Case Studies On Hvac System Performance Using A Whole Building Simulation Based Real-Time Energy Evaluation Approach With Bems
Case Studies On Hvac System Performance Using A Whole Building Simulation Based Real-Time Energy Evaluation Approach With Bems
14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
Hyeun Jun Moon1, Min Seok Choi1, Seung Ho Ryu1, Jung Chul Lee2, Dong Gu Kim2
1
Department of Architectural Engineering, College of Architecture, Dankook University,
Yongin-si, Gyeonggi-do, Republic of Korea
2
R&D Division, Hyundai Engineering & Construction Co. Ltd.,
Yongin-si, Gyeonggi-do, Republic of Korea
- 2735 -
Proceedings of BS2015:
14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
building is a residential building equipped with a consumption deviations from design intent by
night electric boiler. The second building is an office comparing to the measured data. Also, when the
building equipped with AHU. system (e.g., HVAC, lighting etc.) or operation
condition are changed in the existing buildings, the
baseline model that represents these changes can be
used to compare with actual performance.
CASE STUDIES
In this study, real-time simulation reflecting the
design intent is applied to the two buildings. The first
building is a residential building equipped with a
night electric boiler. The second building is an office
building equipped with AHU. In this study, the
results from a real-time simulation model reflecting
the design intent is compared to the actual energy
Figure 1 A framework of commissioning method data measured from BEMS. This real-time energy
using real-time energy performance evaluation enables to identify the abnormal operation
of the HVAC systems in real-time.
COMMISSIONING USING REAL TIME
Case Study 1 : Residential building equipped with
ENERGY SIMULATION MODEL a night electric boiler
Figure 1 shows a framework of the continuous The selected residential building is a two stories
commissioning approach using real-time energy rectangular shape house. The first floor is mainly
performance assessment with a whole building used as a dining space and the second floor is used as
simulation. Real-time building simulation refers to a residential space for children. The second floor has
the use of a reference (virtual) model whose eight conditioned zones (1~7 rooms and a living
simulation time is synchronized in real time. This room). The heating system of this building is
real-time simulation model utilizes measured weather configured to the radiant floor heating system with a
data at each time step. The actual weather data are night storage electric boiler as shown in Figure 2.
used as input values in real-time building energy
simulation through BCVTB (Building Controls
Virtual Test Bed). BCVTB is an open-source
software environment developed for co-simulation
and data exchange among hardware/software. This
software couples different simulation tools for co-
simulations, and enables data exchange with building
automation systems and databases (Wetter, 2011). In
the previous study, Moon (2013) evaluated the effect
of weather data in an integrated real-time building
simulation.
A simulation model reflecting the design intent can Figure 2 Schematic diagram of a radiant floor
be used for commissioning by comparing to the heating system with a night storage electric boiler in
measured data. For newly constructed buildings, a the 1st case building
design intent baseline model can be applied to
identify and quantify the building energy
- 2736 -
Proceedings of BS2015:
14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
This building is collecting a large amount of building variable flow rate and correctly connect the pipes
energy data through BEMS. Additionally, we with the flow control valves, the simulation results of
installed a BCVTB server connected to BEMS based supply and return water temperature matched with
on a BACnet/IP. The BCVTB was configured to the actual results. Figure 6 shows a comparison of
receive the data associated with a heating system and measured and simulated zone temperature. Actual
environment as shown in Figure 3. The zone air temperatures ranged from 23˚C~27˚C.
BACnetReader actor reads building energy data from However, Simulated result for the zone air
BACnet devices, and these data are sent to a database temperatures were maintained close to the set
program (i.e., PostgreSQL) through the SQL temperature (24˚C). Through this difference, we
Statement actor. could confirm the mismatching between control
valves and pipes. Zone air temperatures were
In addition, a weather station is installed on the site
maintained close to the set temperature (24˚C) after
and collects information including outdoor air dry
commissioning.
bulb and relative humidity, wind speed and direction,
direct normal solar radiation, solar radiation, which
are suitable for energy simulation with EnergyPlus.
The actual data about boiler operation statuses, boiler
set temperature and weather data were used for the
input values in real-time building energy simulation.
The weather data including solar irradiation, outside
air temperature and RH and wind speed and direction
were collected from the on-site weather station. The
real-time monitoring data on boiler water supply and
return temperature are compared with the simulation
results (Table 1). The real-time simulation is
performed during 10th ~12th in Febrary, 2013. This
climate condition is a heating season and The
distribution of the outdoor dry bulb are about - Figure 4 Comparison of measured and simulated
5˚C~10˚C. boiler supply water temperatures
The real-time simulation was conducted to compare Figure 5 Comparison of measured and simulated
the simulation results and monitoring data of boiler
boiler return water temperatures
supply water temperatures and return water
temperatures in real time.
As a result, simulation results for the boiler supply
water temperature agreed to monitoring data for the
boiler supply water temperature (Figure 4). However,
simulation results for the boiler return water
temperature did not correspond with the actual return
water temperature (Figure 5). The reason for this was
that the actual flow control valves were not set to a
variable flow rate, but to a constant flow rate. These
have been set to a constant flow rate ever since the
control valves were installed.
Thus, we could confirm that the actual flow control
valves were not operated according to the design Figure 6 Comparison of measured and simulated
intent. It can be seen that the energy is wasted as an zone temperature
ineffective system setting. After we change to a
- 2737 -
Proceedings of BS2015:
14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
Case Study 2 : Office building equipped with the The comparison module is constructed to compare
AHU system data associated with the AHU and an absorption
The selected office building is located in Yongin, chiller (such as AHU supply and return fan power,
Korea. This building is equipped with two air AHU supply air temperature, AHU supply water
handling unit (AHU) with an absorption chiller heater temperature, AHU return water temperature, AHU
(Figure 7). This building is collecting a large amount supply air flow rate, AHU water flow rate, CHW
of building energy data through BEMS. We installed pump power, zone temperature, and so on). Table 2
a BCVTB server connected to the BEMS based on shows input data and comparison data used in the
LabVIEW. We installed a BCVTB server connected case study.
to the BEMS (LabVIEW) through XML files.
Figure 8 shows the real-time simulation system using Table 2 Real time input data and comparison data in
BCVTB in the 2nd case study. This real-time the office building case
simulation system is composed of four modules; REAL TIME REAL TIME
BEMS, Simulation, Comparison, and Database. INPUT DATA COMPARISON DATA
BEMS module reads monitoring data from BEMS AHU supply / return fan
system (based LabVIEW) through XML files at each outdoor air dry bulb power
time step (10 min.). The monitoring data include the dew point temperature AHU supply air temperature
real-time input data and comparison data. Simulation relative humidity AHU supply / return water
module performs simulation reflecting the actual diffuse solar, direct solar, temperature
weather data at each time step. The results from the wind speed, and wind Zone temperature
real-time simulation are sent to the comparison direction CHW pump power
module and database module. Comparison module Water flow rate
compares monitoring data and simulation results.
Database module store monitoring data and
simulation results. Database module is based on a Figure 9 shows comparison results from measured
customized XML schema to store building CHW pump power and simulated CHW pump power.
information, building operation data, simulation data The highlighted areas enclosed by the dashed line
and analysis results. represent the differences between measured and
simulated results. As shown in the figure, The CHW
pump operated in the simulation, although it was not
operated in the actual operation. However, at that
same time, AHU 1 supply fan power and simulated
AHU 1 supply fan power operated as shown in
figure 10. It can be seen that the energy is wasted
about 30% due to ineffective operation of the AHU
system. If the actual CHW pump power is monitored
without simulation, it would be difficult to identify
the abnormal operation of AHU system. By
comparing with the simulation results, it could be
easily be found the abnormal operation of the AHU
system.
Figure 7 Schematic diagram of AHU systems with a
chiller heater in the 2nd case building
- 2738 -
Proceedings of BS2015:
14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
CONCLUSION
This study successfully demonstrated the integrated
whole building simulation based real-time energy
evaluation with BEMS in two case studies. Using the
comparison between simulation results and
monitoring data in real time, we could identify faulty
operation, control problems, sensor errors. The key
findings from two case studies are summarized as
follows:
Figure 9 Comparison of measured and simulated
CHW pump power 1. Two case studies showed that real-time
simulation system can help identify the
abnormal operation of HVAC systems and
sensor errors.
2. Through the suggested real-time simulation-
based commissioning approach, anomalies in
the heating system and AHU system were
corrected and potential energy savings were
identified.
REFERENCES
Chandan, V. and Alleyne, A.G. 2014. Decentralized
predictive thermal control for buildings. Journal
of Process Control (24), 820-835.
Clarke, J.A., Cockroft, J., Conner. S., Hand, J.W.,
Kelly. N.J., Moore. R. 2002. Simulation-Assisted
control in building energy Management systems.
Energy and Buildings (33), 933-940.
Figure 12 Comparison of measured and simulated 3F Dong, B., O’Neill, Z., Li, Z., Luo, D., Madhusudana,
zone temperature S., Ahuja, S. and Bailey, T. 2012. An integrated
infrastructure for real-time building energy
- 2739 -
Proceedings of BS2015:
14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
modeling and fault detection and diagnostics, with a building energy monitoring system,
SimBuild 2012, Madison, USA. Sensor Letters (12), 1-7.
Haves. P., Salsbury. T., Claridge. D., Liu. M. 2001. O’Neill, Z., Haves, P. 2009. Automated continuous
Use of whole building simulation in online commissioning of commercial buildings, final
performance assessment: modeling and report.
implementation issues. Proceedings of building Pang, X., Wetter, M., Bhattacharya P. and Haves, P.
simulation 2001, Rio de Janeiro, Brazil. 2012. A framework for simulation-based real-
Lee, S., Painter, F.L., Claridge, D.E. 2007. Whole- time whole building performance assessment,
Building commercial HVAC system simulation Building and Environment (54). 100-108.
for use in energy consumption fault detection. Scherer, H.F., Pasamontes, M., Guzman, J.L.,
ASHRAE Transaction (113) n.2. 52-61. Alvarez, J.D., Camponogara, E., Normey-Rico,
Mirinejad, H., Welch, K., Spricer, L. 2012. A review J.E. 2014. Efficient building energy management
of intelligent control techniques in HVAC using distributed model predictive control.
systems, Proceedings of the IEEE Energytech, Journal of Process Control (24). 740-749.
Cleveland, USA. Xu, P., Haves, P., Deringer, J.A. 2004. Simulation-
Moon, H.J. and Choi, M.S. 2013. The effect of Based testing and training environment for
weather data in an integrated real-time building building controls. Proceedings of SimBuild 2004,
simulation connected to a monitoring system, Boulder, USA.
Proceedings of ISOEN, Daegu, Korea. Wetter, M. 2011. Co-simulation of building energy
Moon, H.J. and Choi, M.S. 2014. Continuous and control systems with the Building Controls
commissioning through real-time simulation Virtual Test Bed, Journal of Building
Performance Simulation (4) n.3. 185-203.
- 2740 -