AC Power Analysis
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
1
11.1 Instantaneous and
Average Power (1)
• The instantaneously power, p(t)
p (t ) v(t ) i (t ) Vm I m cos (w t v ) cos (w t i )
1 1
Vm I m cos ( v i ) Vm I m cos (2w t v i )
2 2
Constant power Sinusoidal power at 2wt
p(t) > 0: power is absorbed by the circuit; p(t) < 0: power is absorbed by the source.
2
11.1 Instantaneous and
Average Power (2)
• The average power, P, is the average of the instantaneous
power over one period.
1 T 1
P p(t ) dt Vm I m cos ( v i )
T 0 2
1. P is not time dependent.
2. When θv = θi , it is a purely
resistive load case.
3. When θv– θi = ±90o, it is a
purely reactive load case.
4. P = 0 means that the circuit
absorbs no average power.
3
11.1 Instantaneous and
Average Power (3)
Example 1
Calculate the instantaneous power and average
power absorbed by a passive linear network if:
v(t ) 80 cos (10 t 20)
i (t ) 15 sin (10 t 60)
Answer: 385.7 600cos(20t 10)W, 387.5W
4
11.1 Instantaneous and
Average Power (4)
Example 2
A current I 10 30 flows through an
impedance Z 20 22 Ω . Find the average
power delivered to the impedance.
Answer: 927.2W
5
6
7
11.3 Effective or RMS Value (1)
The total power dissipated by R is given by:
1 T R T 2
P i Rdt i dt I rms
2 2
R
T 0 T 0
T
1
Hence, Ieff is equal to: I eff
T
0
i 2 dt I rms
The rms value is a constant itself which
depending on the shape of the function i(t).
The effective of a periodic current is the dc current that delivers the
same average power to a resistor as the periodic current. 8
11.3 Effective or RMS Value (2)
The rms value of a sinusoid i(t) = Imcos(wt)
is given by:
Im
I 2
rms
2
The average power can be written in terms of
the rms values:
1
I eff Vm I m cos (θ v θ i ) Vrms I rms cos (θ v θ i )
2
Note: If you express amplitude of a phasor source(s) in rms, then all the
answer as a result of this phasor source(s) must also be in rms value.
9
11.4 Apparent Power and
Power Factor (1)
• Apparent Power, S, is the product of the r.m.s. values of
voltage and current.
• It is measured in volt-amperes or VA to distinguish it from
the average or real power which is measured in watts.
P Vrms I rms cos (θ v θ i ) S cos (θ v θ i )
Apparent Power, S Power Factor, pf
• Power factor is the cosine of the phase difference between
the voltage and current. It is also the cosine of the angle
of the load impedance.
10
11.5 Complex Power (1)
Complex power S is the product of the voltage and the
complex conjugate of the current:
V Vm θ v I I m θ i
1
V I Vrms I rms θ v θ i
2
11
11.5 Complex Power (2)
1
S V I Vrms I rms θ v θ i
2
S Vrms I rms cos (θ v θ i ) j Vrms I rms sin (θ v θ i )
S = P + j Q
P: is the average power in watts delivered to a load and it is
the only useful power.
Q: is the reactive power exchange between the source and
the reactive part of the load. It is measured in VAR.
• Q = 0 for resistive loads (unity pf).
• Q < 0 for capacitive loads (leading pf).
• Q > 0 for inductive loads (lagging pf). 12
11.5 Complex Power (3)
S Vrms I rms cos (θ v θ i ) j Vrms I rms sin (θ v θ i )
S = P + j Q
Apparent Power, S = |S| = Vrms*Irms = P 2 Q 2
Real power, P = Re(S) = S cos(θv – θi)
Reactive Power, Q = Im(S) = S sin(θv – θi)
Power factor, pf = P/S = cos(θv – θi)
13
11.5 Complex Power (4)
S Vrms I rms cos (θ v θ i ) j Vrms I rms sin (θ v θ i )
S = P + j Q
Power Triangle Impedance Triangle Power Factor 14
15
16
Power Factor
17
18
19
11.7 Power Factor Correction (1)
Power factor correction is the process of increasing the
power factor without altering the voltage or current to
the original load.
Power factor correction is necessary for economic reason. 20
11.7 Power Factor Correction (2)
Qc = Q1 – Q2
= P (tan θ1 - tan θ2)
= ωCV2rms
Q1 = S1 sin θ1 Qc P (tan θ1 tan θ 2 )
C 2
2
= P tan θ1 ωVrms ω Vrms
P = S1 cos θ1 Q2 = P tan θ2 21
Practice Problem 11.15: Find the value of the capacitance needed to correct
a load of 140 kVAR at 0.85 lagging pf to unity pf. The load is supplied by a 110
Volt (rms), 60 Hz line.