4TTR60
4TTR60
4TTR60
Optional Accessories:
2 22-1916-1A-EN
Pr o d u c t S p e c i fi c a ti o n s
Dimensions H x W X D Crated (IN.) 42 x 35.1 x 38.7 50.4 x 35.1 x 38.7 50.4 x 35.1 x 38.7
Optional Accessories:
22-1916-1A-EN 3
Pr o d u c t S p e c i f i ca t i o n s
Dimensions H x W X D Crated (IN.) 50.4 x 35.1 x 38.7 50.4 x 35.1 x 38.7 50.4 x 35.1 x 38.7
Optional Accessories:
4 22-1916-1A-EN
Sound Power Level
A-Weighted
Sound
MODEL Full Octave Sound Power(dB)
Power Level
[dB(A)]
63 125 250 500 1000 2000 4000 8000
Hz* Hz Hz Hz Hz Hz Hz Hz
4TTR6018J 73 79 69 67 70 70 64 59 53
4TTR6024J 73 79 69 67 70 70 64 59 53
4TTR6030J 73 79 69 67 70 70 64 59 53
4TTR6036J 71 78 72 69 68 66 61 58 53
4TTR6042J 72 81 75 71 70 68 63 58 53
4TTR6048J 72 81 75 71 70 68 63 58 53
4TTR6049J 72 81 75 71 70 68 63 58 53
4TTR6060J 72 81 75 71 70 68 63 58 53
4TTR6061C 74 68 56 63 73 69 64 59 51
Note: Rated in accordance with AHRI Standard 270–2008 *For Reference Only
22-1916-1A-EN 5
Accessory Description and Usage
A n t i - S h o rt C y c l e T i m e r — Solid state timing device that prevents compressor recycling until
five (5) minutes have elapsed after satisfying call or power interruptions. Use in area with
questionable power delivery, commercial applications, long lineset, etc.
E v a p o r a t i o n D e f r o s t C o n t r o l — SPST Temperature actuated switch that cycles the condenser
off as indoor coil reaches freeze-up conditions. Used for low ambient cooling to 30°F with TXV.
R u b b e r I s o l a t o r s — Five (5) large rubber donuts to isolate condensing unit from transmitting
energy into mounting frame or pad. Use on any application where sound transmission needs to
be minimized.
H a r d S t a rt K i t — Start capacitor and relay to assist compressor motor startup. Use in areas with
marginal power supply, on long linesets, low ambient conditions, etc.
E x t r e m e C o n d i t i o n M o u n t K i t — Bracket kits to securely mount condensing unit to a frame or
pad without removing any panels. Use in areas with high winds, or on commercial roof tops, etc.
A H R I S t a n d a r d C a p a c i t y Ra t i n g C o n d i t i o n s
AHRI Standard 210/240 Rating Conditions
1. Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil.
2. High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering
indoor coil.
3. Low Temperature Heating 17°F DB air entering indoor coil.
4. Rated indoor airflow for heating is the same as for cooling.
A H R I S t a n d a r d 2 7 0 R a t i n g C o n d i t i o n s — (Noise rating numbers are determiend with the unit in
cooling operations.) Standard Noise Rating number is at 95°F outdoor air.
Model Nomenclature
Outdoor Units 4 T W V 0 0 3 6 A 1 0 0 0 A A
Re frig e ra n t Typ e
2 = R-22
4 = R-41 0A
TRANE
Pro d u ct Typ e
W = Split Heat P ump
T = Split Cooling
Pro d u ct Fa m ily
V = Va ria b le S p e e d M o r B = Ba s ic
Z = Leader ship – Tw o S ta g e A = Lig h t Co m m e rcia l
X = Leader ship
R = Replacement/R etail
Fa m ily S EER
3 = 13 6 = 16 0 = 20
4 = 14 8 = 18
5 = 15 9 = 19
Split S ystem Connections 1 -6 To n s
0 = Braz e d
Nominal Capacity in 0 00s o f BTUs
Major Design Modifications
Po w e r S u p p ly
1 = 20 0-230/1/60 or 208-230/1/60
3 = 20 0-230/3/60
4 = 460/3/60
Se co n d a ry Fu n ctio n
Minor Design Modifications
Unit P a rts Id e n tifie r
6 22-1916-1A-EN
Schematic Diagrams
Figure 1. 018 — 048 Models
22-1916-1A-EN 7
S ch e m a t i c D i a g r a m s
8 22-1916-1A-EN
S ch e m a t i c D i a g r a m s
PRINTED FR
OM D157048P01
22-1916-1A-EN 9
Outline Drawing
Model Base A B C D E F G H J K
730 829 756 127 76 197 60 508
4TTR6018J 3 3/4 3/8
(28–3/4) (32–5/8) (29–3/4) (5) (3) (7–3/4) (2–3/8) (20)
730 829 756 127 76 197 60 508
4TTR6024J 3 3/4 3/8
(28–3/4) (32–5/8) (29–3/4) (5) (3) (7–3/4) (2–3/8) (20)
933 829 756 143 92 210 79 508
4TTR6030J 3 3/4 3/8
(36–3/4) (32–5/8) (29–3/4) (5–5/8) (3–5/8) (8–1/4) (3–1/8) (20)
943 946 870 143 98 219 86 508
4TTR6036J 4 3/4 3/8
(37–1/8) (37–1/4) (34–1/4) (5–5/8) (3–7/8) (8–5/8) (3–3/8) (20)
1147 946 870 152 98 219 86 813
4TTR6042J 4 7/8 3/8
(45–1/8) (37–1/4) (34–1/4) (6) (3–7/8) (8–5/8) (3–3/8) (32)
1147 946 870 152 98 219 86 813
4TTR6048J 4 7/8 3/8
(45–1/8) (37–1/4) (34–1/4) (6) (3–7/8) (8–5/8) (3–3/8) (32)
1147 946 870 152 98 219 86 813
4TTR6049J 4 7/8 3/8
(45–1/8) (37–1/4) (34–1/4) (6) (3–7/8) (8–5/8) (3–3/8) (32)
1147 946 870 152 98 219 86 813
4TTR6060J 4 7/8 3/8
(45–1/8) (37–1/4) (34–1/4) (6) (3–7/8) (8–5/8) (3–3/8) (32)
1147 946 870 152 98 219 86 813
4TTR6061C 4 7/8 3/8
(45–1/8) (37–1/4) (34–1/4) (6) (3–7/8) (8–5/8) (3–3/8) (32)
10 22-1916-1A-EN
Mechanical Specification Options
General
The Outdoor Units are fully charged from the factory for up to 15 feet of piping. This unit is
designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are
matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is
certified to UL 1995. Exterior is designed for outdoor application.
Casing
Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant
powder paint finish on all louvered panels and the fan top panel. The corner panels are
prepainted. All panels are subjected to our 1,000 hour salt spray test . The base is made of a
CMBP-G30 weatherproof material to resist corrosion.
Ref rig er an t Con tro ls
Refrigeration system controls include condenser fan, compressor contactor and high pressure
switch. High and low pressure controls are inherent to the compressor. A factory supplied liquid
line drier is standard. Some models may require field installation.
Compressor
The compressor features internal over temperature, pressure protection and total dipped
hermetic motor. Other features include: Centrifugal oil pump and low vibration and noise.
Condenser Coil
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected
on all four sides by louvered panels.
Low Ambient Cooling
As manufactured, this system has a cooling capacity to 55°F. The addition of an evaporator
defrost control permits operation to 40°F. The addition of an evaporator defrost control with TXV
permits low ambient cooling to 30°F.
T h e r m o s t a t s —Cooling only and heat/cooling (manual and automatic change over). Sub-base to
match thermostat and locking thermostat cover.
E v a p o r a t o r D e f r o s t C o n t r o l — See Low Ambient Cooling.
22-1916-1A-EN 11
Notes
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
©2015 Trane
22-1916-1A-EN 01 Oct 2015
Supersedes (New)