This is a map document of standard MODBUS RTU protocol for only GoodWe energy storage inverters compatible with HV
Inverter Address: Can be assigned from 1~247. 247 is factory default assignment.
Communication baud rate: The default baud rate is 9600 bps
2.1.3 Data Frame Format from Inverter (Register Addr. or register number is wrong)
Data NO Content Description
1 Inverter Address Communication Address(1-247)
2 83H Function code
3 02H Error Code
4 High byte of CRC16 verification code CRC verification code
5 Low byte of CRC16 verification code CRC verification code
2.2Set/Writing Register(Function code: 10H)
2.2.4 Data Frame Format from Inverter (when address or amount of register is faulty)
Sr. CODE EXPLANATION
1 Device Address Device communication address(1-247)
2 90H Function Code
3 02H Error Code
4 CRC16 Verification (high bit) CRC Verification
5 CRC16 Verification (low bit)
This is the basic wiring and instructions before starting reading interactive log between GoodWe energy storage inverter and the
Solar inverter must be powered up by DC or AC power before it can communicate successfully to the compatible device.
#Address English Name Chinese Name #R/W #Type #Size #SF #Units Range Flash Save Note(English) Note(Chinese)
Parallel System
设置的机器数量是1,
并机系统系统标记/ 1:Single inverter system
1 10400 Inverter Quantity RO U16 1 1 N/A 即单机系统;机器数
并机系统机器数量 >1:Parallel system
量大于1即并机系统
2 10401 Firmware Version_ARM ARM软件版本号 RO U16 1 1 N/A Refer to 35020 参考寄存器 35020
Firmware
3 10402 主DSP软件版本号 RO U16 1 1 N/A Refer to 35016 参考寄存器35016
Version_DSP_Master
4 10403 Firmware 副DSP软件版本号 RO U16 1 1 N/A Refer to 35017 参考寄存器35017
5 10404 Online Quantity 机器在线数量 RO U16 1 1 N/A
Refer to app mode
6 10405 APP Mode EMS 工作模式 RO U16 1 1 N/A 参考寄存器 47000
47000
7 10406 Safety Country 系统安规 RO U16 1 1 N/A Refer to 45244 参考寄存器 45244
workmode: 工作模式:
waiting/Ongrid/battery waiting/Ongrid/battery
8 10407 Work Mode 并机工作模式 RO U16 1 1 N/A
mode/check/fault mode/check/fault
Refer to 35187 参考 35187
9 10408 Meter comm status 电表通信状态 RO U16 1 1 N/A Refer to 36003 参考寄存器 36003
backup功能开关状
10 10409 BackUp Enable RO U16 1 1 N/A Refer to 45252 参考寄存器 45252
态
用于主机控制
DRED,RCR,一键关断
等,
11 10410 Controller Status Code 控制状态码 RO U16 1 1 N/A 本地址为复用地址当
DRED使能时为DRED
状态码,RCR使能时
为RCR状态码
12 10411 Reserved 预留 RO U16 1 1 N/A
Master DSP add up all 由主dsp累加各路PV,
13 10412 PV Total Power PV总功率 RO U32 2 1 W
PV power arm直接读取
参考寄存器 35182-
14 10414 Battery Total power 电池总功率 RO S32 2 1 W Refer to 35182-35183
35183
参考寄存器 35169-
15 10416 Total Back-Up Load Power Backup总功率 RO S32 2 1 W Refer to 35169-35170
35170
参考寄存器 36025-
16 10418 Meter Power 电表功率 RO S32 2 1 W Refer to 36025-36026
36026
参考寄存器 35137-
17 10420 Total Inverter Power 逆变总功率 RO S32 2 1 W Refer to 35137-35138
35138
参考寄存器 35124-
18 10422 R Phase Inverter Power R相逆变功率 RO S32 2 1 W Refer to 35124-35125
35125
参考寄存器 35129-
19 10424 S Phase Inverter Power S相逆变功率 RO S32 2 1 W Refer to 35129-35130
35130
参考寄存器 35134-
20 10426 T Phase Inverter Power T相逆变功率 RO S32 2 1 W Refer to 35134-35135
35135
Back-Up负载端R相 参考寄存器 35149-
21 10428 Backup Active Power-R RO S32 2 1 W Refer to 35149-35150
功率 35150
Back-Up负载端S相 参考寄存器 35155-
22 10430 Backup Active Power-S RO S32 2 1 W Refer to 35155-35156
功率 35156
Back-Up负载端T相 参考寄存器 35161-
23 10432 Backup Active Power-T RO S32 2 1 W Refer to 35161-35162
功率 35162
24 10434 Meter Frequence MeterFrequence RO U16 1 100 HZ Refer to 36014 参考寄存器 36014
25 10435 Battery Mode 充放电模式 RO U16 1 1 N/A Refer to 35184 参考寄存器 35184
26 10436 Battery Voltage 1 电池电压1 RO U16 1 10 V Refer to 35180 参考寄存器 35180
27 10437 Battery Voltage 2 电池电压2 RO U16 1 10 V Refer to 35262 参考寄存器 35262
28 10438 Total Inverter Power 机器额定总功率 RO U32 2 1 W Refer to 35001 参考寄存器35001
参考寄存器47001,可
1 10470 Meter Check Value CT 检测结果 RO U16 1 1 N/A Refer to 47001
以使用同一变量
参考47002,可使用同
2 10471 Meter Connect Check Flag CT检测使能状态 RO U16 1 1 N/A Refer to 47002 一变量,10439只读,
47002读写
云板根据每台机器
3 10472 SOC 每台SOC RO U16 1 1 N/A SOC计算平均值,获
取每台寄存器37007
4 10473 Battery Capacity 电池容量 RO U16 1 1 N/A
5 10474 Battery Communication 电池通讯状态 RO U16 1 1 N/A
Battery Charge Allow [00xFFF
6 10476 电池可充瓦时 RO U32 2 1 W·H N
Kilowatt-Hour Sum FFFFF]
Battery Disharge Allow [00xFFF
7 10478 电池可放瓦时 RO U32 2 1 W·H N
Kilowatt-Hour Sum FFFFF]
0: Need to be averaged
0:不可进行均分
8 10480 AbleBalanceFlag 可平衡标志位 RO U16 1 1 N/A [0,1] N 1: No need to be
1:需要进行均分
averaged
9 10481 Meter Active Power R 电表R相有功功率 RO S32 2 1 W Refer to 36127 参考寄存器 36127
10 10483 Meter Active Power S 电表S相有功功率 RO S32 2 1 W Refer to 36129 参考寄存器 36129
11 10485 Meter Active Power T 电表T相有功功率 RO S32 2 1 W Refer to 36131 参考寄存器 36131
Evcharger
1 10600 CP Voltage CP电压 RO U16 1 10 V
2 10601 Leak Current 漏电流 RO U16 1 1 mA
0 disconnected 0 连接断开
1 connected 1 已连接
3 10602 CP Status CP状态 RO U16 1 NA NA
2 charging 2 充电中
3 fault 3 故障
4 10603 Solar Power for Charge 太阳能充电 RO U16 1 1 W
5 10604 Battery Power for Charge 电池充电 RO U16 1 1 W
6 10605 Grid Power for Charge 电网充电 RO U16 1 1 W
7 10606 Current Charge Energy 当前充电量 RO U16 1 10 kwh
8 10607 Current Charge Time 当前充电时间 RO U16 1 1 min
9 10608 Charge Current 充电电流 RO U16 1 10 A
0 Initial state
0 初始状态
1 Fault state
1 故障状态
2 Standby state, no
2 待机状态,机器无故
machine failure, waiting
障,等待外部
for external conditions to
条件满足
be met.
3 运行状态
3 Running state
4 停机(没有故障,用
电动汽车充电器状 4 Shutdown (no fault,
10 10609 EV Charger Status RO U16 1 N/A N/A 户主动关机)
态 user-initiated shutdown)
5 预约状态
5 Reservation status
6 自检中
6 Self-testing
7 启动中
7 Starting
8 机器做好开机准备,
8 The machine is ready
但还需要等待
to power on, but it still
一定时间才能真正开
needs some time to really
机
power on.
电动汽车充电器故
11 10610 EV Charger Error Message RO U32 2 N/A N/A
障信息
12 10612 Charging Mode 充电模式 RO U16 1 N/A N/A
13 10613 Max Charge Current 最大充电电流 RO U16 1 1 A
14 10614 Current Charge Power 当前充电电流 RO U16 1 1 W
15 10615 Total Charge Energy 总充电量 RO U32 2 10 kwh
16 10617 Total Charge Time 总充电时间 RO U32 2 10 H
17 10619 EV Ouput Voltage EV端口电压 RO U16 1 10 V
18 10620 AC Input Voltage AC输入电压 RO U16 1 10 V
0: Com not loss 0:通讯未丢失
19 10621 EV Communication lost flag EV通讯丢失位 RO U16 1 N/A N/A
1: Com loss 1:通讯丢失
Evcharger Fault
1 10700 Total Pages 总页数 RO U16 1 N/A N/A
Auto-increment for each
read 每读一次自动递增
2 10701 Current Page 当前页 RO U16 1 N/A N/A Read page can be set via 可通过20321设置读取
20321 to prevent read 页,防止读取失败
failure
3 10702 Error Time 故障时间 RO U32 2 N/A N/A unixtime unixtime
0 Over Temperature
1 Overload 0 过温
2 Utility over-voltage 1 过载
3 Utility undervoltage 2 市电过压
4 Utility overcurrent 3 市电欠压
5 Utility overfrequency 4 市电过流
6 Utility under-frequency 5 市电过频
7 User shutdown 6 市电欠频
8 Emergency shutdown 7 用户关机
4 10704 Error Code H 高位故障代码 RO U16 1 N/A N/A
9 Low temperature 8 紧急停机
10 Leakage current 9 温度过低
11 low res ground fault 10 漏电流
12 Bluetooth connection 11 低电阻接地故障
failure 12 蓝牙连接故障
13 lock rocker blocked 13 lock摇臂遇阻
14 relay abnormal 14 relay异常
15 Ground fault 15 接地故障
0 Inverted phase
1 Abnormal leakage
current circuit
2 Attitude detection 0 反相
3 Bluetooth module 1 漏电流电路异常
matching fault 2 姿态检测
4 Range module 3 蓝牙模块匹配故障
matching fault 4 测距模块匹配故障
5 10705 Error Code L 低位故障代码 RO U16 1 N/A N/A
5 can communication 5 can 通讯异常
abnormality 6 电表通信故障
6 Meter communication 7 cp异常 cp低于2V
failure 8 B枪过温
7 cp abnormality,cp 9 B枪低温
below 2V
8 B-gun over-temperature
9 B-gun low temperature
Evcharger Charging
1 10800 Total Pages 总页数 RO U16 1 N/A N/A
Auto-increment for each
read 每读一次自动递增
2 10801 Current Page 当前页数 RO U16 1 N/A N/A Read page can be set via 可通过20322设置读取
20321 to prevent read 页,防止读取失败
failure
3 10802 Operation Time 运行时间 RO U32 2 N/A N/A unixtime unixtime
4 10804 Charging Mode 充电模式 RO U16 1 N/A N/A
0:Charge start 1:Charge 0:充电起始 1:充电结
5 10805 Charging Status 放电模式 RO U16 1 N/A N/A
end 束
Display when charging is
finished
充电结束时显示
u16:Current charging
6 10806 Operation Information 运行信息 RO U32 2 N/A N/A u16:当前充电时长
time
u16:当前充电电能
u16:Current charging
power
7 10808 Operation Code Count 运行代码计数 RO U16 1 N/A N/A
8 10809 Check Sum 检测汇总 RO U16 1 N/A N/A
0: Disabled(default)
33 20332 Off Grid Charge Enable 离网充电使能 RW U16 1 1 N/A Y 1: Enabled 0:失能 1:使能 默认0
#Address English Name Chinese Name #R/W #Type #Size #SF #Units Range Flash Save Note(English) Note(Chinese)
32000 - 32099(Erro Message)
电网端故障信
1 32000 Utility Fault 1 RO U16 1 1
息1
电网端故障信
2 32001 Utility Fault 2 RO U16 1 1 NA NA
息2
3 32002 System Fault 1 系统故障信息1 RO U16 1 1 NA NA
4 32003 System Fault 2 系统故障信息2 RO U16 1 1 NA NA
5 32004 Device Fault 1 设备故障信息1 RO U16 1 1 NA NA
6 32005 Device Fault 2 设备故障信息2 RO U16 1 1 NA NA
7 32006 DC Fault 1 DC侧故障信息 RO U16 1 1 NA NA
8 32007 PV Fault 1 PV侧故障信息1 RO U16 1 1 NA NA
9 32008 PV Fault 2 PV侧故障信息2 RO U16 1 1 NA NA
10 32009 BAT Fault 1 Bat侧故障信息 RO U16 1 1 NA NA
11 32010 BAT Fault 2 Bat侧故障信息 RO U16 1 1 NA NA
12 32011 BAT Fault 3 Bat侧故障信息 RO U16 1 1 NA NA
17 32016 Alarm 1 告警信息1 RO U16 1 1 NA NA
Hitsink
1 33500 Temperature- DCDC散热器温度 RO S16 1 10 ℃
DCDC
Hitsink
2 33501 Temperature- MPPT散热器温度 RO S16 1 10 ℃
MPPT
Hitsink For BTC/ETC BTC/ETC专用
3 33502 STS散热器温度 RO S16 1 10 ℃
Temperature-STS
Hitsink
DCDC2散热器温
4 33503 Temperature- RO S16 1 10 ℃
度
DCDC2
Hitsink
MPPT2散热器温
5 33504 Temperature- RO S16 1 10 ℃
度
MPPT2
D #Address English Name Chinese Name #R/W #Type #Size #SF #Units Range Flash Save Note(English) Note(Chinese)
Device Info
2 35001 Rate Power 额定功率 RO U16 1 1 N/A Inverter rated power 逆变器额定功率
ASCII code,16
ASCII码,16个字节。
bytes.Read together,
4 35003 Inverter SN 逆变器序列号 RO STR 8 1 N/A 一起读,包括OEM产
include OEM
品。
products.
5 35011 Model Name 模型名称 RO STR 5 1 N/A ASCII code, 10 bytes ASCII码,10个字节
Firmware 主控DSP固件
6 35016 RO U16 1 N/A N/A
Version_DSP_Master 版本
Firmware 从属DSP固件
7 35017 RO U16 1 N/A N/A
Version_DSP_Slave 版本
主控DSP的
8 35018 Beta Version_DSP_Master RO U16 1 N/A N/A
SVN版本号
ARM测试版
10 35020 Beta Version_ARM RO U16 1 N/A N/A
(小版本号)
0: Deault 1:Power
0:默认 1:功率快速
23 35043 System control mode 系统控制模式 RO U16 1 1 N/A fast set, without step
给定,无步长调节
size adjustment
ID of GPRS/4G
1 35050 SIMCCID SIMCCID RO STR 10 N/A N/A GPRS/4G模块的ID
module
Inverter Operation Data
High Byte Year/Low
Real-Time Clock_Year 实时时钟_年 高字节年/低字节月:13-
1 35100 RO U16 1 1 N/A Byte Month:13-99/1-
Month 月 99/1-12
12
High Byte
Real-Time Clock_Minute 实时时钟_分 高字节分,低字节秒:0-
3 35102 RO U16 1 1 N/A minute/Low Byte
Second 秒 59/0-59
Second:0-59/0-59
4 35103 PV1 Voltage PV电压1 RO U16 1 10 V
5 35104 PV1 Current PV电流1 RO U16 1 10 A
6 35105 PV1 Power PV功率1 RO U32 2 1 W 200ms Average 200ms平均值
7 35107 PV2 Voltage PV电压2 RO U16 1 10 V
8 35108 PV2 Current PV电流2 RO U16 1 10 A
9 35109 PV2 Power PV功率2 RO U32 2 1 W 200ms Average 200ms平均值
10 35111 PV3 Voltage PV电压3 RO U16 1 10 V
11 35112 PV3 Current PV电流3 RO U16 1 10 A
12 35113 PV3 Power PV功率3 RO U32 2 1 W 200ms Average 200ms平均值
13 35115 PV4 Voltage PV电压4 RO U16 1 10 V
14 35116 PV4 Current PV电流4 RO U16 1 10 A
15 35117 PV4 Power PV功率4 RO U32 2 1 W 200ms Average 200ms平均值
R Phase Inverter
19 35123 R相逆变频率 RO U16 1 100 Hz
Frequency
Inverter Power
20 35124 R Phase Inverter Power R相逆变功率 RO S32 2 1 W 逆变功率200ms平均值
200ms Average
Inverter Power
24 35129 S Phase Inverter Power S相逆变功率 RO S32 2 1 W 逆变功率200ms平均值
200ms Average
Inverter Power
28 35134 T Phase Inverter Power T相逆变功率 RO S32 2 1 W 逆变功率200ms平均值
200ms Average
Grid connection
电网连接状态,见表8-
29 35136 Grid Mode 电网模式 RO U16 1 N/A status,Refer to Table
10
8-10
30 35137 Total Inverter Power 逆变器总功率 RO S32 2 1 W 200ms Average 200ms平均值
Back-up端负
52 35169 Total Back-Up Load Power RO S32 2 1 W
载总功率
Inverter Internal
55 35174 Air Temperature 空气温度 RO S16 1 10 ℃ 逆变器内部温度
Temperature
Inverter Unit
56 35175 Model Temperature 模块温度 RO S16 1 10 ℃ 逆变器单元温度
Temperature
Inverter Heat Sink
57 35176 Hitsink Temperature 散热器温度 RO S16 1 10 ℃ 逆变器散热器温度
Temperature
58 35177 Function Bit Value 比特值函数 RO U16 1 N/A N/A
66 35186 Safety Country 安规国家 RO U16 1 N/A N/A Refer to Table 8-21 见表8-21
67 35187 Work Mode 工作模式 RO U16 1 N/A N/A Refer to Table 8-1 见表8-1
69 35189 Error Message 故障信息 RO U32 2 N/A N/A Refer to Table 8-12 见表8-12
The total PV
自安装之日起光伏发电
70 35191 PV Energy-Total 光伏发电总量 RO U32 2 10 1KW.Hr production energy
总量
from installation date
The accumulated
74 35199 Energy-Day-Sell 当日卖电量 RO U16 1 10 1KW.Hr exporting energy to 当天逆变的输出电量
grid of the day
The accumulated
76 35202 Energy-Day-Buy 当日买电量 RO U16 1 10 1KW.Hr energy imported from 当天逆变的输入电量
grid of the day
Accumulated load
当日负载消耗 consumption energy 每天负载消耗的电量,
78 35205 Energy-Load-Day RO U16 1 10 1KW.Hr
电量 of the day, not 不包括backup负载
include backup load
当日电池充电
80 35208 Energy-Charge-Day RO U16 1 10 1KW.Hr Not from BMS 不来自BMS
量
From the installation 自安装之日起,不来自
81 35209 Energy-Battery Discharg 电池放电总量 RO U32 2 10 1KW.Hr
date Not from BMS BMS
当日电池放电
82 35211 Energy-Discharg-Day RO U16 1 10 1KW.Hr Not from BMS 不来自BMS
量
number of battery
83 35212 Battery Strings 电池节数 RO U16 1 N/A N/A 电池模块的数量
modules
only for after-
CPLD警告代
84 35213 CPLD Warning Code RO U16 1 N/A N/A sales,Refer to Table 仅用于售后,见表8-17
码
8-17
88 35218 Diagnosis Status High 高位诊断状态 RO U32 2 N/A N/A Refer to Table 8-13 见表8-13
89 35220 Diagnosis Status Low 低位诊断状态 RO U32 2 N/A N/A Refer to Table 8-14 见表8-14
0: failure 1: Activated
0:失效 1:已激活 2:未
EH电池功能 2: Deactivated 3:
93 35225 EH Battery Function Active RO U16 1 N/A N/A 激活 3:锁止
激活 Locked
仅用于HER
only for HER
0: failure 1: Activated
0:未检测 1:正常 2:检
2: Deactivated 3:
拉弧自检测状 测中 3:失败
94 35226 ARC Self Check Status RO U16 1 N/A N/A Locked
态 仅用于带AFCI保护的
only for inverters with
逆变器
AFCI protection
Detail information of
安全详细故障 电网相关详细故障告
1 35250 Safety Detailed Error Message RO U64 4 1 N/A grid failure,Refer to
信息 警,见表8-30
Table 8-30
Detail information of
逆变器详细故 逆变器保护相关详细故
2 35254 Inverter Detailed Error Messag RO U64 4 1 N/A inverter failure,Refer
障信息 障报警,见表8-31
to Table 8-31
逆变器详细状
3 35258Inverter Detailed Status Messag RO U64 4 1 N/A Refer to Table 8-32 见表8-32
态信息
每分钟最大电
9 35268
Max Grid Frequency within 1min RO U16 1 100 Hz
网频率
每分钟最小电
10 35269Min Grid Frequency within 1minu RO U16 1 100 Hz
网频率
每分钟R相电
11 35270Max Grid Voltage within 1minute RO U16 1 10 V
网最大电压
每分钟R相电
12 35271Min Grid Voltage within 1minute RO U16 1 10 V
网最小电压
每分钟S相电
13 35272Max Grid Voltage within 1minute RO U16 1 10 V
网最大电压
每分钟S相电
14 35273Min Grid Voltage within 1minute RO U16 1 10 V
网最小电压
每分钟T相电
15 35274Max Grid Voltage within 1minute RO U16 1 10 V
网最大电压
每分钟T相电
16 35275Min Grid Voltage within 1minute RO U16 1 10 V
网最小电压
每分钟R相
17 35276
Max Backup Power within 1minut Backup负载端 RO U32 2 1 W
最大频率
每分钟S相
18 35278
Max Backup Power within 1minutBackup负载端 RO U32 2 1 W
最大频率
每分钟T相
19 35280
Max Backup Power within 1minutBackup负载端 RO U32 2 1 W
最大频率
每分钟Backup
20 35282
Max Backup Power within 1minute 负载端最大功 RO U32 2 1 W
率
电网高压穿越
21 35284 Grid Hvrt Event Times RO U16 1 1 N/A
次数
clear after restart 重启后清零
电网低压穿越
22 35285 Grid Lvrt Event Times RO U16 1 1 N/A
次数
离网转并网等
26 35292 Offline To Online Delay Second RO U16 1 1 N/A
待时间
电网高压穿越
27 35293 Grid Hvrt Status RO U16 1 1 N/A
状态
电网低压穿越
28 35294 Grid Lvrt Status RO U16 1 1 N/A
状态
安规国家分类 1:Australian 2:North
29 35295 Safety National Category Flag RO U16 1 1 N/A 1:澳洲类 2:北美类
标志 American
电池组1采样
32 35298 Battery1 Sample Voltage RO U16 1 10 V
电压
电池组2采样
33 35299 Battery2 Sample Voltage RO U16 1 10 V
电压
35 35301 PV Total Power 总PV功率 RO U32 2 1 W
36 35303 PV channel PV路数 RO U16 1 1 N/A
和并网保持一致,代表
37 35304 PV5 Voltage PV电压5 RO U16 1 10 V String Voltage
组串电压
和并网保持一致,代表
38 35305 PV5 Current PV电流5 RO U16 1 10 A String Current
组串电流
39 35306 PV6 Voltage PV电压6 RO U16 1 10 V
40 35307 PV6 Current PV电流6 RO U16 1 10 A
41 35308 PV7 Voltage PV电压7 RO U16 1 10 V
42 35309 PV7 Current PV电流7 RO U16 1 10 A
43 35310 PV8 Voltage PV电压8 RO U16 1 10 V
44 35311 PV8 Current PV电流8 RO U16 1 10 A
45 35312 PV9 Voltage PV电压9 RO U16 1 10 V
46 35313 PV9 Current PV电流9 RO U16 1 10 A
47 35314 PV10 Voltage PV电压10 RO U16 1 10 V
48 35315 PV10 Current PV电流10 RO U16 1 10 A
49 35316 PV11 Voltage PV电压11 RO U16 1 10 V
50 35317 PV11 Current PV电流11 RO U16 1 10 A
51 35318 PV12 Voltage PV电压12 RO U16 1 10 V
52 35319 PV12 Current PV电流12 RO U16 1 10 A
43 35320 PV13 Voltage PV电压13 RO U16 1 10 V
44 35321 PV13 Current PV电流13 RO U16 1 10 A
45 35322 PV14 Voltage PV电压14 RO U16 1 10 V
46 35323 PV14 Current PV电流14 RO U16 1 10 A
47 35324 PV15 Voltage PV电压15 RO U16 1 10 V
48 35325 PV15 Current PV电流15 RO U16 1 10 A
49 35326 PV16 Voltage PV电压16 RO U16 1 10 V
50 35327 PV16 Current PV电流16 RO U16 1 10 A
Warning information,
bit mode, different 警告信息,位模式,区
51 35328 Warning Message 32bit警告信息 RO U32 2 N/A N/A from 35185. See the 别于35185,具体故障
fault table for specific 详见不同机型的故障表
faults
电网R相
52 35330 Grid10minAvgVoltR 10min平均电 RO U16 1 10 V
压
电网S相
53 35331 Grid10minAvgVoltS 10min平均电 RO U16 1 10 V
压
电网T相10min
54 35332 Grid10minAvgVoltT RO U16 1 10 V
平均电压
Warningr information,
bit mode, extend 警告信息,位模式,扩
32bit警告信息
57 35335 Warning Message Extend RO U32 2 N/A N/A from 35328. See the 展于35328,具体故障
扩展
fault table for specific 详见不同机型的故障表
faults
Pv_boost1 total
为Pv_boost1路总功
59 35337 MPPT Power 1 MPPT1功率 RO U16 1 1 W power, not string
率,而非组串功率
power
Pv_boost2 total
为Pv_boost2路总功
60 35338 MPPT Power 2 MPPT2功率 RO U16 1 1 W power, not string
率,而非组串功率
power
Pv_boost3 total
为Pv_boost3路总功
61 35339 MPPT Power 3 MPPT3功率 RO U16 1 1 W power, not string
率,而非组串功率
power
Pv_boost4 total
为Pv_boost4路总功
62 35340 MPPT Power 4 MPPT4功率 RO U16 1 1 W power, not string
率,而非组串功率
power
Pv_boost5 total
为Pv_boost5路总功
63 35341 MPPT Power 5 MPPT5功率 RO U16 1 1 W power, not string
率,而非组串功率
power
Pv_boost6 total
为Pv_boost6路总功
64 35342 MPPT Power 6 MPPT6功率 RO U16 1 1 W power, not string
率,而非组串功率
power
Pv_boost7 total
为Pv_boost7路总功
65 35343 MPPT Power 7 MPPT7功率 RO U16 1 1 W power, not string
率,而非组串功率
power
Pv_boost8 total
为Pv_boost8路总功
66 35344 MPPT Power 8 MPPT8功率 RO U16 1 1 W power, not string
率,而非组串功率
power
逆变R相无功
75 35353 Inventer Reactive Power R RO S32 2 1 VAR
功率
逆变S相无功
77 35355 Inventer Reactive Power S RO S32 2 1 VAR
功率
逆变T相无功
79 35357 Inventer Reactive Power T RO S32 2 1 VAR
功率
逆变R相视在
81 35359 Inventer Apparent Power R RO S32 2 1 VA
功率
逆变S相视在
83 35361 Inventer Apparent Power S RO S32 2 1 VA
功率
逆变T相视在
85 35363 Inventer Apparent Power T RO S32 2 1 VA
功率
接收的信号强
2 36001 RSSI RO U16 1 N/A N/A RSSI of wifi module RSSI的WIFI模块
度指示
1:connect correctly
2:connect
1:连接正确 2:连接保
reverse(CT)
留(CT)
4:connect incorrectly
4:连接不正确 8:CT和
0:not checked
电压采样同时错相 0:未
4 36003 Meter Connect Status 电表连接状态 RO U16 1 N/A N/A For example: 0X0124
检测
means Phase
例如:0X0124就是R相
connect incorrectly,
连接不正确,T相连接
Phase T connect
保留,S相连接正确
reverse, Phase S
connect correctly
Meter Communication
5 36004 电表通讯状态 RO U16 1 N/A N/A 1:OK 0:NG 1:成功 0:失败
Status
电表R相有功
6 36005 Meter Active Power R RO S16 1 1 W
功率
If ARM
电表S相有功
7 36006 Meter Active Power S RO S16 1 1 W Version>9,please
功率 ARM09版后由
refer to
电表T相有功 36019~36041新地址替
8 36007 Meter Active Power T RO S16 1 1 W 36019~36041,which
功率 换,服务器端识别处理
can be identified by
电表总有功功
9 36008 Meter Total Active Power RO S16 1 1 W the server
率
电表总无功功
10 36009 Meter Total Reactive Power RO S16 1 1 W
率
电表R相功率
11 36010 Meter Power Factor_R RO S16 1 1000 N/A
因数
电表S相功率
12 36011 Meter Power Factor_S RO S16 1 1000 N/A
因数
电表T相功率
13 36012 Meter Power Factor_T RO S16 1 1000 N/A
因数
电表S相有功
19 36021 Meter Active Power S RO S32 2 1 W
功率
电表T相有功
20 36023 Meter Active Power T RO S32 2 1 W
功率
电表总有功功
21 36025 Meter Total Active Power RO S32 2 1 W
率
电表R相无功
22 36027 Meter Reactive Power R RO S32 2 1 W
功率
电表S相无功
23 36029 Meter Reactive Power S RO S32 2 1 W the address of ARM
功率 ARM09版后的地址
Version>9
电表T相无功
24 36031 Meter Reactive Power T RO S32 2 1 W
功率
电表总无功功
25 36033 Meter Total Reactive Power RO S32 2 1 W
率
电表R相视在
26 36035 Meter Apparent Power R RO S32 2 1 W
功率
电表S相视在
27 36037 Meter Apparent Power S RO S32 2 1 W
功率
电表T相视在
28 36039 Meter Apparent Power T RO S32 2 1 W
功率
电表总视在功
29 36041 Meter Total Apparent Power RO S32 2 1 W
率
Only for GoodWe
仅用于固德威智能电表
Smart Meter(0:Single
(0:单相 1: 三相三线
30 36043 Meter Type 电表类型 RO U16 1 1 N/A phase 1:3P3W
2:三相四线 3:HomeKit
2:3P4W 3:HomeKit
4:GM1000D)
4:GM1000D)
Bit0
(Communication
status between
Bit0(在SEC1000S和
SEC1000S and
逆变器之间通讯状态)
Parallel Communication inverters. )--0:NG
44 36066 并机通讯状态 RO U16 1 1 N/A 0:失败 1:成功
Status 1:Success
Bit1(逆变器并机通讯
Bit1(Communication
状态)0:失败 1:成功
status between
parallel inverters.)--
0:NG 1:Success
电弧故障分段
45 36067 ARC Software Version RO U16 1 1 N/A AFCI Version 电弧故障分段器版本
器软件版本
R相总有功电
54 36092 Active Energy Total Sell_R RO U64 4 100 1KW.Hr
量(卖电)
S相总有功电
55 36096 Active Energy Total Sell_S RO U64 4 100 1KW.Hr
量(卖电)
T相总有功电
56 36100 Active Energy Total Sell_T RO U64 4 100 1KW.Hr
量(卖电)
S相总有功电
59 36112 Active Energy Total Buy_S RO U64 4 100 1KW.Hr
量(买电)
T相总有功电
60 36116 Active Energy Total Buy_T RO U64 4 100 1KW.Hr
量(买电)
High Byte
Real-Time Clock_Minute 实时时钟_分 高字节分,低字节秒:0-
64 36126 RO U16 1 1 N/A minute/Low Byte
Second 秒 59/0-59
Second:0-59/0-59
电表R相有功
65 36127 Meter Active Power R RO S32 2 1 W
功率
电表S相有功
66 36129 Meter Active Power S RO S32 2 1 W 用于第二路计量芯片数
功率
据
电表T相有功
67 36131 Meter Active Power T RO S32 2 1 W
功率
电表总有功功
68 36133 Meter Total Active Power RO S32 2 1 W
率
R相总有功电
69 36135 Active Energy Total Sell_R RO U64 4 100 1KW.Hr
量(卖电)
S相总有功电
70 36139 Active Energy Total Sell_S RO U64 4 100 1KW.Hr
量(卖电)
T相总有功电
71 36143 Active Energy Total Sell_T RO U64 4 100 1KW.Hr
量(卖电)
S相总有功电
74 36155 Active Energy Total Buy_S RO U64 4 100 1KW.Hr
量(买电)
T相总有功电
75 36159 Active Energy Total Buy_T RO U64 4 100 1KW.Hr
量(买电)
SAPN防逆流
82 36172 SAPN FeedPower State 2 RO U16 1 1 N/A
计划组2状态
SAPN防逆流
83 36173 SAPN FeedPower State 3 RO U16 1 1 N/A
计划组3状态
SAPN防逆流
84 36174 SAPN FeedPower State 4 RO U16 1 1 N/A
计划组4状态
SAPN防逆流
85 36175 SAPN FeedPower State 5 RO U16 1 1 N/A
计划组5状态
SAPN防逆流
86 36176 SAPN FeedPower State 6 RO U16 1 1 N/A
计划组6状态
SAPN防逆流
87 36177 SAPN FeedPower State 7 RO U16 1 1 N/A
计划组7状态
SAPN防逆流
88 36178 SAPN FeedPower State 8 RO U16 1 1 N/A
计划组8状态
SAPN防逆流
89 36179 SAPN FeedPower State 9 RO U16 1 1 N/A
计划组9状态
SAPN防逆流
90 36180 SAPN FeedPower State 10 RO U16 1 1 N/A
计划组10状态
SAPN防逆流
91 36181 SAPN FeedPower State 11 RO U16 1 1 N/A
计划组11状态
unexecuted:0
未执行:0
running:1
执行中:1
execution is
执行完成:2
completed:2
unexecuted:0
SAPN防逆流 未执行:0
92 36182 SAPN FeedPower State 12 RO U16 1 1 N/A running:1
计划组12状态 执行中:1
execution is
执行完成:2
completed:2
SAPN防逆流
93 36183 SAPN FeedPower State 13 RO U16 1 1 N/A
计划组13状态
SAPN防逆流
94 36184 SAPN FeedPower State 14 RO U16 1 1 N/A
计划组14状态
SAPN防逆流
95 36185 SAPN FeedPower State 15 RO U16 1 1 N/A
计划组15状态
SAPN防逆流
96 36186 SAPN FeedPower State 16 RO U16 1 1 N/A
计划组16状态
SAPN防逆流
97 36187 SAPN FeedPower State 17 RO U16 1 1 N/A
计划组17状态
SAPN防逆流
98 36188 SAPN FeedPower State 18 RO U16 1 1 N/A
计划组18状态
SAPN防逆流
99 36189 SAPN FeedPower State 19 RO U16 1 1 N/A
计划组19状态
SAPN防逆流
100 36190 SAPN FeedPower State 20 RO U16 1 1 N/A
计划组20状态
SAPN防逆流
101 36191 SAPN FeedPower State 21 RO U16 1 1 N/A
计划组21状态
SAPN防逆流
102 36192 SAPN FeedPower State 22 RO U16 1 1 N/A
计划组22状态
SAPN防逆流
103 36193 SAPN FeedPower State 23 RO U16 1 1 N/A
计划组23状态
SAPN防逆流
104 36194 SAPN FeedPower State 24 RO U16 1 1 N/A
计划组24状态
SAPN实时防
105 36195 SAPN FeedPower Limit RO S32 2 1 W
逆流设定值
电池剩余电量
8 37007 SOC RO U16 1 1 % Capacity of BAT1 第1组电池容量
百分比
BMS低位警告
11 37010 BMS Warning Code Low RO U16 1 N/A N/A
代码
12 37011 Battery Protocol 电池协议 RO U16 1 N/A N/A
BMS高位故障
13 37012 BMS Error Code High RO U16 1 N/A N/A
代码
BMS高位警告
14 37013 BMS Warning Code High RO U16 1 N/A N/A
代码
Battery module
Minimum Cell Temperature 最小电池温度 电池模块ID(1Byte) +
18 37017 RO U16 1 1 N/A ID(1Byte) + Battery
ID ID 电池采样点(1Byte)
sample point(1Byte)
最大电池电压
19 37018 Maximum Cell Voltage ID RO U16 1 1 N/A
ID
最小电池电压
20 37019 Minimum Cell Voltage ID RO U16 1 1 N/A
ID
0x00:Shutdown 0x00:Shutdown 关机
0x01:Blowing 0x01:Blowing 送风
空调系统运行 0x02:Cooling 0x02:Cooling 制冷
1 37150 Air conditioner status RO U16 1 NA N/A
状态 0x03:Warming 0x03:Warming 加热
0x04:Arefaction 0x04:Arefaction除湿
0xFFFF: Unsupport 0xFFFF: Unsupport
盘管温度(出风
2 37151 Coil temperature RO U16 1 10 ℃
温度)
BMS2充电最
3 39002 Max BMS2 Charge Current RO U16 1 1 A
大电流
BMS2低位故
5 39004 BMS2 Error Code Low RO U16 1 N/A N/A
障代码
BMS2电池剩
6 39005 BMS2 SOC RO U16 1 1 %
余电量百分比
BMS2电池健
7 39006 BMS2 SOH RO U16 1 1 %
康度
BMS2电池节
8 39007 BMS2 Battery Strings RO U16 1 N/A N/A
数
BMS2低位警
9 39008 BMS2 Warning Code Low RO U16 1 N/A N/A
告代码
BMS2高位故
11 39010 BMS2 Error Code High RO U16 1 N/A N/A
障代码
BMS2高位警
12 39011 BMS2 Warning Code High RO U16 1 N/A N/A
告代码
BMS2软件版
13 39012 BMS2 Software Version RO U16 1 1 N/A
本
电池组2固件
14 39013 Battery2 Hardware Version RO U16 1 1 N/A
版本
LG电池故障数
4 39502 LG Fault Data analyze Flag RO U16 1 1 N/A
据解析标志
BMS1电池状
1 39503 BMS1 Battery state RO U16 1 1 N/A
态
BMS1 DC
2 39504 BMS1 DC Bus voltage RO U16 1 10 V
BUS电压
BMS1 实时功
3 39505 BMS1 Real-time power RO S16 1 1 W
率
BMS1 剩余能
5 39507 BMS1 Energy remaining RO U16 1 1 Wh
量
BMS1 电池电
12 39514 BMS1 Battery voltage (BPI) RO U16 1 10 V
压
BMS1电池电
13 39515 BMS1 Battery current (BPI) RO S16 1 10 A
流
BMS1 DC
16 39518 BMS1 DC Bus current RO S16 1 10 A
BUS电流
BMS1 State of charge BMS1充电状
17 39519 RO U16 1 10 %
(SOC) 态
BMS1健康状
18 39520 BMS1 State of health (SOH) RO U16 1 10 %
态
BMS1 CB状
21 39523 BMS1 CB status RO U16 1 1 N/A
态
BMS2 剩余能
5 39554 BMS2 Energy remaining RO U16 1 1 Wh
量
BMS2 电池电
12 39561 BMS2 Battery voltage (BPI) RO U16 1 10 V
压
BMS2电池电
13 39562 BMS2 Battery current (BPI) RO S16 1 10 A
流
BMS2 CB状
21 39570 BMS2 CB status RO U16 1 1 N/A
态
BMS1 DC/DC
4 39603 BMS1 DC/DC FW version1 RO U16 1 1 N/A
固件版本1
BMS1 DC/DC
5 39604 BMS1 DC/DC FW version2 RO U16 1 1 N/A
固件版本2
BMS1 固件版
6 39605 BMS1 FW version RO U32 2 1 N/A
本
BMS1 逆变器
8 39607 BMS1 Inverter type RO U16 1 1 N/A
类型
BMS1 标称能
9 39608 BMS1 Nameplate energy RO U16 1 1 Wh
量
BMS2 Protocol version BMS2协议版
1 39630 RO U16 1 1 N/A
number 本号
BMS2电池SN
2 39631 BMS2 Battery serial number RO U32 2 1 N/A
号
BMS2 DC/DC
4 39633 BMS2 DC/DC FW version1 RO U16 1 1 N/A
固件版本1
BMS2 DC/DC
5 39634 BMS2 DC/DC FW version2 RO U16 1 1 N/A
固件版本2
BMS2 固件版
6 39635 BMS2 FW version RO U32 2 1 N/A
本
BMS2 逆变器
8 39637 BMS2 Inverter type RO U16 1 1 N/A
类型
BMS2标称能
9 39638 BMS2 Nameplate energy RO U16 1 1 Wh
量
BMS1故障0计
1 39660 BMS1 Fault 0 Count RO U16 1 1 N/A
数
BMS1故障0
4 39663 BMS1 Fault 0 ID RO U16 1 1 N/A
ID
BMS1故障1计
11 39670 BMS1 Fault 1 Count RO U16 1 1 N/A
数
BMS1故障1
14 39673 BMS1 Fault 1 ID RO U16 1 1 N/A
ID
BMS1故障2计
21 39680 BMS1 Fault 2 Count RO U16 1 1 N/A
数
BMS1故障2
24 39683 BMS1 Fault 2 ID RO U16 1 1 N/A
ID
BMS1故障
BMS1 Fault 2 BMS internal
30 39689 2BMS内部检 RO U16 1 1 N/A
check
查
BMS1故障3计
31 39690 BMS1 Fault 3 Count RO U16 1 1 N/A
数
BMS1故障3
34 39693 BMS1 Fault 3 ID RO U16 1 1 N/A
ID
BMS1 Fault 3 Battery BMS1故障3电
35 39694 RO U16 1 100 V
internal voltage 池内部电压
BMS1故障4计
41 39700 BMS1 Fault 4 Count RO U16 1 1 N/A
数
BMS1故障4
44 39703 BMS1 Fault 4 ID RO U16 1 1 N/A
ID
BMS1故障5计
51 39710 BMS1 Fault 5 Count RO U16 1 1 N/A
数
BMS1故障5
54 39713 BMS1 Fault 5 ID RO U16 1 1 N/A
ID
BMS1故障
BMS1 Fault 5 BMS internal
60 39719 5BMS内部检 RO U16 1 1 N/A
check
查
BMS1故障6计
61 39720 BMS1 Fault 6 Count RO U16 1 1 N/A
数
BMS1故障6
64 39723 BMS1 Fault 6 ID RO U16 1 1 N/A
ID
BMS1故障7计
71 39730 BMS1 Fault 7 Count RO U16 1 1 N/A
数
BMS1故障7
74 39733 BMS1 Fault 7 ID RO U16 1 1 N/A
ID
BMS1 Fault 7 Battery BMS1故障7电
75 39734 RO U16 1 100 V
internal voltage 池内部电压
BMS2故障0计
1 39760 BMS2 Fault 0 Count RO U16 1 1 N/A
数
BMS2故障0
4 39763 BMS2 Fault 0 ID RO U16 1 1 N/A
ID
BMS2故障1计
11 39770 BMS2 Fault 1 Count RO U16 1 1 N/A
数
BMS2故障1
14 39773 BMS2 Fault 1 ID RO U16 1 1 N/A
ID
BMS2故障2计
21 39780 BMS2 Fault 2 Count RO U16 1 1 N/A
数
BMS2故障2
24 39783 BMS2 Fault 2 ID RO U16 1 1 N/A
ID
BMS2故障
BMS2 Fault 2 BMS internal
30 39789 2BMS内部检 RO U16 1 1 N/A
check
查
BMS2故障3计
31 39790 BMS2 Fault 3 Count RO U16 1 1 N/A
数
BMS2故障3
34 39793 BMS2 Fault 3 ID RO U16 1 1 N/A
ID
BMS2 Fault 3 Battery BMS2故障3电
35 39794 RO U16 1 100 V
internal voltage 池内部电压
BMS2故障4计
41 39800 BMS2 Fault 4 Count RO U16 1 1 N/A
数
BMS2故障4
44 39803 BMS2 Fault 4 ID RO U16 1 1 N/A
ID
BMS2故障5计
51 39810 BMS2 Fault 5 Count RO U16 1 1 N/A
数
BMS2故障5
54 39813 BMS2 Fault 5 ID RO U16 1 1 N/A
ID
BMS2故障
BMS2 Fault 5 BMS internal
60 39819 5BMS内部检 RO U16 1 1 N/A
check
查
BMS2故障6计
61 39820 BMS2 Fault 6 Count RO U16 1 1 N/A
数
BMS2故障6
64 39823 BMS2 Fault 6 ID RO U16 1 1 N/A
ID
BMS2故障7计
71 39830 BMS2 Fault 7 Count RO U16 1 1 N/A
数
BMS2故障7
74 39833 BMS2 Fault 7 ID RO U16 1 1 N/A
ID
BMS2 Fault 7 Battery BMS2故障7电
75 39834 RO U16 1 100 V
internal voltage 池内部电压
Maximum Discharging
3 39872 最大放电电流 RO U16 1 10 A
current
4 39873 Batttery Voltage 电池电压 RO U16 1 10 V
5 39874 Batttery Current 电池电流 RO S16 1 10 A
6 39875 Batttery Temperature 电池温度 RO U16 1 10 °C
电池软件版本
23 39892 BMS SW Version RO U16 1 1 N/A
号
24 39893 Battery series 电池系列 RO U16 1 1 N/A
电池剩余电量
29 39898 SOC RO U16 1 1 % Capacity of BAT
百分比
EMS Power
1 42000 能量管理模式 RW U16 1 N/A N/A N
Mode
For BTC/ETC BTC/ETC使用
能量管理功率
2 42001 EMS Power Set RW U32 2 N/A N/A N
设置
0:Disable 1:Enable 0:禁止 1:使能
Feed Power
3 42003 防逆流开关 RW U16 1 N/A N/A [0,1] Y Used together with 和寄存器42004一起使
Enable
register 42004 用,BTC/ETC使用
as FeedPowerEnable is
set as 1, then use this
register to set the max 将防逆流开关设置为 1,
export power allowed,For 然后使用该寄存器设置
BTC/ETC 允许的最大输出功率 ,
Feed Power [-
防逆流允许并 If the maximum AC power BTC/ETC使用
4 42004 Allowable On RW S32 2 N/A W 50000,5 Y
网功率 of the energy storage 储能机单机最大AC功率
Grid Power 0000]
machine is greater than 大于30K或并机时,防逆
30K or when the machine 流功率设置值使用该寄
is combined, the anti- 存器
counter-current power is
set using this register
R Phase Feed [-
6 42007 Power R相防逆流功率 RW S32 2 N/A W 20000,2 Y
Parameter 0000] For BTC/ETC BTC/ETC使用
S Phase Feed [-
7 42009 Power S相防逆流功率 RW S32 2 N/A W 20000,2 Y
Parameter 0000]
T Phase Feed [-
8 42011 Power T相防逆流功率 RW S32 2 N/A W 20000,2 Y
Parameter 0000]
ETC Parameter
Config Remote
Communication Loss
配置远程通讯异常时间
Remote Comm 远程通讯异常 [0,65536 Time
2 42101 RW U16 1 1 S Y 0:禁止远程通讯异常检
Loss Time 时间 ] 0: Disable Remote
测功能
communication loss
detection feature
ETC Parameter
Config installation of STS
module 配置STS模块是否安装
STS Module
1 42200 STS模块安装 RW U16 1 1 N/A [0,1] Y 0:STS module not 0:STS模块未安装
Installed
installed 1:STS module 1:STS模式安装
installed
Flash
#Address English Name Chinese Name #R/W #Type #Size #SF #Units Range Note(English) Note(Chinese)
Save
Com Setting
默认值为247。如果多
The deFault is 247. if multiple
台逆变器连接在同一个
inverters are connected to the
控制器上,每台逆变器
12 45127 Modbus Address Modbus地址 RW U16 1 1 N/A [0,247] Y same controller, addr of each
的地址必须不同,且任
inverter must be different and 247
何一台逆变器不能使用
should not be used for any inverter
247
当值在1到5之间
When the value is between 1 and
时,1:9600; 2:19200;
5, 1:9600; 2:19200; 3:38400;
[1,5]||[9600,11520 3:38400; 4:57600;
14 45132 485 Modbus Baudrate 485 Modbus波特率 RW U32 2 1 N/A Y 4:57600; 5:115200
0] 5:115200
if set wrong, EMS communicaiton
若果设置错误,则EMS
fails
通讯失败
“0”固德威 “1”
17 45153 Modbus Protocol Type modbus协议类型 RW STR 1 1 N/A Y “0”goodwe “1” sunspec
SUNSPEC
Function Setting
1 45200 RTC Setting 设备RTC时间 RW U16 1 1 N/A [13,99]-[1,12] N High Byte:Year/Low Byte:Month 高字节:年/低字节:月
2 45201 RTC Setting 设备RTC时间 RW U16 1 1 N/A [1,31]-[0,23] N High Byte:Day/Low Byte:Hour 高字节:日/低字节:时
3 45202 RTC Setting 设备RTC时间 RW U16 1 1 N/A [0,59]-[0,59] N High Byte:Minute/Low Byte:Second 高字节:分/低字节:秒
36 45254 Grid Wave Check 电网波形检测 RW U16 1 1 N/A [0,2] Y Default: 0 默认为"0"
Reapid shutdown,to cut Grid
快速关闭,切换电网连
37 45255 Rapid Cut Off 快速切断 RW U16 1 1 N/A N connection, System turn to off-Grid
接系统至离网运行 。
operation.
38 45256 Backup Start Delay backup启动延时 RW U16 1 1 N/A N Default: 1500 (30s) 默认1500(30s)
UPS Standard Voltage 不间断电源标准电压类 0:208V, 1:220V,
39 45257 RW U16 1 N/A N/A [0,3] Y 0:208V, 1:20V, 2:240V, 3:230V
Type 型 2:240V, 3:230V
decrease the load,only can set 70, 降载70%,只能设置70,
45 45263 Derate Rate(VDE) 安规降额 RW U16 1 N/A N/A [0,100] Y
only for German 且仅用于德国
48 45266 High Impedance Mode 高阻抗模式 RW U16 1 N/A N/A Y For weak Grid area 用于弱电区域
only for inverters with AFCI 仅用于带电弧分段保护
53 45271 ARC Self Check 拉弧自检 WO U16 1 N/A 1 [1450] N
function 功能的逆变器
54 45272 ARC Fault Remove 拉弧故障手动清除 WO U16 1 N/A 1 [1290] N
0:Normal mode 1:cancel ISO test 0:常规模式 1:当离网转
57 45275 ISO Check Mode ISO检测模式 RW U16 1 N/A 1 [0,1] Y
when offGrid to onGrid 并网时取消ISO测试
Off Grid To On Grid The delay time when Grid is
58 45276 离网转并网延迟 RW U16 1 N/A sec [10,7200] Y 电网可用时的延时时间
Delay available
如果设置为80%,当离
If set 80%, when offGrid output
网输出电压小于
Off Grid Under Voltage Voltage less than 230*80%=184V,
59 45277 离网输出欠压保护系数 RW U16 1 N/A % [50,90] Y 230*80%=184V,逆变器
Protect Ccoefficient inverter will have the error.DeFault
会发生故障。默认设置
setting is 80%.
为80%。
当离网和电池剩余电量
Battery Mode PV When offGrid and the Battery SOC
60 45278 PV给电池模式充电使能 RW U16 1 1 1 [0,1] Y 过低, PV优先给电池充
Charge Enable is low, PV charge the Battery first.
电
61 45279 DCV Check Coefficient 离网DCV检测系数 RW U16 1 N/A N/A [1,20] Y Default: 1 默认设置为1
仅用于具有微网功能的
Only for MircoGrid Function 逆变器
62 45280 Force MircoGrid Run 微网强制启动充电 RW U16 1 N/A N/A [0,1] Y
inverter 0:常规模式 1:无视电池
DOD,进入微网充电
Over Frequency
49 45448 过频恢复等待时间 RW U16 1 100 s [0,1200] Y
Recovery Waiting Time
Over Frequency
52 45451 过频恢复斜率 RW U16 1 1 N/A [0,1200] Y
Recovery Slope
Frequency Power 频率功率曲线配置寄存
53 45452 RW U16 1 1 N/A [0,65535] Y
Curve Configuration 器
Over Frequency
54 45453 过频降载斜率 RW S16 1 1 ‰/Hz [-1000, 1000] Y
Decrease Load Slope
Over Frequency
55 45454 欠频加载斜率 RW S16 1 1 ‰/Hz [-1000, 1000] Y
Increase Load Slope
Over Frequency
56 45455 过频恢复速率 RW S16 1 1 ‰/Min [-1000, 2000] Y
Recover Rate
57 45456 QU Curve QU曲线 RW U16 1 1 N/A [0,1] Y
83 45482 Fixed Power Factor 固定功率因数 RW U16 1 1 N/A [0,20]||[80,100] Y 80=0.8Pf , 20= -0.8Pf 80=0.8Pf , 20= -0.8Pf
108 45507 Hvrt Start Trip Time 高穿起点跳脱时间 RW U16 1 1 periods [1,65535] Y
109 45508 Hvrt End Trip Time 高穿终点跳脱时间 RW U16 1 1 periods [1,65535] Y
110 45509 Hvrt Trip Limit Voltage 高穿跳脱阈值 RW U16 1 10 V [2300,3000] Y
Under Frequency
116 45515 欠频恢复等待时间 RW U16 1 1 s [0,1200] Y
Recovery Waiting Time
Under Frequency
117 45516 欠频恢复斜率 RW U16 1 1 s [0,1200] Y
Recovery Slope
Under Frequency
118 45517 欠频恢复速率 RW U16 1 1 ‰/Min [-1000, 2000] Y
Power Rate
On Grid Charging
119 45518 并网充电功率斜率 RW U16 1 1 s [0,1200] Y
Power Slope
On Grid Charging 故障条件并网充电功率
120 45519 RW U16 1 1 s [0,1200] Y
Power Slope of Fault 斜率
Under Frequency Stop
121 45520 欠频停止充电频率 RW U16 1 100 Hz [3000,8000] Y
Charging Frequency
Over Frequency Stop
122 45521 过频停止放电频率 RW U16 1 100 Hz [3000,8000] Y
Charging Frequency
Over/Under Frequency
123 45522 过/欠频曲线两段标志 RW U16 1 1 N/A [0,1] Y
Two Step Flag
Frequency Response
32 45557 频率响应分辨率 RW U16 1 100 Hz [1,1000] Y
Resolution Ratio
33 45558 Min Discharge SOC 放电最小剩余电量 RW U16 1 1 % [0,100] Y
34 45559 Max Charge SOC 充电最大剩余电量 RW U16 1 1 % [0,100] Y
35 45560 Discharge Duration 放电持续时间 RW U16 1 1 sec [0,65535] Y
Discharge Max Power
36 45561 放电最大功率偏移量 RW U16 1 1 W 0-4600 Y
Delta
37 45562 Charge Duration 充电持续时间 RW U16 1 1 sec [0,65535] Y
38 45563 Charge Max Power 充电最大功率偏移量 RW U16 1 1 W 0-4600 Y
Battery Power
39 45564 Charge/Discharge 充放电使能 RW U16 1 1 N/A [0,1] Y
Enable
40 45565 Battery Charge Limit 电池充电功率上限 RW U16 1 1 W 0-4600 Y
41 45566 Battery Discharge Limit 电池放电功率上限 RW U16 1 1 W 0-4600 Y
Inverter AC
42 45567 逆变器买卖电上限 RW U16 1 1 W 0-4600 Y
Input/Output Limit
Fixed Q Filter Time 定无功响应滤波时间常
43 45568 RW U16 1 10 s [0,60000] Y
Constant 数
44 45569 uwFrtK_Value 中压低穿无功K值 RW U16 1 N/A N/A 0-10 Y
45 45570 Fixed Q Over\Under 固定无功超前\滞后 RW U16 1 1 N/A [0,1] Y 1:Lead;0:Lag 1:超前;0:滞后
QU curve operation 0:Basic Mode 0:基础模式;1:斜率
46 45571 QU曲线模式 RW U16 1 1 N/A [0,1] Y
mode 1:Slope Mode 模式
%Qmax/1%
47 45572 QU curve Slope1 V1点对应斜率 RW S16 1 10 [-2000,2000] Y
Vn
%Qmax/1%
48 45573 QU curve Slope2 V4点对应斜率 RW S16 1 10 [-2000,2000] Y
Vn
日本安规参数
Output Control Time Japanese safety Parameters
61 45586 出力制御时间设置 RW S16 1 1 min [0,10] Y 0:取消线性增加/减少功
Set 0:Disable 5-10:5min-10min
率 5-10:5min-10min
Output Control Power
62 45587 出力制御功率设置 RW S16 1 1 ‰ [0,1000] Y Japanese safety Parameters 日本安规参数
Set
Number of Standby
63 45588 待机转移次数设置 RW U16 1 1 N/A [0,65535] Y Japanese safety Parameters 日本安规参数
Transfer Set
Recovery Cycle Setting
When the Number of 待机转移次数小于等于
64 45589 RW U16 1 1 periods [0,65535] Y Japanese safety Parameters 日本安规参数
Standby Transfer is 2时的回复周期设置
Less Than 2
Recovery Cycle Setting
When the Number of 待机转移次数等于 3时
65 45590 RW U16 1 1 periods [0,65535] Y Japanese safety Parameters 日本安规参数
Standby Transfer is 的回复周期设置
Less Than 3
Lost Communication
66 45591 通信丢失标志位 RW U16 1 1 N/A [0,65535] Y Japanese safety Parameters 日本安规参数
Flag
Frequency Feedback
频率反馈无功注入标幺
67 45592 Reactive Power RW U16 1 1 0.0001p.u [0,2500] Y Japanese safety Parameters 日本安规参数
值
Infection Standard Unit
Upper limit of the
发电机工作电压范围上
68 45593 generator operating RW U16 1 1 V [80, 280] Y default 280v 默认280v
限
voltage range
Lower limit of the
发电机工作电压范围下
69 45594 generator operating RW U16 1 1 V [80, 280] Y default 180v 默认180v
限
voltage range
Upper limit of the
发电机工作频率范围上
70 45595 generator operating RW U16 1 100 HZ [4000, 6000] Y default 550 默认5500
限
frequency range
Lower limit of the
发电机工作频率范围下
71 45596 generator operating RW U16 1 100 HZ [4000, 6000] Y default 450 默认4500
限
frequency range
72 45597 Delay before load 投载前延时间 RW U16 1 1 S [10, 300] Y default 10s 默认10s
73 45598 Generator safety trip 安规跳脱时间 RW U16 1 1 S [1,65535] Y Generator's Safety Parameter 发电机安规参数
74 45599 reserved 预留 1
75 45600 uwPFUCurveFlag PFU曲线使能 RW U16 1 1 N/A [ 0 1] Y default 0 默认0
77 45602 wPFUCurvePointAPf A点功率因数 RW S16 1 100 N/A [-100 100] Y default 90 默认90
79 45604 wPFUCurvePointBPf B点功率因数 RW S16 1 100 N/A [-100 100] Y default 100 默认100
81 45606 wPFUCurvePointCPf C点功率因数 RW S16 1 100 N/A [-100 100] Y default 100 默认100
82 45607 uwPFUV4Volt V4点电压 RW U16 1 10 V [600 3000] Y default 2484 默认2484
83 45608 wPFUCurvePointDPf D点功率因数 RW S16 1 100 N/A [-100 100] Y default -90 默认-90
85 45610 wPFULockInPower 进入曲线有功功率 RW S16 1 10 %Pn [-1000 1000] Y default 200 默认200
86 45611 wPFULockOutPower 退出曲线有功功率 RW S16 1 10 %Pn [-1000 1000] Y default 100 默认100
Qmax/10
98 45623 QP Curve Slope1 QP曲线P1对应斜率 RW S16 1 10 [-2000,2000] Y
%Pn
Qmax/10
99 45624 QP Curve Slope2 QP曲线P4对应斜率 RW S16 1 10 [-2000,2000] Y
%Pn
100 45625 Int QP Curve Grid Volt QP曲线检入电压 RW U16 1 10 %Vn [500,1500] Y
QU Reference Voltage
45 45695 QU曲线响应时间参数 RW U16 1 10 s [0,60000] Y
Regulation Time
PU Curve OutPut
46 45696 PU曲线响应时间参数 RW U16 1 10 s [0,60000] Y
Regulation Time
cos φ(P) curve cos φ(P)曲线响应时间
47 45697 RW U16 1 10 s [0,60000] Y
response time 参数
PQ Reactive power
48 45698 PQ曲线响应时间参数 RW U16 1 10 s [0,60000] Y
variation filter
Power Frequency Filter
49 45699 频率曲线滤波时间常数 RW U16 1 10 s [0,60000] Y
Time Constant
QU Curve
0:Pn Rated Power 0:Pn 额定功率
1:Ps Apparent Power 1:Ps 视在功率
50 45700 QU curve ref QU曲线功率基准 RW U16 1 1 N/A [0,3] Y
2:Po Current Power 2:Po 当前功率
3:Pm Max Power 3:Pm 最大功率
51 45701 QU Voltage1(0.1%) V1电压值(0.1%) RW U16 1 10 %Vn [0,1400] Y
52 45702 QU Voltage2(0.1%) V2电压值(0.1%) RW U16 1 10 %Vn [0,1400] Y
53 45703 QU Voltage3(0.1%) V3电压值(0.1%) RW U16 1 10 %Vn [0,1400] Y
54 45704 QU Voltage4(0.1%) V4电压值(0.1%) RW U16 1 10 %Vn [0,1400] Y
QU reference voltage
55 45705 QU基准电压值 RW U16 1 10 %Vn [800,1200] Y
value
QU Reference Voltage QU基准电压自动调节
56 45706 RW U16 1 1 N/A [0,1] Y
Autoscale Enable 使能
QU curve response QU曲线响应无功变化
57 45707 RW U16 1 10 %Pn/s [0,65000] Y
slope 斜率
0:OFF 0:关闭
QU curve output
58 45708 QU曲线输出响应方式 RW U16 1 1 N/A [0,2] Y 1:Slope Response 1:斜率响应
regulation mode
2:Low-pass filter Response 2:低通滤波模式响应
QU Enter the curve QU曲线进入条件使能 0:OFF 0:关闭
59 45709 RW U16 1 1 N/A [0,1] Y
condition enabling 开关 1:ON 1:打开
60 45710 reserved 1
61 45711 reserved 1
62 45712 reserved 1
63 45713 reserved 1
Others
Normal condition upper
64 45714 limit of connection 启机并网电压下限 RW U16 1 10 %Vn [150,1000] Y
voltage(0.1%)
Normal condition
65 45715 lowerer limit of 启机并网电压上限 RW U16 1 10 %Vn [800,1400] Y
connection
Fault condition upper
66 45716 重连并网电压下限 RW U16 1 10 %Vn [150,1000] Y
limit of connection
Fault condition lowerer
67 45717 limit of connection 重连并网电压上限 RW U16 1 10 %Vn [800,1400] Y
voltage
68 45718 reserved 2
PU Curve
70 45720 PU Voltage1(0.1%) V1电压值(0.1%) RW U16 1 10 %Vn [0,1400] Y
71 45721 PU Voltage2(0.1%) V2电压值(0.1%) RW U16 1 10 %Vn [0,1400] Y
72 45722 PU Voltage3(0.1%) V3电压值(0.1%) RW U16 1 10 %Vn [0,1400] Y
73 45723 PU Voltage4(0.1%) V4电压值(0.1%) RW U16 1 10 %Vn [0,1400] Y
0:OFF 0:关闭
PU Curve OutPut
74 45724 PU曲线输出响应模式 RW U16 1 1 N/A [0,2] Y 1:Slope Response 1:斜率响应
Regulation Mode
2:Low-pass filter Response 2:低通滤波模式响应
Slope of PU Curve PU曲线输出功率变化速
75 45725 RW U16 1 10 %Pn/s [0,65000] Y
power slope 率
PU Curve operation
76 45726 PU曲线模式 RW U16 1 1 N/A [0,65535] Y
mode
77 45727 reserved 1
78 45728 reserved 4
cosφ P Curve
voltage ofEnter the
83 45733 进入曲线电压(0.1%) RW U16 1 10 %Vn [0,1400] Y
curve (0.1%)
voltage of quit the
84 45734 退出曲线电压(0.1%) RW U16 1 10 %Vn [0,1400] Y
curve(0.1%)
cos φ(P) curve cosφ(P)曲线输出响应
85 45735 RW U16 1 10 %Pn/s [0,65000] Y
response Slope 斜率
0:OFF 0:关闭
cos φ(P) curve cosφ(P)曲线响应时间
86 45736 RW U16 1 1 N/A [0,2] Y 1:Slope Response 1:斜率响应
response Model 方式
2:Low-pass filter Response 2:低通滤波模式响应
[-1000,-800]
87 45737 cos φ A(pf,0.001) A点cos φ值(pf,0.001) RW S16 1 1000 N/A Y
[800,1000]
[-1000,-800]
88 45738 cos φ B(pf,0.001) B点cos φ值(pf,0.001) RW S16 1 1000 N/A Y
[800,1000]
[-1000,-800]
89 45739 cos φ C(pf,0.001) C点cos φ值(pf,0.001) RW S16 1 1000 N/A Y
[800,1000]
[-1000,-800]
90 45740 cos φ D(pf,0.001) D点cos φ值(pf,0.001) RW S16 1 1000 N/A Y
[800,1000]
[-1000,-800]
92 45742 cos φ E(pf,0.001) E点cos φ值(pf,0.001) RW S16 1 1000 N/A Y
[800,1000]
二阶欠频穿越频率点
5 45905 FRT UF2 RW U16 1 100 Hz [4500,6000] Y
_UF2
6 45906 FRT UT2 二阶欠频穿越时间 _UT2 RW U32 2 1 ms [20,7200000] Y
三阶欠频穿越频率点
8 45908 FRT UF3 RW U16 1 100 Hz [4500,6000] Y
_UF3
一阶过频穿越频率点
11 45911 FRT OF1 RW U16 1 100 Hz [5000,6500] Y
_OF1
一阶过频穿越时间
12 45912 FRT OT1 RW U32 2 1 ms [20,7200000] Y
_OT1
二阶过频穿越频率点
14 45914 FRT OF2 RW U16 1 100 Hz [5000,6500] Y
_OF2
二阶过频穿越时间
15 45915 FRT OT2 RW U32 2 1 ms [20,7200000] Y
_OT2
三阶过频穿越频率点
17 45917 FRT OF3 RW U16 1 100 Hz [5000,6500] Y
_OF3
三阶过频穿越时间
18 45918 FRT OT3 RW U32 2 1 ms [20,7200000] Y
_OT3
Optional Function
4 46903 External fan selection 外部风扇选配 WO U16 1 N/A 1 [0,1] Y
1: Correct connection 2:
Connection reserved (CT) 1:连接正确 2:连接保留
4: Incorrect connection 8: Wrong (CT)
phase for CT and voltage sampling 4:连接不正确 8:CT和
0: Not detected 电压采样同时错相 0:未
2 47001 Meter Check Value 电表检测结果 RO U16 1 N/A N/A [0, 60000] N
For example: 0X0124 means R 检测
phase connection is incorrect, the 例如:0X0124就是R相
T phase connection is retained, 连接不正确,T相连接
and the S phase connection is 保留,S相连接正确
correct.
数据发送到云或 EMS的
Time interval for data send to cloud
7 47006 Data Send Interval 数据传输间隔 RW U16 1 N/A *5s [0,256] Y 时间间隔,默认为1分
or EMS,deFault is 1 minute.
钟
DRED0:0x00FF
DRED1:0x0001
DRED0:0x00FF DRED1:0x0001 DRED2:0x0002
DRED2:0x0002 DRED3:0x0004 DRED3:0x0004
DRED4:0x0008 DRED5:0x0010 DRED4:0x0008
8 47007 DRED command 命令响应设备指令 RW U16 1 N/A N/A [0,255] N DRED6:0x0020 DRED7:0x0040 DRED5:0x0010
DRED8:0x0080 DRED6:0x0020
Only for Australia, Refer to Table DRED7:0x0040
8-22 DRED8:0x0080
仅用于澳大利亚,见表8-
22
16 47515 Start Time_1 启动时间_1 RW U16 1 N/A N/A [0,23]-[0,59] Y hh:mm hh:mm
20 47519 Start Time_2 启动时间_2 RW U16 1 N/A N/A [0,23]-[0,59] Y hh:mm hh:mm
24 47523 Start Time_3 启动时间_3 RW U16 1 N/A N/A [0,23]-[0,59] Y hh:mm hh:mm
28 47527 Start Time_4 启动时间_4 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
"设置SOC水平来启动/
To set the SOC Level to start/stop
停止电池强制充电 。
Battery force charge.
(这不是BMS的指令,
(this is not the command from
而是对逆变器侧的保护
BMS, but the protection on inverter
。例如,
side. Eg. StartchgSOC (47531) is
StartchgSOC(47531)
set as 5%, but the Battery
设置为5%,但电池
BMSgives a force charge signal at
BMS在SOC为6%时发
SOC 6%, then Battery will start
出强制充电信号,那么
32 47531 Start Charge SOC 强充起始剩余电量 RW U16 1 10 % Y force charge at 6% SOC; if
电池将在SOC为6%时
BMSdoes not send force charge
开始强制充电;如果
command at 5% SOC, then Battery
BMS没有在SOC为5%
will still start force charge at 5%
时发出强制充电指令 ,
SOC. )
那么电池仍将在SOC为
Note: the deFault setting is 5%
5%时开始强制充电。)
SOC to start and 10% to stop.
注意:默认设置是SOC
force charge power is 1000W from
为5%时开始,10%停
PV or Grid as well.
止。强行充电的功率是
1000W,来自光伏或电
33 47532 Stop Charge SOC 强充停止剩余电量 RW U16 1 10 % Y
to clear all economical mode 清除所有的经济模式设
清除电池时间设置使能
34 47533 Clear ECO Time WO U16 1 N/A N/A N settings (47515~47530), enter 置(47515~47530),进
位
Self-Use Mode 入自发自用模式化
40 47539 Wifi Reset 复位wifi模块 WO U16 1 N/A N/A [0,1] N
42 47541 Wifi Reload wifi模块恢复出厂 WO U16 1 N/A N/A [0,1] N
47 47547 Start Time_1 启动时间_1 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
[-
0xFF:Battery power percentage 0xFF:电池功率百分比
1/NA/ 100,100]/NA/[0,1
%/N/A/KW/K 0xFE:N/A 0xFE:N/A
50 47550 Parameter1_1 参数1_1 RW U16 1 100/1 0000]/[0,50000]/[ Y
W/N/A/%/‰ 0xFD:Rated Power 0xFD:额定功率
00/1 0,100]/[-
0xF9:Battery power permillage 0xF9:电池功率千分比
1000,1000]
53 47553 Start Time_2 启动时间_2 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
[-
0xFF:Battery power percentage 0xFF:电池功率百分比
1/NA/ 100,100]/NA/[0,1
%/N/A/KW/K 0xFE:N/A 0xFE:N/A
56 47556 Parameter2_1 参数2_1 RW U16 1 100/1 0000]/[0,50000]/[ Y
W/N/A/%/‰ 0xFD:Rated Power 0xFD:额定功率
00/1 0,100]/[-
0xF9:Battery power permillage 0xF9:电池功率千分比
1000,1000]
59 47559 Start Time_3 启动时间_3 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
65 47565 Start Time_4 启动时间_4 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
[-
0xFF:Battery power percentage 0xFF:电池功率百分比
1/NA/ 100,100]/NA/[0,1
%/N/A/KW/K 0xFE:N/A 0xFE:N/A
68 47568 Parameter4_1 参数4_1 RW U16 1 100/1 0000]/[0,50000]/[ Y
W/N/A/%/‰ 0xFD:Rated Power 0xFD:额定功率
00/1 0,100]/[-
0xF9:Battery power permillage 0xF9:电池功率千分比
1000,1000]
71 47571 Start Time_5 启动时间_5 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
77 47577 Start Time_6 启动时间_6 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
[-
0xFF:Battery power percentage 0xFF:电池功率百分比
1/NA/ 100,100]/NA/[0,1
%/N/A/KW/K 0xFE:N/A 0xFE:N/A
80 47580 Parameter6_1 参数6_1 RW U16 1 100/1 0000]/[0,50000]/[ Y
W/N/A/%/‰ 0xFD:Rated Power 0xFD:额定功率
00/1 0,100]/[-
0xF9:Battery power permillage 0xF9:电池功率千分比
1000,1000]
83 47583 Start Time_7 启动时间_7 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
89 47589 Start Time_8 启动时间_8 RW U16 1 N/A N/A [0,23],[0,59] Y hh:mm hh:mm
[-
1/NA/
%/N/A/KW/K 100,100]/NA/[0,1 0xFC:Peak shaving power limit 0xFC:削峰功率限制
92 47592 Parameter8_1 参数8_1 RW U16 1 100/1 Y
W/N/A/‰ 0000]/[0,50000]/[ 0xFA:Limit permillage 0xFA:限制千分比
00/1
0,1000]
105 47605 Backup Mode Enable backup模式使能 RW U16 1 N/A N/A 1Enable Y
Max Charge Power 来自电网的最大充电功
106 47606 RW U16 1 N/A ‰ [0,1000] Y
from Gird 率
107 47607 Reserved 预留 RW U32 2 N/A N/A N
Smart Charging Mode
108 47609 智能充电模式使能 RW U16 1 N/A N/A 1Enable Y
Enable
109 47610 Reserved 预留 RW U32 2 N/A N/A N
110 47612 ECO Mode Enable 经济模式使能 RW U16 1 N/A N/A Y
111 47613 PV sell first PV卖电优先 RW U16 1 N/A N/A Y
112 47614 Bat FeedPower offset 耦合机电池防逆流偏移 RW U16 1 1 W Y
113 47615 Battery Current Coff 电池电流系数 RW U16 1 1 % [0,100] Y
Parallel Strong Charge
并簇强充可调功率千分
113 47616 Power RW U16 1 1 ‰ [0,1000] Y
比
permillage
15 47618 Battery2 Protocol 电池2协议 RW U16 1 N/A N/A [0,511] Y Refer to 8-33 见表8-33
Feed Power Start
115 47619 防逆流起始时间1 RW U32 2 N/A S N
Time_1
116 47621 Feed Power limit_1 防逆流限值1 RW S32 2 N/A W N
117 47623 Feed Power Period_1 防逆流持续时间1 RW U16 1 N/A S N
Feed Power Start
118 47624 防逆流起始时间2 RW U32 2 N/A S N
Time_2
119 47626 Feed Power limit_2 防逆流限值2 RW S32 2 N/A W N
120 47628 Feed Power Period_2 防逆流持续时间2 RW U16 1 N/A S N
Feed Power Start
121 47629 防逆流起始时间3 RW U32 2 N/A S N
Time_3
122 47631 Feed Power limit_3 防逆流限值3 RW S32 2 N/A W N
123 47633 Feed Power Period_3 防逆流持续时间3 RW U16 1 N/A S N
Feed Power Start
124 47634 防逆流起始时间4 RW U32 2 N/A S N
Time_4
125 47636 Feed Power limit_4 防逆流限值4 RW S32 2 N/A W N
126 47638 Feed Power Period_4 防逆流持续时间4 RW U16 1 N/A S N
Feed Power Start
127 47639 防逆流起始时间5 RW U32 2 N/A S N
Time_5
128 47641 Feed Power limit_5 防逆流限值5 RW S32 2 N/A W N
129 47643 Feed Power Period_5 防逆流持续时间5 RW U16 1 N/A S N
Feed Power Start
130 47644 防逆流起始时间6 RW U32 2 N/A S N
Time_6
131 47646 Feed Power limit_6 防逆流限值6 RW S32 2 N/A W N
132 47648 Feed Power Period_6 防逆流持续时间6 RW U16 1 N/A S N
Feed Power Start
133 47649 防逆流起始时间7 RW U32 2 N/A S N
Time_7
134 47651 Feed Power limit_7 防逆流限值7 RW S32 2 N/A W N
135 47653 Feed Power Period_7 防逆流持续时间7 RW U16 1 N/A S N
Feed Power Start
136 47654 防逆流起始时间8 RW U32 2 N/A S N
Time_8
137 47656 Feed Power limit_8 防逆流限值8 RW S32 2 N/A W N
138 47658 Feed Power Period_8 防逆流持续时间8 RW U16 1 N/A S N
Feed Power Start
139 47659 防逆流起始时间9 RW U32 2 N/A S N
Time_9
140 47661 Feed Power limit_9 防逆流限值9 RW S32 2 N/A W N
141 47663 Feed Power Period_9 防逆流持续时间9 RW U16 1 N/A S N
Feed Power Start
142 47664 防逆流起始时间 10 RW U32 2 N/A S N
Time_10
143 47666 Feed Power limit_10 防逆流限值10 RW S32 2 N/A W N
144 47668 Feed Power Period_10 防逆流持续时间 10 RW U16 1 N/A S N
Feed Power Start
145 47669 防逆流起始时间 11 RW U32 2 N/A S N
Time_11
146 47671 Feed Power limit_11 防逆流限值11 RW S32 2 N/A W N
147 47673 Feed Power Period_11 防逆流持续时间 11 RW U16 1 N/A S N
Feed Power Start
148 47674 防逆流起始时间 12 RW U32 2 N/A S N
Time_12
149 47676 Feed Power limit_12 防逆流限值12 RW S32 2 N/A W N
150 47678 Feed Power Period_12 防逆流持续时间 12 RW U16 1 N/A S N
Feed Power Start
151 47679 防逆流起始时间 13 RW U32 2 N/A S N
Time_13
152 47681 Feed Power limit_13 防逆流限值13 RW S32 2 N/A W N
153 47683 Feed Power Period_13 防逆流持续时间 13 RW U16 1 N/A S N
Feed Power Start
154 47684 防逆流起始时间 14 RW U32 2 N/A S N
Time_14
155 47686 Feed Power limit_14 防逆流限值14 RW S32 2 N/A W N
156 47688 Feed Power Period_14 防逆流持续时间 14 RW U16 1 N/A S N
Feed Power Start
157 47689 防逆流起始时间 15 RW U32 2 N/A S N
Time_15
158 47691 Feed Power limit_15 防逆流限值15 RW S32 2 N/A W N
159 47693 Feed Power Period_15 防逆流持续时间 15 RW U16 1 N/A S N
Feed Power Start
160 47694 防逆流起始时间 16 RW U32 2 N/A S N
Time_16
161 47696 Feed Power limit_16 防逆流限值16 RW S32 2 N/A W N
162 47698 Feed Power Period_16 防逆流持续时间 16 RW U16 1 N/A S N
Feed Power Start
163 47699 防逆流起始时间 17 RW U32 2 N/A S N
Time_17
164 47701 Feed Power limit_17 防逆流限值17 RW S32 2 N/A W N
165 47703 Feed Power Period_17 防逆流持续时间 17 RW U16 1 N/A S N
Feed Power Start
166 47704 防逆流起始时间 18 RW U32 2 N/A S N
Time_18
167 47706 Feed Power limit_18 防逆流限值18 RW S32 2 N/A W N
168 47708 Feed Power Period_18 防逆流持续时间 18 RW U16 1 N/A S N
Feed Power Start
169 47709 防逆流起始时间 19 RW U32 2 N/A S N
Time_19
170 47711 Feed Power limit_19 防逆流限值19 RW S32 2 N/A W N
171 47713 Feed Power Period_19 防逆流持续时间 19 RW U16 1 N/A S N
Feed Power Start
172 47714 防逆流起始时间 20 RW U32 2 N/A S N
Time_20
173 47716 Feed Power limit_20 防逆流限值20 RW S32 2 N/A W N
174 47718 Feed Power Period_20 防逆流持续时间 20 RW U16 1 N/A S N
Feed Power Start
175 47719 防逆流起始时间 21 RW U32 2 N/A S N
Time_21
176 47721 Feed Power limit_21 防逆流限值21 RW S32 2 N/A W N
177 47723 Feed Power Period_21 防逆流持续时间 21 RW U16 1 N/A S N
Feed Power Start
178 47724 防逆流起始时间 22 RW U32 2 N/A S N
Time_22
179 47726 Feed Power limit_22 防逆流限值22 RW S32 2 N/A W N
180 47728 Feed Power Period_22 防逆流持续时间 22 RW U16 1 N/A S N
Feed Power Start
181 47729 防逆流起始时间 23 RW U32 2 N/A S N
Time_23
182 47731 Feed Power limit_23 防逆流限值23 RW S32 2 N/A W N
183 47733 Feed Power Period_23 防逆流持续时间 23 RW U16 1 N/A S N
Feed Power Start
184 47734 防逆流起始时间 24 RW U32 2 N/A S N
Time_24
185 47736 Feed Power limit_24 防逆流限值24 RW S32 2 N/A W N
186 47738 Feed Power Period_24 防逆流持续时间 24 RW U16 1 N/A S N
187 47739 SAPN UP Rate 输入输出上升斜率 RW U16 1 100 %Pn/min Y
188 47740 SAPN Down Rate 输入输出下降斜率 RW U16 1 100 %Pn/min Y
SAPN Feed Power
189 47741 SAPN预设防逆流 RW S32 2 N/A W Y
Preset
Single Battery Paral
190 47743 单电池并机使能位 RW U16 1 N/A N/A Y
Enable
电池汇流排接入模式使
191 47744 Battery Busbar Mode RW U16 1 N/A N/A Y
能位
Generator start mode 0:Automatic,1:Manual, 0:自动,1:手动,
192 47745 发电机启动方式选择 RW U16 1 N/A N/A Y
selection 2(Default): Without Generator 2:未安装发电机,默
193 47746 One-click enable 一键启动使能 RW U16 1 N/A N/A Y 0:Disabled,1:Enabled 0:Disabled,1:
Generator charge to 发电机给电池充电额定 0:Disabled,Other:Rated 0:Disabled,其它:
194 47747 RW U16 1 1 ‰ [0,1000] Y
the battery permillage 功率千分比 charging power permillage 额定充电功率千分比
195 47748 reserved 预留 1
Higher 8 bits are flag bits, 0xFF: 高8位为标志位,
enabled, 0x00: disabled, 0x55: not 0xFF:使能,0x00:
set 未使能,0x55:未设置
bit0-Sunday bit0-Sunday
bit1-Monday bit1-Monday
196 47749 Week1 工作周1 RW U16 1 N/A N/A Y
bit2-Tuesday bit2-Tuesday
bit3-Wednesday bit3-Wednesday
bit4-Thuesday bit4-Thuesday
bit5-Friday bit5-Friday
bit6-Saturday bit6-Saturday
Prohibit the start time
197 47750 禁止工作起始时间 1 RW U16 1 N/A N/A [0,23]-[0,59] Y Start time 时间段1开始时刻
of work1
Prohibit work end
198 47751 禁止工作结束时间 1 RW U16 1 N/A N/A [0,23]-[0,59] Y End time 时间段1结束时刻
time1
高8位为标志位,
高8位为标志位,0xFF:使能,
0xFF:使能,0x00:
0x00:未使能,0x55:未设置
未使能,0x55:未设置
bit0-Sunday
bit0-Sunday
bit1-Monday
bit1-Monday
199 47752 Week2 工作周2 RW U16 1 N/A N/A Y bit2-Tuesday
bit2-Tuesday
bit3-Wednesday
bit3-Wednesday
bit4-Thuesday
bit4-Thuesday
bit5-Friday
bit5-Friday
bit6-Saturday
bit6-Saturday
Prohibit the start time
200 47753 禁止工作起始时间 2 RW U16 1 N/A N/A [0,23]-[0,59] Y Start time 时间段2开始时刻
of work2
Prohibit work end
201 47754 禁止工作结束时间 2 RW U16 1 N/A N/A [0,23]-[0,59] Y End time 时间段2结束时刻
time2
202 47755 reserved 预留 1
SOC 40% by default; The default
open soC or open [20, 90]%、[40, SOC默认40%;电压默
203 47756 开启SOC或开启电压 RW U16 1 1 N/A Y voltage corresponds to the battery
voltage 55]V 认值与电池类型相对应
type
SOC 90% by default; The default
close soC or close [40, 95]%、[45, SOC默认90%;电压默
204 47757 关闭SOC或关闭电压 RW U16 1 1 N/A Y voltage corresponds to the battery
voltage 60]V 认值与电池类型相对应
type
Generator max operating time, 发电机最大运行时间 ,
205 47758 Generator run time 发电机运行时间 RW U16 1 10 h [0, 240] Y
default 8h 默认8h
206 47759 Generator rated power 发电机额定功率 RW U16 1 100 KW Y
207 47760 reserved 预留 1
208 47761 reserved 预留 1
209 47762 reserved 预留 1
SPAN功能开关,1为
210 47763 SAPN Enable SAPN使能标志 RW U16 1 1 N/A [0, 1] Y SPAN, 1:ON,0: OFF
开,0为关
lead_Acid Battery Float
211 47764 铅酸电池浮充电压 RW U16 1 10 v [0,65535] Y
Charge Voltage
lead_Acid Battery
212 47765 铅酸电池恒充电压 RW U16 1 10 v [0,65535] Y
Absorp Charge
lead_Acid Battery
213 47766 铅酸电池均充电压 RW U16 1 10 v [0,65535] Y
Equal Charge Voltage
lead_Acid Battery
214 47767 铅酸电池内阻 RW U16 1 1 mΩ [0,255] Y
InterRes
lead_Acid Battery
215 47768 铅酸电池均充使能 RW U16 1 1 N/A [0,1] Y 0:OFF,1:ON 0:关闭,1:使能
Equal Charge Enable
lead_Acid Battery
216 47769 铅酸电池充电系数 RW U16 1 100 % [0,100] Y
Charge Coefficient
lead_Acid Battery Max Max current of lead-acid battery 铅酸电池浮充阶段最大
217 47770 铅酸电池浮充最大电流 RW U16 1 10 A [0,100] Y
Float Charge Current during floating charge 电流
lead_Acid Battery
218 47771 铅酸电池均充周期 RW U16 1 1 day [0,365] Y
Equal Charge cycle
lead_Acid Battery 铅酸电池进入浮充阶段
219 47772 Current To Float 电流 RW U16 1 10 A [0,255] Y
ChrgSts 闽值
lead_Acid
220 47773 BattleTempcCompens 铅酸电池温度影响系数 RW S16 1 1 ‰ [-200,200] Y
ation
lead_Acid 铅酸电池进入浮充时间
221 47774 RW U16 1 1 S [0,65535) Y
BattleToFloatStsTime 阙值
ARM BMS Passthrough
1 47900 BMS Version BMS版本 RW U16 1 N/A N/A N
2 47901 Battery Strings 电池串2 RW U16 1 N/A N/A N
Max BMS Battery Real-time max charge voltage limit 电池BMS的实时最大充
3 47902 BMS电池最大充电电压 RW U16 1 N/A V N
Charge Voltage for BAT BMS 电电压限制
Max BMS Battery Real-time max charge current limit 电池BMS的实时最大充
4 47903 BMS电池最大充电电流 RW U16 1 N/A A N
Charge Current for BAT BMS 电电流限制
Min BMS Battery Real-time min charge voltage limit 电池BMS的实时最小放
5 47904 BMS电池最小放电电压 RW U16 1 N/A V N
Discharge Voltage for BAT BMS 电电压限制
Min BMS Battery Real-time min charge current limit 电池BMS的实时最小放
6 47905 BMS电池最小放电电流 RW U16 1 N/A A N
Discharge Current for BAT BMS 电电流限制
Real-time BAT voltage(BMS 实时电池电压(电池
7 47906 BMS Battery Voltage BMS电池电压 RW U16 1 N/A V N
Detection) BMS检测)
Real-time BAT current(BMS 实时电池充放电电流
8 47907 BMS Battery Current BMS电池电流 RW U16 1 N/A A N
Detection) (电池BMS检测)
BMS电池剩余电量百分
9 47908 BMS Battery SOC RW U16 1 N/A % N
比
10 47909 BMS Battery SOH BMS电池健康度 RW U16 1 N/A N/A N
BMS Battery
11 47910 BMS电池温度 RW U16 1 10 ℃ N
Temperature
12 47911 BMS Warning Code BMS警告代码 RW U32 2 N/A N/A N
13 47913 BMS Alarm Code BMS报警代码 RW U32 2 N/A N/A N
14 47915 BMS Status BMS状态 RW U16 1 N/A N/A N
BMS Communication
15 47916 BMS通信损失禁用 RW U16 1 N/A N/A N
Loss Disable
BMS Battery String
16 47917 BMS电池串额定电压 RW U16 1 10 V [200,2000] N
Rate Voltage
17 47918 BMS Version2 BMS版本2 RW U16 1 N/A N/A N
18 47919 Battery Strings2 电池串2 RW U16 1 N/A N/A N
Max BMS Battery2 BMS电池2最大充电电
19 47920 RW U16 1 N/A V N
Charge Voltage 压
Max BMS Battery2 BMS电池2最大充电电
20 47921 RW U16 1 N/A A N
Charge Current 流
Min BMS Battery2 BMS电池2最小放电电
21 47922 RW U16 1 N/A V N
Discharge Voltage 压
Min BMS Battery2 BMS电池2最小放电电
22 47923 RW U16 1 N/A A N
Discharge Current 流
23 47924 BMS Battery2 Voltage BMS2电池电压 RW U16 1 N/A V N
24 47925 BMS Battery2 Current BMS2电池电流 RW U16 1 N/A A N
BMS电池2剩余电量百
25 47926 BMS Battery2 SOC RW U16 1 N/A % N
分比
26 47927 BMS Battery2 SOH BMS2电池健康度 RW U16 1 N/A N/A N
BMS Battery2
27 47928 BMS2电池温度 RW U16 1 10 ℃ N
Temperature
28 47929 BMS2 Warning Code BMS2警告代码 RW U32 2 N/A N/A N
29 47931 BMS2 Alarm Code BMS2报警代码 RW U32 2 N/A N/A N
30 47933 BMS2 Status BMS2状态 RW U16 1 N/A N/A N
BMS2 Communication
31 47934 BMS2通信损失禁用 RW U16 1 N/A N/A N
Loss Disable
BMS Battery String2
32 47935 BMS电池串2额定电压 RW U16 1 10 V [200,2000] N
RateVoltage
Max BMS Battery
33 47936 离网放电BMS限流值 RW U16 1 10 A N
Discharge Current
Max BMS Battery
34 47937 Discharge Current 离网放电BMS限流值2 RW U16 1 10 A N
Offline2
English Chinese Flash
#Address #R/W #Type #Size #SF #Units Range Note(English) Note(Chinese)
Name Name Save
Self-check Parameter
Self check
设备自检支持
1 50000 Support RO U16 1 N/A N/A 1:Support Self-check 1:表示支持设备自检
标识
Flag
Self check
设备自检支持
2 50001 Function RO U16 1 N/A N/A First version is 0 起始版本0
功能版本
Version
Bit0:PV1, Bit1:PV2, Bit0:PV1, Bit1:
Bit2:PV3, Bit3:PV4, PV2,
Bit4:PV5, Bit5:PV6, Bit2:PV3, Bit3:
Bit6:PV7, Bit7:PV8, PV4,
Bit8:BAT1, Bit9: Bit4:PV5, Bit5:
Self check 设备自检支持 BAT2, PV6,
3 50002 RO U16 1 N/A N/A
Function1 功能清单1 Bit10:BAT3, Bit11: Bit6:PV7, Bit7:
BAT4, PV8,
Bit12:Grid, Bit13: Bit8:电池1, Bit9:
Backup output, 电池2,
Bit14:Meter configuration Bit10:电池3,
and com, Bit15:CT Bit11:电池4,
Self-check, Bit12:电网, Bit13:
Self check 设备自检支持
4 50003 RO U16 1 N/A N/A Reserved 预留
Function2 功能清单2
Self-check Parameter
Internal
内置风扇1转 Percentage of Max fan 转速标定为最大转速的百
1 50200 fan1 duty RW U16 1 100 % [0,100]
速标定 speed 分比
set
External
外部风扇1转 Percentage of Max fan 转速标定为最大转速的百
2 50201 fan1 duty RW U16 1 100 % [0,100]
速标定 speed 分比
set
Internal
内部风扇1转
3 50202 fan1 speed RO U16 1 1 rad/min [0,65535]
速反馈
feed
External
外部风扇1转
4 50203 fan1 speed RO U16 1 1 rad/min [0,65535]
速反馈
feed
此处预留寄存
4 50204 Reserved 器用于更多的 RO U16 16 1 rad/min [0,65535] Reserved 预留
风扇测试
Table 8-1 Work Mode
Mode Code Description
Wait 0x00 cut off all the connection to Inverter
On-Grid 0x01 PV intputs to Inverter, Inverter outputs to Grid
Off-Grid 0x02 PV inputs to Inverter(1st),Battery inputs to Inverter(2nd),Inverter work as AC source
Fault 0x03 Fault ,fault mode, something is in fault mode
Flash 0x04 Inverter upgrade
Check 0x05 Power on self-check of inverter
DSP communication
Bit28 Communication between ARM and DSP is failure
failure
Bit27 PhaseAngleFailure Phase angle out of range (110°~140°)
Bit26 TBD NA
Bit25 Relay Check Failure Relay check is failure
Bit24 TBD NA
Bit23 Vac Consistency Different value between Master and Slave for grid voltage
Failure
Bit22 Fac Consistency Different value between Master and Slave for grid frequency
Failure
Bit21 TBD NA
Bit20 Back-Up Over Load NA
Bit19 DC Injection High The DC injection to grid is too high
Bit18 Isolation Failure Isolation resistance of PV-plant too low
Bit17 Vac Failure Grid voltage out of tolerable range
Bit16 External Fan Failure The external fan failure
Bit15 PV Over Voltage Pv input voltage is over the tolerable maximum value
Mode
Description
Code
0x00 No Battery, or battery disconnected
0x01 Standby, no discharging or charging
0x02 Discharging
0x03 Charging
Mode
Description
Code
0x00 ON, inverter connects to Load
0x01 OFF, inverter disconnects to Load
Table 8-12 Operation Mode
Mode
Description
Code
0x01 Cut off all the connection to Inverter(wait mode)
0x02 PV intputs to Inverter, Inverter outputs to Grid(online mode)
0x04 PV inputs to Inverter(First),Battery inputs to Inverter(Second),Inverter work as AC source(battery mode)
0x10 Fault, fault mode, something is in fault mode(fault mode)
Auto 0x0001 NA
Self-use Note: PBattery =PInv - Pmeter – Ppv (Discharge/Charge)
The battery power is controlled by the meter power when the meter communication is normal.
【2】 【1】
Charge-PV 0x0002 Xmax High Low Energy In
Control the battery to
Note :PBattery =Xmax + PV (Charge)
keep charging
Xmax is to allow the power to be taken from the grid, and PV power is preferred. When set to 0, only PV power is used.
【3】
Import-AC 0x0004 Xset Low High Energy In
Note :PBattery = Xset + PV (Charge)
The inverter is used as
Xset refers to the power purchased from the power grid. The power purchased from the grid is preferred. If the PV power
a unit for power grid
Export-AC 0x0005 Xset High Energy Out Low
energy scheduling
Note : PBattery = Xset (Discharge)
Xset is to sell power to the grid. PV power is preferred. When PV energy is insufficient, the battery will discharge.PV
Conserve 0x0006 NA
Off-grid reservation
Note : PBattery = PV (Charge)
mode
In on-grid mode, the battery is continuously charged, and only PV power (AC Couple model takes 10% of the rated power
Off-Grid 0x0007 NA
Off-Grid Mode Note : PBattery =Pbackup – Ppv (Charge/Discharge)
Forced off-grid operation (Disconnect from grid)
Note:
[1] for low-priority energy sources, when the battery charging power is limited or the rated output power of the inverter is limited, the load shall be
[2] Xmax represents the upper limit of the power control value, and the actual power will be adjusted according to the working condition.
[3] Xset represents the target value of power control, and the actual power must reach the set value.
Table 8-17 CPLD Warning Code
Table 8-21
Code Description Grid connection standards
0x00 Italy ENEL (Un: 230Vac)
0x01 Czech EN50438(CZ) (Un: 230Vac)
0x02 Germany VDE-AR-N 4105(Un: 230Vac)
0x03 Spain RD1699(Un: 230Vac)
0x04 GreeceMainland EN50438(GR) (Un: 230Vac)
0x05 Danmark EN50438(DK)
0x06 Belgium C10/C11(Un: 230Vac)
0x07 Romania (Un: 230Vac)
0x08 G98 G83/2 G59/3 (Un: 230Vac)
0x09 Australia AS/NZS 4777.2
0x0A France VDE0126
0x0B China NB-T
0x0C 60Hz Grid Default CSA
0x0D Poland EN50438
0x0E South Africa (Un: 230Vac)
0x0F AustraliaL AS/NZS 4777.2
0x10 Brazil (Un: 220Vac)
0x11 Thailand MEA MEA
0x12 Thailand PEA PEA
0x13 Mauritius (Un: 230Vac)
0x14 Holland EN50438
0x15 G99 Northern Ireland
0x16 ChinaHigher NB-T
0x17 French 50Hz (Un: 230Vac)
0x18 French 60Hz (Un: 230Vac)
0x19 Australia Ergon AS/NZS 4777.2
0x1A Australia Energex AS/NZS 4777.2
0x1B Holland 16/20A EN50438
0x1C Korea (Un: 220Vac)
0x1D China Station NB-T
0x1E Austria (Un: 230Vac)
0x1F India IEC61727
0x20 50Hz Grid Default Default
0x21 Warehouse Warehouse
0x22 Philippines Philippines
0x23 Ireland EN50438 Ireland
0x24 Taiwan (Un: 230Vac)
0x25 Bulgaria EN50438
0x26 Barbados (Un: 230Vac)
0x27 ChinaHighest NB-T
0x28 G99 reserve G59/3 (Un: 230Vac)
0x29 Sweden EN50438 (Un: 230Vac)
0x2A Chile BISI 4.0 (Un: 220Vac)
0x2B Brazil LV (Un: 220Vac)
0x2C NewZealand AS/NZS 4777.2
0x2D IEEE1547 208Vac IEEE1547 (Un: 120/208Vac)
0x2E IEEE1547 220Vac IEEE1547 (Un: 127/220Vac)
0x2F IEEE1547 240Vac IEEE1547 (Un: 138.6/240Vac)
0x30 60Hz LV Default 60Hz LV Default
0x31 50Hz LV Default 50Hz LV Default
0x32 Australia Western AS/NZS 4777.2
0x33 Australia MicroGrid AS/NZS 4777.2
0x34 JP_50Hz JP_50Hz
0x35 JP_60Hz JP_60Hz
0x36 India Higher IEC61727 (Un: 230Vac))
0x37 DEWA LV DEWA (Un:230Vac)
0x38 DEWA MV DEWA (Un:230Vac)
0x39 Slovakia EN50438(SV) (Un: 230Vac)
0X3A GreenGrid AS/NZS 4777.2
0x3B Hungary (Un: 230Vac)
0x3C SriLanka (Un: 230Vac)
0x3D SpainIslands RD1699 (Un: 230Vac)
0x3E Ergon30K (Un: 230Vac)
0x3F Energe30K (Un: 230Vac)
0x40 IEEE1547_230VAC IEEE1547 (Un: 230/400Vac)
0x41 IEC61727_60Hz IEC61727 (Un: 230Vac)
0x42 Switzerland VDE-AR-N 4105 (Un: 230Vac)
0x43 CEI_016 CEI-016 (Un: 230Vac)
0x44 Australia Horizon AS/NZS 4777.2
0x45 Cyprus (Un: 230Vac)
0x46 Australia SAPN AS/NZS 4777.2
0x47 Australia Ausgrid AS/NZS 4777.2
0x48 Australia Essential AS/NZS 4777.2
0x49 Australia AS/NZS 4777.2
0x4A China Hongkong
0x4B Poland MV
0x4C Holland MV
0x4D Sweden MV
0x4E VDE4110
0x4F Germany
0x50 Spain MV
0x51 Australia Endeavour
0x52 Argentina
0x53 AustralianB
0x54 AustralianC
Table 8-22
DRED0 DRED1 DRED2 DRED3 DRED4
0x00FF 0x0001 0x0002 0x0004 0x0008
Table 8-30
Bit NO Grid detailed fault Description
Bit0 GridZeroLossErr 电网停电/Power outage
Bit1 GridVoltLowErrSt1 电网欠压一级故障/Grid undervoltage first level failure
Bit2 GridVoltLowErrSt2 电网欠压二级故障/Grid undervoltage second level fault
Bit3 GridVoltLowErrSt3 电网欠压三级故障/Grid undervoltage third level fault
Bit4 GridVoltHighErrSt1 电网过压一级故障/Grid overvoltage first level failure
Bit5 GridVoltHighErrSt2 电网过压二级故障/Grid overvoltage second level fault
Bit6 GridVoltHighErrSt3 电网过压三级故障/Grid overvoltage third level fault
Bit7 Grid10minAvgVoltErr 电网平均电压高故障/Grid average voltage high fault
Bit8 GridFreqLowErrSt1 电网欠频一级故障/Grid underfrequency first level failure
Bit9 GridFreqLowErrSt2 电网欠频二级故障/Grid underfrequency second level fault
Bit10 GridIslandFreqLowErr 孤岛保护欠频故障/Islanding protection underfrequency fault
Bit11 GridFreqHighErrSt1 电网过频一级故障/Grid overfrequency first level failure
Bit12 GridFreqHighErrSt2 电网过频二级故障/Grid overfrequency second level fault
Bit13 GridIslandFreqHighErr 孤岛保护过频故障/Islanding protection overfrequency fault
Bit14 GridFreqShiftChkErr 电网频移故障/Grid frequency shift fault
Bit15 GridWaveCheckErr 电网波形检测故障/Grid waveform check fault
Bit16 GridLLVoltErrFlag 电网线电压故障标志/Grid line voltage fault flag
Bit17 GridLvrtErr 电网低电压穿越故障/Grid low voltage ride-through fault
Bit18 GridHvrtErr 电网高电压穿越故障/Grid high voltage ride-through fault
Bit19 GridVoltSampOverErr 电网电压超出采样上限/ Grid voltage exceeds the upper sampling limit
Bit20 GridConnVoltHighErr 电网连接电压高/Grid connection voltage high
Bit21 GridConnVoltLowErr 电网连接电压低/Grid connection voltage low
Bit22 GridConnFreqHighErr 电网连接频率高/Grid connection Frequency high
Bit23 GridConnFreqLowErr 电网连接频率低/Grid connection Frequency low
Bit...
Bit63
Table 8-31
Bit NO Inverter detailed error Description
Bit0 BattLLCHardOCErr LLC硬件过流/LLC hardware overcurrent
Bit1 BattBoostHardOCErr 电池boost硬件过流/Battery boost hardware overcurrent
Bit2 BattBoostSoftOCErr 电池boost软件过流/ Battery boost software overcurrent
Bit3 BattBMSFaultErr 电池BMS故障/Battery BMS fault
Bit4 BattBMSDischgDisErr 电池BMS禁止放电/Battery BMS discharge disable
Bit5 BattCurrRmsOCErr 电池电流有效值过流/Battery current rms overcurrent
Bit6 OffgridBmsCurrLimitErr 离网模式超出BMS限流/Off-grid mode exceeds BMS current limit
Bit7 BusSoftStartFailedErr Bus电压软启动失败/Bus voltage soft start failed
Bit8 BusVoltTooLowErr Bus电压过低/Bus voltage is too low
Bit9 BusSampVoltTooHigh Bus采样电压过高/ Bus voltage is too High
Bit10 InvHardOCErr 逆变硬件过流/Inverter hardware overcurrent
Bit11 InvCurrSoftOCErr 逆变软件过流/Inverter software overcurrent
Bit12 PvBoostHardOCErr PV boost硬件过流/PV boost hardware overcurrent
Bit13 PvBoostSoftOCErr PV boost软件过流/PV boost software overcurrent
Bit14 GridBackflowErr 电网倒灌/Grid backflow
Bit15 OffgridBattVoltLowErr 离网电池电压低/Off-grid mode battery voltage is low
Bit16 OffgridUpsVoltHighErr 离网AC电压过高/Off-grid mode AC voltage is too low
Bit17 OffgridUpsVoltLowErr 离网AC电压过低/ Off-grid mode AC voltage is too high
Bit18 UpsOverLoadErr Backup overload
Bit19 OffGridZeroLossErr 离网过零错误/OffGridZero Error
Bit20 PowerFastRetrackErr 功率快速重追错误/Power fast retrack Error
Bit21 BypassRelaySwErr Backup旁路继电器切换错误/Bypass Relay Switch Error
Bit22 LoadRelaySwErr Backup负载继电器闭合错误/Backup load Relay switch Error
Bit23
Bit...
Bit63
Table 8-32
Bit NO Inverter detailed Description
Bit0 SafetyOverFreqCurveF 进入过频曲线/Over-frequency curve running
Bit1 SafetyUnderFreqCurve 进入欠频曲线/Under frequency curve running
Bit2 SafetyFreqRecoCurve 频率曲线退出恢复中/Frequency curve exiting recovery
Bit3 SafetyPUCurveOVFlag 进入PU过压曲线/PU overvoltage curve running
Bit4 SafetyPUCurveUVFlag 进入PU欠压曲线/PU undervoltage curve running
Bit5 SafetyQUCurveFlag 进入QU曲线/QU curve running
Bit6 SafetyPFCurveFlag 进入PF曲线/PF curve running
Bit7 FixedPFSettingFlag 固定PF已设定/Fixed PF is set
Bit8 FixedQSettingFlag 固定无功已设定/Fixed reactive power is set
Bit9 InvOverTempFlag 机器过温降载/Inverter over-temp. derating curve operation
Bit10 DREDSellPowerLimitFl 澳洲DRED卖电/Australian DRED electricity sale status
Bit11 DREDBuyPowerLimitFl 澳洲DRED买电/Australian DRED purchase status
Bit12 ActivePowerSettingFla 有功功率限制已设定/Active power limit is set
Bit13 GeDratePowerFlag 德国70%降额打开70% derating (Germany) has been opened
Bit14 AutoTestEnableFlag CEI021 selftest running
Bit15 GridVoltSt1DrateFlag 一级电压保护前降载/Inverter first level overvoltage derate
Bit16 ForceOffGridFlag 外部强制离网标志/Force OffGrid Flag
Bit17 ForceStopModeFlag 外部强制停机标志/Force StopMode Flag
Bit18 OffGridMpptChgUpsOff 离网充电关backup输出标志/PV charge,Off backup output Flag
Bit19 SafetyQUCurveOVFlag QU曲线过压状态/QUCurveOverVoltageFlag
Bit20 SafetyQUCurveUVFlag QU曲线欠压状态/QUCurveUnderVoltageFlag
Bit...
Table 8-33
Battery manufacture Battery series Code comments
GoodWe SECU-S/LX S-H/LX F-H 0x122
PYLONTECH Powercube H1/Force H1/Force 0x101
BYD BYD-Box H 0x102
BYD BYD-Box Premium HVS 0x106
BYD BYD-Box Premium HVM/HVL 0x105
LG RESU_HV_Type-R 0x104
OLOID LBS 0x11E
DYNESS Tower 0x11E
Soluna HV BATTERY 0x11E
EMS Use EMS Battery 0x11F Used when there is no direct communication between inverter and battery
Table 8-34
Not set 0x55
0xFF-Enable
ECO mode
0x00-Disable
0xFE-Enable
Dry contact load mode
0x01-Disable
H-byte 0xFD-Enable
Dry contact smart load mode
0x02-Disable
0xFC-Enable
peakshaving function
0x03-Disable
0xFB-Enable
Back-up mode
0x04-Disable
bit0-Sunday
bit1-Monday
bit2-Tuesday
L-byte Day select bit3-Wednesday
bit4-Thuesday
bit5-Friday
bit6-Saturday
const INT8U auchCRCHi[] = {0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40, 0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41,
0x00, 0xC1, 0x81, 0x40, 0x01, 0xC0, 0x80, 0x41, 0x01, 0xC0, 0x80, 0x41, 0x00, 0xC1, 0x81, 0x40
};
const INT8U auchCRCLo[] = { 0x00, 0xC0, 0xC1, 0x01, 0xC3, 0x03, 0x02, 0xC2, 0xC6, 0x06, 0x07, 0xC7, 0x05, 0xC5, 0xC4,
0x04,
0xCC, 0x0C, 0x0D, 0xCD, 0x0F, 0xCF, 0xCE, 0x0E, 0x0A, 0xCA, 0xCB, 0x0B, 0xC9, 0x09, 0x08, 0xC8, 0xD8, 0x18, 0x19, 0xD9,
0x1B, 0xDB, 0xDA, 0x1A, 0x1E, 0xDE, 0xDF, 0x1F, 0xDD, 0x1D, 0x1C, 0xDC, 0x14, 0xD4, 0xD5, 0x15, 0xD7, 0x17, 0x16, 0xD6,
0xD2, 0x12, 0x13, 0xD3, 0x11, 0xD1, 0xD0, 0x10, 0xF0, 0x30, 0x31, 0xF1, 0x33, 0xF3, 0xF2, 0x32, 0x36, 0xF6, 0xF7, 0x37,
0xF5, 0x35, 0x34, 0xF4, 0x3C, 0xFC, 0xFD, 0x3D, 0xFF, 0x3F, 0x3E, 0xFE, 0xFA, 0x3A, 0x3B, 0xFB, 0x39, 0xF9, 0xF8, 0x38,
0x28, 0xE8, 0xE9, 0x29, 0xEB, 0x2B, 0x2A, 0xEA, 0xEE, 0x2E, 0x2F, 0xEF, 0x2D, 0xED, 0xEC, 0x2C, 0xE4, 0x24, 0x25, 0xE5,
0x27, 0xE7, 0xE6, 0x26, 0x22, 0xE2, 0xE3, 0x23, 0xE1, 0x21, 0x20, 0xE0, 0xA0, 0x60, 0x61, 0xA1, 0x63, 0xA3, 0xA2, 0x62,
0x66, 0xA6, 0xA7, 0x67, 0xA5, 0x65, 0x64, 0xA4, 0x6C, 0xAC, 0xAD, 0x6D, 0xAF, 0x6F, 0x6E, 0xAE, 0xAA, 0x6A, 0x6B, 0xAB,
0x69, 0xA9, 0xA8, 0x68,
0x78, 0xB8, 0xB9, 0x79, 0xBB, 0x7B, 0x7A, 0xBA, 0xBE, 0x7E, 0x7F, 0xBF, 0x7D, 0xBD, 0xBC, 0x7C, 0xB4, 0x74, 0x75, 0xB5,
0x77, 0xB7, 0xB6, 0x76, 0x72, 0xB2, 0xB3, 0x73, 0xB1, 0x71, 0x70, 0xB0, 0x50, 0x90, 0x91, 0x51, 0x93, 0x53, 0x52, 0x92,
0x96, 0x56, 0x57, 0x97, 0x55, 0x95, 0x94, 0x54, 0x9C, 0x5C, 0x5D, 0x9D, 0x5F, 0x9F, 0x9E, 0x5E, 0x5A, 0x9A, 0x9B, 0x5B,
0x99, 0x59, 0x58, 0x98, 0x88, 0x48, 0x49, 0x89, 0x4B, 0x8B, 0x8A, 0x4A, 0x4E, 0x8E, 0x8F, 0x4F, 0x8D, 0x4D, 0x4C, 0x8C,
0x44, 0x84, 0x85, 0x45, 0x87, 0x47, 0x46, 0x86, 0x82, 0x42, 0x43, 0x83, 0x41, 0x81, 0x80, 0x40
};