonly used protection class is a 5PX, where X is the accuracy limit factor (ALF) or
multiplication factor of the rated primary current. The secondary current is +/-1% accurate at rated primary current
and +/-5% accurate at X times rated primary current.
2.Transformer Feeder:
MV/LV transformer (TXR2): 2 MVA, 11/0.4 kV, 5% Z
Instantaneous overcurrent trip setting = 10 × In for digital protection relay (OC2) driven off CT2
Here power(S) = 2000VA
Impedance (Z)= 5%
Primary Voltage ( Up) = 11Kv
Secondary Voltage (Us )= 0.4Kv
Step 2 –any
Ignoring Calculated max.orexpected
power cable short circuit current at CT1 installation: Isc (A)
busbar impedances:
Isc = In × 100/Z = 262 × 100/10 = 2620 A
The maximum expected short circuit current at CT1 is 2620 A
Accuracy Class
Use Class 1.0 (common class for general metering)
Step 1 – Select ratings common to both the metering and protection CTs
Primary/secondary rated current: Use 300/1 A (already done for the CT1-1. will be same)
Short-time withstand rating [Ith]: Use 10 kA rating (already done for the CT1-1. will be same)
Primary circuit voltage [Up]: Use 12 kV rating (already done for the CT1-1. will be same)
In this case Isec= 3900/300 × 1 = 13.1 A (as we have selectec 300/1A CT so our instanatious level will be 13.1 )
The instantaneous trip current level for the CT secondary is 13.1 A
As per rule The trip current level should fall between 100 to 50% of the accuracy limit factor (ALF).
IF we use an ALF of 10 (5P10), the trip current level of 3930 A falls outside the range as( 10*300)=3000
100% to 50% ALF, so a 5P10 protection class CT is not suitable.
100%(ALF) = 1.0 × 10 × 300 = 3000 A
50%(ALF) = 0.5 × 10 × 300 = 1500 A
Step 2 – Calculated maximum expected short circuit current at CT2 installation: Isc (A)
Ignoring any power cable or busbar impedances
Isc = In × 100/Z = 105 × 100/5 = 2100 A
The maximum expected short circuit current at CT2 is 2100 A
Real output power: Typically > 1 VA for digital type protection relay.
Use 2.5 VA (this allows 1.5 VA for cable burden, etc.)
The trip current level should fall between 100 to 50% of the accuracy limit factor (ALF).
Using an ALF of 10 (5P10), the trip current level of 1050 A falls within the range of 100% to 50% ALF
so a 5P10 protection class CT is suitable.
100%(ALF) = 1.0 × 10 × 150 = 1500 A
50%(ALF) = 0.5 × 10 × 150 = 750 A
We may notice that 750 ≤ 1050 ≤ 1500 A
Use protection class 5P10
CALCULATIONS FOR CT & PT PARAMETERS IN ARAR CPS EXTENSION PROJECT
REFERENCE DATA
ASSUMPTIONS :
2)Presuming Numerical relays for differential protection, Aux CTs are not used.
1) Calculation of CT parameters for Generator Transformer Feeder Differential Protection (87GT FDR)
CT Ratio Selection :
Formula for calculating Knee point voltage requirement for differential protection
Vk = 40 x I (Rct + 2 Rl+Rrelay)
= 234.8 Volts
We choose Vk >= 300V to account for variation in cable length, variation in CT, relay types etc.
Hence, Vk >=300V
Selection of Class of CT
As the CT is meant for Transformer differential protection, Class X CT is selected.
CT Class = X
Therefore, CT parameters for 87GT FDR are
R relay = 1 VA (Assumed)
= 35.5425 Volts
Vk = 2 Vr = 71.085 Volts
Selection of Class of CT
3) Calculation of parameters for 132kV Generator Transformer Neutral side CT used for 51GTT protection.
= 531.6 Volts
Selection of Class of CT
UAT CT Sizing
However CT ratio selected on 13.8kV side is = 1000 /1 Amp ( To ensure non-saturation of CT for
faults )
Formula for calculating Knee point voltage requirement for differential protection
Vk = 40 x I (Rct x 2 Rl+Rrelay)
= 314.8 Volts
We choose Vk >= 400V to account for variations in cable length, variation in CT, relay types etc.
Hence, Vk >=400V
Selection of Class of CT
For the operation of Instantaneous protection, the CT will see the higher value of subtransient current.Due
to this high fault current the CT may get saturated if lower ratio is used. To avoid CT saturation and to keep knee point
voltage low, a separate CT of higher ratio is selected for Instantaneous(50) protection.
CT Ratio Selection :
However CT ratio selected on 13.8kV side is = 1000 /1 Amp ( To ensure non-saturation of CT for
faults )
Relay Burden : 0.5 ( Assumed)
Since the secondary Current is 1A, the above burden can be taken as the total burden in ohms.
i.e., Rrelaytotal in ohms = Rrelaytotal in VA/(Is2) , where Is = Secondary Current of CT.
Therefore Rrelaytotal in ohms = 0.5
= 0.5 ohms
Contribution from system through GT = 26.1 kA (From ARAR Short circuit study
CT Ratio Selection :
For a fault on HV side of UAT, the fault is cleared by 50UAT, 87OA. Therefore 51UAT
acts as a back up for UAT LV side faults and as such CT for 51UAT will be designed for the LV fault.
Fault on LV side of UAT as seen from HV side of UAT = 30.8 x 0.48 / 13.8
= 1.0713 kA
Selection of Class of CT
CT Ratio Selection :
Since the secondary Current is 1A, the above burden can be taken as the total burden in ohms.
i.e., Rrelaytotal in ohms = Rrelaytotal in VA/(Is2) , where Is = Secondary Current of CT.
Selection of Class of CT
8) Calculation of parameters for UAT Neutral side CT used for 51G protection.
Selection of Class of CT
Formula for calculating Knee point voltage requirement for differential protection
Vk = 40 x I (Rct x 2 Rl+Rrelay)
= 354.8 Volts
We choose Vk >= 400V to account for variations in cable length, variation in CT, relay types etc.
Hence, Vk >=400V
Selection of Class of CT
Equipment VA Burdens
Frequency Transducer 8
Voltage Transducer 8
### 25
### 3
Total 44
Presuming Numerical Meters to be provided. The VA burden of the multipurpose meter is assumed to be less than 10VA