10/3/21, 1:42 PM Viewpoint Administration web page is blank

Rockwell Automation
Rockwell logo
Automation
Listen
Think
Solve ekchandrase… 
Support Center Get Support  Training & Webinars Online Forum My TechConnect Customer Care
logo


Please be advised that we are experiencing intermittent activation service outages. We are actively working on a resolution and
apologize for the inconvenience.

ID: BF9290 | Access Levels: TechConnect

Viewpoint Administration web page is blank


READ LATER:  Email this page  Print

To find an answer using a previous Answer ID, click here

Search Knowledgebase... SEARCH ADD TO FAVORITES

Document ID BF9290

Published Date 02/12/2020

Summary
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1084512 1/5
10/3/21, 1:42 PM Viewpoint Administration web page is blank

Viewpoint Administration web page is blank

Problem

When I try to open the FactoryTalk Viewpoint Administration web page, it is blank. There
are no errors showing, it is just blank.

Solution

In the Windows Event Viewer, the Application log showed the following two errors :

Could not load all ISAPI filters for site ’DEFAULT WEB SITE’.
Therefore site startup aborted.

ISAPI Filter
’C:\windows\Microsoft.NET\Framework\v4.0.30319\\aspnet_filter.dll’
could not be loaded due to a configuration problem. The current
configuration only supports loading images built for a AMD64
processor architecture. The data field contains the error number. To
learn more about this issue, including how to troubleshooting this

https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1084512 2/5
10/3/21, 1:42 PM Viewpoint Administration web page is blank

kind of processor architecture mismatch error, see


http://go.microsoft.com/fwlink/?LinkId=29349. (This link does not work)

To fix the issue, do the following:


1. Open the IIS Manager on the computer.
2. Highlight the Default Webpage
3. Open the ISAPI filters.
4. In the filter for the .NET Framework 4.0.30319, you will see a path that has double
slashes \\ towards the end of the file path right before the aspnet_filter.dll.
5. Edit the filter path, and remove one of those slashes, so there is just one slash.
6. Save the filter.
7. Click on the Default Webpage on the left
8. Then select the Restart link on the right side of the screen.
The FactoryTalk ViewPoint Administration should now open. This seems to be an issue of
.NET 4.0.30319

Was this answer helpful?


https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1084512 3/5
10/3/21, 1:42 PM Viewpoint Administration web page is blank

Yes No

RATE CONTENT

Recently Viewed

FactoryTalk ViewPoint
Cables to connect a 1747-UIC to
Administration Console gets a Cable / Processor Pinouts
DH-485 PanelViews
blank page

DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment
of such subjects. Accordingly, the information in this web site is not intended to constitute application, design, software or other professional
engineering advice or services. Before making any decision or taking any action, which might affect your equipment, you should consult a qualified
professional advisor.
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE
AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS
PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL,
CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1084512 4/5
10/3/21, 1:42 PM Viewpoint Administration web page is blank

ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE)
PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT.
Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.

www.rockwellautomation.com

Copyright © 2021 Rockwell Automation, Inc. All Rights Reserved.

https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1084512 5/5

You might also like