انتقال حرارة الثالث كورس ثاني
انتقال حرارة الثالث كورس ثاني
انتقال حرارة الثالث كورس ثاني
In the preceding course, we considered heat conduction under steady conditions, for which the
temperature of a body at any point does not change with time. This certainly simplified the
analysis, especially when the temperature varied in one direction only, and we were able to
obtain analytical solutions. In this lecture, we consider the variation of temperature with time
as well as position.
To analyze a transient heat-transfer problem, we could proceed by solving the general heat-
conduction equation:
˙
∂2 𝑇 ∂2 𝑇 ∂2 𝑇 𝑞 1 ∂𝑇
+ + + =
∂𝑥 2 ∂𝑦 2 ∂𝑧 2 𝑘 𝛼 ∂𝑡
Salwan Alturki
Heat Transfer Unsteady state conduction
ball changes with time, but it does not change much with
is not even close to being uniform. You can easily verify this
by taking the roast out before it is completely done and cutting it in half. You will see that the
outer parts of the roast are well done while the center part is barely warm. Thus, lumped system
analysis is not applicable in this case.
Salwan Alturki
Heat Transfer Unsteady state conduction
Salwan Alturki
Heat Transfer Unsteady state conduction
Thus, the magnitude of the maximum temperature difference within the body depends strongly
on the ability of a body to conduct heat toward its surface relative to the ability of the
surrounding medium to convect this heat away from the surface. The Biot number is a measure
of the relative magnitudes of these two competing effects.
Example: A steel ball [c = 0.46 kJ/kg · ◦C, k = 35 W/m · ◦C] 5.0 cm in diameter and initially
at a uniform temperature of 450◦C is suddenly placed in a controlled environment in which the
temperature is maintained at 100◦C. The convection heat-transfer coefficient is 10 W/m2 · ◦C.
Calculate the time required for the ball to attain a temperature of 150◦C. (ρsteel= 7800 kg/m3)
Solution:
We anticipate that the lumped-capacity method will apply because of the low value of h and
high value of k. We can check by using Bi:
Lc=D/6=0.05/6=0.0083 m
ℎ𝐿𝑐 (10)(0.0083)
𝐵𝑖 = = = 0.0023 < 0.1
𝑘 (35)
So we can use the equation of LHC system:
𝑇 = 150∘ C 𝜌 = 7800kg/m3
𝑇∞ = 100∘ C ℎ = 10W/m2 ⋅∘ C
𝑇𝑖 = 450∘ C 𝑐 = 460J/kg ⋅∘ C
𝜌𝑐𝑉 (7800)(460)(0.0083)
= = 2990 𝑠
ℎ𝐴𝑠 10
𝜃 = 𝜃𝑖 𝑒 −𝑡/𝜏
𝜃 = 𝑇 − 𝑇∞ = 150 − 100 = 50 °C
𝜃𝑖 = 𝑇𝑖 − 𝑇∞ = 450 − 100 = 350 °C
50 = 350 𝑒 −𝑡/2990
t≈ 5818 𝑠 = 1.62 ℎ
Salwan Alturki
Heat Transfer Unsteady state conduction
Example: An ingot (K=40 W/m.°C) has a cylindrical shape with 10 cm diameter and 30 cm
long passes through a heat treatment furnace .The ingot must reach a temperature of 800 °C
before if comes out of the furnace. The furnace gas is at 1250 °C and ingot initial temperatures
is 90 °C. What is the time with which the ingot should stay in the furnace to attain the required
temperature? The convective surface heat transfer coefficient is 100 W/m 2. °C. Take the
thermal diffusivity of ingot=1.16 m2/sec, (ρ=7800 kg/m3, C=460 J/kg. °C).
Salwan Alturki
Heat Transfer Unsteady state conduction
Salwan Alturki
Heat Exchanger Heat Transfer (II)
The overall heat-transfer coefficient may be based on either the inside or the outside area
of the tube. Accordingly,
Heat Exchanger Heat Transfer (II)
Fouling Factor
The performance of heat exchangers usually deteriorates with time as a result of
accumulation of deposits on heat transfer surfaces. The layer of deposits
represents additional resistance to heat transfer, which is represented by a fouling
factor Rf.
Rf must be included along with the other thermal resistances making up the
overall heat-transfer coefficient, thus For an unfinned shell-and-tube heat
exchanger, it can be expressed as:
Heat Exchanger Heat Transfer (II)
Heat Exchanger Heat Transfer (II)
Heat Exchanger Heat Transfer (II)
We will discuss the two methods used in the analysis of heat exchangers, the log
mean temperature difference (or LMTD) method and the effectiveness–NTU
method.
But first we present some general considerations. Heat exchangers usually
operate for long periods of time with no change in their operating conditions.
Therefore, they can be modelled as steady-flow devices. As such,
- the mass flow rate of each fluid remains constant.
- the fluid properties such as temperature and velocity at any inlet or outlet
remain the same.
- Axial heat conduction along the tube is usually insignificant and can be
considered negligible.
- The specific heat of a fluid, in general, changes with temperature. But, in
a specified temperature range, it can be treated as a constant.
- Finally, the outer surface of the heat exchanger is assumed to be perfectly
insulated, so that there is no heat loss to the surrounding medium, and any
heat transfer occurs between the two fluids only.
Heat Exchanger Heat Transfer (II)
˙
𝑞 = 𝑚𝑐 𝐶𝑝𝑐 (𝑇𝑐,out − 𝑇𝑐,in )
˙
𝑞 = 𝑚ℎ 𝐶𝑝ℎ (𝑇ℎ,in − 𝑇ℎ,out )
Where the subscripts c and h stand for cold and hot fluids, respectively.
The heat transfer rate can be calculated by:
q = 𝑈𝐴𝑠 Δ𝑇lm
Where:
Δ𝑇Im : is called the log mean temperature difference (LMTD).
Δ𝑇1 − Δ𝑇2
Δ𝑇Im =
Δ𝑇
ln ( 1 )
Δ𝑇2
Here ∆T1 and ∆T2 represent the temperature difference between the two fluids at
the two ends (inlet and outlet) of the heat exchanger.
Heat Exchanger Heat Transfer (II)
For specified inlet and outlet temperatures, the log mean temperature difference
for a counter-flow heat exchanger is always greater than that for a parallel-flow
heat exchanger. That is,Δ𝑇Im,CF ˃Δ𝑇Im,PF and thus a smaller surface area (and thus
a smaller heat exchanger) is needed to achieve a specified heat transfer rate in a
counter-flow heat exchanger.
Therefore, it is common practice to use counter-flow arrangements in heat
exchangers.
Heat Exchanger Heat Transfer (II)
Heat Exchanger Heat Transfer (II)
Heat Exchanger Heat Transfer (II)
H.W: It is desired to heat 230 kg/h of water [cp =4.175 kJ/kg. ◦C] from 35 to 93◦C
with oil [cp =2.1 kJ/kg .◦C] having an initial temperature of 175◦C. The mass flow
of oil is also 230 kg/h. Two double-pipe heat exchangers are available:
exchanger 1: U =570 W/m2 · ◦C A=0.47 m2
exchanger 2: U =370 W/m2 · ◦C A=0.94 m2
Which exchanger should be used?
: مالحظة مهمة
When Tc,out > Th,out counter flow must be used
Heat Transfer Heat Exchangers
In the process and power industries, or related activities, many heat exchangers are
purchased as off-the-shelf items, and a selection is made on the basis of cost and
such as the aerospace and electronics industries, a particular design is frequently called for.
warrant, the heat exchanger may be specially designed for the application. Whether the heat
exchanger is selected as an off-the-shelf item or designed especially for the application, the
This is the most important quantity in the selection of a heat exchanger. A heat exchanger
should be capable of transferring heat at the specified rate in order to achieve the desired
ii. Cost
Budgetary limitations usually play an important role in the selection of heat exchangers,
except for some specialized cases where “money is no object.” An off-the-shelf heat
exchanger has a definite cost advantage over those made to order. However, in some cases,
none of the existing heat exchangers will do, and it may be necessary to undertake the
expensive and time-consuming task of designing and manufacturing a heat exchanger from
scratch to suit the needs. This is often the case when the heat exchanger is an integral part
1|Page
Heat Transfer Heat Exchangers
of the overall device to be manufactured. The operation and maintenance costs of the heat
In a heat exchanger, both fluids are usually forced to flow by pumps or fans that consume
electrical power. The annual cost of electricity associated with the operation of the pumps
Where the pumping power is the total electrical power consumed by the motors of the
For example, a heat exchanger that involves a 1-hp pump and a 1/3-hp fan (1 hp = 0.746
kW) operating 8 h a day and 5 days a week will consume 2017 kWh of electricity per year,
Normally, the smaller and the lighter the heat exchanger, the better it is. This is especially
the case in the automotive and aerospace industries, where size and weight requirements
v. Type
The type of heat exchanger to be selected depends primarily on the type of fluids involved,
the size and weight limitations, and the presence of any phase change processes.
2|Page
Heat Transfer Heat Exchangers
vi. Materials
The materials used in the construction of the heat exchanger may be an important
consideration in the selection of heat exchangers. In the case of corrosive fluids, we may
titanium.
3|Page
Heat Transfer Heat Exchangers
HEAT EXCHANGERS
Heat exchangers are devices that used to promote the exchange of heat between two
fluids that are at different temperatures while keeping them from mixing with each other.
Heat exchangers are commonly used in practice in a wide range of applications, from
heating and air-conditioning systems in a household, to chemical processing and power
production in large plants.
Heat exchangers are often given specific names to reflect the specific application for
which they are used. For example, a condenser is a heat exchanger in which one of the
fluids is cooled and condenses as it flows through the heat exchanger.
A boiler is another heat exchanger in which one of the fluids absorbs heat and vaporizes.
A space radiator is a heat exchanger that transfers heat from the hot fluid to the
surrounding space by radiation.
Heat exchangers are typically classified according to flow arrangement and types of
construction.
Either the hot or cold fluid occupying the annular space and the other fluid occupying the
inside of the inner pipe. Heat Exchangers can be classified depending on the basic of the
fluid paths into:
• Parallel flow: Both the hot and cold fluids enter the heat exchanger at the same
• Counter flow: Hot and cold fluids enter the heat exchanger at opposite ends and
1|Page
Heat Transfer Heat Exchangers
Fig: Scheme of flow regimes and associated temperature profiles in a double-pipe heat
exchanger
2. Cross flow: the two fluids usually move perpendicular to each other (mixed and
unmixed).
2|Page
Heat Transfer Heat Exchangers
Another type of heat exchanger, which is specifically designed to realize a large heat
transfer surface area per unit volume. The ratio of the heat transfer surface area of a heat
exchanger to its volume is called the area density (β).
A heat exchanger with β ˃700 m2/m3 (or 200 ft2/ft3) is classified as being compact.
Examples of compact heat exchangers are car radiators (β ≈1000 m 2/m3), glass ceramic
gas turbine heat exchangers (β ≈ 6000m2/m3), and the human lung (β ≈ 20,000 m2/m3 ).
Compact heat exchangers enable us to achieve high heat transfer rates between two fluids
in a small volume, and they are commonly used in applications with strict limitations on
the weight and volume of heat exchangers (see Fig. below).
The large surface area in compact heat exchangers is obtained by attaching closely spaced
thin plate or corrugated fins to the walls separating the two fluids. Compact heat
exchangers are commonly used in gas-to-gas and gas-to-liquid (or liquid-to-gas) heat
exchangers to counteract the low heat transfer coefficient associated with gas flow with
increased surface area. In a car radiator, which is a water-to-air compact heat exchanger,
for example, it is no surprise that fins are attached to the air side of the tube surface.
In compact heat exchangers, the two fluids usually move perpendicular to each other, and
such flow configuration is called cross-flow.
3|Page
Heat Transfer Heat Exchangers
A type of heat exchanger widely used in the chemical-process industries is that of the shell-
and-tube arrangement, One fluid flows on the inside of the tubes, while the other fluid is
forced through the shell and over the outside of the tubes.
4|Page
Heat Transfer Heat Exchangers
Shell-and-tube heat exchangers are further classified according to the number of shell and
tube passes involved. Heat exchangers in which all the tubes make one U-turn in the
shell, for example, are called one-shell-pass and two tube-passes heat exchangers.
Likewise, a heat exchanger that involves two passes in the shell and four passes in the
tubes is called a two-shell-passes and four-tube-passes heat exchanger.
Fig: The schematic of a shell-and-tube heat exchanger (one-shell pass and one
tube pass)
5|Page
Heat Transfer Heat Exchangers
A plate heat exchanger is a unit which transfers heat continuously from one media
to another media without adding energy to the process. The basic concept of a plate
and frame heat exchanger is two liquids flowing on either side of a thin corrugated
metal plate so heat may be easily transferred between the two. (By conduction
across the plate)
6|Page
Heat Transfer Heat Exchangers
The plates are compressed by means of tie bolts between a stationary frame part
(called the head) and a movable frame part (called the follower).
The plate heat exchanger efficiency requires less floor space compared to other
types of heat transfer equipment and is lighter in weight.
Also, plate heat exchangers can grow with increasing demand for heat transfer by
simply mounting more plates. They are well suited for liquid-to-liquid heat
exchange applications, provided that the hot and cold fluid streams are at about the
same pressure.
7|Page
H.W: It is desired to heat 230 kg/h of water [cp =4.175 kJ/kg. ◦C] from 35 to 93◦C
with oil [cp =2.1 kJ/kg .◦C] having an initial temperature of 175◦C. The mass flow
of oil is also 230 kg/h. Two double-pipe heat exchangers are available:
exchanger 1: U =570 W/m2 · ◦C A=0.47 m2
exchanger 2: U =370 W/m2 · ◦C A=0.94 m2
Which exchanger should be used?
Heat Exchanger Heat Transfer (II)
If a heat exchanger other than the double-pipe type is used, the heat transfer is
calculated by using a correction factor applied to the LMTD for a counterflow
double-pipe arrangement with the same hot and cold fluid temperatures. The heat-
transfer equation then takes the form:
q=UA FΔTlm,CF
Where:
F: is the correction factor, which depends on the geometry of the heat exchanger
and the inlet and outlet temperatures of the hot and cold fluid streams.
ΔTlm,CF : is the log mean temperature difference for the case of a counter-flow
heat exchanger with the same inlet and outlet temperatures and is determined
from below:
Δ𝑇1 − Δ𝑇2
Δ𝑇Im,CF =
Δ𝑇
ln ( 1 )
Δ𝑇2
By taking
Values of the correction factor are plotted in Figures below for several different
types of heat exchangers versus two temperature ratios P and R defined as.
and
Where the subscripts 1 and 2 represent the inlet and outlet, respectively. Not that
for a shell-and-tube heat exchanger, T and t represent the shell- and tube-side
temperatures, respectively, as shown in the correction factor charts. It makes no
difference whether the hot or the cold fluid flows through the shell or the tube.
The determination of the correction factor F requires the availability of the inlet
and the outlet temperatures for both the cold and hot fluids.
Remember that:
cen58933_ch13.qxd 9/9/2002 9:57 AM Page 684
684
HEAT TRANSFER
1.0
T1
0.9 t2
Correction factor F
t1
0.8 T2
R = 4.0 3.0 2.0 1.5 1.0 0.8 0.6 0.4 0.2
0.7
0.6 T1 – T2
R = ——–
t2 – t1
0.5 t2 – t1
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 P = ——–
T1 – t1
(a) One-shell pass and 2, 4, 6, etc. (any multiple of 2), tube passes
1.0
T1
0.9
Correction factor F
t2
0.8
R = 4.0 3.0 2.0 1.5 1.0 0.8 0.6 0.4 0.2 t1
0.7
T2
0.6 T1 – T2
R = ——–
t2 – t1
0.5 t2 – t1
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 P = ——–
T1 – t1
(b) Two-shell passes and 4, 8, 12, etc. (any multiple of 4), tube passes
1.0
T1
0.9
Correction factor F
0.8 t1 t2
R = 4.0 3.0 2.0 1.5 1.0 0.8 0.6 0.4 0.2
0.7
0.6 T1 – T2 T2
R = ——–
t2 – t1
0.5 t2 – t1
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 P = ——–
T1 – t1
(c) Single-pass cross-flow with both fluids unmixed
1.0
T1
0.9
Correction factor F
0.8 t1 t2
R = 4.0 3.0 2.0 1.5 1.0 0.8 0.6 0.4 0.2
0.7
FIGURE 13–18 T1 – T2
0.6 T2
Correction factor F charts R = ——–
t2 – t1
for common shell-and-tube and 0.5 t2 – t1
cross-flow heat exchangers (from 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 P = ——–
T1 – t1
Bowman, Mueller, and Nagle, Ref. 2). (d) Single-pass cross-flow with one fluid mixed and the other unmixed
re
ho
try to use other methods to calculate the effectiveness
cen58933_ch13.qxd 9/9/2002 9:57 AM Page 695
695
CHAPTER 13
100 100
=0 =0
ax ax
Cm Cm
80 55
/
80
/
0.2
n
0.25
mi
mi
C
C
Effectiveness ε, %
Effectiveness ε, %
5
0.50 0.71.00
0
0.5
60 0.75 60
1.00
40 40 Shell fluid
Tube Tube
fluid fluid
20 20
Shell fluid
0 0
1 2 3 4 5 1 2 3 4 5
Number of transfer units NTU = AsU/Cmin Number of transfer units NTU = AsU/Cmin
(a) Parallel-flow (b) Counter-flow
100 100
=0 =0
x ax
/C ma / C m
n 0.25 80 in 0.250
80 0.5
m
i
C
m
0.50
C
0.75
Effectiveness ε, %
Effectiveness ε, %
0.75 1.00
60 1.00 60
20 20
Tube fluid
Tube fluid
0 0
1 2 3 4 5 1 2 3 4 5
Number of transfer units NTU = AsU/Cmin Number of transfer units NTU = AsU/Cmin
(c) One-shell pass and 2, 4, 6, … tube passes (d ) Two-shell passes and 4, 8, 12, … tube passes
100 100
,
=0 =0 0.25
d 4
xe
ax mi 0.5
Cm un
5 80
d /C
80 2
0.2 0
n/
0.75
mi
0.5 5
xe
C
1.33
mi
Effectiveness ε, %
0.7 00
Effectiveness ε, %
1
60 1. 60
Cold fluid
40 Hot 40 Mixed
fluid fluid
20 20
Unmixed fluid
0 0
1 2 3 4 5 1 2 3 4 5
Number of transfer units NTU = AsU/Cmin Number of transfer units NTU = AsU/Cmin
(e) Cross-flow with both fluids unmixed ( f ) Cross-flow with one fluid mixed and the
other unmixed
FIGURE 13–26
Effectiveness for heat exchangers (from Kays and London, Ref. 5).
Heat Transfer
(4) A stainless-steel rod (ρ=7817 kg/m3, C=460 J/kg. °C) 6.4 mm in diameter is initially at a
uniform temperature of 150◦C and is suddenly immersed in a liquid at 25◦C with h = 120
W/m2°C. Using the lumped-capacity method of analysis, calculate the time necessary for the
rod temperature to reach 120◦C.
Sol:
Given information:
𝑇 = 120∘ C 𝜌 = 7817 kg/m3
𝑇∞ = 25 °C ℎ = 120W/m2 ⋅∘ C
𝑇𝑖 = 150∘ C 𝑐 = 460J/kg ⋅∘ C
Lc=D/4=0.0064/4=0.0016 m
𝜃 = 𝜃𝑖 𝑒 −𝑡/𝜏
𝜌𝑐𝑉 (7817)(460)(0.0016)
𝜏= = = 47.94 𝑠
ℎ𝐴𝑠 120
𝜃 = 𝜃𝑖 𝑒 −𝑡/𝜏
𝜃 = 𝑇 − 𝑇∞ = 120 − 25 = 95 °C
𝜃𝑖 = 𝑇𝑖 − 𝑇∞ = 150 − 25 = 125 °C
95 = 125 𝑒 −𝑡/47.94
t=13.16 𝑠
(11) A sphere has a thermal diffusivity of 9.5 ×10-7 m2/s, a diameter of 2.5 cm, and a thermal
conductivity of 1.52 W/m.◦C. The sphere is initially at a uniform temperature of 25 ◦C and
is suddenly subjected to a convection environment at 200 ◦C. The convection heat-transfer
coefficient is 110 W/m2◦C. Calculate the temperatures at the center and at a radius of 6.4
mm after a time of 3 min. Ans: To= 179 ◦C , T(6.4)= 181.3◦C
Given information:
k = 1.52 W/m · ◦C
1|Page
Heat Transfer
Ti=25◦C
T∞=200◦C
h = 110 W/m2 · ◦C
t = 3 min = 180 s
r0 = 1.25 cm=0.0125 m
r = 0.064 cm
Then:
To calculate (To):
𝑘 1.52 𝜃0
= = 1.105 = 0.12
ℎ𝑟0 (110)(0.0125) 𝜃𝑖
𝜃0
𝜃0 = ∗ 𝜃𝑖 = 0.12 ∗ (25 − 200) = −21 °𝐶
𝜃𝑖
𝜃0 = To-T∞→To=-21+200=179 °𝐶
To calculate (T):
𝑟
= = From figure ( )
𝑟0
𝜃
𝑘 =
= 𝜃𝑜
ℎ𝑟0
𝜃
𝜃= × 𝜃𝑜 = … … × … … = ℃
𝜃𝑜
𝜃 = 𝑇 − 𝑇∞ → 𝑇 =
2|Page
Heat Transfer
Principles of Convection
We have considered conduction, which is the mechanism of heat transfer through a solid or a
quiescent fluid. We now consider convection, which is the mechanism of heat transfer through
a fluid in the presence of fluid motion.
Conduction and convection are similar in that both mechanisms require the presence of a
material medium. But they are different in that convection requires the presence of fluid
motion. The higher the fluid velocity, the higher the rate of heat transfer.
Convection is classified as natural (or free) and forced convection, depending on how the fluid
motion is initiated. In forced convection, the fluid is forced to flow over a surface or in a pipe
by external means such as a pump or a fan. In natural convection, any fluid motion is caused
by natural means such as the buoyancy effect, which manifests itself as the rise of warmer fluid
and the fall of the cooler fluid.
3|Page
Heat Transfer
VISCOUS FLOW
For a flow over a flat plate as shown in Figure above, different flow region develops
by the influence of viscous forces.
The viscous forces are described in terms of a shear stress τ between the fluid layers.
The region of flow that develops from the leading edge of the plate in which the
effects of viscosity are observed is called the boundary layer.
The development of boundary layer from the leading edge passes three stages:
For flat plate the transition from laminar to turbulent flow occurs when:
𝑢∞ 𝑥 𝜌𝑢∞ 𝑥
= > 5 × 105
𝑣 𝜇
Where
4|Page
Heat Transfer
The boundary layer thickness,𝛿, is typically defined as the distance y from the surface to
the position at which u= 0.99 u∞.
This region of the flow above the plate bounded by 𝛿 in which the effects of the viscous
shearing forces caused by fluid viscosity, it is called the velocity boundary layer.
Consider the boundary-layer flow system shown in Figure. The free-stream velocity outside
the boundary layer is u∞ , and the boundary-layer thickness is δ.
The thickness of the boundary layer at any distance on the flat plate can be estimated by
using the following equation:
𝛿 4.64
= 1
𝑥
Re2𝑥
Where:
𝑢∞ 𝑥 𝜌𝑢∞ 𝑥
Re𝑥 = =
𝑣 𝜇
5|Page
Heat Transfer
Example: Air at 27◦C and 1 atm flows over a flat plate at a speed of 2 m/s. Calculate the
boundary-layer thickness at distances of 20 cm and 40 cm from the leading edge of the plate.
The viscosity of air at 27◦C is 1.85 × 10−5 kg/m.s.
Solution:
H.W: Air flows over a flat plate at a constant velocity of 20 m/s and ambient conditions of
1 atm and 60 °C. Calculate the boundary-layer thickness at a 3 cm distance from the leading
edge of the plate.
6|Page
Heat Transfer
7|Page
Heat Transfer
We have already seen that the temperature and flow fields are related. Now we seek an
expression whereby the frictional resistance may be directly related to heat transfer.
The shear stress at the wall may be expressed in terms of a friction coefficient Cf:
2
𝜌𝑢∞
𝜏𝑤 = 𝐶𝑓
2
𝐶𝑓𝑥 −1/2
= 0.332Re𝑥
2
And:
1/2
Nu𝑥 = 0.332Pr1/3 Re𝑥
1
Nu𝑥 ℎ𝑥 −
2 −
= = 0.332 Pr 3 Re𝑥 2
Re𝑥 Pr 𝜌𝑐𝑝 𝑢∞
ℎ𝑥
St 𝑥 =
𝜌𝑐𝑝 𝑢∞
so that
2 1
−
St 𝑥 Pr 3 = 0.332Re𝑥 2
And
The last equation called the Reynolds-Colburn analogy, expresses the relation between
fluid friction and heat transfer for laminar flow on a flat plate.
1|Page
Example: For the flow system in the previous example which includes: Air at 27°C and 1
atm flow over a flat plate at a speed of 2 m/s. Assume that the plate is heated over its entire
length to a temperature of 60◦C. compute the drag force exerted on the first 40 cm of the
plate using the analogy between fluid friction and heat transfer. Assume unit depth in the z
direction.
Solution:
27 + 60
𝑇𝑓 = = 43.5∘ C = 316.5K
2
2|Page
H.W
1) Air at 90◦C and 1 atm flows over a flat plate at a velocity of 30 m/s. How thick is
the boundary layer at a distance of 2.5 cm from the leading edge of the plate?
Ans: 6.21x10-4 m
2) Air at 1 atm and 30◦C flows over a 15-cm-square plate at a velocity of 10 m/s.
Calculate the maximum boundary layer thickness.
Ans: 0.00225 m
3) Helium at 1 atm and 300 K is used to cool a l-m-square plate maintained at 500 K.
The flow velocity is 50 m/s. Calculate the total heat loss from the plate. What is the
boundary-layer thickness as the flow leaves the plate?
Ans: 10.52 kW, 0.0094 m
3|Page
Example: Calculate the ratio of thermal boundary layer thickness to hydrodynamic
boundary layer thickness for the following liquids:
Solution:
Subs Pr
Solution:
Then:
Properties of gases at atmospheric pressure† (Continued).
Values of , , , and Pr are not strongly pressure-dependent for He, H2 , O2 , and N2
and may be used over a fairly wide range of pressures
Carbon dioxide
Ammonia, NH3
Water vapor
the plate is heated over its entire length to a temperature of 60 C. Calculate the heat
transferred in (a) the first 20 cm of the plate and (b) the first 40 cm of the plate.
Solution:
Heat Transfer (II)
Heisler Charts
A group of curves are used with unsteady-state case when Biot no. is greater than 0.1. The most
cases that to be treated are:
1- Infinite plate (plate where thickness is very small in comparison to other dimension).
3- Sphere.
T∞ = Environment temperature
Ti = Initial temperature of the solid(t = 0)
𝜃 = 𝑇(𝑥, 𝑡) − 𝑇∞ or𝑇(𝑟, 𝑡) − 𝑇∞
𝜃𝑖 = 𝑇𝑖 − 𝑇∞
𝜃0 = 𝑇0 − 𝑇∞
The first chart is to determine the temperature To at the center of the geometry at a given time
(t).
Heat Transfer (II)
𝜃0
= (𝑇0 − 𝑇∞ )/(𝑇𝑖 − 𝑇∞ )
𝜃𝑖
The second chart is to determine the temperature at other locations at the same time in terms
of To.
𝜃/𝜃0 = (𝑇 − 𝑇∞ )/(𝑇0 − 𝑇∞ )
The third chart is to determine the total amount of heat transfer up to the time t (Q/Qo).
Where:
𝑄0 = 𝜌𝑐𝑉(𝑇𝑖 − 𝑇∞ ) = 𝜌𝑐𝑉𝜃𝑖
- If a centreline temperature (To) is desired, only one chart is required to obtain a value
for θ0 and then T0, i.e Chart (1) for infinite plate, Chart (4) for infinite cylinder and
Chart (7) for sphere.
- To determine an off-center temperature, two charts are required to calculate the product:
𝜃 𝜃0 𝜃
=
𝜃𝑖 𝜃𝑖 𝜃0
For example, Charts (1) and (2) would be employed to calculate an off-center
temperature for an infinite plate.
-The heat losses for the infinite plate, infinite cylinder, and sphere are given in
Charts 3, 6 and 9, respectively, where Q0 represents the initial internal energy content
of the body in reference to the environment temperature, and Q is the actual heat lost
by the body in time t.
Note that: (x,r) is measured from the center towards the surface.
ℎ𝑠
Biot number = Bi =
𝑘
𝛼𝑡 𝑘𝑡
Fourier number = Fo = =
𝑠 2 𝜌𝑐𝑠 2
In these parameters s for the plate it is the half-thickness, whereas for the cylinder and
sphere it is the radius.
The value of Fo no. means that the period of time is required to heat or cool the body.
A low value of (Fo) indicates that a long period of time is required to cool or heat the
body.
𝛼𝑡
(Fo) = > 0.2
𝑠2
Example: A large plate of aluminum (k = 215 W/m · ◦C) 5.0 cm thick and initially at 200◦C
is suddenly exposed to the convection environment of 70◦C with a heat-transfer coefficient of
525 W/m2 · ◦C. Calculate the temperature at a depth of 1.25 cm from one of the faces 1 min
after the plate has been exposed to the environment. How much energy has been removed per
unit area from the plate in this time?
Solution:
The Heisler charts of Figures (1) and (2) may be used for solution of this problem. We first
calculate the center temperature of the plate, using Figure (1), and then use Figure (2) to
calculate the temperature at the specified x position.
Given information:
k = 215 W/m · ◦C
ρ=2700 kg/m3
Heat Transfer (II)
cp=900 j/kg.°C
Ti=200◦C
T∞=70◦C
h = 525 W/m2 · ◦C
t = 1 min = 60 s
Then
𝑥 1.25
= = 0.5
𝐿 2.5 From figure (2)
𝑘 𝜃
= 16.38 = 0.98
ℎ𝐿 𝜃0
𝜃 𝜃0 𝜃
= × = 0.61 ∗ 0.98 = 0.5918
𝜃𝑖 𝜃𝑖 𝜃0
𝜃 𝑇 − 𝑇∞ 𝑇 − 70
= = → 𝑻 = 𝟏𝟒𝟕. 𝟕 °𝑪
𝜃𝑖 𝑇𝑖 − 𝑇∞ 200 − 70
Heat Transfer (II)
𝑄0 𝜌𝑐𝐴(2𝐿)𝜃𝑖
= = 𝜌𝑐(2𝐿)𝜃𝑖
𝐴 𝐴
= (2700)(900)(0.05)(130)
= 15.8 × 106 J/m2
𝑄 𝐉
= (15.8 × 106 )(0.41) = 𝟔. 𝟒𝟖 × 𝟏𝟎𝟔 𝟐
𝐴 𝐦
Example: A long aluminum cylinder (k = 215 W/m · ◦C) 5.0 cm in diameter and initially at
200◦C is suddenly exposed to a convection environment at 70◦C and h = 525 W/m2 · ◦C.
Calculate the centreline temperature; and temperature at a radius of 1.25 cm and the heat lost
per unit length 1 min after the cylinder is exposed to the environment.
Solution:
Given information:
k = 215 W/m · ◦C
ρ=2700 kg/m3
cp=900 j/kg.°C
Ti=200◦C
Heat Transfer (II)
T∞=70◦C
h = 525 W/m2 · ◦C
t = 1 min = 60 s
r0 = 2.5 cm=0.025 m
r = 1.25 cm
Then:
To calculate (To):
𝑘 215 𝜃0
= = 16.38 = 0.38
ℎ𝑟0 (525)(0.025) 𝜃𝑖
𝜃0
𝜃0 = ∗ 𝜃𝑖 = 0.38(200 − 70) = 49.4 °𝐶
𝜃𝑖
𝜃0 = To-T∞→To=49.4+70=119.4 °𝐶
To calculate (T):
𝑟 1.25
= = 0.5 From figure (5)
𝑟0 2.5
𝜃
𝑘 = 0.98
= 16.38 𝜃𝑜
ℎ𝑟0
𝜃 = 𝑇 − 𝑇∞ → 𝑇 = 70 + 48.4 = 118.4∘ C
𝑄0 𝜌𝑐𝐿𝜋𝑟02 𝜃𝑖
= = 𝜌𝑐𝜋𝑟02 𝜃𝑖 = (2700)(900)𝜋(0.025)2 (130) = 6.203 × 105 J/m
𝐿 𝐿
𝑄
= (6.203 × 105 )(0.65) = 4.032 × 105 J/m
𝐿
Unsteady-State Conduction (Charts & Tables) Plate
Chart (1)
2
Salwan Alturki
Unsteady-State Conduction (Charts & Tables) Plate
Chart (2)
Chart (3)
3
Salwan Alturki
Unsteady-State Conduction (Charts & Tables) Cylinder
Chart (4)
4
Salwan Alturki
Unsteady-State Conduction (Charts & Tables) Cylinder
Chart (5)
Chart (6)
5
Salwan Alturki
Unsteady-State Conduction (Charts & Tables) Sphere
Chart (7)
6
Salwan Alturki
Unsteady-State Conduction (Charts & Tables) Sphere
Chart (8)
Chart (9)
7
Salwan Alturki