SNA-US-12K-User-Manual-2024.07.12-1
SNA-US-12K-User-Manual-2024.07.12-1
SNA-US-12K-User-Manual-2024.07.12-1
User Manual
SNA US 12K
UP
Return Enter
Down
L1 L2 L1 L2
Battery Breaker
Smar t Load
Load
Version: UM-SNAUS02001
User Manual
Copyright© 2024 Lux Power Technology Co., Ltd. All Rights Reserved. This manual, protected by the
copyright and intellectual property rights of Lux Power Technology, may not be modified, copied, or
reproduced without prior written permission. Brands and trademarks mentioned belong to their
respective owners. Read carefully for product reliability and warranty eligibility. For warranty details,
refer to Lux Power Technology Limited Warranty. Intended for professional service providers; no
Descriptions may contain predictive statements; differences may occur. Provided for reference, subject
🔎 www.luxpowertek.com
Scan to download
User Manual
Table Of Contents
Information on this Manual 1
Validity 1
Scope 1
Target Group 1
Safety Instructions 1
1. Brief Introduction 2
2. Installation 6
2.1 Preparation 6
2.5 PV Connection 11
3. Working Modes 17
7. Specifications 38
Revision History
Scope
This manual provides the installation, operation and troubleshooting of this unit, please read this manual
carefully before installations and operations.
Target Group
For qualified persons and end users. Qualified persons and end users must have the following skills:
Knowledge about this unit operation
Training in deal with the security issues associated with installations and electrical safety
Training in the installation and commissioning of electrical devices and installations
Knowledge of the applicable local standards and directives
Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this
manual for future reference.
All the operation and connection need to be operated by qualified persons.
Before using the unit, read all instructions and cautionary marking on the unit. Any damage caused
by inappropriate operation is not warranted by Luxpower.
All the electrical installation must comply with the local electrical safety standards.
Do not disassemble the unit. Take it to a qualified service center when service or repair is required,
incorrect re-assembly may result in a risk of electric shock or fire. Do not open inverter cover or
change any components without Luxpower's authorization, otherwise the warranty commitment for
the inverter will be invalid.
To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or
cleaning, turning off the unit will not reduce this risk.
CAUTION-To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries and
lithium batteries, other types of batteries may burst, causing personal injury and damage.
NEVER charge a frozen battery.
For optimum operation of this unit, please follow required spec to select appropriate cable size and
breaker.
Please strictly follow installation procedure when you want to disconnect AC or DC terminals, please
refer to INSTALLATION section of this manual for the details.
GROUNDING INSTRUCTIONS -This unit should be connected to a permanent grounded wiring
system, be sure to comply with local requirements and regulation to install this inverter.
NEVER cause AC output and DC input short circuited. Do not connect to the mains when
DC input short circuits.
1
User Manual
1. Brief Introduction
1.1 Features of the inverter
LuxPower APP
Wifi/4G Internet
User name
Pass word
LOGIN
Forget password?
or
REGISTER
DONGLE CONNECT
DOWNLOAD FIRMWARE
Version 3.2.3 - Privacy Policy
UP
Return Enter
Down
Battery Breaker
Smart Load
Load
Generator
Battery
SNA series is a multifunctional, high frequency pure sine wave Offgrid inverter solar inverter, features:
Applicable for pure off grid inverter / backup power / self-consumption / ongrid situation
Integrated with 2 MPPT solar charge controllers, MPPT ranges 120V~385V
Each PV input MPPT supports up to 12kW, with a total input power of 24kW when both PV inputs
are used, and a power factor of 1.
Be able to run with or without battery in ongrid and offgrid mode
With separated generator input interface, able to control generator remotely
With integrated advanced parallel function, up to 6pcs max paralleling
Support CAN/RS485 for Li-ion battery BMS communication
WIFI/ GPRS remote monitoring, setting and firmware update, support website, free IOS/Android APP
2
User Manual
UP
Return Enter
Down
SC1
50
49
BAT.NTC
M3.COM CT1 CT2
CN10 CN3 CN2
ON
ON
1+ 1+ 1- 1- 2+ 2+ 2- 2-
BAT.COM Parallel PV INPUT
BAT+ BAT-
PV Interface
L1 L2
Smart L1 L2 L1 L2 L1 L2
OFF Load Load Gen Grid
PSD.SW
COM2
COM1
GND
GND
NO2
OFF
NC2
NO1
NC1
12V
ON ON
OFF
EPS OUTPUT
ON
POWER
N PE
BAT.NTC
M3.COM CT1 CT2
Parallel communication
Resistor switch
BAT.COM Parallel
COM2
COM1
GND
GND
NO2
NC2
NO1
NC1
12V
Dry contacts
3
User Manual
Off-grid Inverter
User Manual
SNA US 12K
UP
Return Enter
Down
L1 L2 L1 L2
Battery Breaker
Smart Load
Load
Version: UM-SNAUS02001
! CAUTION
a) The inverter and its components must be stored in its original packaging.
b) The storage temperature should be within -13~140 F(-25~60) and humidity within 0~85%.
c) The packing should be upright and maximum stacked layers is 6 .
d) Do not directly exposed the inverter and its packaging to sunshine, raindrops and keep away
from corrosion.
4
User Manual
Temperature<60℃
Height<6.6ft
Height<2m
Humidity<85%
5
User Manual
2. Installation
2.1 Preparation
The system connection is as below:
600V, 2*4AWG
L1
L2 Grid
Grid
PE
600V, 2*4AWG
PE
L1
Load L2 LOAD1
600V, 2*4AWG QF1
100V, 2*1/ 0AWG or 4*2AWG
L1
Smart Load LOAD2
L2
600V, 2*4AWG
QF2
L1
GEN L2 G Generater
N
BAT P V1 P V2
600V, 4*8AWG
MAX: 250A
QF 1 In ≥ 100A
QF 2 In ≥ 63A
QF 1 is Double interlock switch or Dual Power Switch In ≥ 100A
1. Battery connection: For safety operation and regulation compliance, it's requested to install a
separate DC over-current protector or disconnect device between battery and inverter. The recom-
mend battery capacity is 200AH-400AH, the spec of DC breaker is 300A/80V. Recommended battery
cable and terminal size:
Ring Terminal
Maximum Battery Dimensions Torque value
Model Wire Size Cable
Amperage capacity
mm2 d2(mm) L (mm)
6
User Manual
2. AC connection: Please install a separate AC breaker between inverter and AC input power source,
inverter and AC output load. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input.
Recommended AC input/ AC output /GEN cable size for each inverter.
3. PV Connection: Please install separately a DC circuit breaker between inverter and PV modules.
The spec of DC breaker is 600V/40A. It's very important for system safety and efficient operation
to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper
recommended cable size as below:
4. Before connecting all wiring, please take off bottom cover by removing 4 screws as shown below.
7
User Manual
NOTICE
Step2. Install the expansion tubes into the holes and tight them, then use the expansion screws
(packaged together with the expansion tubes) to install and fix the wall-mounting bracket on the wall.
Step3. Install the inverter on the wall-mounting bracket and lock the inverter using the security screws.
344mm
800mm
UP
Return Enter
Down
L1 L2 L1 L2
Battery Breaker
Smart Load
Load
500mm
200mm 200mm
UP UP UP
L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1 L2
8
User Manual
ON
1 RS 4 8 5 B ---
2 RS 4 8 5 A ---
3 --- ---
4 --- CA NH
5 --- CA NL
BAT.NTC
CT1 CT2
M3.COM
6 /7 /8 --- ---
Battery Pack
BAT.COM Parallel
Inverter
9
User Manual
! CAUTION
- There are two terminal blocks with “GRID” and “LOAD” markings. Please do NOT mis-connect input
and output connectors.
- Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may
cause utility short-circuited when these inverters are worked in parallel operation.
10
L1→LINE (black)
L2→LINE (red)
N→Neutral (blue) 10
PE→Ground(green)
BAT.NTC
M3.COM CT1 CT2
BAT.COM Parallel 1+ 1+ 1- 1- 2+ 2+ 2- 2-
BAT+ BAT- L1
Smart
L2
L1 L2 L1 L2 L1 L2
PV INPUT
PSD.SW
GND
NO2
NC2
NO1
NC1
12V
N PE
10
User Manual
2.5 PV Connection
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Check correct polarity of connection cable from PV modules and PV input connectors.
3. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect
negative pole (-) of connection cable to negative pole (-) of PV input connector.
4. Make sure the wires are securely connected.
BAT.NTC
M3.COM CT1 CT2
BAT.COM Parallel 1+ 1+ 1- 1- 2+ 2+ 2- 2-
BAT+ BAT- L1
Smart
L2
L1 L2 L1 L2 L1 L2
PV INPUT
PSD.SW
GND
NO2
NC2
NO1
NC1
12V
N PE
11
User Manual
BAT.NTC
M3.COM CT1 CT2
BAT.COM Parallel 1+ 1+ 1- 1- 2+ 2+ 2- 2-
BAT+ BAT- L1
Smart
L2
L1 L2 L1 L2 L1 L2
PV INPUT
PSD.SW
GND
NO2
NC2
NO1
NC1
12V
N PE
12
User Manual
PV Breakers
UP
N
Return Enter
Down
L1 L2 L1 L2
Gride Breaker
Battery Breaker
PE
Smart Load
Load
Smart
BAT Load EPS GEN Grid PV
PE N L1 L2 L1 L2 L1 L2 L1 L2
Generator Breaker
PE
Battery Breaker
Load Breaker
UPS L o ad
The system will use AC first if there is both utility input and generator input.
2 parallel >30KW
It is supported to parallel 2~3pcs inverter with single phase in single phase parallel system to
charge battery with Generator! And it is depends on the load performance of the generator too.
13
User Manual
N L1 L1 PE
L2 L2
L1
L2
Inverter #2
L1 L2 Manual
LOAD GEN GRID
BAT PE N L1 L2 L1 L2 L1 L2
PV+ PV- Bypass
Switch
N L1 L1
PE
L2 L2
+
L1
L2
L1 L2
Inverter #3 Panel
L1 L2
LOAD GEN GRID
BAT PV+ PV-
-
PE N L1 L2 L1 L2 L1 L2
N PE Load
L1 L1
L2 L2
L1
L2
PE
N
L1 Generator
L2
Please put the 2-bit CAN balancing resistor switch to ON status for the first and end inverter of the daisy chain loop.
14
User Manual
N U PE
W
V
+
V
U V W
-
PE N L1 L2 L1 L2 L1 L2
N PE Load
U
W
V
PE
N
U Generator
V
W
Please put the 2-bit CAN balancing resistor switch to ON status for the first and end inverter of the daisy chain loop.
Step2. Please put the CAN communication PIN to on status for the first and the end inverter
11 00 00 11
1 ON
1 ON
1 ON
1 ON
3 n 36 3 3
0 1 2
No.1 0 1 2
No.2 0
1 2
No.n-1 0 1 2
No.n
BAT COM Parallel BAT COM Parallel BAT COM Parallel BAT COM Parallel
4 4 4 4
Parallel line1 Parallel line2 Parallel line(n-1 to n)
Parallel line(n to 1)
15
User Manual
Step3. Setup the monitor for the system, add all datalogs in one station. Users can login to the visit
User Cent er
Asia English
T T
文 A
Plant name Installer End User Country Timezone Daylight saving time Create date Action
Dongles
1 Genesis Aspergo Install South Africa GMT+2 No 2019-03-14 Station Management
Devices
2 Butler Home Elangeni johnbut ler South Africa GMT+2 No 2019-03-25 Station Management
Users
3 Office South Africa GMT+2 No 2019-06-03 Station Management
Operation Record
4 Cronje Home Broomhead cronje South Africa GMT+2 No 2019-07-16 Station Management
Step4. Enable share battery for the system if the system share one battery bank, otherwise disable the
shared battery function
TT
文 A
Device Overview Serial number Status Solar Power Charge Power Discharge Power Load Solar Yield Battery Dischar Feed Energy ConsumptionEr Station name Parallel Action
1 Normal 228 W 42 W 0W 182 W 215.3 kWh 39.6 kWh 0 kWh 551.2 kWh Dragonview A-1 Parallel
2 35 W 32 W 0W 0W 158.7 kWh 21.1 kWh 0 kWh 160.5 kWh Dragonview A-2 Parallel
3 1 kW 129 W 0W 1 kW 170.3 kWh 49.9 kWh 0 kWh 434.5 kWh Dragonview A-3 Parallel
4 79 W 48 W
0W 106 W 99 kWh 85.6 kWh 0 kWh 257.1 kWh Dragonview A-4 Parallel
For more detailed guidance for paralleling system, please visit https://www.luxpowertek.com/download/
And download the guidance
ON
EPS OUTPUT
POWER
ON
OFF
ON
OFF
After connection, please turn on both switch. Users can turn off the LOAD output switch to turn off
power supply in some emergency case
16
User Manual
CT1 CT2
PSD.SW
COM2
COM1
GND
GND
NO2
NC2
NO1
NC1
BAT COM Parallel 12V
P V INP UT
P 1 -RS485B BAT COM: Battery comm Port
P2-RS485A Parallel: PCS parallel comm port
P4---CANH 120Ω: Paralle balance resistor
P5---CANL Only used for first and last PCS
P1-RS485B
P2-RS485
3. Working modes
3.1 Offgrid inverter modes introduction:
17
User Manual
18
3.2 Working Modes related setting description
Bypass Mode
In the AC first time NA
AC will take the load and Solar is used to charge battery
19
User Manual
1. SNA-US 12000 can working as a traditional off grid inverter. In this situation, inverter either use
(solar+battery) to take load or use AC take load. Related settings
AC First: During the setting time, system will use AC to take load first, use solar power to charge the
battery.
If the battery is full, solar power may be wasted. When out of the setting time, system will use battery
and solar to take load until battery voltage/SOC is lower than cut off voltage/SOC
2. AC Charge function Disable: The system will not use AC to charge the battery(except Li ion BMS set
force charge flag )
According to Time: During the setting time, system will use AC to charge the battery until battery full
and battery will not discharge during the setting time.
According to Battery Voltage: During the setting time, system will use AC to charge the battery if
battery voltage is lower than AC Charge Start Battery Voltage and will stop when Voltage is higher
than AC Charge End Battery Voltage. And battery will not discharge during the setting time.
According to Battery SOC: During the setting time, system will use AC to charge the battery if battery
SOC is lower than AC Charge Start Battery SOC and will stop when Voltage is higher than AC Charge
End Battery SOC. And battery will not discharge during the setting time.
20
User Manual
① ⑦
②
③
④ ⑤
21
User Manual
LOAD output information This area will display LOAD voltage, frequen-
4
and data cy, power.
22
User Manual
If the system displays the icon in the When the icon in the red box is
red box. Indicates that the AC input displayed, it indicates that the AC
port is connected to the power grid. input port is connected to a generator.
23
User Manual
Button Operations
UP
Return Enter
Down
Button Fuction
ESC Exit
ENTER Confirm, Enter menu
UP Previous step or Slide right
DOWN Next step or Slide left
Note: Long-pressing the UP and DOWN keys will continuously input the
corresponding key signals.
General Operations
Through button control, press ENTER on the home screen to access the menu options
Using the UP and DOWN buttons, select the desired function, then press ENTER to enter.
Press ESC to return to the previous level. The options include Home for the main page,
Data for operational data, Notice for fault and warning information, and Setting for
configuration settings.
Note: Click the Down button again, then jump to Notifications, Settings, Home, and
complete a loop..
24
User Manual
1 Solar
2 Battery (1)
3 Battery (2)
The second page contains the following information: the number of charge
and discharge times of the battery, the capacity of the battery, the maximum
charge current, the maximum discharge current, BMS event 1, BMS event 2,
the charge power in a day, the discharge power in a day, the total charge
power, the total discharge power.
25
User Manual
4 Grid (1)
The first page contains the following information: grid voltage, grid frequency,
split phase L1-N voltage, split phase L2-N voltage, generator voltage, genera-
tor frequency, power input from the grid to the inverter, power output
from the inverter to the grid, inverter power, rectified power, load power.
5 Grid (2)
6 UPS (1)
The first page contains the following information: LOAD voltage, LOAD
frequency. L1-N voltage of LOAD, L2-N voltage of LOAD. The active power of
LOAD, the apparent power of LOAD. The L1-N active power of LOAD and the
L1-N apparent power of LOAD. The L2-N active power of LOAD and the L2-N
apparent power of LOAD.
26
User Manual
7 UPS (2)
The second page shows the output power of LOAD (L1-L2) in a day. LOAD
(L1-L2) Indicates the total power output. LOAD (L1-N) Output power in a day.
LOAD (L1-N) Indicates the total power output. LOAD (L2-N) output power in
a day. LOAD (L2-N) Total power output.
8 Parallel
This page contains information about the role of the inverter in the parallel
state (master and slave), the type of parallel connection (single-phase or
three-phase), the parallel phase (U, V, or W), the number of parallel machines,
and the parallel address.
9 Other
This page contains text information about the current status of the inverter.
Inverter error code. Inverter alarm code. Voltage of BUS1. Voltage of BUS2.
Positive BUS voltage. Negative voltage of the BUS. The temperature of T1 is
the temperature of the I/O board (the highest value). T2 is the temperature
of the motherboard (take the highest value).
27
User Manual
1 Fault
Status
Alarm
2
Status
3 Record
This page contains information that lists the history of failures and alarms.
Specific to the time and date of failure or alarm. The fault history is displayed
on pages 1 to 4. Pages five through eight show the history of the call.
28
User Manual
2 Application
(1)
29
User Manual
3 Application
(2)
4 Application
(3)
The third page contains the following information: Mixed mode Settings.
PV and AC are loaded together. empower Export to the grid. Percentage
of electricity output to the grid. Enable the CT function on the inverter
power grid side. The default CT ratio is 1000:1. It can also be set to
2000:1 and 3000:1.
5 Application
(4)
The fourth page contains information: Type of parallel machine (no parallel
machine or single phase parallel machine or three phase parallel machine).
Parallel phase (R,S,T) can be set. The battery sharing function was enabled.
30
User Manual
6 Charge (1)
7 Charge
(Numerical
setting
operation) This page contains: Setting values. After pressing Down, exit move to +1,
+1 to -1, -1 to +0.1, +0.1 to -0.1, and -0.1 to Enter. Press UP to roll back.
If you press Enter when the cursor moves to +1, 55 becomes 56. If you
press Enter when the cursor moves to -1, 55 becomes 54. If you press
Enter when the cursor moves to -0.1, 55 becomes 54.9. If you press Enter
when the cursor moves to +0.1, 55 becomes 55.1.
8 Charge (2)
31
User Manual
9 Charge
(according
to the time)
Charge
10 (according
to the
battery
voltage)
The second page contains information:
The AC is charged according to the battery voltage. The starting
charge voltage and cut-off charge voltage can be set.
Charge
11 (according
to
the battery
SOC)
The second page contains information:
The AC is charged according to the battery SOC.
Start charge SOC and stop charge SOC can be set.
32
User Manual
Charge
(according
12 to the
battery
voltage
and time) The second page contains information:
The AC is charged according to the battery voltage and time.
Meet one of the three time periods and the battery voltage
between the starting charge voltage and the cut-off charge
voltage. The AC will be charged.
Charge
13 (according
to
time and
SOC) The second page contains information:
The AC is charged according to time and SOC. Meet one of the
three time periods and the battery SOC between the start charge
SOC and the cut-off charge SOC. The AC will be charged.
14 Charge (3)
The third page contains information about the Settings for charging the
generator. The generator is charged according to the battery voltage or
battery SOC. Battery charging current can be set. The battery voltage can be
set to start charging. You can set the battery voltage at the end of charging.
Battery SOC can be set to start charging. Battery SOC can be set to end
charging. The maximum input power of the generator can be set.
33
User Manual
15 Discharge (1)
16 Discharge (2)
The second page contains the following information: Enable Smart Load.
When the actual PV input power is greater than the value, the Smart
Load function takes effect. Normally open when connected to the grid.
Smart Load takes effect voltage point. Smart Load End voltage point.
Smart Load takes effect on the SOC. Smart Load Ends the SOC.
17 Discharge (3)
34
User Manual
Other
Include information:
CT power compensation setting. Set the maximum speed of five fans.
Set five fan control slope curves.
18 Basic
Contains information:
SN Indicates the serial number of the inverter. FW Indicates the firmware
version of the inverter (cEaa indicates the US version, cFaa indicates the
European version).
35
User Manual
Enter
Up or Down
Enter
36
User Manual
2. Monitor system setup for Distributors and Monitor system setup for endusers, Monitor system
registration, wifi password setting, and wifi local monitor and setting
3. Lux_Monitor_UI_Introduction
Introduction of monitor interface
Device: 9532004127
724 W Notice
PV Power
270 W 0W
Battery Power
53.6Vdc
89%
Battery Level(SOC)
Standby 448 W
Backup Power(EPS) Consumption
37
User Manual
7. Specifications
Table 1 MPPT Mode Specifications
120Vac/208Vac
Output Voltage Regulation
120Vac/240Vac
38
User Manual
Low DC Warning Voltage 20% ≤ load < 50% Warning Voltage @load < 20% -1.2V
100%
Charging Curve
50%
T0 T1
T1=10*T0, minimun 10mina, maxmum 8hour
Current
39
User Manual
110Vac/120Vac
Nominal Input Voltage
220Vac/240Vac
120Vac/208Vac
Rated GEN Voltage
120Vac/240Vac
40
User Manual
UL STD. 1741
Safety Certification
CSA STD. C22.2 No.107.1
Warranty 2 Years
Topology Transformer-less
Altitude <2000m(6561ft)
41
User Manual
E001 Model fault Restart inverter, if the error still exist, contact us
Off-gird, short-circuit of Check if the load is short circuit, try to turn off the
E012
the Load or Smart Load. load and restart inverter
E013 UPS reserve current Restart inverter, if the error still exist, contact us
BUS short circuit Restart inverter, if the error still exist, contact us
Phase Error in three phase Check if the AC connection is right for three phase system,
E015
parallel system there should one at least one inverter in each phase
E019 Bus voltage high Check if PV input voltage is higher than 495V
E022 Hardware Over current Restart inverter, if the error still exist, contact us
Sync triger signal lost in Check CAN cable connection is connected to the
E029
parallel system right COM port
42
User Manual
W013 Over temperature The temperature is a little bit high inside inverter
W020 PV Isolation low Restart inverter, if the error still exist, contact us
W022 DC injection high Restart inverter, if the error still exist, contact us
W029 The load output voltage is high Restart inverter, if the error still exist, contact us
W031 Load DCV high Restart inverter, if the error still exist, contact us
43
YOUR RELIABLE ENERGY SOLUTIONS PARTNER
luxpowertek