LV Grid Connection of PV
LV Grid Connection of PV
PH O T O V O L T A I C PO W E R S Y S T E MS
E T S U Re p o r t No . S / P2/ 0 0 2 1 5 / R E P
EATL Report No: 5010
Con tractor:
EA Technology Ltd
Prep ared b y:
A C ollinson, EA Technology
J Thornycroft, Halcrow Gilbert
The use of photovoltaic (PV) systems is well established for stand-alone applications,
but in recent years there has been growing interest in grid-connected PV systems using
DC to AC inverters. Building-integrated PV systems for the domestic market have
been identified as offering a large potential power source in the UK. However, the
integration of photovoltaic power systems into local electricity supply networks in the
UK is currently in the early stages of development. The current high costs of PV
systems mean that relatively few requests have been received by UK electricity
companies to date for the connection of such systems. However, the increasing
international activity related to cost-reduction of PV systems, especially in the area of
building integration, means that significant reductions in basic system costs will
continue to be made. If the current trend in cost reduction continues it will not be
long before PV systems are a true commercial proposition. Consequently, any
increased use of PV systems is likely to have a significant impact on the design,
operation and management of electricity supply networks. The electricity supply
industry has identified several technical and commercial issues which have caused
them some concern. These issues needed resolution before grid connected systems
could become more widespread.
With this in mind, and taking into account the greater practical experience of grid-
connected PV systems of countries overseas, the UK Government made the decision
to become involved in the international collaborative research work which was being
established to investigate the technical issues related to grid-connected PV, with the
aim of tackling these issues to ensure that no unnecessary technical barriers existed to
inhibit the future expansion of grid connected PV systems in the UK. Involvement in
this work would have the added benefit of encouraging UK research and
manufacturing companies to develop PV power systems for the UK and overseas
markets.
Objectives of the Work
• explore the concerns of the UK ESI and address the concerns where possible
• raise awareness of the potential for application of PV in the UK
• provide the UK input to Task V of the IEA PV Power Systems Implementing
Agreement and benefit from the results of that programme.
Summary of Work
In order to address the technical issues and develop a consensus view, the project
established a consultative group of representatives from the ESI. This group has been
instrumental in both guiding the technical work and raising awareness in the industry.
This report also summarises the important findings from the first stage of activities of
the International Energy Agency Implementing Agreement on Photovoltaic Power
Systems working group examining “Grid Interconnection of Building Integrated and
Other Dispersed Photovoltaic Power Systems” (commonly known as Task V) and
critically examines these issues from a UK perspective. The Task V work took place
between 1993 and 1998 and covered a review of existing techniques and rules related
to grid interconnection of photovoltaic power generation systems and included both
theoretical and experimental investigations.
The main objective of this work was to provide technical input into the development
of technical guidelines for the grid-connection of photovoltaic (PV) inverter
generators. These technical guidelines have subsequently been taken on board by the
electricity supply industry, who are about to produce Engineering Recommendation
G77, entitled , “UK Technical Guidelines for Inverter Connected Single Phase
Photovoltaic (PV) Generators up to 5kVA” to provide an industry-endorsed guide to
grid-connected PV in the UK. The technical guidelines produced as part of this work
formed the original basis for G77.
Summary of Results
A major output from the project has been the Draft G77 “UK Technical Guidelines
for Inverter Connected Single Phase Photovoltaic (PV) Generators up to 5kVA”
which is currently being prepared for publication as formal guidance to the ESI. The
provisional draft guidelines were launched to an audience of ESI representatives and
PV industry representatives at a workshop 1999 hosted by EA Technology in February
1999. As well as this, the sharing of experiences between the members of this group
and the PV specialists has helped to smooth the path for new PV installations during
the life of the project.
The UK Consultative Group in conjunction with the IEA PVPS Task V working
group has successfully completed the first stage of work by identifying grid
interconnection issues of PV systems and drafting possible recommendations for
improvement. During the period of this work it has been observed that some
countries have developed new guidelines for grid interconnection and some countries
have revised their guidelines due to the increased knowledge of requirements for grid
interconnection of PV systems. The introduction of small-scale, grid-connected PV
systems have also progressed in the UK and on a larger scale abroad. AC modules, a
new concept of a PV module with a tiny embedded inverter (typically up to 100Wp
output power), have been developed and are now sold in some countries, including the
UK.
There are still many issues still to be resolved such as islanding issues,
interconnection of many PV systems in a concentrated area, cost evaluation of grid
interconnected PV systems and so on. These issues will be studied in future work,
both within the UK PV Experimental Programme (Phase 2) and the newly established
UK Strategic PV Network Study, in collaboration with the continuing work of the
Task V Working Group.
In general there is a need to look at the effects of a range of PV penetration scenarios
on system operation and performance, with concentrations of multiple PV systems
operating in UK climatic conditions. The development of the technical guidelines
document highlighted the main areas of concern for electricity companies. These
areas of concern are:
There is a need to increase the awareness of photovoltaics within the UK and a need
for further research focused on the wider impacts of large-scale embedded PV
generation. Also, many of the issues discussed within the context of PV are also
considered by electricity companies to be very relevant to the future development of
other network-connected generator systems, such as fuel cells and small-scale micro-
CHP.
It is also clear from the work carried out to date that the development of international
standards is essential to allow the grid-connected PV market to develop in a
sustainable fashion for the commercialisation of grid-connected PV systems. It has
proven difficult to establish complete unanimity amongst the international community
on grid-connected PV standards because of the differences in electrical network
topologies in different countries. These differences have been magnified by some PV
manufacturers who naturally endeavour to develop standards which are advantageous
to their own products. However, a major step forward from the UK perspective has
been the recent development of the UK's "Action Plan for PV Standards". The
overall action plan covers PV cells and modules, stand-alone systems and building
integration issues as well as grid connection issues. The main issues which were
identified include the development of a type approval testing methodology (this is
actually being carried out as part of the UK PV Experimental Programme), including
type approval accreditation and installation testing and commissioning procedure
specification.
Many of the issues raised during the course of this study will be tackled by a new
project supported by the DTI, entitled "Strategic PV Network Study". This study will
concentrate on the main areas of technical uncertainty which will need to be resolved
before grid-connected PV systems become widespread. Consideration in this study
will be given to possible roll-out scenarios for grid-connected PV inverter systems as
a pre-cursor to developing models for PV/grid interaction (primarily looking at
voltage levels and profiles on the LV distribution network). Another important
element of the study will be a risk analysis of islanding. The results of the modelling
work and the risk analysis will then be used to produce an impact study, examining
the likely effects multiple grid-connected PV inverters will have on conventional
electricity supplies.
Part of the UK activity will involve continued liaison with the activities of the IEA
“Task V” working group, who will be continuing their successful work carried out to
date within a new subtask, Subtask 50. The objective of the new subtask, called
“Study on Highly Concentrated Penetration of Grid-Interconnected PV Systems”, is
to assess the net impact of highly concentrated PV systems on electricity distribution
systems and to establish recommendations for both distribution and PV inverter
systems to enable widespread deployment of solar energy.
GLOSSARY OF TERMS
AC Alternating Current
DNO Distribution Network Operator
DC Direct Current
ESI Electricity Supply Industry
IA Implementing Agreement
IEA International Energy Agency
LV Low Voltage
MV Medium Voltage
MWp MegaWatt (peak)
OECD Organisation for Economic Co-operation and Development
PES Public Electricity Supplier
PV Photovoltaic
PVPS Photovoltaic Power Systems
RCD Residual Current Device
REC Regional Electricity Company
STP Strategic Technology Programme
Contents
Page
1 Photovoltaics in the UK 1
1.1 Background 1
1.2 Installed Systems 1
1.3 The UK Initiative 3
1.3.1 Early Grid-Connected PV Studies 3
1.3.2 Current Grid-Connected PV Studies 4
5 Results 20
6 Conclusions 22
7 Future Work 23
8 Acknowledgements 26
References 27
Appendices
1.1 Background
The technology of solar photovoltaic (PV) cells and systems has developed rapidly
over the last two decades in parallel with the development of the markets. Frequently
a first choice power source in remote locations as ‘stand alone’ battery systems,
photovoltaics are now being developed for connection to the local electricity
distribution network as ‘embedded generators’. These systems are described as
‘network connected’, ‘mains connected’ or ‘grid connected’ in international parlance.
Although they are not yet fully competitive with conventional power generation, or
even most other renewable generators on purely economic grounds they attract interest
because:-
In addition, they offer the following advantages over stand alone systems:-
• they do not require expensive battery storage, as the grid provides the back-up
source
• they can be integrated into buildings and other structures, thus saving on cladding
costs and land requirements
1
The table in Appendix G lists some of the systems installed to date in the UK (derived
from ETSU report ‘Update of the Database of Photovoltaic Installations in the UK,
ETSU S/P2/00301/REP’ by Altechnica). Statistics from the table are that over 100
buildings utilised some form of photovoltaic array, with a total generating capacity
approaching 1MWp. The buildings include some 60 houses, 9 offices, 5 university
buildings, 10 school buildings and a factory. It is assumed that the majority of the
systems are grid-connected although this data is not supplied in the report.
Ten of the schools are part of the Scolar Programme which is now installing 100 small
systems in schools and colleges. Two of the projects are petrol service stations in the
south of England which utilise various types of PV modules incorporated into the
facia and roof canopies of the fuel retail areas. These are both part of roll out
programmes, and will be the first contact with photovoltaic embedded generators for
many Electricity Companies.
The scene internationally is very different. Environmental benefits and other positive
factors are providing significant motivation to accelerate the technological and market
development of grid connected PV systems. In the USA, Japan, Germany and the
Netherlands there are major projects to introduce the systems on a large scale. There
are demonstration projects in many countries and under the European Union RD&D
programmes.
The USA initiated the ‘Million Solar Roofs’ programme in 1997 to install PV systems
and/or solar hot water on one million roofs by the year 2010, Japan has planned to
increase its installed capacity from 10,000 residential systems in 1997 to a capacity of
4,600MWp by 2010, and the German 1,000 roofs project in fact led to the installation
of more than 2,250 systems.
With this in mind, and taking into account the greater practical experience of grid-
connected PV systems of countries overseas, the UK Government made the decision
to become involved in international collaborative research work which was being
established to investigate the technical issues related to grid-connected PV. This as
part of a UK programme would aim to tackle these issues to ensure that no
unnecessary technical barriers existed to inhibit the future expansion of grid connected
PV systems in the UK. Involvement in this work would have the added benefit of
encouraging UK research and manufacturing companies to develop PV power systems
for the UK and overseas markets.
2
1.3 The UK Initiative
1.3.1 Early Grid-Connected PV Studies
In the UK the potential for the application of grid connected and building integrated
photovoltaic systems for the home market has been investigated in a previous series of
reports prepared for DTI between 1992 and 1993:
The first by the Newcastle Photovoltaic Applications Centre (1992), “The Potential
Generating Capacity of PV-Clad Buildings in the UK”, ETSU Report S1365-P1,
confirmed the large potential to integrate PV power generators into many of the
building types found in the UK.
This research has been both on the UK level and on an international level, in
collaboration with countries where more systems have been installed. It has involved
a diverse range of interested parties all of whom are crucial to the take-up of PV in the
UK, bringing together the expertise from the Electricity Industry, the PV industry and
University research as well as interaction with the IEA Task V working group. This is
shown in the figure below:
RECs CONSULTATIVE
GROUP
UNIVERSITY INTERNATIONAL
COLLABORATIVE
RESEARCH IEA TASK V
PROJECTS
PV INDUSTRY STANDARDS
BODIES
3
1.3.2 Current Grid-Connected PV Studies
As part of the work programme developed by the DTI, a project was initiated in 1995,
entitled “Technical Criteria for Electrical Integration of PV Systems”. This project
was developed by EA Technology and Halcrow Gilbert with funding from both the
DTI and the Electricity Supply Industry. This report forms the final report from this
study.
• explore the concerns of the UK ESI and address the concerns where possible
• raise awareness of the potential for application of PV in the UK
• provide the UK input to Task V and benefit from the results of that programme.
The project established a consultative group of representatives from the ESI who have
been instrumental in both guiding the technical work and raising awareness in the
industry. A major output from the project has been the Draft G77 “UK Technical
Guidelines for Inverter Connected Single Phase Photovoltaic (PV) Generators up to
5kVA” which is currently being prepared for publication as formal guidance to the
supply industry. As well as this, the sharing of experiences between the members of
this group and the PV specialists has helped to smooth the path for new PV
installations during the life of the project. It also resulted in the identification of the
experimental work described below.
The objectives for Phase I which were developed in conjunction with the electricity
supply industry (ESI) were:
4
• to provide the UK R&D input for Task V of the IEA Photovoltaic Power Systems
Programme
The key issues chosen were the performance of small power conditioners in terms of
power quality and safety of the network and connected equipment, the interaction
between power conditioners, and the cumulative effect of multiple installations on a
section of the distribution network.
The contract was extended to ensure that the activities in the first phase of the
programme were brought to a satisfactory conclusion and to achieve full benefit from
participation in Task V after that programme was extended. The plan for the
extension emphasised the dissemination activities and the preparatory work for the
5
development of international standards. A final seminar in the UK was also added to
the programme.
Additional effort and interest from the academic community and interested
manufacturers is encouraged and has resulted in useful contributions as well as wider
dissemination of the results.
1. This is the core activity for the programme. A draft document on Guidelines for
grid connection of small PV systems has been drafted with the ESI to supplement
current Engineering Recommendations. Available standards and recommendations
have been reviewed with the REC consultative group and the routes for
introduction of change have been explored.
2. A review of BS 7671 (16th of IEE Wiring Regulations) for areas that are unclear
about PV systems or may need revision and stimulation of action for the next
revision of the standard was proposed, but has not been progressed into a
documented form because it is not of direct interest to the electricity utilities.
1. Experience of both UK and overseas projects has been exchanged within the REC
consultative group to increase awareness, and has been a resource for the draft
Guidelines.
2. Guidance for the REC system planners is contained in the draft Guidelines.
6
1. Metering: A study of acceptable two way power metering systems has been
difficult to develop as the electricity industry has been engaged in the greater task
of dealing with metering issues for the open market. OFFER have been
approached and a dialogue established on the concerns of the PV industry
regarding the impact of new metering arrangements.
2. The work in this project identified the research themes for the co-ordinated
experimental programme which is discussed in section 1.3.3. A study of the effects
of multiple inverter connections to typical UK distribution lines has been
undertaken. A research programme on power conditioner performance and
interaction has also been undertaken.
Activity 4 Dissemination
3. An interface and improved understanding between the RECs and the PV industry
has been established which will assist the connection of new systems on to
networks and the development of mutually acceptable standards.
7
Sub Task 20 Definition of Guidelines
• Liaise with ESI over their technical concerns and presentation of their
requirements for inclusion in the guidelines;
• Arrange consultation with the ESI through a technical workshop;
• Assist with drafting the guidelines and identifying key issues, representing the
UK views;
• Disseminate the guidelines in the UK and collate comments for feedback to Sub
Task. Workshop on new standards and new products for grid connection;
• Endeavour to obtain commitment from the ESI and industry to develop practical
projects for inclusion in the remaining stages of the programme.
A new Subtask 50 has now been established, with the UK input to be provided
under the follow-on ‘Network Strategy’ project.
There are no fundamental principles that prevent the connection of PV systems into
local electricity supply . However, electricity companies have a legal requirement to
maintain safety standards and at the same time achieve a high quality of supply to
customers, both of which could be compromised by the characteristics of PV systems
incorporated into the network. Safety considerations include the fact that in the event
of a network power supply interruption, the PV generator could still maintain power
in some parts of the network - referred to as 'islanding'.
The Task V working group has provided useful background information and
validation for the UK’s technical guidelines document (see Appendix A), which was
8
officially launched in conjunction with the 2nd UK PV Conference which took place
at the Renaissance Hotel in Manchester on the 17th/18th February 1999. The
guidelines have been taken on board by the Electricity Association and (following on
from an official electricity industry review) are shortly to be issued as an official
industry standard document in the form of an Engineering Recommendation, G77.
• the Electricity Association as the overall body responsible for publishing ESI
regulations in the UK
London Electricity
South Western Electricity
Eastern Electricity
East Midlands Electricity
South Wales Electricity
Northern Electric
Manweb
PowerGen
Midlands Electricity
Seeboard
Its terms of reference are to meet approximately twice a year to consolidate work with
other working groups on topics such as the guidelines for grid connection.
Information was exchanged between the PV and Electricity Industry, including
experience on other forms of distributed generation and research on photovoltaic
systems. It has also provided valuable input into the Task V work through the supply
of survey data and feedback on international results.
9
together by Halcrow Gilbert in 1994, to set up a consultative group of industry
representatives which grew to involve the companies or their subsidiaries listed above.
The requirement for the work was that, despite the large potential, the integration of
Photovoltaic Power Systems into local electricity supply networks in the UK was
currently in the early stages of development compared with countries abroad. The
current high costs of PV systems and lack of a major government installation
initiative, meant that relatively few requests had been received by UK electricity
companies to date to stimulate development for the connection of such systems. In
fact, despite the table in the previous chapter, the UK has one of the lowest quotients
of installed PV capacity per head of population (i.e. kWp/capita) of any of the
countries involved in the IEA’s PV agreement.
The Consultative Group has been instrumental in both guiding the technical work and
raising awareness in the industry. The sharing of experiences between the members of
this group and the PV specialists has helped to smooth the path for new PV
installations during the life of the projects so far.
Considered in its simplest form, the design of the distribution network is based on the
assumption that power flows from the higher voltage levels to the lower levels via
transformers and the direction of current flow is from the primary and distribution
transformers to the customer loads. This assumption is used to predict the voltage
profiles along the cables and overhead lines which supply the customers In this way,
10
it can be ensured that the electricity supply that customers receive is within the
statutory voltage limits (i.e. 230V+10%, -6%). The size and ratings for the network
plant (such as the distribution transformer, associated switchgear, cables/overhead
lines and protection) are determined, based on predicted consumer load profiles and
known local physical topology. However, the addition of dispersed generation makes
these original design calculations no longer valid, since the embedded generation will
effect the actual voltage profiles on the network, as well as associated fault levels and
protection settings.
Many technical aspects related to the connection of embedded generators are covered
by the electricity supply industry (ESI) Engineering Recommendation G59/1
(amendment 1). Whilst this document does consider single-phase LV connected
generators, it was written mainly to cater for larger generators (typically >1MW power
rating), which would typically be connected to the MV network, (11kV is the typical
MV distribution voltage level in the UK). Also, G59/1 tends to treat the connection
of single-phase LV generators as a special case derived from the general case, but if
the numbers of single-phase embedded generators increases significantly in the near
future, a different approach will need to be taken towards such generation.
The procedures laid down in G59/1 place a significant burden in terms of time on the
technical engineering departments of electricity companies to ensure safe, competent
installation of embedded generators. This is acceptable when dealing with a handful
of larger (i.e. >1MW) schemes. However, such a high level of direct involvement by
technical personnel would not be appropriate for a larger number of smaller schemes.
Thus, the aim of the technical guidelines (and associated type approvals document) is
to provide a cost effective solution to the safe and reliable connection of single phase
PV generators to the LV network.
The technical guidelines document covers the four main areas considered to be
important in the context of achieving safe and practical interconnection of single
phase PV inverter generators. These areas are:-
• protection
• operation and safety
• power quality
• commissioning and acceptance testing
The technical guidelines document gives recommendations for best practice and
highlights any existing standards that need to be adhered to in the grid connection
process, including European standards, British standards and ESI standards and
regulations. In the absence of formal standards, the guidelines recommend tests
which can be carried out to allow grid connected PV systems to obtain “approved”
status from the UK electricity supply industry, in the form of "type testing".
The concept of an “ESI Approved” inverter is an important one, since it shows that
the inverter design has considered the relevant factors related to grid connected
operation and the inverter meets the criteria laid down by the electricity industry to
11
ensure safe operation, with the correct protection functions and can operate without
significantly degrading power quality to the PV owner/operator and other consumers.
When evaluating the likely effect that small-scale single phase PV generators might
have on the electricity distribution network, the following principles are considered:-
• ensuring that the statutory requirements set out in the Electricity Supply
Regulations 1988 are met
• meeting the requirements of the Distribution Code (and Grid Code, if
appropriate)
• ensuring the security of supply to other customers is not prejudiced
• ensuring quality of supply to other customers is not prejudiced.
• ensuring plant and equipment already on the distribution system will operate
within their rating
• ensuring the grid inter-connection meets appropriate technical standards
The issues which are of primary concern include the effect that PV-inverter generators
connected to the network will have on:-
• network capacity
• network security
• voltage regulation
• power quality
• earthing
• fault level
• asset utilisation
• losses
It is part of the network operator's licence that the design of the network connection
for any generator must be achieved at minimum cost, whilst meeting all of the
relevant legal, regulatory and safety requirements.
3.2 Protection
Protection can mean different things to different people, depending on perspective and
viewpoint. In general, protection is necessary to fulfil several different requirements
and in the context of electrical safety of PV systems these requirements include:
The voltage and frequency protection trip limits specified in the guidelines document
are fairly straightforward, being identical to the G59/1 limits (which are in turn
directly related to the supply limits set in the Electricity Supply Regulations (1988)).
12
The issue which causes the most discussion and commands the least consensus is the
issue of loss of mains (LOM) protection under an “islanding” condition. Islanding is
a phenomenon which can only occur when generation is embedded within the
distribution network. The islanding phenomenon refers to the condition which can
exist whereby part of the network has become electrically isolated from the main
network and all the loads within that network are being supplied by the generators
embedded within that network. The electricity company (or more accurately the
public electricity supplier, or PES) has no way of controlling the voltage and
frequency of an islanded network, since it has no control over the generation within
the islanded section of network Since the PES is responsible for the safety of the
network and for maintaining satisfactory power quality, it will require all generation
within the 'island' to be shut down to ensure the system is in a safe state and to prevent
customers receiving a supply that could jeopardise their equipment.
However, power quality is not the only issue which is raised by islanding. The debate
surrounding the risks of islanding is normally associated with megawatt scale
generators. With these larger generators, the energy stored by virtue of the inertial
mass of the rotor shaft means that the consequences of an "out-of-sync" circuit breaker
reclosure on a multi-megawatt generating set can be quite dramatic. Such events
have been recorded and have resulted in the generator shaft being torn out of its
bearings, allowing it to make contact with the generator stator and thereby completely
destroying the generator. An out-of-sync reclosure is still an event that could effect
grid connected PV inverters, but the lack of mechanical inertia within the inverter
should mean that the inverted is in a better position to survive such an event without
damage to itself.
The concern for safety is the main reason for the clauses within the technical
guidelines document stating the need for various switches, including a manual
isolation switch and a mechanical isolation switch (often referred to as the automatic
disconnection switch). There has been some confusion over the various terms used
and this has resulted in confusion in understanding the purpose and the reasons behind
the requirement for each switch. The following paragraphs attempt to clarify the
situation.
13
otherwise someone could close the switch whilst someone else was still working on
the installation. The use of lockable isolation switches is standard practice within the
ESI.
14
In the context of the technical guidelines document, power quality includes
harmonics, power factor, flicker, EMC and DC injection.
3.4.1 Harmonics
Levels of harmonic generation by non-linear loads have been subject to limits for
many years. Harmonics can be viewed as a form of electrical pollution on the
distribution network, since they provide no useful benefits but their existence can
interfere with the correct operation of certain types of systems connected to the
network. Such systems include line-commutated rectifiers and mains-synchronised
clock circuits, etc. Excess harmonics can also result in network plant having to be
operated at reduced ratings. Thus, it is in the interest of both distribution network
operator (DNO) and consumers alike to minimise the levels of harmonics present on
the network. The most notable incident related to excess harmonics occurred in the
late 1960's and was caused as a result of the rapid expansion of television. The
power supplies used within the TV sets of that period were very crude, with the
cheapest using half-wave rectification (which saves the cost of three diodes, compared
with full-wave rectification!) and produces high levels of even-order harmonic
distortion. The effect on the network of the high level of harmonics was:
a) some household clocks which were synchronised with the mains frequency ran too
fast
b) large harmonic currents were present at the LV distribution transformer, causing
localised overheating
The problem was cured mainly by simple, minor changes in the manufacturing
procedures used in the TV's power supplies. The principle change in the
manufacturing process allowed for a random orientation of the half-wave rectifier
diode, which allowed for a statistical spread of load between the positive and negative
sine wave cycles of the mains supply, thus balancing out the even-order harmonic
currents.
Power factor is a technical term defining the relative displacement in time between the
mains voltage waveform and the current waveform. (Both of these waveforms are
sinusoidal, but the peaks will only be co-incident at unity power factor).. “Real
power" relates to the current component at peak voltage, whilst “reactive power"
relates to the current component at voltage zero. Many domestic loads (most notably
induction motors, commonly found in refrigerator compressor units etc.), require a
reactive power component to operate correctly. In this context, the network is often
referred to as “supplying Vars”. Approximately 30-50% of domestic load (excluding
space heating) is made up of loads requiring reactive power (i.e. induction motors).
"Useful work” is only done by the “real” part of the power (the domestic meter
measures only “real” power). So, since for a sustained island to occur there needs to
be a match of both real and reactive power components, restricting grid connected PV
inverters to only exporting real power dramatically reduces the chances of the
necessary conditions for islanding being met.. This is why the technical guidelines
15
document restricts PV inverters to export between unity power factor and 0.95 leading
(i.e. importing Vars). Note, this refers to reactive current "exported” to the network,
and does not restrict the inverter from supplying reactive power to the loads within the
same premises as the PV generator. However, the simpler inverter designs are not
likely to be able to distinguish between power exported to the network and power
taken by the domestic loads. In this case, the inverter output will be restricted to
operate between unity power factor and 0.95 leading.
3.4.4 Flicker
Flicker problems are normally associated with non-linear or pulsed loads, such as
welding equipment. As its name suggests, flicker is associated with lighting and is
caused by repetitive, periodic voltage fluctuations. The eye is particularly sensitive to
fluctuations in the range once per second to ten times per second, where voltage
fluctuations of 1% or less can be detected by the human eye. Concerns over flicker is
much greater in other European countries than it is in the UK, mainly because of
differences in electrical network configurations. However, there is general concern
that because of the time-varying output of PV systems, they have the potential to
cause flicker problems. Thus, flicker is given consideration in the connection
guidelines document.
3.4.5 DC injection
The 5mA limit could be changed in the future (either up or down), dependent on
operational experience, further research or additional information on the likely effects
of DC on the network.
16
larger embedded generator (of typically 1 to 5 MW size). Such a procedure is
obviously not practical for grid-connected PV inverters at the domestic-level and so
the technical guidelines document aims to simplify the process by agreeing to a
minimum number of commissioning tests for an “Approved” inverter. DNOs have
reserved the right to have additional commissioning tests carried out for “Non-
approved” inverters, and may wish to witness the commissioning also.
3.5.1 Metering
Much has been written about metering for PV systems and so only a brief review will
be given here. Needless to say, the metering aspect will form part of the Connection
Agreement. "Net metering", where exported units run the meter backwards (making
the PV-generated unit selling price effectively the same as the purchase rate for utility-
supplied electricity), is seen as the most attractive option for PV system owners and
gives quite an attractive rate of return (some estimates have shown that this method
can contribute approximately 15% of the PV system cost recovery). However, for
any electricity import/export arrangement, a meter with two separate metering
registers is required. It is not satisfactory to allow the meter to simply run backwards
for exported units, since this leaves the meter open to fraudulent abuse. In any case,
the commonly used Ferraris electro-mechanical meter is mechanically damped to
prevent the meter from rotating backwards. Also, modern electronic meters can be
programmed to run only in one direction (i.e. only forwards), again to combat meter
fraud. A more conventional approach is to use a PV-generated unit selling price
equivalent to the electricity pool price (approximately 1/3 of the domestic purchase
rate). However, the cost of the two-way import/export meter becomes a major cost
factor for smaller PV installations . For smaller systems the value of units exported is
likely to be small and so it may be beneficial to ensure that as much of the PV output
as possible is used within the house. A final option may be to negotiate a fixed,
unmetered, annual payment from the local PES.
3.5.2 Labelling
Adequate labelling of the installation provides a very simple but effective way of
ensuring improved safety of PV inverter installations. This is particularly important
in the early development of the grid connected PV market, since these types of
systems will be unfamiliar to many people until they become much more widely used.
Simply indicating the presence of on-site generation at the key electrical locations
(service termination, meter position and isolation switch - normally in the same place
anyway) will encourage people to proceed with additional care. For electricians and
electricity company personnel, having a circuit diagram available of the PV system
wiring as well as summaries of protection settings within the equipment can save
valuable time on-site. It is also helpful to have contact details for the
supplier/installer/maintainer of the equipment should queries arise, and so labels on
the equipment giving such information would also improve maintenance efficiency.
17
4 Summary of Task V Activities
The International Energy Agency (IEA), headquarters in Paris, is an autonomous body
within the framework of the Organisation for Economic Co-operation and
Development (OECD). The Agency was established in November 1974 to carry out a
programme of energy co-operation among its 23 member countries: Australia, Austria,
Belgium, Canada, Denmark, Finland, France, Germany, Greece, Ireland, Italy, Japan,
Luxembourg, the Netherlands, New Zealand, Norway, Portugal, Spain, Sweden,
Switzerland, Turkey, the United Kingdom and the United States.
Comprehensive Task Reports have been issued under the auspices of the International
Photovoltaic Power Systems Programme and so those readers interested in the details
of the work and would like further reading are invited to obtain copies of other
reports, as listed in the Reference section of this report, with supplementary material
listed in Appendix F. Task V has proved to be one of the most productive and focused
groups within the IEA PV Implementing Agreement.
In order to achieve the objectives of Task V, three sub-tasks were established and
collaborative work between participating experts in Task V was conducted.
18
• Sub-task 20 : Theoretical studies on various aspects for grid interconnection and
configuration of PV systems
• Sub-task 30 : Experimental tests using the Rokko Island and/or other test facilities
4.1.1 Subtask 10
Sub-task 10 had four items of study. The first item was a review of existing technical
guidelines or local regulations for the interconnection of PV systems with the utility
network. This survey enabled an understanding of the general requirements for safe
and reliable interconnection to be obtained. The result of the survey was summarised
as Task V internal report, “Grid-connected photovoltaic power systems: Status of
existing guidelines and regulations in selected IEA member countries (Revised
Version)”, Task V Report IEA-PVPS V-1-03, March 1998. The second study item
reviewed utility distribution network configurations in order to understand the
differences in grid interconnection requirements from country to country. The result of
the survey was also summarised as a Task V internal report, “Information on
electrical distribution systems in related IEA countries (Revised Version)”, Task V
Report IEA-PVPS V-1-04, March 1998. The third study item reviewed the status of
technology for interconnecting equipment (inverters and protective devices) in order
to identify the applied criteria to satisfy the requirement for grid interconnection.
Specifications and characteristics of many inverters and protective devices have been
collected and summarised as a Task V internal document. The fourth item was a
review of the operating experience of grid interconnected PV systems to identify any
known problems relating to PV system operation.
4.1.2 Subtask 20
The scope of work for sub-task 20 was to analyse present day and possible future
problems relating to the grid interconnection of PV systems and to draft possible
recommendations for improvement. The following subjects were considered.
• Harmonics
• AC-Modules
• Multiple inverters and AC grid
• Grounding of equipment in PV systems
• Ground-fault detection and array disabled for PV systems
• Overvoltage protection
• Islanding
• Electro-magnetic compatibility (EMC) of inverter
• External disconnect
• Re-closing
• Isolation transformer and DC injection
19
The results of the work were given in the formal IEA PVPS report, “Utility aspects of
grid connected photovoltaic power systems”, Task V Report IEA-PVPS-T5-01,
December 1998. The scope of the work, theoretical results, experimental results,
conclusions and recommendation for future work were described for each subject.
The information within the subtask 20 report is easy to access and useful for readers
with a technical background.
4.1.3 Subtask 30
The results of the work was given in the formal IEA PVPS Task V report,
“Demonstration Tests of Grid-Connected PV Power Systems”, Task V Report IEA-
PVPS- V-3-01, May 1999.
5 Results
A major output from the project has been the Draft G77 “UK Technical Guidelines
for Inverter Connected Single Phase Photovoltaic (PV) Generators up to 5kVA”
which is currently being prepared for publication as formal guidance to the ESI. The
provisional draft guidelines were launched to an audience of ESI representatives and
PV industry representatives at a workshop hosted by EA Technology in February
1999. As well as this, the sharing of experiences between the members of the REC
consultative group and the PV specialists has helped to smooth the path for new PV
installations during the life of the project.
The UK technical guidelines document was itself based on the foundation work
carried out within the international Task V working group activities. Several Task V
reports produced the background information which was subsequently used to identify
areas of common concern related to grid-connected PV systems. The information
gathered together in the reports was also helpful in understanding the reasons behind
any differences in approach adopted by different countries.
20
Firstly, the fundamental parameters and characteristics of electrical networks were
compared from each country in order to identify common features and differences
between countries. This information is contained in the following reports:
Other reports included several survey reports on the status of guidelines development,
including:-
• “Proceedings of the IEA Workshop on Existing and Future Rules and Safety
Guidelines for Grid Interconnection of Photovoltaic Systems”, Zurich, September
1997.
A report of a more technical nature was then produced which examined the technical
issues of grid-connected PV systems in more detail. This report was entitled “Utility
Aspects of Grid Interconnected PV systems”, IEA-PVPS Report, IEA-PVPS T5-01:
1998, December 1998. Those readers who wish to develop a deeper understanding of
the technical issues of grid-connected PV systems are encouraged to read this report.
Finally, the results of experimental work carried out by members of the Task V
working group (principally Japan - Rokko Island) are detailed in the report
“Demonstration Tests of Grid Connected Photovoltaic Power Systems”, IEA-PVPS
Report, IEA-PVPS T5-02: 1999, March 1999.
From the above, it can be clearly seen that the development of the technical grid
connection guidelines document illustrates the successful interaction that has taken
place between the REC consultative group and the Task V working group, where a
wealth of international experience has been tapped into as well as the UK experts
contributing to the developing international knowledge on the subject of grid-
connected PV systems.
21
6 Conclusions
The UK Consultative Group in conjunction with the IEA PVPS Task V working
group has successfully completed the first stage of work by identifying grid
interconnection issues of PV systems and drafting possible recommendations for
improvement. During the period of this work it has been observed that some
countries have developed new guidelines for grid interconnection and some countries
have revised their guidelines due to the increased knowledge of requirements for grid
interconnection of PV systems. The introduction of small-scale, grid-connected PV
systems have also progressed in the UK and on a larger scale abroad. AC modules, a
new concept of a PV module with a tiny embedded inverter (typically up to 100Wp
output power), have been developed and are now sold in some countries, including the
UK.
There is a need to increase the awareness of photovoltaics within the UK and a need
for further research focused on the wider impacts of large-scale embedded PV
generation. Also, many of the issues discussed within the context of PV are also
considered by electricity companies to be very relevant to the future development of
other network-connected generator systems, such as fuel cells and small-scale micro-
CHP.
It is also clear from the work carried out to date that the development of international
standards is essential to allow the grid-connected PV market to develop in a
sustainable fashion for the commercialisation of grid-connected PV systems. It has
proven difficult to establish complete unanimity amongst the international community
22
on grid-connected PV standards because of the differences in electrical network
topologies in different countries. These differences have been magnified by some PV
manufacturers who naturally endeavour to develop standards which are advantageous
to their own products. However, a major step forward from the UK perspective has
been the recent development of the UK's "Action Plan for PV Standards". The
overall action plan covers PV cells and modules, stand-alone systems and building
integration issues as well as grid connection issues. The main issues which were
identified include the development of a type approval testing methodology (this is
actually being carried out as part of the UK PV Experimental Programme), including
type approval accreditation and installation testing and commissioning procedure
specification.
It is anticipated that by the time this report is published, G77 will have reached
official approval status as an ESI standard engineering recommendation. In view of
the pioneering nature of G77, it is fully anticipated that it will need to undergo formal
revision early in its lifetime (say, after about 18 months) in the light of practical
experience in order to gain a long-lasting mutual acceptance from both the ESI and the
PV industry.
The success of the present project and related work in reducing technical and non-
technical barriers to an enlarged PV market have resulted in the confidence to
continue activities in this area. Phase II of the ‘Co-ordinated Experimental Research
into PV Power Interaction with the Supply Network’ Project was established in 1998
to carry out research to progress the type-testing requirements for PV power
conditioners to be connected to the UK network and draft the procedures for testing.
It also provides the mechanism to continue the successful collaboration with the
Consultative Group from the Regional Electricity Companies (RECs) and prepare for
constructive UK participation in the international work on inverter standards.
At the end of these projects, it is hoped that the majority of the technical barriers will
have been researched and where feasible measures put in place to remove or reduce
them.
7 Future Work
Many of the issues raised in the previous section of this report will be tackled by a
new project supported by the DTI, entitled "Strategic PV Network Study". This study
will concentrate on the main areas of technical uncertainty which will need to be
resolved before grid-connected PV systems become widespread. Consideration in this
study will be given to possible roll-out scenarios for grid-connected PV inverter
systems as a pre-cursor to developing models for PV/grid interaction (primarily
looking at voltage levels and profiles on the LV distribution network). Another
important element of the study will be a risk analysis of islanding. The results of the
modelling work and the risk analysis will then be used to produce an impact study,
examining the effects likely effects multiple grid-connected PV inverters on
conventional electricity supply.
23
Part of the UK activity will involve liaison with the activities of the IEA “Task V”
working group, who will be continuing their successful work carried out to date
within a new subtask, Subtask 50. The objective of the new subtask, called “Study
on Highly Concentrated Penetration of Grid-Interconnected PV Systems”, is to assess
the net impact of highly concentrated PV systems on electricity distribution systems
and to establish recommendations for both distribution and PV inverter systems to
enable widespread deployment of solar energy. Subtask 50 can be broken down into
the following smaller subtasks:-
Subtask 51: Guidelines for Grid Interconnection, Certification Test Methods and
New Technologies
Subtask 52: The Islanding Phenomena, Probability of Occurrence, Detection
Methods, Impact of Islanding and Mitigation.
Subtask 53: Multiple PV Systems and their effect on power quality and power system
design and operation.
Subtask 54: Capacity of PV Systems
The activities of the Task V group are arranged with different countries taking a “lead
role” and additional countries acting as “co-worker” on some of the identified
subtasks. The UK has agreed to take a lead role in co-ordinating the activities of
Subtask 51. In addition, the UK has agreed in principle to act as co-worker on the
following subtasks:
The UK ranked these subtasks in order of importance to the UK, based on current and
future predicted areas of interest (1= highest, 5 = least important).
Subtask 51, Guidelines for Grid Interconnection, Certification Test Methods and New
Technologies
(UK ranking = 2)
The status of grid connection guidelines in each country will be reviewed at each
meeting and the internal Task V report will be updated accordingly every year. This is
relevant to the UK PV connection guidelines, which are shortly to be launched as an
“Engineering Recommendation” by the UK Electricity Association. It is important
that the progress and experiences of other countries are monitored and fed back to the
UK electricity industry during the early life of the official PV guidelines document.
24
A third, smaller, element of this subtask is the “new technologies” activity. As well as
being a product market survey, it is also a survey of new technologies, including novel
system configurations. This sub activity was ranked low by the UK representatives
and so will involve only a “watching brief” from the UK.
The aim of this subtask is to quantify the islanding issue in terms of the likelihood of
part of the network becoming disconnected from the grid (due to a local fault, etc.) at
the same time as there is a match between PV generation and local load requirements.
The task will rely heavily on results from an international study being co-ordinated by
the Dutch representative within Task V. The likelihood of islanding will be quantified
using statistical probability studies. The task will also assess the operation of
islanding detection methods (including ‘active’ techniques), the likely impact of an
islanding event (i.e. effect on the network, equipment connected to the network, the
inverter itself, and people (electricity company personnel and the general public).
The task will also look at what practical steps could be taken to mitigate the impact of
islanding (i.e. can inverters be made to withstand an out-of-sync reclose operation?,
new LV live-line working practices (isolation and earthing of supplies), etc.).
Subtask 53: Multiple PV Systems and their effect on power quality and power
system design and operation
(UK ranking = 3).
The network issues are effectively covered from a UK perspective by Subtasks 52 and
53. Thus, the main new area of interest to the UK are the capacity issues. The
subtask will look at how PV can be accredited with some kind of capacity rating.
25
It is the purpose of this project to develop the theoretical and practical understanding
of the likely effects that large-scale connection of dispersed photovoltaic power
systems could have on the electricity supply network.
8 Acknowledgements
EA Technology would like to thank the many people who have assisted in the
production of this report, including all of the Task V working group members,
especially the chairman, Mr Tadao Ishikawa, CRIEPI, Japan, the members of the
REC’s Consultative Group especially the chairmen, formally Geoff Finlay and now
John Sinclair of the Electricity Association, the members of STP Module 5,
Embedded Generation especially the chairman, Pete Thomas, Manweb. Additionally,
I would like to thank our colleagues Rod Hacker and Jim Thornycroft from HGa who
did such sterling work on developing the technical guidelines document. Finally, we
would like to thank Harry Edwards of ETSU, for his encouragement in helping to
guide the "vision" of grid-connected PV in the UK.
26
References
[1] Task I Report, “Photovoltaic Power Systems in Selected IEA Member
Countries”, Report IEA PVPS ExCo: T1 1997:1, March 1997.
[9] “Proceedings of the IEA Workshop, “Existing and Future Rules and Safety
Guidelines for Grid Interconnection of Photovoltaic Systems”, Zurich,
September 1997.
27
Appendix A:
Generally speaking, UK electricity company personnel will not be very familiar with
photovoltaic power generation systems, especially grid-connected systems. Therefore,
the UK technical guidelines were originally developed as an unoffical document to
assist electricity company personnel in dealing efficiently with requests for the
connection of grid-connected PV systems. The guidelines would also be useful to PV
system designers and installers in providing information on the electrical network
requirements for grid-connected PV systems.
Subsequently, in Autumn 1998, the technical guidelines document was taken on board
by the electricity supply industry under the chairmanship of the Electricity Association
and developed into its current form as “G77”, an official ESI Engineering
Recommendation. The document is currently undergoing the final stages of formal
review and it is anticipated that the final version of G77 will be formally approved in
Autumn 1999. It is also anticipated that the final version of G77 will not be
significantly different from the draft version contained here. However, it is
recommended that once it is officially published, an official version should be
obtained directly from the Electriciy Association, Millbank, rather than relying on the
draft version reproduced for information here.
28
DRAFT (Dated: 15/7/1999)
SUMMARY
This document also contains guidance on the approval and type testing of inverters.
The aim of this document is to encourage the use of “approved” inverter equipment
and recognised connection procedures in order to lessen the need for DNO personnel
to perform local tests.
The guidelines do not cover practical or safety issues related to the customer’s
installation.
29
CONTENTS
1 INTRODUCTION
2 DEFINITIONS
3 PROTECTION
3.1 Automatic Protection
3.2 Automatic Disconnection
30
1. INTRODUCTION
The following principles underlie the national technical guidelines for inverter
connected single phase photovoltaic (PV) generators to the DNO’s distribution
system:
1.1 It is anticipated that DNOs will use these guidelines as a basis for formulating
their specific requirements for connection of inverter-connected PV generators
in conjunction with:
1.2 The Guidelines are only concerned with the interface between the DNO
distribution system and the inverter connected PV generator.
1.4 The guidelines are written from a functional perspective. They are not
technology specific, i.e. they do not require specific technologies to be used for
connection to the DNO’s distribution system or the energy generation schemes
themselves. This approach allows for ongoing development to continually
improve the cost and technical performance of the equipment connected to the
DNO’s distribution system.
1.5 This document is only applicable for single installations where the total installed
PV generation capacity is 5 kVA or below.
31
2. DEFINITIONS
2.1 Inverter
A device for conversion from DC to nominal frequency AC.
2.7 Islanding
Islanding of inverter connected PV generator systems means any situation where the
source of power from the DNO’s distribution system is disconnected from the
network section in which the generator is connected, and one or more inverters
maintains a supply to that section of the distribution system or consumers installation.
32
3 PROTECTION
The voltage and frequency limit settings should not be capable of adjustment by the
user.
The inverter should incorporate a recognised technique for providing loss of mains
protection (such as frequency shift or vector shift). Active techniques that distort the
voltage waveform beyond the limits specified in section 4.1 or inject current pulses
into the DNO’s network are not approved.
This protection must ensure that the inverter disconnects from the DNO’s distribution
system within 5 seconds, and does not reconnect until at least 3 minutes after the
supply from the DNO system has been restored to within the voltage and frequency
limits already specified.
33
4. SUPPLY POWER QUALITY
4.1 Harmonics
All equipment shall meet:
For equipment rated >16 A, the emission currents shall not exceed the limits quoted in Technical
Report IEC 61000-3-4 when the PV inverter generator is supplying a purely resistive load of equal
rating to the output of the PV inverter generator.
Note: for the purpose of assessing emission currents in accordance with 61000-3-4, the ‘Short Circuit
Power’ Scc, shall be assumed to be 548 KVA - derived using maximum values for open circuit voltage
and network impedance i.e. (2532/0.35) x 3.
Note: the automatic protection settings of section 3.1 afford adequate immunity for
operation of the PV inverter generator, against : voltage dips, short supply
interruptions (up to 5 seconds, dependent on protection time setting) and frequency
dips.
34
BS EN 50082-1: 1998 Electromagnetic Compatibility
Generic Immunity Standard
4.5 DC Injection
DC currents entering the AC distribution system can give rise to technical problems.
G5/3 deprecates the existence of DC currents on the UK distribution system but does
not specify levels.
It is recommended that a transformer be installed between the inverter and the DNO’s
distribution system to prevent DC from entering the distribution system. However if a
DC detection device is installed at the point of connection on the AC side then the
transformer may be omitted; provided that the output of the inverter(s) is disconnected
if the level of DC injection exceeds 5mA (present regulation is zero).
Where fitted the DC isolation transformer will normally be located adjacent to the
inverter, which will either be in close proximity to or an integral part of the PV array.
5.2 Labelling
There shall be labelling at the service termination, meter position and isolation switch
to indicate the presence of on-site generation and the point of isolation. The Health
and Safety (Safety Signs & Signals) Regulations 1996 stipulates that labels should display
the prescribed triangular shape, using black on yellow colouring. A typical label is
shown below:
35
the context of small single phase generators, which will typically be installed in
domestic environments, it is envisaged that this requirement can be met by displaying:
1) a circuit diagram showing the relationship between the inverter equipment and
supply
2) a summary of the protection settings incorporated within the equipment
3) a contact telephone number for the supplier/installer/maintainer of the equipment
5.4 Earthing
The system shall meet:
In the UK, the majority of new low voltage (LV) electrical supplies are of the
Protective Multiple Earthing (PME) type. These supply cables have a Combined
Neutral and Earth (CNE) metallic outer conductor, which is earthed at multiple points
on the supplier’s Terra-Neutral-Combined (TNC) distribution network. Separate earth
and neutral terminals are then provided within the customer’s premises (TNC-S).
Generally the PME earthing facility is not allowed to be extended outside of the
equipotential zone and so exposed metalwork on the outside of the building must be
earthed independently using a local earth electrode.
36
6 COMMISSIONING / ACCEPTANCE TESTING
37
FIGURE 1 - TYPICAL CIRCUIT DIAGRAM
single phase
consumer unit fused switch export meter import meter
(only if reqd.)
PME
earthing
terminal blocks service cutout terminal
customer's
earthing
block
equi-potential bonds to
other metallic services
service cable
38
APPENDIX - APPROVAL & TYPE TESTING
The following points will be checked and tests carried out as necessary to establish if
an inverter can be classed as an ‘Approved Inverter for PV Generators’ for the
purposes of the UK Technical Guidelines for Inverter Connected Single Phase
Photovoltaic (PV) Generators up to 5kVA.
In the first instance, the equipment should be checked for compliance with European
CE Mark Regulations. The following table can be used to identify equipment
specifications which may be covered by European Norm (EN) standards, those which
are covered by British Standards (BS), those which are covered by Electricity Supply
Industry (ESI) standards and those which in the absence of official standards will
require additional verification:
Protection
39
A2 TESTING OF AUTOMATIC PROTECTION
The inverter equipment shall be tested by operation into a variable AC voltage test
supply system, whilst being fed from a DC source (which is simulating the PV DC
output). The set points for over and under voltage at which the inverter system
disconnects from the supply will be established by varying the AC supply voltage.
These set points and trip times shall be within the guideline requirements of section
3.1.
DC Source Variable AC
(simulating Inverter Voltage Test
PV generator) Supply
The inverter equipment shall be tested by operation into a variable frequency test
supply system) whilst being fed from a DC source (which is simulating the PV DC
output). The set points for over and under frequency at which the inverter system
disconnects from the supply will be established by varying the supply frequency.
These set points and trip times shall be within the guideline requirements of section
3.1.
DC Source Variable
(simulating Inverter Frequency
PV generator) Test Supply
Note: It may be necessary to disable any loss of mains protection function built in
to the inverter in order to perform this test.
40
A2.3 Loss of Mains Protection
The time to trip upon loss of mains will be verified to be less than the time required by
the guidelines under the conditions below:
The inverter equipment shall be fed from a DC source to simulate the output from a
PV source. The inverter output shall be connected to a variable impedance test set to
model the local load (at the inverter output terminals) and a switch placed between the
local load/inverter combination and the DNO’s distribution system as shown below:-
DC Source DNO’s
(simulating PV Inverter Variable Distribution
generator) Impedance Test System
Circuit to Model
Local Load
The inverter equipment is to be tested at three output powers and two local load
conditions, giving six tests in all (see table below):
Load match conditions are defined as being when the current from the inverter
connected generator meets the requirements of the local load i.e. there is no export or
import of current to or from the DNO’s distribution system. (It is assumed that the
local load will be mostly resistive. If other power factors are allowed these tests
would have to be modified depending on the controllability of the inverter).
The tests will record the inverter output voltage and frequency from at least 2 cycles
before the switch is opened until the inverter protection system operates and isolates
itself from the DNO’s distribution system. The time from the switch opening until the
protection isolation occurs is to be measured and must comply with the guidelines
under all conditions of output power and local load.
41
A2.4 Re-connection
Further tests will be carried out with the three test circuits to check the inverter time-
out feature prior to automatic network reconnection. This test will confirm that once
the AC supply voltage and frequency have returned to their nominal values following
an automatic protection trip operation there is a minimum time delay (as specified in
the guidelines) before the inverter output is restored (i.e. before the inverter
automatically reconnects to the network). The inverter shall be tested for connection
to a mains supply which is 180 degrees out of phase and at peak voltage to ensure no
damage occurs.
A3 POWER QUALITY
A3.1 Harmonics
For this test, the inverter can be fed by a DC source to simulate the DC output of a PV
generator. The inverter generator supplies full load to the DNO system via the power
factor (pf) meter and the variac shown below. The inverter pf should be within the
limits given in 4.2, for the three test voltages:
DC Source DNO’s
(simulating PV Inverter pf Variac Distribution
generator) System
230V +8%
230V
230V-8%
42
A3.3 Voltage Flicker
A3.5 DC Injection
The level of DC injection from the inverter connected PV generator in to the DNO
network shall not exceed 5mA when measured during tests A2.1, A2.2, A2.3 and
A3.2. This condition is satisfied by installation of a transformer on the AC side of
the inverter connected PV generator.
A4 SAFETY
A4.1 Earthing
The manufacturer shall ensure that the equipment is tested to the relevant British
standards.
A4.2 Labelling
There shall be labels supplied with the inverter for use at the service termination,
meter position and isolation switch as outlined in the guidelines.
43
Appendix B:
44
Summary of IEA Task V Activities
http://www.iea.org
The PVPS Programme has members from 20 countries (Australia, Austria, Canada,
Denmark, Finland, France, Germany, Israel, Italy, Japan, Korea, Mexico, the
Netherlands, Portugal, Spain, Sweden, Switzerland, Turkey, the United Kingdom and
the United States) and the European Commission.
The PVPS Programme is divided up into a number of Task Sharing group activities,
each focusing on different aspects of PV.
45
• Task V is entitled “Grid Connection of Building Integrated and Other Dispersed
Photovoltaic Power Systems” and has the overall objective to identify the technical
requirements and develop technical guidelines for grid-connected PV systems.
This task forms much of the background to this report.
• Task VII is entitled “Photovoltaic Power Systems in the Built Environment” and
aims to improve the architectural design and implementation of PV in buildings,
including residential and commercial buildings as well as infrastructure
installations.
More specifically, the main objective was to identify the technical requirements in
pre-normative technical guidelines for the network interconnection of building-
integrated and other dispersed photovoltaic (PV) systems. The aims of the guidelines
were to allow a safe, reliable and low cost interconnection of PV systems to the
electric power network.
Sub-task 10 had four items of study. The first item was a review of existing technical
guidelines or local regulations for the interconnection of PV systems with the utility
network. This survey enabled us to understand the general requirements for safe and
reliable interconnection. The second item was a review of utility distribution network
configurations in order to understand the difference of grid interconnection
requirements from country to country. The third item was a review of the status of
technology for interconnecting equipment (inverters and protective devices) and to
identify the applied criteria to satisfy the requirement for grid interconnection.
46
Specifications and characteristics of many inverters and protective devices have been
collected and summarised as a Task V internal document. The fourth item was a
review of the operating experience of grid interconnected PV systems to identify any
known problems relating to PV system operation.
The scope of work for sub-task 20 was to analyse present day and possible future
problems relating to the grid interconnection of PV systems and to draft possible
recommendations for improvement.
47
Appendix C:
(Subtask 10)
48
1 Introduction to Subtask 10
• The actual characteristics of inverters and related protection equipment and actual
operating experience of grid interconnected PV systems.
The following information relating to the guidelines was clarified according to the
research on the guidelines of each country participating in Task V.
49
Detection of islanding phenomena
Voltage fluctuation
Short-circuit capacity
- Safety and wiring of DC side
- Metering
- Lightning protection
- Authorisation procedure
- Standard configuration and electrical layout
- Islanding Protection
In general it can be said that no common guidelines for the connection of PV systems
to the utility grid exist in the participating countries. Every country has its own set of
rules, and in many countries these rules vary in different regions. This reflects the fact
that in many countries it is up to the individual utilities to define rules for connecting
independent power generators to their grid.
Safety is the most important issue in all of the regulations. At this moment it seems
that the problem of possible islanding (i.e. continued operation of a PV inverter even
when the grid is off) is a crucial issue and needs further study as it could immediately
lead to severe accidents. Topics such as cabling and earth fault detection seem to be
well known and can be readily adopted from guidelines governing conventional
electrical systems. However, the potential for DC currents to flow from the solar
panels leads to possible dangers that are different from those associated with AC
currents.
50
- Capacity of transformers - Feeders - Capacitors
Transformer
Feeders per transformer
Impedance
Average length
Number of switches per feeder
Number of sectionalisers per feeder
Capacitor for p.f. improvement
Average number of customer per feeder per phase for LV
Power rating of customer for LV
- Protective devices
Protective device installed in the public network
Reclosing
Protective co-ordination with independent producer
- Type and setting levels of the interface devices installed in the independent
producer’s network
- Operation criteria
Voltage fluctuation
Voltage regulation
Temporary supply
Work method for fault repair
It is worth noting that some data contained in the report must be considered as
referring to mean or typical conditions. As a consequence data referring to countries
where many local utilities exist and network characteristics and operating procedures
differ from region to region, should be treated carefully.
In general, it can be said that the LV grids in Europe have similar voltage levels while
USA and Japan have a different voltage level for the LV grid. Distribution system
configuration are different from country to country, and protection schemes also vary.
This is one of the reasons why the grid interconnection guidelines for PV systems are
different in each country.
This electrical distribution system report aids understanding of the differing electrical
grid configurations and the different approaches to the grid interconnection
requirements.
51
specifications, protective device specifications etc. More than 50 responses were
obtained including 5 inverters for AC modules, a new PV system concept in which an
inverter is integrated into a PV module. The summarised results are as follows:-
Type of Conversion
Most converters are self-commutated PWM inverters with current control. Some
voltage controlled self-commutated PWM inverters and line-commutated inverters are
listed.
- Europe
- Japan
- USA
Harmonic current
52
Almost constant in each power output point except for very low power
(around 1).
Isolation transformer
Control system
Depend on the inverter design. Either DC side or AC side is used. Some inverters
can be powered from both DC side and AC side.
53
1.3.2 Protective Devices
Transient: Varistor, TSV-Diodes, Metal oxide varistor (in Europe and USA)
Dynamic: Over-voltage relay or software detection
Europe
- Required in most countries:
frequency relay, voltage relay, harmonic increase, frequency shift
Japan
- Yes:
combination of both passive measure and active measures
USA
- Not required yet (although P929 will require active frequency shift technique)
some inverters already use the frequency shift technique
Restart
30 sec (Austria),
180 sec, adjustable (Italy),
150 sec, 160 sec, 0-300 sec adjustable (Japan),
first zero crossing, 6 sec, 120 sec after utility return to spec. (USA),
5 sec, 15 sec, 2 to 4 min (Switzerland),
3 minutes (UK)
54
Location of protective device
Depends on output power and quantity to be sold. Cost 1000 to 3000 (5000) $/kW for
under 5 kW devices. Less than 1000 $/kW for large power inverters. AC module
could be 1$/W.
- Noise reduction
- Full evaluation of islanding prevention measures
- Transformer-less design
- To customise control board and other components
- Islanding prevention measures with a number of interactive inverters
- Minimisation of wiring in construction
- Minimisation of heat dissipation
- Minimisation of certification procedure
- Inclusion of external disconnecter into the inverter
- External transient protection may be needed in some installation
- Standard EMI specifications could define minimum standards
From some seconds to some hours per outage, few times per year
No information available
PV array
55
total number of incidents: around 90. Typical reasons given are:-
Inverter
human error
design error (poor MPPT, malfunction of control circuit)
manufacturing (defective fuse)
Other (unspecified internal cause, grid transients, power limitation)
Utility interface
loose terminal in junction boxes, varistor burnt, burned contacts in circuit breaker
in front of battery (stand alone system), break of battery case (stand alone system)
damaged inverter
Lightning strike
module destroyed
Grounding fault
frequent tripping under high humidity, GFCI worked well with transformerless
inverter
56
Experience of islanding
Some old inverters caused disturbances on radio and TV, no problem with new
design.
Disturbance on telephone
It was found that inverter failure is the most frequent incident. This is mostly caused
by the lack of experience in first generation equipment and newly designed inverters
have good reliability. Only a few faults or failures caused by interconnection of PV
systems have been reported so far. However, this fact does not always indicate that
there is no problem for grid interconnection of PV systems. It is difficult to identify
the cause of the fault in some cases due to the absence of precise measuring
equipment. Some unexplained inverter failures may have been caused by grid
disturbances, reclosing and other interconnection issues.
57
Appendix D:
(Subtask 20)
58
1 Introduction to Subtask 20
In subtask 20, several topics were studied on the utility interface of grid connected PV
systems and summaries of the selected topics are described below. Detailed
information on the topics is given in the subtask 20 report “Utility aspects of grid
connected photovoltaic power systems”, Task V Report IEA-PVPS T5-01: 1998.
1.1 Harmonics
Problems
The harmonic problem has assumed a particular relevance starting from the 1960s
with the increasing use of static converters, which directly effect the quality of the
electricity supply.
In general, the harmonic problem can be defined as that particular disturbance that is
caused by the presence of non-linear loads which cause a modification of the voltage
and current sinusoidal waveforms in terms of sinusoidal components at a frequency
which is an integer multiple of the fundamental frequency.
Findings
It was found that since PV generators are connected to the distribution network
through solid state inverters they are potentially liable to cause harmonics, thereby
downgrading the quality of electricity and altering the performance of other equipment
sensitive to voltage harmonics. In addition, static converters themselves can be
sensitive to harmonics and may operate incorrectly as a result of harmonic voltage
distortion. An investigation of the harmonic phenomena as applied to PV systems
took into account aspects relevant to the generation (emission) and effects on
(susceptibility) the PV systems.
The work done has also showed the necessity to further investigate the effects on
harmonics in the case of multiple PV systems.
1.2 AC Modules
Problems
59
This modularity allows for very simple systems that can easily be expanded by simply
paralleling several AC Modules at the AC side. An AC Module is an electric product
and comparable to other appliances. It is anticipated that AC Modules will become
easily available at local retail outlets, which will enable people to buy and install them
without consulting a certified electrical engineer.
This “plug and play “ idea of AC Modules has raised several questions by experts
from electrical safety bodies and utilities. Plug and play means that the AC Module is
equipped with a standard AC-plug that allows for a direct plug-in to a regular mains
socket outlet in the electrical installation of a building. Some national and
international safety standards do not allow this, other standards are unclear.
Findings
A survey revealed that only a restricted number of countries are actually developing
and/or using AC Module systems. Other countries have no objections to AC Modules
but wait for other countries to gain hands-on experience. Nevertheless it is expected
that AC Modules will be used world-wide within a few years.
The Netherlands have issued a pre-draft guideline that AC Modules (or other types of
small generators) may be connected to normal feeders if the generated power is below
approximately 500 W. This philosophy is also under discussion in Switzerland.
However, some countries for example Australia and USA, have strict regulations not
to allow AC Modules or other types of small generators to be connected to a regular
feeder; a separate feeder is always necessary.
There are two certification standards for AC Modules available in the world. Both
these standards provide a set of rules to guarantee the electrical, mechanical safety of
an AC Module. The Dutch standard is issued by KEMA, in the USA the standard is
issued by Underwriters Laboratories (UL). UL and KEMA are working to harmonise
both these standards.
Although AC Modules have been available on the market for some years now, there is
still a lot of discussion on methods for interconnecting AC-Modules with the network.
Also, the method of interconnection is an important topic; is there a need for an AC-
60
marshalling box or is an AC-cord with (special) plugs an option, and what about the
connection to the AC-mains supply, bolted terminals or a separate plug?
Problems
Findings
The voltage at the customer’s terminals may exceed the upper statutory limit because of
reverse power flow from PV systems during light-load hours in the daytime. Leading
power factor operation of the PV system is an effective countermeasure to prevent the
voltage rise without reducing effective power.
In the event of a short-circuit fault condition occuring in the distribution line, the
increase in short-circuit capacity of the distribution line and the malfunction of OCRs
or fuses in the distribution system may occur as part of short circuit current is supplied
from PV systems. It would be necessary to develop a new fault detection system for
the PV system. A method of detecting the voltage phase change occurring in the fault
condition may be one useful option.
The effects anticipated to occur when a large number of PV power generation systems
are interconnected with distribution lines were investigated. The theoretical results
and experimental result regarding the effects and countermeasures are reported.
Recommendations for future work are as follows.
61
Development of a new fault detection for PV systems to detect a short-circuit fault
occurring at an end of a long distribution line, with a high resistance, or during
distribution line overload.
Further studies on the effect on distribution line voltage variation caused by the wide-
spread application of PV power generation, covering different application areas and
the number of interconnected systems.
Problems
When rules for early power generation and electrical distribution systems were being
developed in the late 1890 to early 1900’s, grounding requirements were limited to
lightning protection. In the United States, the National Electrical Code (NEC) and its
grounding requirements were first published in 1897. Most other countries throughout
the world, often independently, developed other versions of electrical codes to address
safety and grounding issues for electrical generation and distribution systems. The
resulting grounding techniques and requirements vary from country to country.
Optimised grounding for personnel protection does not optimise fire safety of a
system and grounding for fire safety does not optimise personnel safety. Grounding to
provide protection for equipment would require a third set of requirements.
Photovoltaic (PV) systems, as distributed current sources, require additional
grounding considerations. Distributed leakage paths, multiple fault paths and new
roles for fuses and circuit breakers are among a few of the new issues that need careful
consideration for PV applications. Codes for PV have closely followed the national
practice for AC power systems in each country, but many PV codes are being
developed as separate documents, rather than being included into existing codes.
Grounding of batteries associated with PV power sources adds another consideration
when grounding the PV array.
Findings
System and equipment grounding practices and requirements vary widely with
applications, among the countries, and sometimes within individual countries and a
survey of participating IEA countries revealed requirements and practices. Codes in
the USA require equipment grounding of all systems, and system grounding for
systems with voltages over 50 volts (open circuit module voltage). European and
Japanese codes require equipment grounding, but do not require system grounding and
most of their PV systems do not have grounded current-carrying conductors on the DC
side.
62
The grounding of power systems is complicated by the introduction of current-limited
PV sources interconnected with batteries and conventional voltage-source
electromechanical generators. Two universal conclusions for grounding were: a) most
codes and standards generally require equipment grounds for all metal surfaces that
might become energised, b) when system grounds are used, single-point grounds are
required. The ungrounded system provides the best fire hazard reduction because
multiple ground faults are needed to create a fire hazard. Ungrounded systems allow
easy ground fault detection and simple PV array disable.
The grounded PV system generally provides the best personnel protection from
electrical shock because the voltages to ground are well defined. The system
grounding ensures a solid or known PV array ground through properly sized
conductors. The distributed capacitance to ground, of the PV modules and wiring,
does not build static charges and the system voltage is stable and known in the
grounded PV system. With proper design, both grounded and ungrounded PV systems
can achieve good personnel, fire and equipment safety.
Problems
Fault currents may occur between active conductors in the circuit called line-to-line or
bolted faults, and active circuit conductors-to-ground called ground faults. Utility-
interconnected PV systems are often installed in close proximity to utility power lines
and accidental cross connection is a possibility that must be addressed. Unintentional
connections or faults may result in insulation failures and line-to-line (bolted) faults or
line-to-ground (ground) faults. The ground-fault protection of the PV system must be
consistent with the ground-fault protection used on the connected AC power system.
The AC circuit ground-fault protection requirements are generally part of electrical
system installation codes for the application.
Findings
A review of PV system experiences and requirements related to ground faults for grid-
connected applications was included as part of a survey of participating IEA countries.
The survey included hardware compatibility reviews and ground-fault detection
requirements as well as detection methods and disable methods. New developments
such as the rapidly evolving AC PV module will not require the use of ground-fault
63
detection on the PV-side DC circuits, since the DC voltage is self-contained within the
module and inverter, and there is no external access to the DC circuits. Additionally,
the tests associated with listing or certifying the self-contained AC PV modules will
assure both fire and personnel safety. It is very unlikely that any conditions will
require DC ground-fault detection in AC PV module applications.
Comparisons of the fire and personnel safety of the grounded and ungrounded PV
systems along with considerable research, showed the advantages and disadvantages
of each with respect to ground-fault detection. Users and operators must be aware of
the grounding methods used and the ground-fault detection and array disable methods.
The work included comparisons of PV array ground-fault detection requirements and
array disable experience, along with hardware, standards, listing guidelines and
practices used for PV system installations. The results of simulated ground faults,
simulated transients and lightning, and measured performance for the selected
grounding methods are reported and referenced.
PV systems are installed on roof tops, facades of buildings and special applications
such as sound barriers on motorways. PV-systems have, by definition, a large
exposure to the external environment and are therefore subjected to atmospheric
influences. A lightning strike is one of the most severe atmospheric influences. To
protect a PV-system for a direct lightning strike is not possible due to the very high
energy content of the lightning strike. However, a PV system must and can be
designed to withstand the effects of an indirect lightning strike.
Findings
Overvoltages due to indirect lightning strikes can be controlled with proper design of
the grounding structure of the PV-system. The main objective is to reduce loops
between the DC and AC wiring and the ground structure. This can be solved by
having a grounding wire running down from the metal support structure of the array,
DC wiring, inverter, AC wiring to the ground structure at the main fuse box. If an
external lightning protection system is available this should be connected to the metal
64
support structure of the array. This deliberately formed ground loop allows currents to
flow, but reduces the presence of overvoltages to a minimum. Since these currents
flow in a well defined path, no hazards are present.
1.7 Islanding
Problems
Findings
A lot of anti-islanding methods have been identified in the literature and have been
tested in practice. They can be divided into 2 groups:
• Passive methods:
a detection circuit monitors grid parameters (e.g. voltage, frequency, voltage
phase jumps, voltage harmonics); these methods do not have any influence on
grid power quality.
• Active methods:
a detection circuit deliberately introduces disturbances (e.g. active or reactive
power variation, frequency shift) and deduces from the reaction to these
disturbances if the grid is still present. Active methods can therefore directly
effect local power quality.
Currently, no two countries have the same rules as far as islanding is concerned, but
there is some common ground: in all countries a PV inverter (or some external
protective device) is required to monitor voltage and frequency. However, the set-
points for shutdown and disconnection from the grid are not generally agreed upon.
65
It is further recommended to perform a scientific risk analysis based on real load
patterns in real distribution systems to determine the probability of islanding. Such an
analysis could form the common ground from where generally accepted anti-islanding
methods could be derived. At present the dangers of islanding seem to be over-
estimated; in some countries this has led to legislation demanding very costly or too
sensitive anti-islanding methods.
From the technical point of view it seems to be possible to include effective and
reliable anti-islanding methods in the inverter control software which would make PV
systems more simple to install and bring costs down.
Therefore a manufacturer of PV inverters has to make sure that his device has a
certain immunity against external electromagnetic phenomena. At the same time it
must not produce emissions disturbing other electronic devices.
Findings
All industrialised nations have some form of legislation which sets limits to the
maximum allowable level of electromagnetic emissions. These limits are usually a
result of long discussions and are well-proven in practice. The compliance with these
limits is tested in well-defined test set-ups with standardised test instruments. The
relevant standards for Australia, Europe, Japan and the US have been compiled and
referenced. Where possible, the relevant immunity standards (if such exist) have also
been cited.
The problem of EMC is not a PV-specific topic. Therefore it does not make sense to
create new standards for PV equipment like inverters as the existing standards are
generally valid. The only remaining topic: the test set-up for measurements of
emissions on the DC lines has to be defined more clearly as conventional devices
usually do not have DC connections.
This topic examined the necessity for PV systems to have an external manual AC
disconnect switch to allow the Utility to disconnect the PV system in the case of
maintenance on the AC network or fire hazard etc., to comply with Health and Safety
Regulations
66
Findings
It was generally agreed that as small generators became more common, the task of
isolating every unit at an external switch would become impossible to implement
reliably, and moreover it did not take into account units that were illegally connected,
and thus not registered with the Utility. For this reason, and the relatively high
installation costs for such a switch, it was proposed to investigate other solutions.
Some countries, such as Germany the Netherlands and Austria, were coming to the
view that in certain circumstances protection relays and operational procedures could
be relied upon. This was backed up by a risk assessment study in Germany by the
Employer’s Liability Insurance Association to IEC guidelines.
It was generally agreed that if anti-islanding devices were used for the external
disconnect function, they would have to be relay devices with a physical opening of
contacts rather than an electronic semiconductor switch.
For PV it is anticipated that the situation evolving in Germany and the Netherlands
will become more widely adopted, where the external switch is not mandatory, and
the Utility relies on the relay 'islanding' protection and their practices for checking and
grounding the conductors, assuming that they are live, before carrying out
maintenance. This relies on the involvement of the Utilities.
It is important to recognise that the problem is not specific to PV but also applies to
other embedded generators, and so it is sensible to harmonise with other work being
carried out in this area.
When more information is available from the anti-islanding work, then these devices
should be assessed for their suitability to provide the function of the external
disconnect also.
1.10 Re-closing
Problems
67
Findings
In fact, the re-closing procedure may lead to out-of-phase parallel conditions with
consequent potentially dangerous stress for the inverters, for the loads, for the line-
breakers and for the transformers installed on the utility network.
A dc current fed from the customer's side into the grid can disturb the regular
operation of the upstream distribution transformer. It can shift the transformers
operating point and cause saturation. This would result in high primary current peaks,
which might trip the input fuse and thus cause a power outage to that specific section
of the grid. It would furthermore cause increased harmonics.
An overview is given how the participating countries view the requirement for an
isolation transformer. The possible impact of a dc current on the operation of a
distribution transformer was assessed using literature review and laboratory
experiments.
Findings
Under high dc components high primary current peaks occur. Also, a high level of
harmonics is generated. The pulsed dc component may reach levels around 10 % of
rated current without jeopardising the proper operation of the transformer.
Conclusions
The hazard of dc currents from small PV systems for the local distribution transformer
seems to be negligible, therefore a general requirement for isolation transformers for
PV inverters is not justified on these grounds. However, dc currents could cause
problems in other areas, such as accelerated corrosion of underground cables due to
cathodic erosion, adverse effects on residual current protection devices (RCD's) as
68
well as adverse effects on the mains transformers within the consumers other mains
appliances.
69
Appendix E:
(Subtask 30)
70
1 Introduction to Subtask 30
In subtask 30, experimental studies using the Rokko Test Centre for Advanced Energy
Systems test facility were conducted. Experiments were conducted for many aspects
like harmonics, islanding, PV system output variation, dc-ac mixing and others.
Summaries of the experimental results are described below. Detailed information on
the test results are given in the IEA PVPS report “Demonstration Tests of Grid
Connected Photovoltaic Power Systems”, Task V Report IEA-PVPS T5-02.
It was found in the experiments carried out at Rokko Island that the third and the fifth
harmonic current increased with the increase in the number of connected inverters.
However, the higher harmonics did not always increase or sometimes decreased with
the number of connected units. From these results, it can be concluded that third and
fifth harmonic current from inverters have almost the same phase displacement and
the total harmonic current is superimposed, while higher harmonics from inverters
have different phase displacement and total harmonic current is cancelled to a degree.
The phenomenon that the third harmonic and the fifth harmonic increases with the
number of connected units is considered to be caused by the exitation current of the
isolation transformers.
Islanding may cause problems such as human and equipment safety if it continues for
a long time. It is therefore important to clarify the conditions under which continued
islanding occurs, and verify the necessity of measures for preventing islanding and the
effectiveness of these countermeasures, especially when a large number of PV systems
are interconnected to one distribution line.
The Rokko Island tests showed that when many PV systems whose inverters have
only ordinary protective relays such as over/under voltage relays and over/under
71
frequency relays, islanding can be continued for a long time if the total output power
the from PV systems is higher than total load on the local distribution system. This
result shows that some measures for detecting islanding conditions are required.
Various kinds of islanding detection or prevention techniques, including passive and
active schemes, have been proposed.
Islanding does not continue for a long period of time if multiple PV systems having
islanding detection functions for their inverters were interconnected to the power
distribution line, especially when inverters manufactured by different manufacturers
were interconnected together. This means that when different islanding detection
schemes co-existed, islanding did not occur. It was confirmed that mainly the passive
scheme detected islanding phenomenon, while the contribution of the active islanding
detection scheme was not clarified. It was also found that islanding detection time
increases when a load which can sustain a distribution line voltage such as induction
motor load is connected.
PV systems may supply fault current under short circuit fault conditions in the
distribution system. Fault current from PV systems could affect fault detection,
causing a delay in the operation of protection. Therefore, it is necessary to verify the
effect of the short circuit current from PV systems on system fault detection.
Fault current from PV systems were measured under short circuit conditions at the LV
side of the distribution transformer. Measurements were conducted for various output
power of the PV system.
The Rokko Island tests showed that some inverters do not supply fault current at all
(only maintaining the current before short circuit fault) and stop operation quickly
(within 1 or 2 cycles) by the under voltage relay. Even for inverters supplying fault
current the magnitude of fault current is only twice the pre-fault value and lasts only 1
or 2 cycles.
It was concluded from the Rokko Island tests that PV systems do not significantly
affect the protection for short circuit faults in distribution systems.
72
injected into the distribution system. The effect of DC injection could be examined by
more severe situation, such as an AC/DC mixing fault condition, in which the DC
circuit of the PV array is directly connected to the AC system. In this AC/DC mixing
fault condition, the effect of an AC current on the DC circuit of the solar cell array
can be also examined.
The propagation range of harmonics generated at the AC-DC mixing fault in the
power system, the effect on other transformers connected to the same high voltage
distribution line and the effect on other inverters for photovoltaic power generation
connected to the same low voltage distribution line are examined.
The exitation current of the utility transformer starts to increase immediately after
AC/DC mixing fault and becomes stabilised (saturated) after several seconds. At this
time, magnetic saturation occurs and harmonic current of even orders are generated on
the high voltage side of the utility transformer. Distortion of the current waveform was
also seen in other utility transformers connected to the same high voltage side of the
distribution line and the isolation transformers of other photovoltaic power generation
systems connected to the same low voltage distribution line.
However, even though the AC/DC mixing fault persisted for several minutes, no
overheating, vibration or sound was observed for the utility transformers. Also, no
effect was observed for the operation of PV systems connected to the low voltage side
of utility transformers located in the vicinity of the utility transformer generating
mixing fault. For conclusion, the effect of DC current injected into the AC system on
the utility's distribution transformer is negligible.
The output of photovoltaic power generation fluctuates with solar irradiance. Solar
irradiance can vary from one second to the next owing to clouds passing overhead.
The fluctuation in output of the photovoltaic power generation causes fluctuations in
power flow or voltage in the connected distribution line. If many PV systems are
interconnected to a limited area, output fluctuation of the PV systems occur
simultaneously and voltage fluctuations in the distribution line increases, possibly
becoming of greater significance than load fluctuations. Moreover, considering that
the voltage fluctuations take places in a timeframe of seconds, it may cause flicker,
which may become a technological issue for the future introduction of photovoltaic
power generation.
73
Findings and Conclusions
In the case that many PV systems are connected, even if the output fluctuation of each
PV system is large, both the magnitude and speed of fluctuation decreases as a whole.
Accordingly, distribution voltage fluctuations due to PV output fluctuations also
decreases.
74
Appendix F: List of Task V Reports
The IEA PVPS Task V group has published the following reports
[3] “Proceedings of the IEA Workshop on Existing and Future Rules and Safety
Guidelines for Grid Interconnection of Photovoltaic Systems”, Zurich,
September 1997.
Note:
“Official” Task V reports are available from the Task V Operating Agent (Mr Takuo
Yoshioka, NEDO, Sunshine 60, 29F, 1-1, 3-Chome, Higashi-Ikebukuro, Toshima-ku
City, Tokyo, Japan).
Once the existing stocks of reports has been depleted it may be necessary for a small
charge to be made to cover printing, packing, postage and administative costs.
There are plans in hand to make as many of the above reports as possible available on
the Internet, from the web site at:
http://www.iea.org/impagr/imporg/iadesc/pvps
75
Appendix G: List of PV Systems Installed in the UK
Installation (Building Integrated) Installed Peak Power (kWp)
76
Installation (Building Attached) Installed Peak Power (kW )
77