Available Fault Current Calculation (Isc

GENERATOR SUPPLY POWER TO MAIN SERVICE PANEL

Generator kW:
Type of Supplay
Voltage Line-Line (V L-L)
Voltage Line-Neutral (V L-N)
Enter Generator Subtransient (Z)
Power Factor
No of Generator in Parallel
Total Generator kva:
Secondary Current ( I L-L)
Secondary Current ( I L-N)
Maximum Generator Short Circuit Current( Line-Line)
Maximum Generator Short Circuit Current( Line-Neutral)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-Neutral)
Total Short Circuit Current:( ISC Gen)(L-L)
Total Short Circuit Current:( ISC Gen)(L-N)

Fault Current Calculation (TRANSFORMER To MAIN PANEL)

MAIN PANEL
Available Utility or Primary KVA(Source) otherwise select"Unlimited"
( Provide By Power supplay Company)

Supply System
Enter transformer KVA rating
Secondary Voltage Line-Line ( V L-L)
Secondary Voltage Line-Neutral ( V L-N)
Enter transformer impedance (Zt)
Transformer Calculations
Secondary Voltage Line-Line ( V L-L)
Transformer Secondary Full Current I (L-L)
Transformer Secondary Full Current I (L-N)
Source Impedance:(Zu)
Total Impedance (Zu+Zt)
Short Circuit Current at T.C Secondary( ISCa)(L-L)
Short Circuit Current at T.C Secondary( ISCa)(L-N)
Short Circuit Current (RMS symmeterical)
At Secondary (Line) Main MCCB Line Terminel
Maximum Secondary Protection per NEC 450.3(B)
Recommended Secondary Breaker Rating
Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
Z
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
Available Fault Current Calculation (Isc Calculation)

No

300
Three Phase
480
240
5.75
0.8
3
0
0
0
0
0
No
0
0
0
0

LINE-LINE S.C CURRENT


24871
Unlimited

Three Phase
1000
380
220
5.75

380
1519.38738300717
2279.08107451076
0
0.0575
26424.1284001247
39636.1926001871

26424.1284001247

1899.23422875896
2000
50
Copper
Three Conductor Cable
Non-metalic Raceway
3
300
150
32154
22525
0.0624278968716015
0.941240344822058
0.230887853844294
0.812421697782468
No
0
0
24871.4557269557
32201.3028858769

LINE-LINE S.C CURRENT


15810
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
120.000
50.000
19779.000
9473.000
0.573
0.636
2.676
0.272
No
0.000
0.000
15810.065
8759.509
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


14404
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

10.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
0.727
0.579
1.625
0.381
No
0.000
0.000
14404.239
12266.801
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

5.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
0.363
0.733
0.813
0.552
No
0.000
0.000
18243.058
17765.857
n)

Kw
1.732
Volts
Volts
%

Kva
Amp
Amp
Amp
Amp

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


32201
Kva

3
Kva
Volts
Volts
%

Volts
Amp
Amp

Amp
Amp

Amp

Amp
Amp
Meter
1
3
5
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


8760 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


12267 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
17766 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A2
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A2
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A2
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A2
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A2
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
8979
A1
Three Phase Feeder System

Three Phase
15810.065
8759.509
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
50.000
25.000
9473.000
3838.000
0.761
0.568
1.797
0.358
No
0.000
0.000
8979.447
3131.974
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
3132 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A3
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
2478
A2
Three Phase Feeder System

Three Phase
8979.447
3131.974
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
2.624
0.276
1.581
0.388
No
0.000
0.000
2478.080
1213.667
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
MAIN PANEL
A1
A2
A3
A1
A1
A1
A1
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777

A1
A2
A1
A1
A1
A1
A1
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777

A1
A2
A1
A1
A1
A1
A1
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777

A1
A2
A1
A1
A1
A1
A1
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777

A1
A2
A1
A1
A1
A1
A1
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
1866.65843286777
LINE-GROUND S.C CURRENT
1214 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
24871.4557269557 32201.3028858769
15810.0654806669 8759.50850701675
8979.44713362247 3131.97420098466
2478.08032312772 1213.66670744231
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 0

3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 0

3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 0

14404.2389965264 12266.8012773826
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 0

10 17765.8567104024
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 1866.65843286777
10 0
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
32201.3028858769
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
0

1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
0

1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
0

1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
0

1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
1.732
0
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
A1
A2
A3
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1

A1
A2
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1

A1
A2
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1

A1
A2
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
15810.0654806669
8979.44713362247
2478.08032312772
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467

3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467

3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467

14404.2389965264
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467
3008.60937621467

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
8759.50850701675 1.732
3131.97420098466 1.732
1213.66670744231 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732

1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732

1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732

12266.8012773826 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732
1866.65843286777 1.732

0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)

PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
PANEL NAME
A1
FED FROM :
Fault Cuurent Calculation ( A1To Branch Circuit Panel)

Feeder System
Fault Circuit Current at Main Service Panel(L-L)
Fault Circuit Current at Main Service Panel(L-N)
Volyage Line-Line (V L-L)
Volyage Line-Neutral (V L-N)

Length (L)
Type of Conductor
(3-Single Conductor cable) or (3 conductor cable)
Type of RaceWay
No of Conductor per Phase (N)
Size of Phase Conductor
Size of Neutral Conductor
Phase Conductor Constant ("C")
Neutral Conductor Constant ("C")
f (L-L)
M (L-L)
f (L-N)
M (L-N)
Do You Have any Motor Contributions
Motor Contributions (Line-Line)
Motor Contributions (Line-neutral)
Fault Current at termination of Main Disconnect (L-L)
Fault Current at termination of Main Disconnect (L-N)
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658

LINE-LINE S.C CURRENT


3009
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
LINE-LINE S.C CURRENT
10
MAIN PANEL
Three Phase Feeder System

Three Phase
24871.456
32201.303
380.000
220.000

100.000
Copper
Three Conductor Cable
Non-metalic Raceway
1.000
10.000
10.000
1560.000
1560.000
7.267
0.121
16.251
0.058
No
0.000
0.000
3008.609
1866.658
Gen p.f Volts
250 0.6 208
300 0.65 480
375 0.7
400 0.75
500 0.8
600 0.85
750 0.9
900 0.95
1000 1
1200
1300
1800
2000
2400
2500

3000
0

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000
mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp

LINE-GROUND S.C CURRENT


1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
LINE-GROUND S.C CURRENT
1867 2

Three Phase Feeder System

1.732
Amp
Amp
Amp
Amp

Meter
1.000
3.000
5.000

mm2
mm2

1.732

1.732

Amp
Amp
Amp
Amp
A1
A2
A3
parallal Utility / Primary KVA A1
1 35000 3 Phase 208Y / 120 A1
2 50000 3 Phase 480Y / 277 2.5 2.5 A1
3 65000 2.5 2.5 A1
4 75000 Three Phase 6 6 A1
5 100000 Single Phase 10 10 A1
6 150000 16 16 A1
250000 Yes 25 25 A1
500000 No 35 A1
Unlimited 50 35 A1
Meter 70 35 A1
Non-metalic Raceway 95 50 A1
Metalic Raceway 120 70
Aluminium in Non-metalic Raceway 150 95 A1
Alumnium in Metalic Raceway 185 95 A2
240 120 A1

3 Single Conductor Cable 300 150


A1
Three Conductor Cable 400
A1
Aluminium 185 A1
Copper 240 A1
300 A1
400 A1
A1
A1
A1
A1
A1
A1
0.000
0.000
0.000
0.000
0.000

0.000
15810.0654806669 8759.50850701675
8979.44713362247 3131.97420098466
2478.08032312772 1213.66670744231
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
#REF! A1
1.732 A1
1.732 A1
1.732 A1
1.732 A1
1.732 A1
1.732 A1
1.732 BY69

3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777

3008.60937621467 1866.65843286777

3008.60937621467 1866.65843286777
3008.60937621467 1866.65843286777
#REF! 1866.65843286777
1.732 A1
1.732 A1
1.732 A1
1.732 A1
1.732 A1
1.732 A1
1.732 A1
1.732 BY69
8760

8979.447
A3
A1
A1
A1
A1
#REF!
1866.658
1866.658
1866.658
1866.658
1866.658
1866.658
BY69

1866.658
3008.609
A1
A1
A1
A1
A1
#REF!
1866.658
1866.658
1866.658
1866.658
1866.658
1866.658
BY102
1866.658
3008.609
A1
A1
A1
A1
A1
#REF!
1866.658
1866.658
1866.658
1866.658
1866.658
1866.658
BY135

12266.801
3008.609
A1
A1
A1
A1
A1
#REF!
1866.658
1866.658
1866.658
1866.658
1866.658
1866.658

BY168

17765.857
10.000
A1
A1
A1
A1
A1
#REF!
1866.658
1866.658
1866.658
1866.658
1866.658
1866.658
BY204
-1.000
0.000 0.000 0.000 1.000 0.000 0.250
0.000 0.000 0.000 1.000 A 0.250
0.000 0.000 0.000 1.000 B 0.250
0.000 0.000 0.000 1.000 C 0.250
#REF! 0.000 0.000 4.000 D 1.000
5.000 E 0.000
0.000 0.000 0.000 6.000 F 1.500
7 G 1.75
8 H 2
9 I 2.25
10 J 2.5
11 K 2.75
12 L 3
13 M 3.25
14 N 3.5
15 O 3.75
16 P 4
17 Q 4.25
18 R 4.5
19 S 4.75
20 T 5
21 U 5.25
22 V 5.5
23 W 5.75
24 X 6
25 Y 6.25
26 Z 6.5
27 AA 6.75
28 AB 7
29 AC 7.25
30 AD 7.5
31 AE 7.75
32 AF 8
33 AG 8.25
34 AH 8.5
35 AI 8.75
36 AJ 9
37 AK 9.25
38 AL 9.5
39 AM 9.75
40 AN 10
41 AO 10.25
42 AP 10.5
43 AQ 10.75
44 AR 11
45 AS 11.25
46 AT 11.5
47 AU 11.75
48 AV 12
49 AW 12.25
50 AX 12.5
51 AY 12.75
52 AZ 13
53 BA 13.25
54 BB 13.5
55 BC 13.75
56 BD 14
57 BE 14.25
58 BF 14.5
59 BG 14.75
60 BH 15
61 BI 15.25
62 BJ 15.5
63 BK 15.75
64 BL 16
65 BM 16.25
66 BN 16.5
67 BO 16.75
68 BP 17
69 BQ 17.25
70 BR 17.5
71 BS 17.75
72 BT 18
73 BU 18.25
74 BV 18.5
75 BW 18.75
76 BX 19
77 BY 19.25
78 BZ 19.5

= C 69 = D
= G 69 = H
= K 69 = L
= O 69 = P
= S 69 = T
= W 69 = X
= AA 69 = AB
= AE 69 = AF
= AI 69 = AJ
= AM 69 = AN
= AQ 69 = AR
= AU 69 = AV
= AY 69 = AZ
= BC 69 = BD
= BG 69 = BH

A1 15810.0654806669 8759.50850701675 1.732


A2 8979.44713362247 3131.97420098466 1.732
A3 2478.08032312772 1213.66670744231 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
A1 3008.60937621467 1866.65843286777 1.732
0.000
0.000
0.000
0.000
1.000
1.000
0.000
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE

69 = E 69
69 = I 69
69 = M 69
69 = Q 69
69 = U 69
69 = Y 69
69 = AC 69
69 = AG 69
69 = AK 69
69 = AO 69
69 = AS 69
69 = AW 69
69 = BA 69
69 = BE 69
69 = BI 69

You might also like