Modbus TCP/IP

Modbus TCP/IP is a communication protocol widely used for connecting industrial electronic
devices. It combines the Modbus protocol with standard TCP/IP networking to enable seamless
communication over Ethernet networks. Here’s a detailed breakdown:

1. Background and Purpose

 Modbus: Originally developed by Modicon (now Schneider Electric) in 1979 for use with
PLCs (Programmable Logic Controllers), it’s a simple, open, and widely adopted
protocol for industrial automation.

 TCP/IP: A suite of communication protocols used for inter-networking devices on the


internet and in local networks.

2. How Modbus TCP/IP Works

Modbus TCP/IP encapsulates Modbus frames within TCP packets, allowing the Modbus data to
be transmitted over standard Ethernet networks. The key components are:

 Master/Client and Slave/Server Relationship: In Modbus TCP/IP, the client (usually a


SCADA system or PLC) initiates communication, and the server (a device like a sensor or
actuator) responds.

 TCP Port: The default port used is 502, reserved for Modbus communication.

 Ethernet Frames: Modbus data is embedded within standard Ethernet frames for
transmission.

 IP Addressing: Each Modbus TCP/IP device has a unique IP address for identification on
the network.

3. Protocol Structure

A typical Modbus TCP/IP message structure consists of:

 MBAP (Modbus Application Protocol) Header:

o Transaction Identifier (2 bytes): Identifies the request-response pair.

o Protocol Identifier (2 bytes): Always set to 0 for Modbus.

o Length Field (2 bytes): Specifies the number of bytes in the message following
this field.

o Unit Identifier (1 byte): Used to identify a specific device on a multi-drop


network, often 0xFF for TCP/IP.

 PDU (Protocol Data Unit):

o Function Code (1 byte): Specifies the operation (e.g., 0x03 for reading holding
registers).

o Data (variable length): Contains parameters such as starting addresses and the
number of registers to read.

4. Function Codes
Common Modbus TCP/IP function codes include:

 0x01: Read Coils (binary outputs)

 0x02: Read Discrete Inputs (binary inputs)

 0x03: Read Holding Registers (data storage)

 0x04: Read Input Registers (analog inputs)

 0x05: Write Single Coil

 0x06: Write Single Register

 0x0F: Write Multiple Coils

 0x10: Write Multiple Registers

Modbus TCP/IP support signalling exceptions to indicate errors, common codes are:

 0x01 :Illegal Function

 0x02 :Illegal Data Address

 0x03 :Illegal Data Value

 0x04 :Slave Device Failure

 0x05 : Acknowledge

5. Communication Example

1. Client Request: A client sends a request to read data from a server, specifying function
code 0x03 (read holding registers) with the starting address and number of registers to
read.

2. Server Response: The server processes the request and returns the data along with any
status information.

6. Advantages of Modbus TCP/IP

 Widely Supported: Compatible with a wide range of industrial devices and systems.

 Standard Networking: Uses the existing TCP/IP stack, making it easy to integrate with
Ethernet-based systems.

 Scalability: Can support multiple connections, allowing many clients to access server
data simultaneously.

7. Modbus TCP/IP vs. Modbus RTU

 Transport Layer: Modbus TCP/IP uses Ethernet (IP-based), while Modbus RTU uses
serial communication (RS-232/RS-485).

 Framing: Modbus TCP/IP includes an MBAP header, whereas Modbus RTU uses a
simpler format with CRC (Cyclic Redundancy Check) for error checking.
 Performance: Modbus TCP/IP generally allows faster data transfer and longer
communication distances compared to Modbus RTU.

8. Applications

 SCADA Systems: For monitoring and controlling industrial processes.

 Building Automation: Connecting HVAC, lighting, and security systems.

 Energy Management: Integrating smart meters and power systems.

9. Security Considerations

While Modbus TCP/IP is straightforward, it lacks built-in security features. It’s recommended to
use:

 Firewalls and VPNs: To protect the network.

 Secure Alternatives: Like Modbus Secure (based on TLS) for encrypted


communication.

10. Implementation Tips

 IP Configuration: Ensure that devices are configured with unique IP addresses and are
reachable within the network.

 Timeouts and Retries: Implement proper handling for timeout and retries to ensure
reliable communication.

 Data Integrity: Verify responses for consistency and error-checking (even though TCP/IP
handles some of this).

Modbus TCP/IP is reliable for industrial use due to its simplicity and the ability to run on
standard Ethernet infrastructure, facilitating modern automation and IoT applications

Modbus TCP/IP: Client/Server Paradigm

Modbus TCP/IP operates on the client/server communication model, a key feature that
distinguishes it from other Modbus variants. Understanding this paradigm is essential for
designing and implementing systems using Modbus over TCP/IP networks.

1. What is the Client/Server Paradigm?

In the client/server model:

 Client:

o Initiates communication.

o Sends requests to the server.

o Asks for specific data or commands the server to perform certain actions.

 Server:
o Waits for requests from the client.

o Processes the request and sends back a response.

o Provides access to data (e.g., sensor readings) or carries out control actions
(e.g., turning on a device).

This paradigm is analogous to how a web browser (client) requests web pages from a web
server.

2. Roles in Modbus TCP/IP

 Client Role:

o Typically a supervisory system like SCADA, an HMI (Human-Machine Interface),


or a PLC.

o It gathers data from multiple servers or sends commands to them.

o Example Request: "Read the holding registers starting at address 100 from a
server device."

 Server Role:

o Devices such as PLCs, sensors, or actuators.

o These devices expose their data (e.g., temperature readings) or allow actions
(e.g., open a valve) upon request.

o Example Response: "Here is the data from holding registers starting at address
100."

3. Communication Workflow

1. Client Initiates Communication:

o The client sends a request to the server using a Modbus function code (e.g., 0x03
to read holding registers).

o The request is encapsulated in a TCP frame and sent to the server's IP address
and port (default: 502).

2. Server Processes the Request:

o The server decodes the request, processes it (e.g., fetches data from memory),
and prepares a response.

3. Server Sends the Response:

o The server sends the response back to the client over the same TCP connection.

o The client processes the response, updating its data or taking action
accordingly.
4. Repeat:

o The client can send multiple requests to the same server or other servers in
sequence.

4. Characteristics of Client/Server Communication in Modbus TCP/IP

 Asynchronous Communication:

o The server does not send unsolicited messages. It only responds when a request
is received from a client.

 Multiple Clients:

o A single Modbus TCP/IP server can handle requests from multiple clients
simultaneously.

o Each client connection is independent, and the server maintains separate


sessions for each.

 Persistent Connection:

o Once established, a TCP connection between a client and server remains open
until explicitly closed, reducing overhead for repetitive communication.

5. Real-World Example

Consider a system where a SCADA application (client) monitors a factory's machines. Each
machine is equipped with a Modbus TCP/IP-enabled controller (server):

 Client (SCADA):

o Periodically sends requests to each machine’s controller.

o Requests might include reading temperatures, pressures, or motor speeds.

 Server (Machine Controller):

o Responds with the requested data.

o Updates machine parameters if the client sends control commands (e.g., "Set
motor speed to 1000 RPM").

6. Benefits of the Client/Server Model in Modbus TCP/IP

 Centralized Control:

o Clients (e.g., SCADA systems) can gather data from multiple servers in one
place, enabling centralized monitoring and control.

 Resource Optimization:
o Servers operate passively, responding only when necessary, optimizing resource
usage on low-power or embedded devices.

 Scalability:

o The client/server model supports multiple clients accessing data from multiple
servers, allowing large-scale, distributed systems.

7. Comparison with Modbus RTU

Feature Modbus TCP/IP Modbus RTU

Communication Type Client/Server Master/Slave

Initiates Requests Client Master

Responds to Requests Server Slave

Multi-Master Support Yes (multiple clients) No

Connection Type Ethernet (TCP/IP) Serial (RS-485/RS-232)

Simultaneous Access Multiple clients to one server Single master to multiple slaves

8. Limitations

 No Push Mechanism:

o Servers cannot initiate communication or send unsolicited data to clients.


Clients must poll servers for updates.

 Latency:

o TCP/IP introduces slight delays compared to the faster Modbus RTU due to
packet encapsulation and transmission overhead.

Conclusion

The client/server paradigm in Modbus TCP/IP provides a robust and flexible framework for
industrial communication over Ethernet. Its ability to support multiple simultaneous client
connections, combined with the reliability of TCP/IP, makes it an ideal choice for modern
automation and IoT systems.