固定式气体探测仪 English

Download as pdf or txt
Download as pdf or txt
You are on page 1of 25

Focus on micro detection

Gas detector Operation and maintenance manual


Document No:001-T00-002
Version number: A,April 2021

Commemoration of millions of sales

True effective value micro-detection

Deep safety of life science


目录
1Safety rules........................................................................................................................................ 3
1.1Correct use..................................................................................................................................... 3
2.2Summary........................................................................................................................................ 5
3.Install 6
3.1Mechanical installation.................................................................................................................. 7
3.1.1Outline dimension diagram(Take the four-in-one detector as an example)......................7
3.1.2Outline dimension diagram(Take a single detector as an example).................................. 8
3.2Electrical installation...................................................................................................................... 8
3.3Required reading for operating instruments................................................................................. 9
Must read before operation.........................................................................................................9
3.4.Brief introduction.................................................................................................................. 9
4、Operation introduction....................................................................................................... 11
4.1Profile description........................................................................................................................ 11
4.2 Installation and assembly............................................................................................................12
8.2 Check..........................................................................................................................................16
8.6Introduction to other operations.................................................................................................18
8.6.1Sensor information operation...........................................................................................18
8.6.2Alarm settings................................................................................................................... 18
8.6.3Data storage...................................................................................................................... 19
8.6.4 Instrument setup..............................................................................................................21
9、About this machine............................................................................................................. 19
10、Design theory............................................................................................................................ 20
13、 Reference standards................................................................................................................21
................................................................................................................................................... 21
1 Safety rules
1.1Correct use
The gas detector is a fixed gas detector,used to detect toxicity、combustible gas
or oxygen,suitable for any outdoor and indoor use,such as drilling platform industry、
Chemical and petrochemical industries, water treatment and sewage industries,
etcThe signal of the detector can be used together with the Gas detector bus
controller for safe or dangerous use.
When using this product, you must read and abide by this operation manual,
especially the safety instructions, use information and product operation. In addition,
the national safety use regulations of the user's country should also be considered.

Dangerous
 This product protects life and health. Improper use, maintenance or
maintenance may affect the function of the equipment, thus seriously
endangering the personal safety of users.
 The operability of the product must be verified before use. If the
product fails to pass the function test, or the product is damaged, or the
maintenance and repair of a component is not completed, or the spare
parts of our original factory are not used, the product cannot be used.

1.2Duty
Not responsible for the consequences caused by the improper use or use of the
product for non-established purposes. Each operator must be responsible for the
selection and use of the product, such as the use of the productIf the maintenance or
service does not follow the instructions in this manual, the product liability
statement and quality assurance and other commitments provided will be invalid.

1.3Safety precautions to be taken


Be careful
The following safety instructions must be strictly observed. Only
in this way can the safety and health of the operator and the normal
function of the instrument be guaranteed

— The equipment described in this manual must be installed, operated and


maintained in strict accordance with its labels, warnings, instructions and specified
limits.
—This equipment is designed to detect gas or steam in the air.
—To prevent excessive vibration of the equipment, it is strictly prohibited to
install the sensor in direct sunlight, otherwise the sensor will overheat. When
installing the equipment, ensure that the sensor inlet is downward to avoid particles
or liquid blocking the gas inlet.
—The electrochemical sensor is a sealed component containing corrosive
electrolyte. If the sensor leaks, it must be immediately removed from the instrument
and properly handled. It is required to operate carefully to prevent the electrolyte
from contacting the skin, clothing or circuit, otherwise it may cause personal burns or
equipment damage.
—The equipment can be checked with gas with known concentration, which is
the only way to ensure the correct operation of the equipment as a whole. Therefore,
calibration inspection must be part of the routine detection of the system.
—Like other devices of this type, the sensor will not be polluted when exposed
to high concentration or certain compounds contained in the test atmosphere for a
long time. In the environment where the equipment may be exposed to these
substances, the equipment must be calibrated frequently to ensure reliable
operation and accurate display.
—The equipment shall not be painted. If there is paint work at the equipment
location, it must be carefully operated to ensure that the paint will not accumulate
on the flameproof disc in the gas sensor inlet, which will interfere with the gas
diffusion process.
—When performing maintenance according to the procedures specified in this
manual, only the original replacement parts can be used. Failure to do so may
seriously damage the performance of the instrument. If the equipment is repaired or
modified beyond the scope of maintenance, or is repaired or modified by
unauthorized maintenance personnel, the product will not reach the design
performance.
一 The equipment is designed for use in hazardous areas under atmospheric
conditions.
—In order to ensure the correct monitoring results, the combustible gas sensor
requires that the oxygen concentration exceed 10% Vo, but in the case of oxygen
enrichment, that is, the oxygen concentration exceeds 21% Vo, the measurement
and electrical safety of the equipment will be affected.
—Excessive dust accumulation on the sensor will prolong the response time of
the device, so it is necessary to regularly check the dust accumulation.
—If the catalytic combustible gas sensor is exposed to silicon, silane, silicate,
halide and compounds containing fluorine, chlorine, iodine or bromine, the
combustible gas probe will be poisoned, and the instrument will not work properly.

1.3 Fixed instrument warranty

Refer to our quality assurance statement.

According to the requirements of our company, we will correctly install, debug and use this

product, and our company will provide the relevant responsibilities of this product during

the warranty period.Our company does not assume the product warranty responsibility

caused by the following factors:

1. Calibration, commissioning and maintenance carried out by personnel other than our

company or authorized by our company;

2.Due to incorrect placement, use and modification of products:

Any confirmation, representation or warranty made by any person on this product without

the authorization of our company will be regarded as invalid terms


Our company is not responsible for quality assurance of parts or accessories not

produced by itself; Our company reserves the right to transfer the quality assurance

responsibilities provided by the manufacturers of these parts or accessories to the relevant

purchasers.

2 Summary

2.1 Device identification

Single gas detector

Four-in-one gas detector


2.2 Summary

The equipment is calibrated by the factory and can be installed after delivery.
Each equipment is only matched and calibrated for a specific gas or steam. After the
detector is put into normal operation, it is recommended to calibrate it every three
months.
The equipment includes (single gas detector is taken as an example in the figure
below):
A gas sensor
The output signal of this device is (4~20) mA, and the protection level is | P67
(excluding the sensor part).
2

1 3

4
5

6
1、Power/signal line incoming, threaded interface m20 * 1.5
2、Fixed footφ8*3
3、Audible and visual alarm light, interfaceM20*1.5
4、Sensor air chamber
5、Vent hood locking ring
6、Air inlet/outlet, thread : G1/8 , Quick intubation φ 6 , external
diameter 6 bore size4mm

3 Install
The equipment must be installed where gas leakage is expected. The installation
position is determined according to the gas density. If the density of the detected gas
is less than that of the air, the equipment can be installed under the indoor ceiling; If
the density of the detected gas is greater than that of the air, the equipment can be
installed near the ground. In addition, the influence of gas flow on the ability of the
equipment to detect gas must also be considered. The installation must also ensure
that the display screen on the front of the equipment is clear and can be seen
without obstruction.
Pay attention to
Before installation, check whether the delivered parts are complete and
accurate according to the packing list.
Pay attention to
When preparing for assembly, ensure that the installation layout is
consistent with the equipment.
3.1Mechanical installation
3.1.1Outline dimension diagram (taking four-in-one detector as an example)

Note: There may be differences between the dimension of the


detector and the actual dimension, please refer to the actual

Overall dimension of detector

3.1.2 Outline dimension diagram (taking single detector as an example)


3.2 Electrical installation
Electrical connection instructions

Pay attention to
The installation of the detector must comply with the applicable rules and
regulations, otherwise its safe operation cannot be guaranteed.
—Shielded cables must be used for detectors. If shielded cables are not used, the
anti-interference performance of the detector design cannot be guaranteed.
—Always observe the maximum cable length and cross section (see section 6.2).
—Water or impurities can penetrate into the detector through the cable. In dangerous areas, it is
recommended to wrap the part of the cable in front of the detector entrance into a circle, or
slightly bend the cable to prevent water from entering the detector.

Pay attention to
The power supply is 12-24V DC. Limit voltage DC9-36V If the detector is greater than
36V, the detector may fail permanently

3.3 Required reading for operating instruments


Must read before operation
Warning!
Any person who may use, maintain or repair the instrument should
carefully read this operation manual,Only by strictly following this
operation manual can the performance of the instrument reach the
design level.

Warning!
For newly purchased instruments, standard gas with known
concentration must be used before useBody. To maximize safety, it is
recommended to use the Calibrate the standard gas with known
concentration at least once.

Be careful!
To reduce the risk of electric shock, the power supply must be turned off
when removing the electrochemical sensor for maintenance. Never
operate the instrument when opening the cover. Only after confirming
that the surrounding environment is safe
The instrument can only be turned on.

3.4. Brief introduction


The color screen fixed gas detection transmitter is applicable to the detection of
CO, H2S, SO2, NO, NO2, Cl2, O2, ClO2, NH3 and other gases. It can work under the
voltage of 12~24VDC and provide 4-20 mA, RS485, relay, audible and visual alarm
and other output signals. The whole instrument is explosion-proof. The instrument
provides the function of field digital reading and field calibration, and can also use
RS485 to realize remote data acquisition and remote calibration.

Main performance:
 4-20 mA, RS485, relay, audible and visual alarm and other output signals
 Explosion-proof design in hazardous environment
 Use the infrared remote control to adjust the operating parameters to reduce
the chance of opening the explosion-proof enclosure
 Standard replaceable 4R/7R electrochemical sensor, PID sensor, infrared sensor
 9 - 30VDC operation
 Up to 3 normally closed and normally open relays
 One transmitter can measure four gases at the same time
4G and 5G data transmission can be expanded
Application:
 Hospitals and pharmaceutical factories
 Water treatment plant, oil well
 Oil refining and petrochemical plants
 Steel plant, power plant, gas plant
 Coal mine, chemical plant, raw material warehouse
 Grain fumigation monitoring
Tunnel

1.1 Parameter

volume 140mm x 214mm x 89mm


weight 2.2 kg
detector standard 4R and 7R electrochemical sensors,
infrared sensors, catalytic combustion
sensors
check two-point on-site correction
source 12 - 24VDC maximum 50mA/24V
export 4-20mA 、RS485、electric relay
sampling internal diffusion
show 2.0 "HD color display
user Action physical keys, infrared remote control
service -20°C ~ 55°C
temperature
humidity 0-95% relative humidity (non condensing)
dry contact maximum 3 relays, maximum 30V, 2A
install 3 hole locations, 8mm aperture
electrical M20 * 1.5 (standard), 3/4 NPT (M)
interface (customized)
wireless function customization function

The accessory box of the instrument includes: remote control, certificate of


conformity and operation instructions.
4、Operation introduction

Before the first use of the newly purchased instrument, the sensor must be
calibrated with a standard gas of known concentration. In order to maximize safety, it
is recommended to calibrate at least once every three months with standard gas of
known concentration.
Calibrate within a fixed period of time in the detection environment to ensure
that the sensor will not fail.

Verify and correct with test gas of known concentration before use. This
"impact" test is very simple and only takes 1 minute to complete. If the reading is out
of range, the instrument should be recalibrated.

The instrument has been calibrated with corresponding standard gas before
delivery. However, after a period of use, the user should also make corrections. The
instrument can be operated immediately after installation and calibration.
As for the service life of the sensor, the general electrochemical sensor life is
inversely proportional to the ambient gas concentration. The higher the ambient
concentration, the more easily the electrochemical substances inside the sensor are
consumed by the reaction, the shorter the service life, and the greater the
attenuation in the process. Therefore, users need to test and maintain the
instrument frequently.

4.1 Profile description

It is convenient to fix the gas detector on a specific occasion


for continuous monitoring. The external dimension of the detector is
213mm x 141mm x 95mm, and the distance between the three mounting holes
is 103mm and 117mm respectively
4.2 Installation and assembly

The hardware structure diagram is digital tube display, and the shape of the LCD
display is the same. The shape of the digital probe is different according to the
difference of single component and multi-component
Warning
1. In Class B environment, use at least 50 cm long explosion-proof
conduit. In Class C environment, if the conduit length exceeds 150 cm,
it needs to be sealed.
2. To ensure the safety of the environment, when opening the cover, make
sure there is no dangerous gas on the site and cut off the power supply.

4.3 Install
First of all, determine the installation position of the detector.
According to the installation drawing, drill three holes at the
installation position (first drill two holes with a horizontal distance
of 116mm, and then drill a third hole 103mm above the center of the two
holes.

Before installation or maintenance, confirm that the power supply is turned off to
ensure environmental safety.

4.4 Wire hole number


wireway grade wireway grade
input power J1-24V high alarm relay common J1-M2
supply+ terminal
input power J1-GND high alarm relay J1-O2
supply- normally open
output current+ J1-4-20mA Low alarm relay common J1-M1
terminal
output current- J1-GND Low alarm relay normally J1-O1
open
output RS485A J1-RS485A
output RS485B J1-RS485B
fault relay J3-C3
normallyclosed
fault relay common J3-M3
terminal
fault relay J3-O3
normally open

Note: J4 can only connect the audible and visual alarm below 24V-100mA, and
the high-power audible and visual alarm may not start or damage the drive
circuit.

5、Function tree

System function tree

The display interface is designed with human-computer interaction. There are


three physical keys on the label panel. Each interface has the function of prompting
corresponding keys. Customers can also complete the calibration and setting work
according to the interface prompts without using the instructions.

6、Introduction to operation interface


6.1 Interface Introduction
After the gas detector is powered on, the interface displays "instrument on",
"equipment information", "range value", "high alarm value", "low alarm value", "TF
card capacity information" and "sensor preheating" countdown.

Configure different detection interfaces according to the number of sensors,


including single gas, two gases, three gases and four gas interfaces

single gas interface two gas interfaces three gas interfaces four gas interfaces

6.2 Modify transmitter RS485 communication address


In the detection interface, press the middle button to enter the address
modification interface. No password is required to log in to the interface. If there is
no operation in 60 seconds under the interface, it will automatically jump back to the
detection interface.

In the transmitter address modification interface, you can


modify the transmitter address by pressing the left and right buttons, and the new
address will be automatically saved.

6.3 Access menu password

In the detection interface, press the key (menu) on the right to


enter the password input interface. After power-on and reset, the password is
required to enter the main menu interface for the first time, and no password is
required for the second and later access.
The password is initialized to "0000". Enter "1234" as prompted to enter the menu
interface.

7、Menu introduction
There are six main menus under the menu interface: "instrument calibration",
"sensor", "alarm setting", "data storage", "instrument setting" and "about the
machine". You can move the cursor to enter the required operation interface

according to different needs.


8、Calibration method
You can select "absolute zero" and "span calibration" under the instrument
calibration menu.

Note: The calibration process needs to pay attention to the size of the ADC, and the
full scale ADC should not be greater than 20000.
ADC value: the number after the signal size of the sensor is converted.

8.1 Calibration process description


Absolute zero point correction - 60 seconds after filling with bottled air
or nitrogen
Calibration of standard gas – 30 seconds after using standard gas
(For most sensors, the countdown time is 30 seconds, and for some
special sensors, the countdown time is longer.)

8.2 Check
Connect the gas detector to the standard cylinder through the flow-type
cover, gas pipe and pressure reducing valve.
Warning
All newly purchased instruments must be calibrated with standard
gas of known concentration before being used for the first time.
In order to maximize safety, it is recommended to calibrate at
least once every three months with standard gas of known
concentration.
.

The gas detector is calibrated by the two-point calibration method. First,


"absolute zero calibration" is performed, that is, the instrument zero is calibrated
with clean air. Then, calibrate the second point of the instrument with a standard gas,
that is, a gas of known concentration. The recommended standard gas shall be
determined by the detection range of the product. Absolute zero correction should
be performed before the second point standard gas correction.
Be careful:
1:Because the air contains oxygen and carbon dioxide, the absolute zero point
of oxygen sensor and low range carbon dioxide sensor can only be corrected with
pure nitrogen.
2:According to the characteristics of the sensor, oxygen is
required to participate in the reaction process of the catalytic
combustion sensor, so the balance gas in the standard gas for
measuring combustible gas using the catalytic combustion
principle must be air.

8.3 Materials required for calibration


To calibrate the instrument, users need to prepare two bottles of
gas (zero standard gas and standard gas) pressure reducing valve, gas pipe
and calibration cover.
The gas detector is connected with the gas cylinder through the calibration
connector.
It is allowed to use the computer to send commands for calibration through RS485
bus or use keys and infrared remote control to calibrate on site.

8.4 Zero calibration:


Toxic and harmful gas: the gas detector is powered on in clean air,
and enters the "instrument calibration" to select the channel to be
calibrated after the countdown is completed. Enter the calibration
interface
Select "absolute zero point" and click "enter"

The program prompts whether to perform zero point calibration. If you


are sure to perform it, click "OK". The program will perform the zeroing
operation of the channel.
Oxygen sensor: The oxygen sensor cannot perform "absolute zero"
operation in the air, and there is 20.9% VOL of oxygen in the air. The
oxygen sensor needs to be filled with pure nitrogen (99.99% VOL) before
performing the "absolute zero" calibration, and can be operated only after
the oxygen in the structure is completely replaced.

8.5 Span calibration:


For the instrument calibrated at two points, the concentration value
of the standard gas should not be less than 10% of the instrument's range,
otherwise the measurement value of a large range of a section may have
a large error. It is recommended to use more than 50% of the full range
of gas for calibration.
The method is as follows:
1:Connect the calibration gas circuit, power on the instrument and
wait to enter the calibration interface.
2:After entering the calibration interface, set the data in the range
calibration to be consistent with the concentration of the
standard cylinder.

3:Release the standard gas and adjust the gas flow to 300 ml/min.
Observe the change of instrument ADC at this time. Click "Confirm"
when the ADC value is stable and will not rise
8.6 Introduction to other operations
8.6.1 Sensor information operation

"Volatile gas type": the factory default display is VOC, but the user can choose to
display the actual gas name.
"Volatile gas compensation coefficient": there are hundreds of volatile gases, and the
reaction coefficient of each gas is different. The manufacturer shall calibrate
according to isobutylene during production. If the user can determine the
composition of the target gas when using it, he can modify the reaction coefficient by
himself. For example, to measure benzene, the coefficient should be modified to
0.53."Combustible gas type": if the instrument is a combustible gas detector, the
default gas type is EX. Users can modify it to methane or propane.

8.6.2 Alarm settings

"Alarm limit": the high alarm point and low alarm point values of the instrument can
be modified.
"Alarm channel": the alarm of the instrument is allowed. If the channel authority is
cancelled, any change in the gas concentration value of the channel will not trigger
the alarm, that is, the alarm limit is invalid.

8.6.3 Data storage


The gas detector has the storage function, but the TF card required for storage is
not a standard configuration and needs to be purchased by the user.
The user can set the time interval for data storage, with a minimum interval of 2
minutes.
Users can browse historical data on this machine, or pull out the TF card and use the
card reader to find the root directory of the disk where the TF card appears. There is
an RT under the folder "HISTORY_DATA"_ The excel file of record can be opened
directly to view historical data.

Note: The TF card should not be larger than 64G. The storage capacity of an
instrument stored in 2 minutes for one year will not be greater than 4G. The saved
EXCEL file is too large to open. It is better to back up the data once a year and format
the TF card before reuse.

8.6.4 Instrument setup

In the instrument setting menu, there are "date and time", "language setting",
"display setting", "current function", "restore factory" and other functions.
The date and time of the user who needs to store historical data need to be set
correctly. In addition, there is a 3V button battery (CR1220) on the motherboard that
needs to be replaced for two years. This battery is used to ensure that the internal
clock can operate normally when the instrument is powered off.
After a long time of use, the current output function may have some drift. If the
accuracy of use is affected, you can enter the "Current function" to re-correct the
output accuracy of 4mA and 20mA.

9、About this machine


About this machine, there are two submenus of "instrument information" and
"import probe information"
The "instrument information" contains the version number and hardware serial
number of the instrument software。
"Import probe information": refers to the information of the digital probe read by
the instrument.
Since the gas detector design follows the digital concept, the gas conversion
data measured by the sensor has been completed in the digital probe. When
the new digital probe is used to communicate with the probe, the configuration
parameters of the digital probe need to be imported.

10、Design theory
Each gas detector uses a digital probe and can support a complete

range of sensors (electrochemical, combustible, infrared and PID are

supported).

The combustible gas sensor adopts the latest generation of carrier

catalytic elements with low power consumption and high anti-interference.

It forms a detection bridge circuit with two fixed resistors. When the

combustible gas in the air diffuses to the surface of the detection element,

the flameless combustion will be carried out rapidly under the action of the

catalyst on the surface of the detection element, and the reaction heat will

increase the platinum wire resistance value of the detection element, and

the detection bridge circuit will output a differential pressure signal. The

magnitude of this voltage signal is directly proportional to the concentration


of combustible gas.

The oxygen sensor applies the principle of Gavanni galvanic cell. Its

structure is to install the anode (lead) and cathode (silver) in the galvanic

cell, which are separated from the outside by a thin film. When the

oxygen-containing gas in the air reaches the cathode through this thin

film, the oxidation-reduction reaction occurs. The sensor will now have a

millivolt voltage output that is proportional to the oxygen concentration.

The toxic and harmful gas sensor adopts the world's advanced

imported electrochemical sensor, which applies the principle of controlled

potential electrolysis. Its structure is to place three electrodes in the

electrolytic cell, namely, the working electrode, the counter electrode and

the reference electrode, and apply a certain polarization voltage. By

replacing the sensor of different gases and changing the polarization

voltage value, different toxic and harmful gases can be measured. The

measured gas will reach the working electrode through the film and

undergo oxidation-reduction reaction. At this time, the sensor will have a

small current output, which is proportional to the concentration of toxic and

harmful gases.

11、Maintain
As a suggestion, it is better to conduct regular impact test on the

gas detection instrument with gas of known concentration.


12、After-sales service commitment

After-sale service commitment of combustible and toxic gas alarm:


1. The warranty period of our products is one year from the date of delivery
(excluding human factors and force majeure).
2. The products within the warranty period can be returned to the factory for free
gas calibration and maintenance at the request of customers, and our company will
not bear the round-trip freight of the products.
3. For products beyond the warranty period, Party A will only charge the
maintenance cost.
4. The company provides 7 × 24 hours of professional service. The company will
respond within 4 hours after receiving the customer's notice and issue a solution
within 24 hours.
5. Generally, the normal service life of the sensor is 2 years for the catalytic
combustion sensor and 1 year for the electrochemical sensor. The actual service
life of the sensor is directly related to the working environment. The service life of
the sensor will change with the use environment.
6. In order to ensure the reliability of product performance, we recommend that
users regularly maintain and calibrate the product within the service life.

13、Reference standards
GB 12358-2006 General technical requirements for environmental gas detection and alarm
apparatus in workplace
IEC 60079-0-2017 Explosive atmospheres - Part 0: Equipment - General requirements
GB3836.1-2010 Explosive atmospheres Part 1: General requirements for equipment
GB3836.2-2010 Electrical equipment for explosive atmospheres and gas atmospheres
Part 2: Flameproof type "d"
GB/T 4208-2017 Enclosure protection class (IP code)
GB/T4857.5-92 Packaging Transport packages Drop test method
JJG 915-2008 Verification regulation of carbon monoxide detection alarm
JJG 695-2003 Verification regulation of hydrogen sulfide gas detector
JJG 365-2008 Verification regulation of electrochemical oxygen meter
JJG 693-2011 Verification regulation of combustible gas detection alarm

14、Addendum A:Sensor characteristics


The following table lists the characteristics of different sensors of the gas detector:
sensor detection resolution response standard gas lower limit high limit
range ratio timeT90(sec concentration (ppm) (ppm)
(ppm) (ppm) ond) (ppm)
CO 0-1000 1 <30 50 35 200
H2 S 0-100 1 <20 25 10 20
SO2 0-100 0.1 <30 5 2 10
NO 0-250 0.5 <20 25 25 50
NO2 0-50 0.1 <25 10 1 10
Cl2 0-30 0.1 <60 10 0.5 5
O2 0-30% 0.1% <20 20.9% 19.5% 23.5%
ClO2 0-1 0.01 <120 0.5 0.2 0.5
NH3 0-100 0.5 <60 50 25 50
PH3 0-20 0.05 <30 5 1 2
HCN 0-100 0.5 <200 10 4.7 50
ETO 0-200 0.1 <80