How Chlor-o-SafeTM works
Brine from a salt saturator is diluted and fed into
an electrochemical cell where the solution is
electrolyzed to sodium hypochlorite and
transferred to a storage tank. The hydrogen
produced is separated in a degasser and vented.
Softened water is automatically supplied to the
saturator, maintaining a stable brine concen-
tration. The generation of hypochlorite is
controlled by level switches to ensure a sufficient
amount of fresh product for varying dosing
requirement. Chlor-o-SafeTM is fully automatic and Installation for disinfection of drinking water at Lovö
controlled from a panel where all necessary safety Waterworks, City of Stockholm
devices are incorporated. All that is needed for
sterilization with the Clor-o-SafeTM unit is salt,
water and electricity. As hypochlorite is produced
Application areas:
at less than 1 % concentration, the hazards and
precautions normally associated with storage of • Swimming pools
chemicals are avoided. • Municipal water plants
• Food processors
• Industrial plants
Standard equipment. • Waste water treatment plants
• Cooling towers
A compact skid mounted unit with easy connections • Power plants
to utilities, featuring: • Chemical manufacturers
• Salt saturator with level sensors
• Hypochlorite storage tank with level sensors
• Brine dilution controls
• Electrolytic cell with degasser
• Rectifier
• Control panel with safety devices
• Brine dosing pump
Technical data
Capacity, Cl2 g/h (nominal) 80 160 240 320 480 640 800 960 1280 1440 1600 1760
Capacity Cl2 kg/24h 1.92 3.84 5.76 7.68 11.52 15.36 19.2 23.04 30.72 34.56 38.4 42.2
Hypochlorite, approx 0.8 % L/h 10.75 21.5 32.25 43 64.5 86 107.5 129 172 193.5 215 236.5
Hypochlorite, approx 0.8 % L/24h 258 516 774 1032 1548 2064 2580 3096 4128 4644 5160 5676
Brine flow, L/h (310g NaCl/L) 0.75 1.5 2.25 3 4.5 6 7.5 9 12 13.5 15 16.5
Salt consumption, kg/h 0.23 0.47 0.7 0.93 1.4 1.86 2.33 2.79 3.72 4.19 4.65 5.11
Salt consumption, kg/kg Cl2 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
Water consumption, L/h 10.5 21.0 31.5 42.1 63.1 84.1 105.2 126.2 168.3 189.3 210.3 231.4
Water consumption, L/kg Cl2 131.5 131.5 131.5 131.5 131.5 131.5 131.5 131.5 131.5 131.5 131.5 131.5
El. connection, V/Hz/phases 230/50/1 230/50/1 230/50/1 230/50/1 400/50/3 400/50/3 400/50/3 400/50/3 400/50/3 400/50/3 400/50/3 400/50/3
Power consumption, kW 0.55 1.09 1.64 2.05 3.07 4.1 5.12 5.79 7.72 8.68 9.11 10
Energy consumption, kWh /kg Cl2 6.8 6.8 6.8 6.4 6.4 6.4 6.4 6 6 6 5.7 5.7
Rectifier size, VDC/A 6/100 6/200 6/300 10/200 6/600 9/400 5/1000 15/400 18/400 15/600 24/400 6/3000
ElectroCell AB
Box 430, SE-691 27 Karlskoga, Sweden,
Telephone: +46 586 641 50, Telefax: +46 586 791 700
e-mail; [email protected] www. chematur.se