The TR-PHOTO-W Series detector sensitivity can be programmed in the control panel
software. Sensitivity is continuously monitored and reported to the panel. Point ID
capability allows each detector’s address to be set with rotary, decimal address switches,
providing exact detector location for selective maintenance when chamber contamina-
tion reaches an unacceptable level.
1 [email protected]
DETECTOR SPACING AND APPLICATIONS INTELLIGENT BASES ACCESSORIES
Triga recommends spacing detectors in NOTE: Detectors must be mounted to one of TR-RA100Z: Remote LED annunciator. 3-32 VDC.
compliance with NFPA 72. In low airflow the Intelligent Bases listed below Mounts to a U.S. single-gang electrical box.
applications with smooth ceiling, space TR-B300-6: White, standard flanged
detectors 30 feet (9m). For specific information low-profile mounting base.
regarding detector spacing, placement, and TR-B300-6-IV: Ivory, standard flanged
special applications refer to NFPA 72. low-profile mounting base.
TR-B501-WHITE: White, standard European
INSTALLATION flangeless mounting base.
The TR-PHOTO-W Series plug-in detectors use TR-B501-BL: Black, standard European
a separate base to simplify installation, service, flangeless mounting base.
and maintenance. Installation instructions are TR-B501-IV: Ivory, standard European
shipped with each detector. Mount base (all flangeless mounting base.
base types) on an electrical backbox which is at TR-B200S-WH: White, Intelligent,
least 1.5" (3.81 cm) deep. programmable sounder base.
TR-B200S-IV: Ivory, Intelligent,
NOTE: programmable sounder base.
• Because of the inherent supervision provided TR-B200SR-WH: White, Intelligent sounder
by the SLC loop, end-of-line resistors are not base for retrofit applications.
required. Wiring “T-taps” or branches are TR-B200SR-IV: Ivory, Intelligent sounder
permitted for Style 4 (Class “B”) wiring. base for retrofit applications.
• When using relay or sounder bases, consult the TR-B200S-LF-WH: White, Low Frequency
installation sheet for device limitations between Intelligent, programmable sounder base.
isolator modules and isolator bases. TR-B200S-LF-IV: Ivory, Low Frequency
Intelligent, programmable sounder base.
ORDERING INFORMATION B200SR-LF-WH: White, Low Frequency
TR-PHOTO-W: White, low-profile intelligent Intelligent sounder base for retrofit
photoelectric sensor. applications.
TR-PHOTO-IV: Ivory, low-profile intelligent TR-B200SR-LF-IV: Ivory, Low Frequency
photoelectric sensor. Intelligent sounder base for retrofit
TR-PHOTO-T-W: White, same as the applications.
TR-PHOTO-W, but includes a built-in TR-B224RB-WH: White, plug-in relay base.
135°F (57°C) fixed-temperature thermal TR-B224RB-IV: Ivory, plug-in relay base.
device. TR-B224BI-WH: White, plug-in isolator detector
TR-PHOTO-T-IV: Same as TR-PHOTO- T base.
but in Ivory. TR-B224BI-IV: Ivory, plug-in isolator detector
TR-PHOTO-R-W: White, low-profile base.
intelligent photoelectric sensor, remote
test capable. For use with duct enclosures
TR-PHOTO-R-IV: Ivory, low-profile
intelligent photoelectric sensor, remote
test capable.
[email protected] 2
Technical Specifications
PHYSICAL COMPATIBILITY
Height: 2.0" (51mm) installed in TR-B300-6 base The TR-PHOTO-W series detectors are This document is not
Diameter: 6.2" (156mm) installed in TR-B300-6 compatible with the following Triga Series intended to be used for
base 4.1" (104 mm) installed in TR-B501 base FACPs: installation purposes. We
Weight: 3.4 oz (95 g) • TR-2100R / TR-2100B try to keep our product
• TR-2100ECSR / TR-2100ECSB information up-to date and
ENVIRONMENTAL • TR-R2100R / TR-R2100B accurate. We cannot cover
Operating Temperature range: all specific applications or
Photo: 32°F to 122°F (0°C to 50°C) AGENCY LISTINGS AND APPROVALS anticipate all requirements.
Photo with Thermal: 32°F to 100°F (0°C to 38°C) For exact certification listings for each model, All specifications are
Thermal Ratings: Fixed Temperature Set point: please reference the respective agency Web site. subject to change without
135°F (57°C) UL listed notice.
Sensitivity: UL Applications: 0.5% to 4.0% per FM approved
foot obscuration.
ELECTRICAL RATINGS
Voltage Range: 15 to 32VDC peak
Operating Current @ 24VDC: 200μA (one
communication every 5 seconds with green LED
blink on communication)
Maximum Current: 4.5mA @ 24VDC (one
communication every 5 seconds with amber LED
solid on).
ELV/24-01-21/R0 3