DC CURRENT/VOLTAGE TRANSDUCERS

Transducer Series M100


These transducers are designed to measure DC values in many applications of energy and process management and convert it
to a standard DC output signal, which is directly proportional to the measured input value. High-rgade insulation between case,
input, output and auxiliary voltage (if applicable) is provided as well as interference immunity. Input and output circuits are
galvanically isolated and protected against damage by shock or permanent overload. The floating output signal is additionally fully
protected against open or short circuited conditions and voltage transients. All products are supplied in flame retardant cases
featuring such properties as self-extinguishing, non-dripping and free of halogens.

Application DC current DC voltage DC voltage


features auxiliary powered auxiliary powered auxiliary powered
various characteristics various characteristics various characteristics
Type case unit M100-DA1 M100-DV1 M100-DV2

Weight approx. 0.4 kg 0.4 kg 0.4 kg


rated value IN ± 0,1 mA ... 10A - -
voltage drop 20 mV - -
Input rated value UN - ± 20 mV ... 11,9V ± 12 V ... 600 V
impedance - 100 kΩ/V 10 kΩ/V
working range ±125% IN ±125% UN ±125% UN
ripple < 5 % peak-peak < 5 % peak-peak < 5 % peak-peak
Overload continuous 4 x IN 1.5 x UN 1.5 x UN
for 1 sec 50 x IN 4 x UN 4 x UN
Output mA rated value ± 1 / 5 / 10 / 20 & 4-20mA
load resistance <15 / 3 / 1.5 / 0.75 kΩ
rated value 0±5 / 10 V & 1-5 V
Output V load resistance > 1kΩ
load influence < 0.1%
ripple < 0.5 % peak-peak at full load
response time < 200 msec for 0-90 % at full load
overload < 2x rated value at full load
no load voltage < 27 V
Adjustment zero ±2%
span ± 10 %
Option voltage AC 115 / 230 / 400 V (±25% (45 – 65 Hz) < 2VA)
Auxiliary voltage DC 24 / 48 / 110 V ( ±20 % / galv. isolated /<3 W)
class ±0,25% comply with IEC 60688
o
Accuracy calibration temperature 23 C ± 2K
temperature coefficient 0,01 % / °C (100 ppm / °C)
stability ±0,05 % per annum non cumulative
warm-up time ≥15 min.
material light grey polycarbonate comply with UL 94 V0
2
connection screw terminals for 2x0.5 – 2.5 mm
Case terminal marking numbering comply with DIN 43807
fixing snap-on to rail 35x7.5 mm comply with DIN-EN 50022 / BS 5584
mounting any position
enclosure code case IP 50 / terminals IP 30 comply with IEC 529 / BS 5490 / DIN 40050
Insulation test voltage 4 kV RMS 50 Hz for 1 min.
impulse test EMC 5 kV transient comply with IEC 801 / EN 55020
HF interference test EHF 2.5 kV, 1 MHz comply with IEC 255-4
protection class II. comply with IEC 348 / BS 47S3 / DIN 57411/VDE 0411
o
working temperature 0 to +60 C
o
Climatic function temperature -25 to +70 C
o
storage temperature -55 to +85 C
humidity ≤ 95% RH non condensing
class of climate HSE comply with DIN 40040 - 3 comply with VDE / VDI 3540
Applied general IEC 60688 / BS 6253 / VDI/VDE 2192
standards safety lEC 348 / BS 4753 / DIN 57411/VDE 0411 / ANSI C37
surge withstand IEC 801 / EN 55020 / ANSI C37-90a
radio screening RFI degree N comply with VDE 0875
subject to change without notice

Order specification:
DC voltage transducer, Input voltage: ±60 mV, Output: ±20 mA
Power supply: 230V AC, Class of accuracy: 0,25

M100-DV1 ±60 mV ±20 mA cl. 0,25 UH = 230V AC


DC CURRENT/VOLTAGE TRANSDUCERS
Transducer Series M100

Installation and safety instructions

All units are built and tested for safety, accuracy, quality and reliability according to the technical data and international standards
of this specification.
These units are delivered fully calibrated and therefore no further adjustments are normally required. However trimming potentio-
meters (if applicable) are located under cover bungs on the front panel for adjustment the DC output signal -
ZERO and SPAN if local conditions are found to be necessary.
Voltage dangerous to human life may be present at some of the terminals of this unit therefore exercise extreme caution. Ensure
all supplies are de-energised before attempting any installation, connection or disconnection.
These units are designed for snap-on fixing Lo 35 mm-DIN-rails.
To snap-on a case on a rail, the top edge of the cutout on the back is hooked over one edge of the rail and the bottom edge
carrying the release clip clicked into place. Check that the unit is firmly fixed. Removal or repositioning may be achieved by
levering down the release clip and lifting the case up and off the rail.
This product must be installed by a qualified engineer. It is necessary to check label data and plant wiring before comissioning.
These units require no service but routine attention. If a malfunction is observed, the unit must be de-energised and forwarded to
authorised service facility. The unit must be separated from all voltage sources before opening. If it is necessary to make any
service on the open unit with voltage connected, it must be done by a qualified engineer only.