Data Sheet

IQ23x
Series Controllers

IQ23x SERIES CONTROLLERS

Description Features
The IQ231 and IQ233 mid range controllers are specifically • good hardware and software compatibility for field replacement
designed for field replacement of the older IQ111 (111+) and of IQ111 (+) and IQ131 (+) controllers
IQ131 (131+) controllers respectively. They are also useful in • 20 universal inputs maximum (IQ231 has 8)
new installations, for a broad range of applications. The IQ231 • 12 analogue voltage outputs maximum (IQ231 has 8)
has 16 input/output points, and the IQ233 has 32 points. Options • integral or external 2-line display options
are available for an integral or external 2-line display panel. • local supervisor or NDP
• 1 second cycle time and extended logging

Physical
mains ac
supply
A U X
2 4 V T + T - R + R - R x
O K
T x
external 2-line R + R - T + T -
R S 2 3 2 /M O D E M

2 3 0 V

display panel option


R D S

RS232/modem
(for auxiliary node) Trend Lan connectors
fail LED local supervisor port address/baud earth stud (M3)
rate switch
auxiliary node knockout power LED Trend Lan LEDs
A D D R E S S B A U D R X

O K
1 9 K 2
9 K 6
1 K 2
1 6
3 2
6 4
1
2
4
8

T X

auxiliary 24 Vdc supply

D P
288 mm

B
integral 2-line
C
display panel
D
option

earth flange

339 mm 93 mm
cable cleats inputs analogue outputs

IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02 1


IQ23x Data Sheet

FUNCTIONALITY
The IQ Controller’s functionality can be divided into three sections, strategy, firmware, and hardware.

STRATEGY FIRMWARE
The strategy processes inputs according to a set of instructions Communications: When operating as part of a Building
and then outputs signals which can be used to control plant. Management System, the IQ23x will be connected to other
devices via the Trend Network. This means that information
Configuration: The IQ23x uses the standard IQ configuration within the IQ23x can be accessed using one of the Trend
mode which enables configuration via the network, or via the supervisor programs, or passed to other Trend IQ controllers
supervisor port. SET can be used to create a strategy data file using inter-controller communications, enabling the sharing of
(.IQ2) which can then be downloaded to the controller and information across the whole system.
subsequently uploaded for backup purposes if connected to the
controller directly or via the network. PowerTool can be used to When connected to the network the controller can use up to 2
upload, and download IQ2 files if connected via a modem. different addresses. One address is for the controller itself, the
second is optional, and is for the supervisor port (locally connected
A strategy data file from an IQ1xx controller (.IQF) can be
supervisor or NDP). The controller’s address is set by a switch,
downloaded to an IQ23x and will require modification as explained and the supervisor port address is set up in the strategy
in the compatibility section configuration (address module).
Modules: The strategy consists of a number of individual HARDWARE
functional blocks known as configuration modules. These blocks
can be linked in various combinations to enable plant to be
Unit: The IQ23x is supplied in a metal enclosure. It has 4
controlled in accordance with the building’s requirements. The mounting points which are on the same centres as the IQ111+
table lists the different types of configuration modules and the and IQ131+; they are also the same as those provided by the
number of each type available with IQ23x. IQ111 or IQ131 using the mounting bars. Its footprint is smaller
than IQ111 or IQ131, and the same as the IQ111 or IQ131 with
Module Type Number Module Type Number
their mounting bars, but it is 13 mm deeper
Sensor 48 Critical Alarm 4
Connectors: Two part connectors are used throughout to
Sensor type 15 Alarm History 20 facilitate wiring. An earth flange is provided for screen termination
with a special M3 earth stud close to the network connection, and
Loop 32 IC Comms 16 there are cleats for cable restraint.
Function 160 Digital Inputs 48
Power: 230 Vac 50/60 Hz.
Logic 160 Fast Sequence 8
Driver 32 Zone 5 Fusing: The controller has no replaceable fuses; protection is
provided by means of a self-resetting thermally protected
Knob 30 Schedule 32 transformer.
Switch 20 Calendar 20
Indicators: LED indicators for receive and transmit network
Sensor log 32 User Password 6 current flow (RX, TX) and network OK ( ), also for all I/O
Sequence step 400 Sequence time 1s channels, power ( ), and fail ( ). See specification section for
details.
Analogue Nodes 255 Digital Nodes 506
Display 200 Directory 40 Network: The network terminals facilitate connection of 4 wire
Page 50 Group 10 cables. The standard Trend node features are included (TX, RX,
and network OK, , indicators, bypass relay, and network
Route 50 Destination 7 alarm generation). There is also the facility for connection of a
New Alarm Log 200 supervisor or network display panel to the network via the
controller without the need for an additional node controller.
Full details of the modules are given in the IQ Configuration
Manual and Addendum. The IQ23x contains the normal IQ2 Internal Node: A node controller card may be fitted inside the
features as described in IQ Configuration Manual Addendum: unit either as a pre-fitted option, or post-fitted using the appropriate
Engineers Journal (J), I/O Summary (i/o) Loader Issue (R(c),’c’ cables. There is a two pin polarised plug to supply 24 Vdc to the
lower case), Serial Number (R(s), ‘s’ lower case), Supply node and a four pin polarised plug which provides a network
Frequency Option, Enhanced Logging, Module position, and connection. There is a set of two pairs of pins adjacent to the
Strategy Cleardown. Differences between the modules covered network plug which are normally shorted by two links; these
in the manuals and the IQ23x’s modules are covered below. must be removed when the node is connected. For an integral
node controller to operate the external network must be connected,
Address Module or the external network terminals must be linked (TX to RX).
It has two additional items described below: A node is post-fitted using KIT/NODE/IQ23x. This provides
mounting plates, pillars, screws, and cables to enable connection
default PIN disable: This increases the controller security by of the current nodes (TMN, CNC2, PNC2, INC2, LINC, and
disabling the default PIN. It is accessed using the character “d”, XN28); the node card is ordered separately. There is a 25 way
setting d=1 will disable the default PIN. It may be enabled by D type knockout on the upper panel for RS232 connection to the
setting d=0 (as long as a valid PIN is used). This change requires node, and a circular knockout for 14.25 mm grommet for
a PIN with level 99. If the IQ23x has lost its strategy, the PINs internetwork, PSTN, ISDN, or Lon cables.
are unknown, and the default PIN is disabled, then the strategy
can be restored by the address/baud rate switch zero reset, and
mounting plate network
a subsequent strategy download. connector
sUperv port addr: This operates as described in the IQ J2
Configuration manual addendum with the additional feature that
if the address is set to 120, the supervisor port will be disabled. J47
This gives increased security. The port can be enabled by setting J48
the address to another value by configuration or text comms over R+T+T-R-
the network and is protected by password level 99. View on top of supply
board connector
Byte 506, Bit 1 network links
This bit now has the fixed function of ‘IQ1 series simulation of
universal input action’ (see Compatibility section, Firmware).

2 IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02


Data Sheet IQ23x

HARDWARE (continued)
Address/Baud rate switch: The address on the Lan is set by
Analogue Voltage Outputs V
poles 1 to 7 in range 1, 4 to 9, 11 to 119 and must be unique on
the Lan. The baud rate is set by poles 8 to 10 in the range 1k2, 4k8, (IQ231: channels 1 to 8; IQ233: channels 1 to 12)
9k6, 19k2 and must match the other nodes on the Lan. The 4k8
baud rate is selected by setting all three poles to zero.The
address/baud rate switch may also be used to perform a strategy
cleardown; this is done by setting all the address/baud rate poles 2 4 V
to zero before power up (see Installation Instructions, TG200539
sheet 3 and IQ Configuration Manual Addendum). For this reason
the address should normally be set non-zero.

Battery Backup: Details about the strategy configuration, time


and date, and logged data are stored in RAM. A plug-in lithium cell 2 2 R
provides power to maintain the data in the event of power failure, 1 0 0 R
or the controller being switched off. B n

y e llo w 0 V
24 Vdc Auxiliary Supply: The IQ23x has a 24 Vdc auxiliary 500
0 V
mA supply protected by a self-resetting passive thermal device. It
is available from two terminals on the back of the unit for relay 2 K 7
modules, interfaces etc. and is completely separate from other
supplies. 0 V
Link Headers
I/O channels: The IQ231 is supplied with 16 I/O channels and A range of link headers is available to enable the input channels to
the IQ233 with 32 I/O channels.
accept a wider range of inputs:
Universal Inputs LKE/5V: Provides 5V, 20 LKE/15V: Provides 15V, 20
mA supply mA supply
(IQ231: channels 1 to 8; IQ233: channels 1 to 20) IQ 2 3 x IQ 2 3 x

- linkable for thermistor (T), digital (D), voltage (V), or current (I);
the digital and current inputs can either be loop powered (powered 1 0 0 K 1 0 8 K 1 0 0 K 1 0 8 K

from the IQ), or can be externally powered (Ix and Dx).


2 4 V 5 V

1 0 K
2 4 0 R 2 4 0 R

0 V 0 V
5 V 1 5 V
R E G R E G
2 4 V 2 4 V

A n C 0 V A n C 0 V
L K E /5 V L K E /1 5 V
A n 1 0 8 K 5 V 1 5 V

S e n s o r S e n s o r

1 0 0 K LKE/10mA: Provides 10 mA supply (e.g. for potentiometers)


IQ 2 3 x
3 9 K
2 4 0 R
1 0 0 K 1 0 8 K
1 0 K
C If the input device is 100 Ω to 1000
1 0 K
y e llo w Ω, the analogue input will be 1 V
to 10 V.

0 V 2 0 0 R 1 2 5 R

0 V

1 5 V
The two links on each input channel must be correctly positioned 2 4 V
R E G

to set up the type of input required.


A n C
L K E /1 0 m A

loop powered loop powered


1 0 m A

T D V I To install a link header on a channel, the input links are removed


and the link header is plugged onto 8 of the 10 input linking pins
as shown below, the two upper pins being left free; care must
be taken to correctly orientate the link header.

A I 4
C
link header in position
A I 4
view on top of
externally powered externally powered board

D x Ix C A n -1 C A n C A n+ 1 C A n+ 2 C

board on left hand side

view on front
edge of board

IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02 3


IQ23x Data Sheet

HARDWARE (continued)
Displays: The IQ23x can have three different types of local display; 2-line Display Panel, PC, or Network Display Panel.

2-line Display Panel: The controller may be purchased with a PC or Network Display Panel : A computer running a
2DP option fitted in the cover. Alternatively an external 2DP (i.e. Trend Supervisor or Engineering Tool can be connected to the
HDP, FPK, ENCLS/FP) may be connected by fitting the KIT/2xx/ Trend network via the controller’s supervisor port without the
RDS option which provides a 25 way D type female connector need for an additional node controller although it does take a
on the upper face of the unit. separate network address. When connected in this way the
If a display panel is mounted in the front cover, it will not be supervisor will have access to all devices on the network, and
possible to connect an external 2-line display. The 2DP provides will function as if it were connected via its own node controller.
access to parameters within the controller. A Network Display Panel may be connected instead of a PC. A
special adaptor cable (CABLE/EJ104029) enables the NDP’s
signal and power to be available from the local supervisor port
connector (RJ11); this supply is limited at 100 mA by a self-
resetting passive thermal device.
The diagrams below illustrate the various combinations in which the display panels, network display panels and supervisor/
engineering tools can be connected.

N D P PC or NDP D P
N D P

(connected via A

supervisor port) B

A D D R E S S B A U D

O K
R X
PC or NDP

1 9 K 2
9 K 6
1 K 2
1 6
3 2
6 4
1
2
4
8
T X

A D D R E S S B A U D

O K
R X

(connected via
1 9 K 2
9 K 6
1 K 2
1 6
3 2
6 4
1
2
4
8

FPK or HDP 2-
T X

D P
supervisor port)
D P

integral 2-line line displays A

B
A

display panel (connected B

D
C

option via DP port if


KIT/2xx/RDS
option fitted)

COMPATIBILITY
Supervisors: 94x series, 921, 962, Viewpoint+.
Utility software: PowerTool, 822+/Toolbox version 6, SET, WupDn.
Controllers: It can communicate to other Trend IQ controllers using inter-controller communications.
Interface: It can be connected to Trend interface modules. Check interface module specification to ensure compatibility.
Local Display: Network Display Panel (external), 2-line Display Panel (external or internal).

The IQ Configuration Reference Manual Addendum covers the compatibility between different types of strategy files, and between
the IQ23x sensor logs, and supervisors and software tools.

Compatibility with IQ111 (+), IQ131 (+)


308
Fixing
The IQ23x will fix to the same centres as the IQ111+ or IQ131+,
and as the IQ111 or IQ131 with mounting bars. If the IQ111 or
263

IQ131 weren’t originally mounted using the bars, then new fixing
holes will need to be drilled. The IQ111+ and IQ131+ also had
semicircular cutouts for mounting in the old small box (380 x 380
x 210 mm - no longer supplied); new holes would have to be drilled
to fix the IQ23x.

Size IQ Controller Height Width Depth


The footprint of the IQ23x is smaller than the IQ111+, IQ131+, IQ111/IQ131 287 mm 335 mm 80 mm
and the IQ111, IQ131 with mounting bars. It is deeper than any with mounting bars
of them. IQ111+/IQ131+ 340 mm 358 mm 80 mm
IQ111/IQ131 240 mm 335 mm 80 mm
IQ23x 288 mm 339 mm 93 mm

Power
IQ Controller Power
The power requirements are shown in the adjacent table. Note
IQ111/IQ131 60 VA
that the requirements of the IQ23x are greater than those of the
IQ111+, IQ131+. IQ111+/IQ131+ 35 VA
IQ23x 60 VA

4 IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02


Data Sheet IQ23x

Connections:
local supervisor local supervisor
(25 W D male) external DP2 (25 W D male) external DP2
power, IEC power, IEC

external DP
external DP

IQ 1 1 1 IQ 1 3 1

outputs
outputs inputs network 4 wide
inputs auxiliary supply 1 wide
auxiliary supply network 8 wide

local supervisor local supervisor


(5 in line) (5 in line)
power, IEC external DP network 8 wide external DP network 8 wide
power, IEC

IQ 1 1 1 + IQ 1 3 1 +

auxiliary inputs auxiliary


inputs outputs outputs
supply supply
comms node local supervisor
auxiliary comms node auxiliary local supervisor
external DP (RJ11)
supply network 8 wide external DP supply (RJ11)
power, IEC network 8 wide
power, IEC

IQ 2 3 1 IQ 2 3 3

inputs outputs inputs outputs


Power: The Power connectors are all IEC plugs and in The IQ23x has a 500 mA auxiliary supply which is separate from the
a similar position. sensors, 2DP, and node supply. This is greater than the IQ111, 131
Inputs/Outputs: These are all compatible 2 wide 2 part (500 mA for auxiliary plus sensors, 2DP, node supply), and the IQ111+,
connectors and it should be possible to unplug from the 131+ (200 mA separate supply).
old controller and into the IQ23x without rewiring unless
the cables were very tight (see I/O channels below). I/O Channels
Note that early IQ111, 131 had single part terminals on
IQ Controller Inputs Outputs
the input channels.
External Display Panel: This has always used a 25 way
D type female connector, and it should be possible to IQ111 1 to 8 Universal channels, 1 to 6 Universal channels,
unplug from the old controller and into the IQ23x unless V, I, T, D V, I
the cables were very tight (see display panel below). IQ111+ 1 to 8 Universal channels, 1 to 8 Analogue V channels
Note that the IQ23x must have a KIT/2xx/RDS fitted to V, I, T, D
support the external 2DP. IQ231 1 to 8 Universal channels, 1 to 8 Analogue V channels
Network: The IQ111+ and IQ131+ have 8 wide network V, I, T, D
terminals like the IQ23x and in the same position. However,
IQ131 1 to 16 Universal channels, 1 to 12 Universal channels,
the IQ111has 8 wide and the IQ131 has 4 wide terminals
V, I, D V, I
at the bottom of the unit; this would require rewiring or
using the appropriate extension cables available in IQ131+ 1 to 20 Channels 1 to 4: Universal, 1 to 12 Analogue V channels
KIT/IQ23x/UPGRADE. V, I, T
Local Supervisor: The IQ111, 131 have a 25 way D type Channels 5 to 16: Universal,
V, I, T, D
male connector. The IQ111+, 131+ have a 5 way in line Channels 17 to 20 D only
connector, and the IQ23x uses an RJ11 connector. The
cable should be replaced with the standard supervisor IQ233 1 to 20 Universal channels , 1 to 12 Analogue V channels
adapter cable 9 way D type female to RJ11, EJ101442. V, I, T, D
For NDP see below. Generally the IQ23x can accommodate the I/O channel requirements
Auxiliary Supply: The IQ111, 111+, 131+ had a two wire of the controller it replaces. However, the IQ111, 131 had outputs which
auxiliary 24 Vdc supply connector. This has moved to the could be linked for either current or voltage whereas the IQ23x has
top edge of the IQ23x, so will require either rewiring or voltage only outputs.
use of an extension available in KIT/IQ23x/UPGRADE. If required current outputs can be provided by adding 2VID, two
On the IQ131 there was a single +24Vdc terminal and the channel voltage to current interface modules. If an SRMI has been
0V was taken from an adjacent channel linked so as to
make the 0V available from a terminal; on the IQ111 the connected it can be replaced by an SRMV or 2SRM (dual channel).
polarity is reversed, so with both these upgrades, even Although the IQ131+ can be replaced by the IQ233, the IQ131+ has a
with the extension cable they will require rewiring. special arrangement of input channel types which affects the fast
sequencing of digital inputs (see firmware section below).

IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02 5


IQ23x Data Sheet

Link Headers:
Link Header Used on Used for Replaced by on IQ23x
LK/A IQ111, 131 Regulated 5V supply at 20 mA LKE/5V
LK/B Regulated 15 V supply at 20 mA LKE/15V
LK/C Regulated 10 mA supply LKE/10mA
LK/D Adds thermistor input capability Link for thermistor T (not required on IQ131
as could be linked for thermistor inputs)
LK/E Regulated 15 V through 4k7 ohms not suppor ted
LK/F Desensitises digital inputs not required on IQ23x
LK/0 Externally powered current sensor Link for externally powered current sensor Ix
LK/5V IQ111+, 131+ Regulated 5V supply at 20 mA LKE/5V
LK/15V Regulated 15 V supply at 20 mA LKE/15V
LK/10mA Regulated 10 mA supply LKE/10mA

As can be seen from the above table, most of the applications requiring link headers are either achieved by the three new link headers,
or by appropriate input channel linking. The LK/E has no replacement but was rarely used.

Integral nodes:
A node controller board may be fitted inside the IQ23x. The IQ23x may be ordered with a board pre-fitted, or it may be post-fitted
using the KIT/NODE/IQ23x. The node may be one of the current range of boards (CNC2, PNC2, INC2, TMNH, TMNE, LINC, XN28),
or it may be one of the older nodes (CNC, PNC, INC, MNC, ANC, AND, XNC, XN28, ENC).

Note that the IQ131 did not have a CNC built in to its firmware so that if the IQ131 was to be networked, it required a CNC to be
fitted which was connected directly to the IQ131 via RS232. Alternatively, a stand-alone IQ131 could have a modem connected
via an ANC or MNC, either of which was also connected directly to the IQ131 via RS232. If an IQ131 is replaced by an IQ23x its
CNC is redundant, and if an integral modem node (e.g. ANC, MNC) were fitted, it would now be connected to the controller via the
network, not by RS232 as previously. The IQ111, 111+, and 131+ all had a CNC built in to the firmware so this note does not apply
to them.

A CNC was sometimes used for local supervisor or NDP network connection; these can now be connected via the local supervisor
port. The local supervisor port also supplies 24 Vdc to the NDP.

Cables: The KIT/NODE/IQ23x contains the cables which are required to connect a node to the IQ23x

Connection Description Connectors Code Applies to Available in Notes

Power 24 Vdc supply to 2 pin in line polarised socket EJ103087 all nodes KIT/NODE/IQ23x Screw terminals must connect to
node (Molex) to two screw terminal correct terminal pins on node.
socket. 450 mm

Network Trend network 4 pin in line polarised socket to EJ103086 all nodes except LINC. KIT/NODE/IQ23x Not used by INC if used as
connection 4 screw terminal socket. 500 internetwork repeater, or ANC, AND,
mm XN28, TMN on internetwork.
LINC requires 2 off 2 way terminal
sockets, and doesn't use this cable if
used as internetwork Lon extension.

Trend external wiring to 4 screw - INC. - Bring wires though 1 cm diameter


internetwork terminal socket ANC, AND, XN28, TMN if on knockout
internetwork.
LINC if internetworkLon extension.

LonWorks external wiring to 2 off 2 way - LINC - Bring wires through1 cm diameter
terminal sockets knockout

Ear th Ear th connection 0.25" fast-on blade type EJ101835 all nodes KIT/NODE/IQ23x -
between IQ23x receptacle to 0.25" fast-on
and node blade type receptacle. 210 mm

RS232 Device/Printer 10 pin in line polarised socket EJ100179A001 CNC, CNC2, PNC, PNC2 KIT/NODE/IQ23x If plug and socket are not both
connection (Molex) to 25 way female D (was 78-0902) polarised, ensure correct polarity.
type. 200 mm Black sheath D type fixes in RS232/Modem
knockout. Additional external adapter
cable required:PNC(2), to connect to
printer (25 way D type male to male
cable, pins 3, 7 , and 20 connected
straight though); CNC(2), to connect to
supervisor (25 way D type male to 9
way D type female - CABLE/58-0750)

Modem 10 pin in line polarised socket EJ103817 TMNE KIT/NODE/IQ23x If plug and socket are not both
(Molex) to 25 way male D type. Red sheath polarised, ensure correct polarity.
230 mm D type fixes in RS232/Modem
knockout. Additional external adapter
10 pin in line socket (Stocko) to 78-0903/1 ANC, AND, XN28 KIT/NODE/IQ23x cable require (25 way D type female
25 way male D type. 230 mm No sheath to 25 way D type male - CABLE/58-
2984)

Non-Trend Special wiring to 10 pin in line - XNC+ - If plug and socket are not both
device socket (Stocko) polarised, ensure correct polarity.

PSTN Flying lead to BT600 plug - MNC, TMNH supplied with node Bring cable through 1 cm diameter
knockout (remove adapter from TMNH
cable first)

Fibre optic to EMMPO meter Flying lead, optic cable from - ENC supplied with meter Bring cable through 1 cm diameter
meter plugs into socket in knockout
adapter

6 IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02


Data Sheet IQ23x

Integral nodes (continued)

CNC, PNC (circa 1988) CNC, PNC (2nd type - circa 1997)
earth tag earth tag

24 Vdc Power 24 Vdc Power

P O W E R
P O W E R J 1 J 2

J 5

J 2 L A N J 3

J 7
R S 2 3 2

RS232 network network RS232


CNC - to device CNC - to device
PNC to printer PNC to printer

INC, ANC, ENC, XN28, XNC+ (TNC board circa 1988) INC, ANC, AND, ENC, XN28 (TNC board, 2nd type - circa 1997)
earth tag earth tag

24 Vdc Power 24 Vdc Power

P O W E R
P O W E R J 1 J 2

Fibre optic to meter Fibre optic to meter fibre optic to TTL adaptor
fibre optic to TTL adaptor ENC only
ENC only (ENC only)
(ENC only)

J 3 J 4
J 1 3 J 1 2
J 4 J 5
J 2 J 3
L a n A L a n B R S 2 3 2 B R S 2 3 2 A

R S 2 3 2 A R S 2 3 2 B L a n A L a n B

RS232 INC, ENC local network


INC - not normally used INC internetwork ANC, AND, XN28 local
ENC to meter via adapter ANC, ENC, XN28, network or internetwork
ANC to modem RS232
XNC+ - not used
XNC+ to non-Trend device INC internetwork INC - not normally used
XN28 to PAD INC, ENC, XNC+ local network ANC, AND, ENC, XN28 - ENC to meter via adapter
ANC, XN28 local network or not used ANC to modem
internetwork AND to modem or terminal adapter
XN28 to PAD

MNC (circa 1989) LINC (circa 1996)


cable to PSTN
earth tag
earth tag
J 1

24 Vdc Power
P O W E R

P O W E R
24 Vdc Power

J 1
9 1 0

L A N

J 1 5 J 1 1 J 1 2 J 9 J 1 7

J 4

L a n

LonWorks bus
Trend Network (8 wide connector)
local network, or internetwork Local network or Internetwork

IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02 7


IQ23x Data Sheet

Integral nodes (continued)


CNC2, PNC2, INC2, TMN (TMN board - circa 1999) 24 Vdc Power
L a n A L a n B
CNC2, PNC2 local network
INC2 local network or internetwork segment A J 7 J 9 J 8

TMN local network or internetwork

CNC2, PNC2, TMN not used


INC2 internetwork or internetwork segment B D e v A

J 1 5
Integral
RS232 modem
M o d e m
CNC2 to device D e v B
(TMNH only)
PNC2 to printer
INC2 not normally used J 1 6

TMNE to modem
earth tag E T 1

PSTN (TMNH only)

XNC220: This node replaces the XNC but is only available in a Controller Address
boxed form (NBOX/XNC220) and cannot be mounted in an IQ. The IQ111 controller address was set in configuration mode so it
should be checked in configuration mode before replacement. The
ENC2: This node is used with the EMMPO2, but is only available IQ131 address is set by DIL switches on its CNC. The Address is
in boxed form (NBOX/ENC2) and cannot be mounted in an IQ. set by DIL switches on the controller board for IQ111+, 131+, and
IQ23x.
Baud Rates: All the nodes are capable of being linked for 1k2,
4k8, 9k6, or 19k2 baud for both of the network connections (Lan Firmware
A, Lan B); except for the LINC which can only be linked for 1k2, File compatibility: The IQ23x module suite has either the same
9k6 or 19k2. The IQ23x is capable of all 4 baud rates. The INC2 is or greater numbers of modules than the IQ111 (+), 131 (+). The
also capable of being linked for 38k4 baud on its internetwork or IQ111 (+), 131 (+) strategy can be uploaded into a strategy file
internetwork segment B port (Lan B). (.IQF) using Power Tool or WupDn. It can then be downloaded
into the IQ23x.
Display Panel Special cables are required to connect to a PC for uploading from
The IQ23x can have an integral 2 line display panel either pre-fitted, IQ111 (+), IQ131 (+). The IQ111, 131 requires CABLE/58-0750
or post-fitted (by replacing the cover with COVER/DP2/IQ23x). The
(9 Way Female D type to 25 Way Male D type), and the IQ111+,
display panel looks different to that of the IQ111 or 131, as the
131+ require the additional adaptor CABLE/78-1172 (25 Way
membrane has been through a layout change. However, although
Female D type to 5 in line Stocko).
the arrow and letter keys are in different places, they have the same
functionality. Certain modifications are required for it to run correctly, and this
Note that the earlier integral display panel may not be used can either be done in the controller using configuration mode (via
with the IQ23x. PowerTool or WupDn), or the strategy file can be uploaded (as
An external 2 line display panel (e.g. HDP, FPK) could be directly an .IQ2 file) into SET and the changes made there before
fitted to an IQ111 (+),131 (+). The same display panel can be downloading to the IQ23x.
connected to an IQ23x, but it requires the internal fitting of KIT/ If strategy diagrams are required they can be loaded into SET
2xx/RDS, the remote display panel support kit. from an earlier ACE or SET file, or can be laid out in SET from
the strategy file (uploaded from the IQ23x after an .IQF download
Controller Baud Rates as either an .IQ2 or .SCN file).
The controllers have different local supervisor port, and network The standard IQ1xx to IQ2xx modifications are described in the
baud rates. The network baud rate is set by a link; the supervisor IQ configuration Manual Addendum (TD200118).
baud rate is now fixed at 9k6 but was configurable by link on the
earlier controllers. The IQ131 is unique in not having CNC Bit 506,1:
functionality built in to its firmware so it needed a CNC to be fitted, This bit is used to set Emulation for IQ1xx Universal Inputs. It
and the network baud rate is set by a link on the CNC board. applies in the case where an internal universal input channel
sensor module is used in internal digital mode.
Controller Super visor Network
INTERNAL DIGITAL NODE
IQ111 1k2 or 9k6 1k2, 4k8, 9k6, or 19k2
IQ131 1k2 or 9k6 via integral CNC board
1k2, 4k8, 9k6, or 19k2 INTERNAL n
S n
IQ111+, IQ131+ 9k6 1k2, 9k6, 19k2 DIGITAL ID
IQ23x 9k6 1k2, 4k8, 9k6, 19k2 NODE digital node corresponding to input n

In IQ1xx controllers, if a sensor (whose number is greater than


the number of real input channels) is set to internal digital mode,
it will take the value from an internal digital node and write it to its
corresponding analogue and digital nodes. This feature was
removed on the IQ2xx series. If this feature was used in the
strategy then Bit 506,1 should be set to 1 to cause the sensor
module to operate in the same mode as IQ1xx controllers. Setting
the bit to zero restores IQ2xx mode.

8 IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02


Data Sheet IQ23x

Firmware (continued)

Sharing Labels: As explained in the IQ Configuration Manual (90- on the IQ131+ was set up so that fast sequence input
1533), the IQ111 (+), 131 (+) sensor and digital input modules references I1 to I4 referred to input channels 17 to 20, and
share labels. The IQ23x has separate labels so that in a file references I5 to I8 referred to input channels 5 to 8. (Note
transferred from IQ1xx to IQ2xx, the sensors will have the original that all other references remained the same e.g. configuring
labels, and the digital inputs will need their labels to be set up. module I1 set up internal digital input 1 for node 1,0 which
corresponded to input channel 1).
IQ131 (+) Input Channels: The differences in the arrangement
of input channels on the IQ131 (+) and IQ231 produce some In the IQ23x, the fast digital input channel references I1
upgrade problems. The IQ111 (+) upgrade doesn’t have similar to I8 refer to input channels 1 to 8. When an IQ131+ file
problems as the controllers have the same numbers of input is transferred to the IQ23x, fast sequence I1 now refers
channels.
to input channel 1. If fast sequencing was required on
Fast Sequencing of Digital Inputs: The fast sequencing
fast sequence inputs 1 to 4 it would require channel
IQ 1 3 1
connections to be changed and the associated strategy
U n iv e r s a l In p u ts In te r n a ls to be transferred across the channels.
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4
IQ131 Internal Digitals: The IQ131 internal channels
IQ 1 3 1 + start at 17 whereas in the IQ23x, channels 17 to 20 are
A n a lo g u e D ig ita l
In p u ts U n iv e r s a l In p u ts In p u ts In te r n a ls real. So if the IQ131 strategy used an internal digital in
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 the range 17 to 20, it would get overridden by the real
input in the IQ23x. If such internal digitals were used,
IQ 2 3 3 they should be moved to a area of unused internals on
U n iv e r s a l In p u ts In te r n a ls
the IQ23x (digital input 21 onwards).
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4

FIELD MAINTENANCE
The IQ Controller requires virtually no routine maintenance, however it is recommended that the lithium battery be replaced every 5 years,
as explained in the IQ23x Installation Instructions, TG200539, Sheet 3, Options.

DISPOSAL
COSHH ASSESSMENT FOR DISPOSAL OF IQ CONTROLLER. The only part affected is the lithium battery which must be disposed
of in a controlled way.

RECYCLING. All plastic and metal parts are recyclable. The printed circuit board may be sent to any PCB recovery contractor
to recover some of the components for any metals such as gold and silver.

INSTALLATION
The IQ23x Controller is installed in a panel, using 4 screws and washers. The procedure involves:

mount the controller in position


connect power, do not power up
connect the network
terminate the I/O, leave unconnected
connect the auxiliary supply output, if used
connect any input or output interfaces
specify network address and baud rate
install any link headers
perform input channel linking
disconnect I/O, network
power up
check network
configure the strategy
check operation
connect outputs
test system
backup configuration

This installation procedure, is covered by the IQ23x Installation Instructions, TG200539. Sheets 1 and 2 cover Fixing and Configuration
respectively. Sheet 3, Options, covers fitting an external 2-line display panel (if KIT/2xx/RDS is already fitted), connecting an external
NDP or local PC, mounting an IQ23x in an enclosure (ENCLS/), Replacing the battery, and the Zero Address Baud Rate Switch Reset.
Replacing IQ111 (+), 131 (+) is covered by Sheets 4 to 7 respectively, and moving an integral node from an IQ111,(+), 131 (+) to an IQ23x
is covered by Sheets 8 and 9.

IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02 9


IQ23x Data Sheet

INSTALLATION (continued)

CONNECTIONS

230 Vac Supply External Display Panel (2DP)


IEC Connector if Kit/2xx/RDS fitted

Local
24 Vdc Auxiliary Supervisor RJ11
Output Supply Port (FCC68)

500 mA max Supervisor NDP

500 mA
0 V 24 V
AUX
A U X
2 4 V T + T - R + R - R x
O K
T x
R + R - T + T -

0V 24 V
R S 2 3 2 /M O D E M

2 3 0 V
R D S

RJ11 to 9 way ’D RJ11 to 9 way ’D type’


type’ female cable female and 2 screw
A D D R E S S B A U D R X CABLE/EJ101442 terminals
O K
1 9 K 2
9 K 6
1 K 2
1 6
3 2
6 4

CABLE/EJ104029
1
2
4
8

T X

D P earth stud

C
Network
D

polarity
independent
2 wire

T - R +
T + R -

X
R + R - T + T - e a rth s tu d

Outputs 4 wire
V
R - T -
R + T +
T - R +
1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 T + R -

X
0 V B 1 0 V 0 V 0 V 0 V 0 V B 6 0 V B 7 0 V B 8 0 V B 9 0 V B 1 0 0 V B 1 1 0 V B 1 2 R + R - T + T - e a rth s tu d
B 2 B 3 B 4 B 5

Inputs

1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0

IN 1 C IN 2 C IN 3 C IN 4 C IN 5 C IN 6 C IN 7 C IN 8 C IN 9 C IN 1 0 C IN 1 1 C IN 1 2 C IN 1 3 C IN 1 4 C IN 1 5 C IN 1 6 C IN 1 7 C IN 1 8 C IN 1 9 C IN 2 0 C

10 IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02


Data Sheet IQ23x

ORDER CODES
IQ231/[Display]/[Node]/230: 8 Universal Inputs, 8 Analogue Voltage Outputs
IQ233/[Display]/[Node]/230: 20 Universal Inputs, 12 Analogue Voltage Outputs

[Display] [Node]
Blank No display. Blank No node
DP IQ23x with DP in front cover. TMNH/.../ Node including 28k8 integral modem TMN type board
TMNE Node external modem TMN type board
CNC2 Node for Trend network TMN type board

PNC2 Node for remote printer TMN type board

INC2 Node for Trend Internetwork TMN type board

LINC/FTT Node for LonWorks internetwork pre-TMN type board


Both controllers complete with mains cable with moulded IEC connector and a bag of screws for the earth flange.
KIT/2xx/RDS: Kit to enable connection of FPK or HDP external 2-line display panels.
ENCLS : 600 mm x 600 mm x 210 mm IP55 enclosure
ENCLS/FP: 600 mm x 600 mm x 210 mm IP55 enclosure fitted with 2-line display panel plus 2DP connection cable
ENCLS/NDP: 600 mm x 600 mm x 210 mm IP55 enclosure with NDP on door plus connection cable
CABLE/EJ101442: Adaptor cable RJ11 to 9 Way ‘D type’ Female for local PC connection.
CABLE/EJ104029: Adaptor cable RJ11 to 9 Way ‘D type’ Female and 2 screw terminals for NDP connection.
KIT/NODE/IQ23x: Kit to mount a node in an IQ23x.
Includes: Mounting plate for TMN type board (TMN, CNC2, PNC2, INC2), mounting plate for pre-TMN type board, pillar,
3 screws to fix plate, 4 screws to fix node to plate, grommet for circular cable entry knockout, power cable (EJ103087),
network cable (EJ103086), earth cable (EJ101835), RS232 cable for CNC/PNC (EJ100179A001), RS232 cable for external
modem from TMNE (EJ103817), RS232 cable for external modem from ANC, AND, or XN28 (78-0903/1),
KIT/IQ23x/UPGRADE: Kit to upgrade an IQ111(+), or IQ131(+) to an IQ23x.
Includes: 1 off auxiliary supply extension (2 wide), 2 off network extensions (4 wide), and 2 off network extensions (2 wide).
Note that if upgrading involves moving a node card, then KIT/NODE/IQ23x is also required.
COVER/DP2/IQ23x: Replacement cover for IQ23x including integral 2 line display panel, and cable

SPECIFICATIONS
Electrical Baud rate
CPU :68332 32 bit micro-controller Network :Selectable by switch 1k2, 4k8, 9k6, or
CPU speed :16.78 MHz 19k2 set to be same as other nodes on
Cycle time :1 s Lan.
Memory :256 kbyte battery backed SRAM, and Supervisor (or NDP) :9k6.
256 kbyte Flash. Network addresses
Supply voltage
Controller :Selectable by switch, 116 nodes
/230 :230 Vac +15 % -10%, 50 to 60 Hz
Auxiliary supply :24 Vdc ±10%, 500 mA maximum. addressable (1,4 to 119 excluding 10)
Protected by a self-resetting thermal set to be unique on Lan.
device. Supervisor port :Software selectable, 116 nodes
Consumption :60 VA maximum addressable (1,4 to 119 excluding 10)
Fusing :No replaceable fuses required. All set to be unique on Lan.
protection self-resetting.
Battery backup :Battery maintains time, and logged data
with mains off for at least 5 years. IQ23x Range
Battery :Varta CR2032, 3 V, or equivalent IQ231 :8UI, 8VO
Clock accuracy :30 s per month (typical). IQ233 :20UI, 12VO
2-line display panel :Optional 2x40 character display, with 4 Key
programmable softkeys. Can be UI :Universal input
mounted in front cover, or externally via
adaptor kit. VO :Analogue voltage output
Network transmission :20 mA serial 2 wire current loop, Signal Cable :Analogue voltage, Analogue current,
opto-isolated, polarity independent Thermistor, or Digital inputs, and Analogue
receiver, balanced transmitter. voltage outputs. Trend TP/1/1/22/HF/500
Supervisor transmission :RS232, EIA/TIA/232E, V28 recommended (Belden 8761)
Distance
Universal Inputs :Linkable for analogue voltage (V),
Supervisor :15 m
Network :Dependent on cable type, see table analogue current (I), thermistor (T) or
below: digital (D).
Analogue voltage (V) :12 bit resolution (4096 steps - effective).
Minimum 60 dB series mode rejection at
Cable 1k2 baud 9k6 baud 19k2 baud No. of Wires supply frequency. 0 to 10V, input
Belden 9182 1000 m 1000 m 700 m 2 resistance 200 kΩ, accuracy 50 mV
Belden 9207 1000 m 1000 m 500 m 2 equivalent to ±0.5% of span.
Trend Analogue current (I) :12 bit resolution (4096 steps - effective).
TP/1/1/22/HF/500 1000 m 700 m 350 m 2 Minimum 60 dB series mode rejection at
(Belden 8761)
supply frequency. 0 to 20 mA, input
Trend
TP/2/2/22/HF/500 1000 m 500 m 250 m 4 resistance 240 Ω 0.1%, accuracy 0.5%
(Belden 8723) of span (i.e. 100 µA). Loop powered input
supply is 20 to 36 Vdc self-limiting at
22 mA.

IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02 11


IQ23x Data Sheet

SPECIFICATIONS (continued)

Thermistor (T) :12 bit resolution (4096 steps - effective). Environmental


Minimum 60 dB series mode rejection at EMC
supply frequency. Thermistor bridge Emissions :EN50081-1.
resistor 10 kΩ 0.1%, accuracy 0.5% of Immunity :EN50082-2.
span. Bridge supply 5V.
Safety :EN61010.
Digital (D) :Volt free contact. Count rate 30 Hz.
Wetting current = 4 mA nominal @ Ambient limits
24 Vdc. 24 V supply pin is self-limiting at storage :-10 °C to 50 °C
22 mA. operating :0 °C to 45 °C
Status LED per channel (ON = closed humidity :0 to 90 %RH non-condensing
contact).
Version This document covers:
Electrical Firmware :v3.1 or greater
Outputs Board :AP104901 issue 1
Analogue voltage :8 bit resolution (256 steps). 0 to 10 V
with 20 mA current limit, accuracy ±100
mV equivalent to ±1% of span. Status
LED per channel, light intensity
increases with output voltage.
Indicators
Inside Unit :Remove cover to view.
Universal Inputs :(yellow) Indicates status, only for digital
inputs (ON= contact closed).
Analogue outputs :(yellow) Light intensity increases with
output voltage.
External :Viewable without removing cover
(power) :(green) ON when supply is connected.
(fail) :(red) ON if controller has a software
fault.
OK (network) :(green) ON if network is operating.
Flashes if prohibited controller network
address set (0, 2, 3, >119).
RX :(yellow) ON if current is entering the
network receiver
TX :(yellow) ON if current is flowing from
network transmitter
Note that the (fail) LED flashes momentarily on power up

Mechanical
Dimensions :339 mm x 288 mm x 93 mm
Material
Box :Mild steel, plated and coated
Protection :IP30
Weight :1.4 kg (including display, 100 gm)
Connectors
/230 :IEC plug
Network :2 off 2 part connectors each with 4
screw terminals for 0.5 to 2.5 mm2 cross
section area cable.
I/O, AUX :2 part connector with 2 screw terminals
for 0.5 to 2.5 mm2 cross section area cable.
Supervisor port :RJ11 (FCC68), for Trend utility software
connected via adaptor cable
CABLE/EJ101442. Supplies signal and
power to NDP via CABLE/EJ104029.
Display panel 25 way D type Female (if adaptor kit
fitted).

Trend Control System Ltd reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions or changes.

Trend Control Systems Ltd. P.O. Box 34 Horsham Sussex RH12 2YF England Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com

12 IQ23x Series Controllers Data Sheet TA200538 Issue 1/A 6/3/02