Over load VK3-Control-Operating-Manual
Over load VK3-Control-Operating-Manual
PROGRAMMING INSTRUCTIONS
VK3
1. Description of Operation
The purpose of EMCO Load System is to measure, monitor and provide usable
information about the load in an elevator cab. This information can be used to protect
the passengers from overload conditions and increase the efficiency of the elevator.
The system usually consists of a sensor or group of sensors to be mounted on the
elevator and a controller. The sensor(s) are used to provide a signal to the controller
directly related to the amount of load in the cab. The controller is used to accept this
signal and provide usable data to the elevator controller in the form of relays, analog
signals or other methods of communication.
2. Electrical Characteristics
Model Power Supply Current Fuse
VK-3 220VAC 60mA 100mA
VK-3 115 VAC 120mA 200mA
VK-3B 24VDC 300mA 800mA
48VDC 150mA 400mA
3. Installation
5. Description of Connections
AL-C, AL-S and AL-A (if provided) are the relays that change state when the
programmed weight values are exceeded.
is usually programmed for the capacity of the cab. When the load in the
cab exceeds this value the relay changes state and if using our MB-D display
the figure will illuminate as the load increases.
is usually programmed for overload. When the load in the cab exceeds
this value the relay changes state and if using our MB-D display it will
activate a buzzer and the KG marking of the display will illuminate.
is an extra relay to be programmed as needed. When the load in the cab
exceeds this value the relay changes state.
Hold is a circuit that requires 24-110VAC or VDC power. The power is to be applied
when the doors close and the power is to be removed when the doors open. When
power is applied the control stops weighing and the weight value will blink on the
display. This insures that movement of the cab will not affect the weighing process.
Also, when the doors are closed since no more people will be entering the cab there is
no reason to continue the weighing process. When the doors open, power is to be
removed from the hold circuit so that the control can begin measuring the load in the
cab.
Power Supply required to operate the controller is shown above the terminals.
Standard voltages are 24VDC, 110VAC and 220VAC depending on the control
ordered.
Sensor connections are shown above the terminals on the controller corresponding to
the load sensor/cell used.
Cabin Display- Our MB-D Display is the factory supplied display that can be used
with the VK Series of controllers. Based upon the setting of AL-C relay the figure
will progressively illuminate starting at the feet and travel up the body of the figure.
Upon reaching the setting of AL-C the complete figure will be illuminated. The KG
marking will illuminate and a buzzer will sound upon reaching the AL-S relay setting
of the control. If you want to use your own buzzer or LED display connect to these
terminals. These terminals provide 0-7.5 VDC at 75mA maximum based upon the
settings of the AL-C and AL-S settings. When connecting your own buzzer of LED
display follow polarity as shown on terminals.
- Pressing this key enters the specific parameter you are going to program. Once
the specific parameter is displayed, pressing this key highlights the digit to be
modified.
7. Menu/Programming Order
Pressing the Key will scroll through the program in the following order:
(Relay/Alarm)
(Relay/Alarm)
(Relay/Alarm)
(Chain Compensation)
9. Calibration
Manual Calibration with Weights
1. Before programming or calibrating sensors and control:
Bring cab to middle floor of its total travel. For instance, if travel is 6 stops or
floors place cab on the 3rd or 4th floors.
Bounce in cab to insure cab is free on guide rails.
2. Properly connect the sensors to control.
3. Power up control and check power supply to control and insure within voltage
range of the control supplied.
4. Install sensors to cable per instructions supplied with sensors.
5. Zero out the controller:
Press key till is displayed.
Press key once.
Press key once.
Controller display will begin to count down. Exit top of cab till unit finishes
counting down.
should be shown on the display. If is not shown the value has
not been saved in the controller and this step must be done again.
6. Adjust for weights:
Press key till is displayed if it is not shown.
Add a known weight to the car. Preferably a minimum of 50% of the car
capacity.
Press and keys to manually enter the value in kilograms of the weight
in the cab.
Press key twice.
As controller display begins to count down, exit top of cab till unit finishes
counting down.
Press the key until the weight is shown on control display. It should be the
value of the weights in the cab in kilograms.
= Bad load cell connection or damaged load cell- Correct error condition by
checking all load cell connections to the controller are per wiring diagram along
with inspecting cables for any cuts or broken wires.
=Negative load cell flow- Correct error condition by checking load cell
connections to the controller and insure they are per wiring diagram.
=Positive load cell flow- Load cells are to small for application and must be
replaced with proper units.
= Polarity error- Correct error condition by checking all load cell
connections to the controller are per wiring diagram and reprogram control and
recalibrate per Paragraph 9.
= Parameter values have been lost ( AL-C, AL-S, AL-A, CERO, PESO…)
Scroll through menu and check parameter values. If necessary reprogram and
calibrate per Paragraph 9.