ALABA Substation Setting calculation parameter requirements

1. System Parameters

 Please provide positive-sequence and zero-sequence impedance of the 132kV network,


in maximum and minimum operation mode respectively.
 Please provide short-circuit current calculation values for 132kV grid side.
2. Detailed requirements

2.1 132kV line parameters

Value
Item Parameter 132KV 132kV W/SODO-DU
SHASHEMENE LINE
LINE
Line Parameter Line length (km) 63.230 61.810
must be provided Line Type (OHL or Cable) OHL OHL
Parallel or single single single
Zero Sequence impedance 0.4892+j1.1921 0.4892+j1.1921
R0 + jX0 (Ω/km) (Ω/km) (Ω/km)
Positive Seq. Impedance 0.2247+j0.4229 0.2247+j0.4229
R1 + jX1 (Ω/km) (Ω/km) (Ω/km)
Maximum load current(A) Ask operation Ask operation
Thermal limit (A) of line 388A 388A
Minimum operation Ask operation Ask operation
voltage(kV)
Minimum power factor Ask operation Ask operation
COS(φ)
Zero sequence Mutual impedance length
mutual (km)
impedance of the Mutual impedance range (%) No mutual
line Zero sequence mutual No mutual
(double impedance R0m + jX0m
transmission (Ω/km)
line)
Adjacent shortest Line name 132kV Hawasa_2 132KV
line to Shashemene Line Wolayta_2-
Wolayta_1 LINE
Length of the shortest line 18.00 15.00
(km)
Zero-sequence current 0.4777+j1.1958 0.4777+j1.1958
impedance R0 + jX0 (Ω/km)
Positive Seq. Impedance 0.2132+j0.4265 0.2132+j0.4265
R1 + jX1 (Ω/km)
Thermal limit(A)of line 388A 399
Adjacent longest Line name 132kV No longest line
line Shashemene-
Melka.W yugo line
Length of the line(km) 119.19
zero-sequence current 0.4892+j1.1921
impedance R0 + jX0(Ω/km)
Positive Seq. Impedance 0.2247+j0.4229
R1 + jX1(Ω/km)
Thermal limit(A)of line 388A

2.2 132 kV Short Circuit Current Calculation Values

2.2.1 Short circuit values

Three phase maximum operation mode


RATED SHORT SHORT CIRCUIT
BUS I"K IP (B)
BUS NAME VOLTAGE CIRCUIT
NUMBER (KA)
(KV) MVA (kA) DEG
105003 ALABA 132 1212.99 5.3055 -71.63 11.9228

Single phase maximum operation mode


RATED SHORT SHORT CIRCUIT
BUS I"K IP (B)
BUS NAME VOLTAGE CIRCUIT
NUMBER (KA)
(KV) MVA (kA) DEG
105003 ALABA 132 1991.69 8.7114 -67.81 18.5343

Maximum load ZS/ ZL ration ALABA - SHASHEMENE LINE


Thevenin Z+Ohm) Zs/zl Z-Ohm) Z0 (Ohm) Zs/zl
Impedanc 14.364 0.56601 14.298 3.013

e ZS
Degree 71.625, 71.499 /-73.642
Line 25.37766
Impedanc

e ZL

Maximum load ZS/ ZL ration ALABA - W/SODO-DU LINE


Thevenin Z+Ohm) Zs/zl Z-Ohm) Z0 (Ohm) Zs/zl
Impedanc
e ZS
14.364 0.643946 14.298 3.013

Degree 71.625, 71.499 /-73.642


Line 22.30622
Impedanc

e ZL

Three phase minimum operation mode


RATED SHORT SHORT CIRCUIT
BUS I"K IP (B)
BUS NAME VOLTAGE CIRCUIT
NUMBER (KA)
(KV) MVA (kA) DEG
105003 ALABA 132 1041.11 4.5537 -72.39 10.3551

Single phase minimum operation mode


RATED SHORT SHORT CIRCUIT
BUS I"K IP (B)
BUS NAME VOLTAGE CIRCUIT
NUMBER (KA)
(KV) MVA (kA) DEG
105003 ALABA 132 1339.29 5.8579 -36.57 9.8812

Fault Current Contribution

Alaba Substation Voltage Maximum short- Minimum short-


level(kV circuit circuit
from Fault at ) 1-phase line to 1-phase Line to
fault(A) line fault(A) line
-phase -phase
fault(A) fault(A)
105003 132 8711.4 4605.3 5857.9 3958.1
[ALABA
105009 132 1593.3 1328.8 1279.8 1237.1
[SHASHEMENE
105012 132 1930.0 1598.8 1547.0 1470.8
[WOLAYTA-2
805005 [ALABA 15 874.3 0.00 4089.8 0.0
3WNDTR [ ] ID 1 2954.5 759.4 6599.5 1261.7
WND 2
3WNDTR [ ] Id2 3066.0 930.8
WND 2

Minimum load ZS/ ZL ration ALABA - SHASHEMENE LINE


Thevenin Z+Ohm) Zs/zl Z-Ohm) Z0 (Ohm) Zs/zl
Impedanc 16.736 0.659478 16.613 22.858

e ZS
Degree 72.393 72.232, -21.875
Line 25.37766

Impedance
ZL

Minimum load ZS/ ZL ration ALABA - W/SODO-DU LINE


Thevenin Z+Ohm) Zs/zl Z-Ohm) Z0 (Ohm) Zs/zl

Impedance ZS
14.364 0.643946 14.298 3.013

Degree 71.625, 71.499 -73.642


Line Impedance ZL 22.30622

2.2.2 Equivalent Impedance of power grid


The equivalent impedance should be calculated from power grid to HVS Busbar.
Based capacity SB: 100 MVA
Based voltage UB: 132 kV
Positive-sequence Zero-sequence
Operation mode impedance impedance
(per unit value) (per unit value)
Maximum
0.025988+j0.078237 004870-j0.016590
operation
Minimum
0.025988+j0.078237 0.004870-j0.016590
operation