NETA World - WR20 - FINAL
NETA World - WR20 - FINAL
SPRING2013
CHALLENGES IN
TRANSFORMER
PROTECTION TESTING
INVESTIGATING AN
ELECTROMECHANICAL DIFFERENTIAL
RELAY MISOPERATION PAGE 52
TESTING TECHNIQUES FOR
PROTECTION-CLASS CURRENT
TRANSFORMERS PAGE 62
TESTING AND COMMISSIONING
A DISTRIBUTION RECLOSER IN
GRID-TIE SOLAR FARMS PAGE 72
Introducing
Rentals
and Leasing
Contact us today to get your hands on the best electrical testing equipment in:
Protection and Relay Testing Insulation Testing
Instrument Transformer Testing Low-Resistance Testing
Cable Test and Diagnostics Battery Testing
FEAT URES
COVER S T O RY
52 Investigating an Electromechanical
Differential Relay Misoperation
Alex Rangel, Saber Power Services, LLC
40
Recloser in Grid-Tie Solar Farms
Mohit Sharma, Megger, and Luis Montoya, PE,
FlexGen Power Systems formerly ABM
Challenges in Transformer
Protection Testing
While the basic premise of transformer
differential protection is straightforward,
features found in relay algorithms compensate
for challenges presented by the transformer
differential application. This article describes
typical functional differential tests and their
challenges and presents a system-based
alternative that reduces challenges and ensures
settings are adequate. Instructions for setup
and execution are accompanied by test cases,
and the benefits and drawbacks of system-
72
based testing are compared.
Scott Cooper, OMICRON electronics
10 NFPA 70E and NETA 108 Insights & Observations — CAP Spotlight
Looking at NFPA 70E 2021 — Part 1 AEMC Instruments: Over 125 Years of Technical
Ron Widup and James R. White, Shermco Industries Heritage and Innovation in Test Instrumentation
19 Relay Column
Combustion Turbine Generator Trip Analysis SPECIFICATIONS AND STANDARDS
Steve Turner, Arizona Public Service Company
112 ANSI/NETA Standards Update
24 Safety Corner
Basic Fall Protection
IMPORTANT LISTS
Paul Chamberlain, American Electrical
Testing Co., LLC
119 NETA Accredited Companies
30 Tech Quiz
Protective Relaying
126 Advertiser List
James R. White, Shermco Industries
32 Tech Tips
Ground Testing Procedures
Jeff Jowett, Megger
INDUSTRY TOPICS
Calibration Services
Our calibration labs Dallas and Chicago offer NIST-
traceable calibration services for all makes and models National Headquarters Houston
of electrical test and measurement equipment. Our 1517 W Carrier Pkwy, Ste 116 14251 Gulfstream Park Drive
qualified technicians will ensure that your electrical test Grand Prairie, TX 75050 Webster, TX 77598
instruments are working at peak performance and meet
all manufacturer standards. Quick turnaround is standard, Los Angeles Chicago
with most equipment completed in 5 business days or 2935 E Ricker Way 1501 Wright Blvd
less. Anaheim, CA 92806 Schaumburg, IL 60193
Reno-Tahoe Atlanta
Asset Management 924 Greg Street 880 Veterans Memorial Hwy
Eliminate your overhead and minimize equipment Sparks, NV 89431 Mableton, GA 30126
downtime with Protec’s asset management services. We
customize a unique solution for your business to store, Denver New York City
calibrate and maintain your equipment for whenever you 12050 E 45th Ave, Ste 400 70 Triangle Boulevard
need it. Receive analytics for ROI, yield and utilization to Denver, CO 80239 Carlstadt, NJ 07072
drive educated business decisions.
NETA Officers
president: Scott Blizard, American Electrical Testing Co., Inc.
first vice president: Eric Beckman, National Field Services
second vice president: Scott Dude, Dude Electrical Testing, LLC
secretary: Dan Hook, Western Electrical Services, Inc.
treasurer: John White, Sigma Six Solutions, Inc.
Delivering Powerful Reliability Solutions technical: Alan Peterson; technical exam: Dan Hook;
continuing technical development: David Huffman;
training: Eric Beckman; finance: John White;
nominations: Alan Peterson; alliance program: Jim Cialdea;
✔ Power System Acceptance Testing association development: Ken Bassett and John White
✔ Maintenance
NOTICE AND DISCLAIMER
✔ Coordination and Arc Flash Studies NETA World is published quarterly by the InterNational Electrical Testing Association.
Opinions, views and conclusions expressed in articles herein are those of the authors and not
necessarily those of NETA. Publication herein does not constitute or imply endorsement of
✔ Troubleshoot and Repair any opinion, product, or service by NETA, its directors, officers, members, employees or
agents (herein “NETA”).
✔ Training and Engineering Services All technical data in this publication reflects the experience of individuals using specific tools,
products, equipment and components under specific conditions and circumstances which may
It is presently October 2020, and the country is in the middle of a COVID-19 virus resurgence.
NETA Member Companies and their technicians throughout the United States and in Canada
have been identified as essential workers as they help support and maintain our nation’s critical
infrastructure. Be sure to follow your company’s and customers’ safety policies for the COVID-19
pandemic. The policy should include many of the preventative measures to limit the spread of
the COVID-19 virus that have been communicated by the CDC in the United States and by the
Public Health Agency of Canada. Be safe, and err on the side of caution.
Mark your calendars for PowerTest 2021, the premier electrical maintenance and safety
conference on March 8–12, 2021. This will be the first hybrid conference in NETA’s
history! If you are unable to attend PowerTest 2021 in person, NETA will provide
an opportunity to attend virtually. This portion of the event will allow people to
interact on a web-based platform rather than meeting in a physical location.
Online sessions will include feature webinars and webcasts as well as opportunity
for NETA Certified Technicians to receive CTDs for attending virtually. Call
the NETA office for details on CTD and CEU credits offered for attending
the virtual portion of PowerTest 2021. Be sure you register to ensure a spot
among the leaders in the electrical testing industry.
Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names,
trademarks or registered trademarks of their respective owners.
LOOKING AT
NFPA 70E 2021:
PA R T 1
Figure 4a: What He Tested Figure 4b: What He Should Have Tested
Deep Dive. Section 110.1 Priority was moved Some of the revisions being made are from the
from Article 105 to bring more prevalence to First Revision based on Public Comments or
it. The Committee believed it was a better fit Committee discussions. This is a fairly common
in 110, as we did with the other changes in occurrence and demonstrates the thought (and
section order. Some changes were made to its discussions) that go into all Public Inputs and
Informational Note: Public Comments. We always have a reason for
Ron Widup and Jim White are NETA’s representatives to NFPA Technical Committee 70E, Electrical Safety Requirements
for Employee Workplaces. Both gentlemen are employed by Shermco Industries in Dallas, Texas, a NETA Accredited Company.
Ron Widup, Senior Advisor, Technical James (Jim) R. White, Vice President
Services and Vice Chairman of the of Training Services, has worked for
Board of Directors, has been with Shermco Industries since 2001. He
Shermco Industries since 1983. He is a NFPA Certified Electrical Safety
is a member of Technical Committee Compliance Professional and a NETA
on NFPA 70E, Electrical Safety in Level 4 Senior Technician. Jim is NETA’s
the Workplace; a Principal Member principal member on NFPA Technical
of National Electrical Code (NFPA 70) Code Panel 11; a Committee NFPA 70E®, Electrical Safety in the Workplace;
Principal Member of the Technical Committee on NFPA 790, NETA’s principal representative on National Electrical Code®
Standard for Competency of Third-Party Evaluation Bodies; Code-Making Panel (CMP) 13; and represents NETA on
a Principal Member of the Technical Committee on NFPA ASTM International Technical Committee F18, Electrical
791, Recommended Practice and Procedures for Unlabeled Protective Equipment for Workers. Jim is Shermco Industries’
Electrical Equipment Evaluation; a member of the Technical principal member on NFPA Technical Committee for NFPA
Committee on NFPA 70B, Recommended Practice for 70B, Recommended Practice for Electrical Equipment
Electrical Equipment Maintenance, and Vice Chair for IEEE Maintenance and represents AWEA on the ANSI/ISEA
Std. 3007.3, Recommended Practice for Electrical Safety in Standard 203, Secondary Single-Use Flame Resistant
Industrial and Commercial Power Systems. Ron also serves on Protective Clothing for Use Over Primary Flame Resistant
NETA’s board of directors and Standards Review Council. He Protective Clothing. An IEEE Senior Member, Jim was
is a NETA Certified Level 4 Senior Test Technician, a State of Chairman of the IEEE Electrical Safety Workshop in 2008
Texas Journeyman Electrician, an IEEE Standards Association and is currently Vice Chair for the IEEE IAS/PCIC Safety
member, an Inspector Member of the International Association Subcommittee.
of Electrical Inspectors, and an NFPA Certified Electrical Safety
Compliance Professional (CESCP).
www.shermco.com l 888-SHERMCO
CAN’T AFFORD TO WAIT FOR
ELECTRICAL
EQUIPMENT?
When equipment fails, every minute spent searching for what you need is bad for the
bottom line. Our massive inventory of millions of new, surplus and repurposed circuit
breakers, switchgear and related products is here for you. We have the expertise to see
the big picture, understand your problem and recommend the best solution. Already know
exactly what you need? Our website is constantly being updated with products and the
online buying process is easy.
performance by design sm
RELAY COLUMN
COMBUSTION TURBINE
GENERATOR TRIP ANALYSIS
B Y S TE V E TU R N E R , Arizona Public Service Company
Relay personnel responsible for testing protective relays are often called
upon to troubleshoot and gather system data such as settings and event
recordings when a major event occurs (for this example, a large generator
trip). If only electromechanical relays are installed and no digital fault
recorder is available, it can be difficult to determine the root cause of the
trip event. This article demonstrates how to analyze a generator trip with
limited information on hand.
A N A LY S IS Figure 1 shows the sequence of events
The initial investigation determined there captured by the numerical line current
was a three-phase bus fault on the low side differential relays located at the high side of
of the generator step-up transformer (GSU). the generator GSU and switchyard breaker.
Follow-up investigation through data analysis The first event occurred at 19:02:56 and
determined there were four individual events. was due to a three-phase bus fault. The
Figure 1: Sequence of Events Compiled from Numerical Line Current Differential Relays
Figure 2: One Line Diagram Figure 3a: Three-Phase Bus Fault on GSU Low Side
Figure 3b: Direct Transfer Trip to Switchyard Breaker via Figure 3c: Disconnect on High Side of Adjacent GSU Opened
Numerical Line Current Differential Relays
Figure 3d: Lockout Relay Reset Figure 3e: Switchyard Breaker Closed
second and third events occurred at 19:09:17 Figure 3a through Figure 3e illustrate the
and 19:20:32, respectively. The fourth sequence of events leading up to the restoration
event occurred at 19:24:56. This time, the of the adjacent generator.
switchyard breaker was successfully closed,
energizing the adjacent GSU. The adjacent generator was brought back on
gear at time equal to 19:28:35.
C ON C L U S I ON
Steve Turner is in charge of system
Advantages offered by numerical protection protection for the Fossil Generation
relays include: Department at Arizona Public Service
Company in Phoenix. After working
with Beckwith Electric Company, Inc.
• Event reporting
for 10 years, Steve spent two years as a
• Event summary reports consultant in San Diego. His previous
experience includes positions as an Application Engineer
• Event history reports at GEC Alstom and in the international market for SEL
focusing on transmission line protection applications. Steve also
• Event reports worked for Duke Energy (formerly Progress Energy), where he
developed the first patent for double-ended fault location on
• Sequential events recorder report overhead high-voltage transmission lines and was in charge
of all maintenance standards in the transmission department
This article demonstrates how the event for protective relaying. Steve has BSEE and MSEE degrees
recording taken from the numerical line from Virginia Tech University. He has presented at numerous
conferences including Georgia Tech Protective Relay Conference,
current differential relays protecting the line to Western Protective Relay Conference, ECNE, and Doble User
the faulted GSU can be used to verify that the Groups, as well as various international conferences. Steve is
overall system protection operated properly. a senior member of IEEE and a member of the IEEE PSRC.
An extensive inventory of over 200,000 sq. ft. across the southeast means the Southland Group has the
products you need most in stock and ready to ship! Our team of experienced technicians provide on-site field
service support and engineering services to ensure that your products are safe, reliable and service ready.
Contact us today and let us create the solutions you need most!
V I S I T NE TAW O R L D J O U R N A L . O R G TO DAY
SAFETY CORNER
BASIC FALL
PROTECTION
B Y PA U L CH AM BERL AIN, American Electrical Testing Co. LLC
PHOTO: © ISTOCKPHOTO.COM/PORTFOLIO/IBRAVE
TECH QUIZ
No. 132
PROTECTIVE RELAYING
James (Jim) R. White,
Vice President of Training
Services, has worked for
Shermco Industries Inc. B Y JA M E S R . W H I TE , Shermco Industries
since 2001. He is a NFPA
Certified Electrical Safety
Compliance Professional This edition of Tech Quiz covers protective relays. Many years ago, as I was teaching
and a NETA Level 4 Senior a protective relay class, a student asked, “What are these things?” I replied, “Relays,”
Technician. Jim is NETA’s
principal member on NFPA to which he answered, “No, relays are those little black plastic things that go
Technical Committee NFPA click-click.” I made sure to call them protective relays from then on. Things in the
70E®, Electrical Safety in protective relaying field have progressed rapidly over the years, and digital protective
the Workplace®, NETA’s
principal representative on relays are now the norm as is digital test equipment.
National Electrical Code®
Code-Making Panel (CMP)
13, and represents NETA
1. One question always seen on the NETA 3. What does Figure 1 illustrate?
on ASTM International exams is about protective relay ANSI a. Mho relay characteristic
Technical Committee numbering. What is the protective relay b. Ohm relay characteristic
F18, Electrical Protective number for a synchronizing relay? c. Reactance relay characteristic
Equipment for Workers. a. 25 d. Offset relay characteristic
Jim is Shermco Industries’
principal member on NFPA
b. 32
Technical Committee for c. 52 X
NFPA 70B, Recommended d. 86
nZ L
Practice for Electrical
Equipment Maintenance 2. Which protective relay looks inside a
and represents AWEA on
the ANSI/ISEA Standard
generator?
203 Secondary Single-Use a. Distance relaying
Flame Resistant Protective b. Mho relays
Clothing for Use Over c. Ohm relays R
Primary Flame Resistant d. Loss-of-excitation relays
Protective Clothing. An
IEEE Senior Member, Jim
received the IEEE/IAS/PCIC
Electrical Safety Excellence Figure 1: Which Relay?
Award in 2011 and NETA’s
Outstanding Achievement
Award in 2013. Jim was
Chairman of the IEEE
Electrical Safety Workshop
in 2008 and is currently
Vice-Chair for the IEEE IAS/
PCIC Safety Subcommittee.
a. _____________________________ d
_____________________________ S1
b. _____________________________
a S1
_____________________________
c. _____________________________
_____________________________
d. _____________________________
_____________________________
c
1 5 7
2 6 8
= SHORT FINGERS
ener es ™
Accredited Company
GROUND
TESTING
PROCEDURES
BY J EFF J OW ET T, Megger
S I M P L IF IE D FA LL OF
PO T E N T IA L
Fall of potential is the best overall method,
but it requires considerable work and possibly
too much room to stretch leads. What then?
Other methods have been derived, some for the
purpose of saving time and others for dealing Figure 2: Comparison of Failed and successful FOP Graphs. The
with difficult test conditions. The first of these, continuously rising graph line (top) may include correct resistance
called simplified fall of potential, requires reading, but it is unrecognizable. The extended horizontal line in the
only three measurements rather than enough correct test (bottom) clearly identifies ground resistance.
to draw a graph line for possibly hundreds of reading at 62% may not be representative. It
feet. A simple and easy mathematical proof is accepted at the operator’s risk unless the site
substitutes for drawing the graph. The most has previously been proven by more rigorous
atypical of the readings is mathematically prospecting. The rule is a quick and handy
compared to the average and then calculated backup test on sites where distances and
as a percentage accuracy. The operator makes directions have been established by rigorous
a decision as to whether this is an acceptable testing. But a new test runs the risk of a gamble.
accuracy. If so, the average is submitted as the
test result. If all three readings were the same,
then this would provide added assurance. But Slope
non-homogeneity of soil, especially around The other reason for established test procedures
graded construction sites, often precludes this. is to effectively address difficult situations. The
main challenge is insufficient space in which
An obvious spinoff here is to dispense with to extend test leads far enough to separate the
any math and merely move the potential probe resistance field around the current probe from
back and forth a few times and decide whether that of the electrode being measured. A coherent
the readings fall reasonably well together. This FOP graph cannot be constructed, and the
could be referred to as the eyeball method. graph line continues to rise as more resistance is
It lacks genuine method but is probably the
added with each move of the potential probe. By
most widely used procedure, at least for less
far the most popular means of dealing with this
demanding locations. An experienced operator
issue is the slope method (Figure 3).
may indeed have sufficiently keen powers of
discernment, but if third parties are involved
If the graphed resistance line continues to rise,
(i.e. inspectors, clients, insurance, lawyers),
most likely the correct value is there somewhere
it may be more practical to do the math and
— it just can’t be discerned from viewing the
submit the report.
graph. Still, even a partial FOP graph can
come in handy. Only three measurements are
62% R ULE necessary for the proof. These are at 20%, 40%,
Finally, the 62% rule brings simplicity down and 60% of the distance to the current probe.
to its base level. Mathematics tracing back to From these three numbers, a slope coefficient,
the ancient Greek scholars supports the 62% typically referenced by the Greek letter μ, is
rule. But none of that is necessary to apply to calculated and referenced to a table commonly
ground testing. All the ground test operator available in the ground testing literature. As the
needs to know is that the 62% position on an slope coefficient represents the distance to the
FOP graph is the one that will give the most potential probe over the distance to the current
accurate reading. probe and the latter is known, the distance at
which the correct ground resistance reading
So why aren’t all ground test readings taken at should be taken is calculated by solving this
that position and be done with it? The answer simple equation: dp/dc = μ for dp.
is because the mathematics is based on an ideal
model, and few construction sites, industrial The actual ground resistance reading can then
sites, or anywhere else are likely to conform to be determined by either reading the graph line
ideality. Grading mixes topsoils from different or physically placing a potential probe at that
locations. The soil may be naturally stony. distance and taking the reading. But suppose
There may be a large subterranean rock, power the calculated μ value cannot be found on the
cable, water main, ground water, or other non- table? That would indicate the resistance field
uniformity to contend with. Put simply, the of the current probe is contained completely
Intersecting Curves
The fallback is intersecting curves. This is a
difficult and tedious procedure to be avoided
if possible, but it works when nothing else will.
Two sets of graphs are constructed. One set is
of three portions of FOP graphs working from
an edge of the grid. These will keep rising. If Figure 3: Typical Slope Method Layout
they did not, they would be complete FOP
graphs and intersecting curves wouldn’t be
necessary. But since these are not readable FOP
graphs, where is the 62% distance? For that, a
second set of graphs is constructed by selecting
arbitrary points for the electrical center of
the grid at a distance x from the connection
on the edge of the grid and then locating the
62% accordingly. The arbitrary values of x are
plotted against the 62% resistances on each of
the curves. These three graph lines will coincide
at one point (Figure 4) for the correct distance
of x from the true electrical center of the grid
to the point of attachment of the test lead(s) at
the edge. All other values for x are wrong (not Figure 4: Center of Triangle Formed by
the true electrical center), and so the resistances Graph Lines is Ground Resistance
will scatter, with only the correct resistance
being common to all three graphs.
Four Potential
Another problem associated with applying FOP
to large grids is that their shapes can become
more and more asymmetrical, rendering it
increasingly difficult to apply even a fair guess
as to the electrical center. Since these grids can
also have very low resistances, it is easy to fall
into incoherent results if a proven method isn’t
followed. A means of addressing this is the
four potential method, but unlike slope and
intersecting curves, it can require prohibitively
long leads. The tester is connected to an arbitrary
point on the edge of the grid. Leads are stretched
in a straight line, and six critical values are taken
at 0.2, 0.4, 0.5, 0.6, 0.7, and 0.8 of the distance
to the current probe (Figure 5). These results are
processed through four simple + and – formulae Figure 5: Typical Layout for Four Potential Method
Dead Earth
Finally, under the worst of urban conditions,
with virtually no room for leads or place to
drive probes, the two-point star delta test
becomes the only option. The second test lead
is attached to any convenient low-resistance
return: a metal fence post, building structure,
Figure 6: Star Delta Test Configuration or best of all, the water pipe system. Test
current circulates through the earth to the
that yield the correct ground resistance. The water pipe system or other connection and
four results should substantially agree, imparting back to the tester through a lead (Figure 7). A
confidence to the calculation. series loop is measured, and its success counts
on the return element being of negligible
resistance. This is commonly called the dead
Star Delta earth method because the return is not part of
Two methods remain for confines so tight an electrical system. It’s not especially accurate
that even minimal extension of current and or reliable, but sometimes it’s all that remains.
potential leads is prohibitive. One of these is
star delta. The tester is shunted into a two–
terminal configuration, either X – PC or CONCLUSI ON
C1P1 – P2C2. Modern testers have selector A ground test performed by random hookup will
likely yield some result, but it’s no more reliable
than rolling dice. Because the earth is so vast,
adherence to established procedure is mandatory.
Know the procedures, where and why they apply,
and results will be trustworthy and effective.
ADVANTAGES OF RENTING
• Cost-Savings Versus Buying
• Available for Immediate Delivery
• Choose From a Variety of Manufacturer’s
Top-of-the-Line Products
• Short-term Solutions for One-Off Tests
• Always Calibrated Equipment
ISO 17025 / NIST Cal / ANSI Z540
SF6 Analysis
Transformer Testing
Power Monitoring
Insulation Resistance/Megohmmeters
Photovoltaic Test
Infrared Cameras
AC and DC Hipots
888.902.6111
[email protected]
intellirentco.com
COVER STORY
CHALLENGES IN
TRANSFORMER
PROTECTION
TESTING
Pickup Testing
Even the simple differential element pickup
test, when performed manually, requires the
test designer to calculate the nominal operating
current amplitude, or tap, for each winding.
The currents on the winding are simply
increased from zero until the relay trips. The
pickup current value is then converted back to
per-unit and compared to the setpoint.
Slope Testing
For differential characteristic tests in the slope
region, the proper phase shift is determined
from the transformer three-line diagram. For
three-phase tests, balanced quantities of a given
multiple of tap and phase shift matching the
application are applied to two or more current
windings, which simulates a balanced load.
Currents on one side are then incrementally
increased until the differential element
operates. For tests of a single differential
element phase, realistic through-fault current
phasors must be calculated. Evaluating the
results of slope characteristic tests is not
straightforward as there is significant variation
in the restraint current calculation between
PHOTO: © ISTOCKPHOTO.COM/PORTFOLIO/MINEMERO
differential relay manufacturers such as the
maximum per-unit phase current, minimum
per-unit phase current, average per-unit
phase current, sum of the per-unit phase
currents, or other calculations. In addition,
CHALLENGES IN TRADITIONAL some differential relays incorporate a reference
FUNCTIONAL TESTING winding in the restraint calculation that can be
A traditional functional test assures that all fixed or calculated automatically.
measurements and derived quantities are
measured and calculated accurately, and that If the simulation of single-phase faults is
the overall relay hardware — including inputs desired, calculation of test values is more
and outputs — function properly. Therefore, complex, and the relay’s method of zero-
the test quantities of a traditional functional sequence elimination must be considered. To
test are defined as a sequence of steady- simplify this process, dedicated software tools
state or phasor values. This type of testing is exist that calculate the required steady state
Differential/Operate Current
harmonic in any phase to restrain all phases.
2
However, other devices use cross-phase
pe
Slo
averaging, where the average even harmonic
content in all phases is used to restrain the Trip Region
differential in all phases, which can substantially 1
pe
complicate testing. In these cases, test operators 5th Harmonic Pickup Slo
Restricted Earth Fault Figure 5: Restricted Earth Fault on Transformer Phase (left); Resultant
Phasor Diagram (right)
Restricted earth fault, or ground differential
elements are gaining popularity. Related to
the transformer differential element, restricted Functional testing of these schemes requires
earth fault elements protect against faults the test designer to properly calculate phase-
occurring near the neutral end of wye-connected current phasors for internal and external faults
transformer windings. In these schemes, the to check proper operation. Additional logic is
calculated zero sequence current from the wye also incorporated to create operating windows
winding phase currents is compared to the and provide protection when the transformer is
measured ground current (Figure 5). energized from one side only.
can be derived from the short-circuit voltage compensation winding, and neutral grounding.
on the nameplate. However, the simulation of Figure 6a – Figure 6f show how these factors
ground faults requires reasonable zero-sequence affect the zero-sequence equivalent circuit
short-circuit impedances for the transformer of a two-winding transformer. P, S, M,
that are not always available on the nameplate. N, and C in the figure subscripts denote
The zero-sequence impedance is influenced primary, secondary, magnetizing, neutral, and
by the core type, vector group, presence of a compensation, respectively.
Saturating Core
Figure 7: Splitting Faulted Coil of Wye Winding into Two All differential relays must incorporate features
Parts (left) and Faulted Coil of Delta Winding into Three to provide security during magnetizing inrush
Parts (right). and transformer overexcitation, both sources
of significant differential current during these
events. To achieve realistic simulated waveforms
for these phenomena, the non-linear saturation
characteristic of the transformer core must be
simulated. Therefore, an iterative approach
for inclusion of non-linear inductors into the
solution is utilized.
Figure 10: Time Domain Plot from a System-Based Testing Case Illustrating Inrush and Resultant
CT Saturation
other, the differential element might not be without adding complexity. Line protection
sensitive enough; a negative sequence element systems where the transformer is within the
might pick up this type of fault. protected zone can also be easily tested.
CALL FOR
SPONSORS
View available
sponsorship items
at powertest.org
Promote your products and services to Take advantage of print and media exposure
a valuable audience of key industry to your target market before, during, and
decision makers while increasing after the conference by customizing your
brand visibility. sponsorship package to suit your needs.
INVESTIGATING AN
ELECTROMECHANICAL
DIFFERENTIAL RELAY
MISOPERATION
B Y A L E X R ANG EL , Saber Power Services, LLC
TRANSFORMER
DI FFERENTI AL
PROTECTI ON USI NG
ELECTROMECHANI CAL
RELAYS
Transformer differential protection was
originally performed using electromechanical
Figure 2: Bus Differential Protection Scheme relays. Many of these devices are still in service
today and are now available with digital relays
as well. These electromechanical relays require
a set of currents at each side of the transformer
(restraint currents) to undergo physical
summation (operate current) to determine
the fault location (internal or external) using a
percentage characteristic method. For a detailed
explanation of this method, refer to the ABB
Type HU and HU-1 Transformer Differential
Relays Instruction Manual. Figure 3 shows the
restraint and operate currents in a differential
electromechanical relay.
Figure 3: Differential Protection Using an Electromechanical Relay
(Simplified) One of the biggest challenges in transformer
It is important to note that CT polarity in differential protection is the delta-wye
these systems plays an important role: The CTs grounded transformer configuration, which
must be installed and wired so that the total is widely applied. In this configuration, the
current summation adds up to zero on load delta-side windings connect one side of a given
and external faults. This is only possible if the winding (i.e. the polarity side) to the opposite
CTs at each end of the apparatus have opposite side of an adjacent winding (i.e. non-polarity
side). With this connection type, currents Note: Proper tap selection must be considered
entering the delta side of the transformer in transformer differential protection. However,
are considered to be phase-to-phase, while in the misoperation being analyzed here, TAP1
currents exiting the wye-grounded side of the and TAP2 were properly selected and did not
transformer are considered to be phase-to- contribute to the issue. Therefore, they will not
ground with all three of the latter windings be discussed further.
grounded on one side. This configuration
creates a 30-degree phase shift between the Figure 5 shows the proper CT configuration to
low- and high-voltage currents, which must be used for transformer differential protection
be considered to properly apply transformer with electromechanical relays. Due to the
differential protection. Figure 4 shows the opposing CT polarity, the restraint currents
phase-angle relationship between the delta- entering the relay are 180 degrees apart.
and wye-grounded primary currents (A phase
shown only). For a more detailed analysis, refer
to Amberg and Rangel’s Tutorial on Symmetrical EXI STI NG SYSTEM
Components. The system discussed in this paper consists of
two incoming 138 kV transmission lines; each
line feeds a 138 kV breaker. Each breaker then
C U R R E N T C OM P E NS AT ION feeds a 25 MVA, 138 kV/12.47 kV transformer.
A N D E L E C TROM E C H A NIC AL On the low-voltage side, each transformer feeds
R E L AY S a 12.47 kV breaker, which then feeds a 12.47
The previous section described a 30-degree kV bus (identified as bus A and bus B). Each
phase shift between both sides of a transformer. bus provides power to three different feeders
To cancel out the CT secondary currents (and (identified as 1, 2, and 3 on bus A and 4, 5, and
satisfy KCL), this shift must be addressed by 6 on bus B). A connection between bus A and
wye-ground connecting the CTs on the delta bus B exists through a tie breaker connected to
side while delta connecting the CTs on the wye- both buses.
grounded side. This CT delta configuration
creates phase-to-phase secondary currents and CTs on the high-voltage side of the
therefore rotates the phase angles by 30 degrees. transformer are wye-ground connected (CT
With this final shift, both sets of secondary ratio of 100:5), while CTs on the low-voltage
currents have a phase angle difference of 180 side of the transformer are delta connected
degrees. (CT ratio of 1200:5). Since the 12.47 kV
Δ Y Δ
Y
Δ
Δ
Δ Y Δ
Y
TROUBLESHOOTI NG
Site personnel identified the ground fault
downstream of feeder 5, determined that both
87 relays had misoperated, and requested
assistance from a third-party testing company
to investigate the reason for the misoperations.
The relay flags had been cleared, the lockout
relays had been reset, the 138 kV breaker on
the A side was closed (the system became
Figure 7: C-Phase to Ground Fault on Feeder 5
Figure 8: Current Testing at Feeder 5 Breaker Figure 9: Tie Breaker CT Terminal Blocks,
(Simplified) Shorting Screws Inserted
NCSCB Certified Cable Splicers | VLF-TD & PD Cable Testing & Analysis
For more information about Group CBS and its affiliate companies, visit GroupCBS.com. CircuitBreaker.com
© 2019 HVM CORP. All rights reserved. HVM and the HVM logo are trademarks or registered trademarks of HVM Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution
has been taken to ensure accuracy and completeness herein, HVM Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
PRESENTED BY PRESENTED BY
PHOTO: © ISTOCKPHOTO.COM/PORTFOLIO/DEEPBLUE4YOU
ṽ v
saturation can then be mathematically converted
back to an equivalent 50 Hz/60 Hz saturation.
+ This will then achieve the same result as the
t t conventional AC excitation test technique.
–
Figure 2 shows an excitation test result with
a knee-point voltage of around 14 kV. The
Figure 1: The area under the curve is flux generated using the AC and advantage of the DC method is to eliminate the
DC method. need for higher levels of AC voltage and achieve
the same results by utilizing a DC voltage at or
The integral of voltage over a period of time below the available line voltage. The technique
would be a measure of flux (Φ) produced as allows testing CTs with higher knee-point
shown in equation (1). It can be generated by voltages using the same concept with a slightly
using AC or DC excitation voltage. The area longer test duration. Additionally, lower levels
under the curve reflects the flux produced as of DC test voltage allow safer testing conditions
shown in Figure 1. and a portable, lightweight instrument ideal for
field conditions.
Flux can be increased by utilizing either of the
two methods. Either the time period can be CT demagnetization is an important step to
kept constant as the voltage is increased, or the ensure that the core has no residual magnetism.
voltage can be kept constant with an increase This can be achieved by reducing the hysteresis
in time. The conventional method used by the loops starting from saturation through a series
industry over the years has been to keep the time of similar DC excitation reoccurring cycles in
period constant (or fixed frequency at 50/60Hz) opposite directions with progressively reduced
as the voltage is increased. Alternatively, the magnitudes.
DC voltage can be kept the same and the time
can be prolonged until the core is saturated. By
integrating the constant DC voltage over time, CONCURRENT TESTI N G
the core saturation can be determined. This TECHNI QUE
The conventional testing method works on
the concept of keeping the primary circuit
open, applying an AC voltage to the secondary
winding, and measuring secondary voltage/
current along with primary voltage values to
obtain test parameters such as ratio, polarity,
winding resistance, and excitation characteristics
curve. For a multi-tap CT, these tests are repeated
for each tap either through a manual operation
or by utilizing an automatic switching technique.
(2)
(3)
REFERENCES
IEC 60044-6, Instrument Transformers Part
6: Requirements for Protective Current
Transformers for Transient Performance.
Figure 7: Testing CT with High Knee-Point IEEE C57.13.1-2006, Guide for Field Testing
Using the DC Method of Relaying Current Transformers.
United States Patent: Concurrent Transformer
line power value to achieve core saturation
Test System and Method. Patent No. US
characteristics for these types of CTs.
9,128,134 B2, Date of Patent: Sep. 8, 2015.
C ONC LUSION
Dinesh Chhajer manages Megger
It is vitally important to test protection class
USA’s Technical Support Group.
CTs during installation and periodically
His responsibilities include
thereafter to ensure they work as intended
providing engineering consultation
for power system protection applications.
and recommendations in relation
The tests recommended for CT testing in to testing of transformers, batteries,
the industry standards are well established. circuit breakers, and other substation assets. Dinesh
However, methods used to perform those tests has presented numerous white papers related to asset
are evolving. maintenance and testing at various conferences
within power industry. Dinesh previously worked as
Efforts are being made to create safer operating an Application Engineer at Megger and a substation
conditions, test special-application CTs, and design Engineer at Power Engineers Inc. He
and improve the efficiency and productivity is an IEEE member and a licensed Professional
of the test system through automation, Engineer in Texas. Dinesh received his MS in
intelligent data processing, and developing electrical engineering from the University of Texas
smart algorithms utilizing basic principles of at Arlington.
transformer operation and electromagnetics.
Sughosh Kuber is a Relay and
New measurement techniques proposed in this Protection Applications Engineer
article, although unique, utilize the concepts at Megger North America, where
well-described in electrical textbooks. DC he provides technical support to
excitation and the concurrent method of service companies and utilities
testing offer an alternative approach for testing responsible for reliable operation
CTs that provides the same measurements of electrical networks. Sughosh brings over 9 years
and results as conventional techniques of field experience and academic research in power
recommended in various international systems from protection schemes and testing to data
standards. The comparative analysis between analysis for energy efficiency and sustainability.
different methods indicates that DC excitation Sughosh received his MS in electrical engineering
and the concurrent method of testing can from New Mexico State University.
CALL FOR
EXHIBITORS
Exhibit to an audience of 500+ electrical For attendee profile and additional
testing professionals including leading information, visit powertest.org
decision-makers looking for new products
and services.
Visit www.belyeapower.com
to nd the parts you need.
Electro Mechanical Relay Bushings
Substation Equipment Arresters
Grounding Resistors Gauges
Motor Controls Fuses
CT’s and PT’s And More....
A Wide Range of
R
➤ Bluetooth connection
to Android devices
➤ Bluetooth to
battery printer
➤ Android App
included
40+ Years
Experience High Voltage - High Current - High Power Test Systems and Components
FEATURE
Rapid photovoltaic (PV) penetration into the electric grid has mandated
deeper operational and technical understanding of protection schemes
in PV farms. An effective protection scheme ensures a grid-connected
system functions reliably and securely, and testing and commissioning the
entire protection scheme to prove its operational success is of paramount
importance. This article presents a standard grid-tie photovoltaic farm
architecture and discusses how to restore the system to regular operation
using reclosing schemes.
72 • WINTER 2020 TESTING AND COMMISSIONING A DISTRIBUTION RECLOSER IN GRID-TIE SOLAR FARMS
FEATURE
NETAWORLD • 73
FEATURE
74 • WINTER 2020 TESTING AND COMMISSIONING A DISTRIBUTION RECLOSER IN GRID-TIE SOLAR FARMS
FEATURE
Table 1: Response Requirements to Abnormal Voltages
Voltage Range Clearing Time Allowable Clearing Time
(% of rated voltage) (seconds/cycles) (seconds)
Grid Voltage > 120 0.16/10 Max 0.16
Grid Voltage > 110 2.0/125 1.0 to 13
Grid Voltage < 0.7 2.0/125 2.0 to 21
Grid Voltage < 0.45 0.16/10 0.16 to 2
SOURCE: IEEE STD. 1547-2018
During fault conditions, grid voltage (line disconnection and reconnection of the solar PV
side of the recloser switch) could experience farm to maintain production while the solar
excursions outside of normal operating values PV injects the maximum power available. The
resulting in power fluctuations. Therefore, recloser sequence should be coordinated with
the standard recommends two levels of the local area EPS since automatic reclosing
undervoltage and overvoltage. To comply, onto a circuit needs approval from the affected
system voltage on the utility side of the recloser utility. Abnormal conditions should result
must be monitored. The MV recloser switch
controller chosen for this article is capable
Overvoltage (59)
of receiving six voltage inputs. Three inputs
are from the utility side, sourced from three Undervoltage (27)
0.5 kVA distribution transformers; three inputs Over frequency (81O)
are from the generating side, sourced from OR
three low-energy capacitive voltage sensors Under frequency (81U)
OR
When an MV recloser switch operates and Relay Sleep Mode
isolates a PV farm from the grid, a relay
mechanism must guarantee reconnection once
Battery Fail
grid conditions are normal and healthy voltage
is established. Schemes involving automatic
reclosing (Figure 3) can ensure proper Figure 3: MV Recloser Switch Relay Trip Conditions
Test Values
Channel Phase Ramp
Magnitude Ø (*) f (Hz)
Voltage A-N Amp 100.300 V 0.00 60.00
Voltage B-N Amp 100.300 V 120.00 60.00
Voltage C-N Amp 100.300 V 240.00 60.00
76 • WINTER 2020 TESTING AND COMMISSIONING A DISTRIBUTION RECLOSER IN GRID-TIE SOLAR FARMS
FEATURE
the dwell time is also crucial in this performed to check whether the
application since undervoltage elements reclosing logic works as intended
are associated with time delay. Figure 5 and the recloser goes to lockout state
shows that the time delay between each if any permanent fault exists. For
increment is kept higher than 100 cycles. the reclosing cycle to be initiated,
the controller provides the ability to
• Timing Test. This timing test can be
set logic equations as a setting. This
done using two state sequences. The
setting is a rising-edge detect setting
first state can be set to simulate nominal
and is supervised by recloser status.
load conditions with a specified time
It is usually programmed to trigger
duration; the second state can be set as
when the trip condition goes true.
a sudden drop in voltage to simulate the
Additionally, the controller under test
undervoltage fault condition. Figure 6A
has independent settings for single-
and Figure 6B show the setup. Refer to
pole and three-pole operation mode.
Table 4 for results. Similarly, overvoltage
Special attention is needed to set the
tests can be performed.
test template to work as per the set
• Reclosing Elements operation mode.
0 Unsuccessful reclose test. As the The scheme uses a three-phase
name indicates, this test can be recloser capable of tripping and
closing all three phases in unison. It
is designed for just one reclose shot
before going to the lock-out state in
case of a permanent fault.
Popularly, state sequencer is used
to design a test template to validate
Figure 6A: Undervoltage Level-1 Timing the auto-reclosing sequence in the
Test Setup: Load Condition State MV recloser switch controller. Both
controller and recloser on the pole
can be simultaneously tested. Any
modern test equipment with an
interface to connect the control cable
can be used. In a situation where only
Figure 6B: Undervoltage Level-1 Timing Test controller testing is desired, there is
Setup: Fault Condition State no need for special equipment with
78 • WINTER 2020 TESTING AND COMMISSIONING A DISTRIBUTION RECLOSER IN GRID-TIE SOLAR FARMS
FEATURE
the main contacts and opens the • Frequency Elements
low-voltage closing circuit of the
Both underfrequency and overfrequency
recloser. The status of the handle is
elements must be tested for their pickup
provided through the control cable level and operation time. These elements
to the controller. The contacts in the are independent in the controller and
trip/close circuits open and stay open follow a definite time operation concept
when the respective external handles where the timer starts the moment pickup
on individual poles are pulled to lock- is reached and stops after the set operation
open positions. In many situations, time irrespective of the frequency level.
just one of the opto-isolated wetting It is crucial to know the unit (cycles or
inputs of the controller monitors seconds) of the set time before advancing
the combined status of the handle to all the tests.
for individual recloser poles. The
controller drives to three-phase For pickup tests, frequency ramp is done
lockout after sensing a time-qualified with a long sequence to control the phase
rising edge on that input. angle at each step of the sequence to
create a smooth waveform and not one
Binary outputs on any modern test with jumps. The formula to calculate
equipment can be used to mimic phase shift to obtain smooth is based
the handle status when the recloser on the rotating phasors with different
breaker is not connected to the pulsation (frequency).
controller. Simulating a closed contact
condition to that wetting voltage Vectors A1 and A2 in Figure 8 represent
input indicates a normal system, present and future frequency vectors. The
whereas an open contact condition algorithm is recursive and is based on
provides a handle operation state to calculating the phase angle of the phasor
the controller. State 1 and state 2 in with higher frequency to make sure that
when the frequency needs to change, the
the test software can be designed in
previous frequency and new frequency
the same fashion as an unsuccessful
vectors are overlapped indicating a
reclose test with an addition of
continuous transition.
providing closed binary output status
for the yellow handle. State 3 should The time from one step to another must
have open binary output. be deterministic to calculate the phase
A1 ϕ 1 (t) = ω1t
ϕ2 (t) = ω2t – ϕ0
A2 At t = t1 ϕ 1 = ϕ2
80 • WINTER 2020 TESTING AND COMMISSIONING A DISTRIBUTION RECLOSER IN GRID-TIE SOLAR FARMS
FEATURE
Commissioning and
Interoperability Tests
This group of tests includes field tests that
are useful to check system operation and
interoperability — that is, the dynamic
response of grid-tie inverters and recloser
switch at the point of common coupling
(PCC).
Step 1. Verify system components. A field Figure 11: Underfrequency Pickup Test Results
commissioning group must verify the
engineering parameters and confirm proper
programming for the inverters and recloser
control settings. Test results should be
documented to comply with ANSI/NETA
ATS and coordination study requirements. The
local SCADA system should provide the status
of each inverter.
800.331.2002 | PotomacTesting.com
INDUSTRY TOPICS
IMPACT OF SFRA
SETUP ISSUES ON
TRANSFORMER
FREQUENCY
RESPONSE
B Y M ICH AEL D. W OL F, P E, Doble Engineering Co.
PHOTO: © ISTOCKPHOTO.COM/PORTFOLIO/YOUR_PHOTO
the entirety of the trace and may be seen across Poor Test Lead Connections
the high-voltage open circuit (HVOC), low- When test leads are poorly connected to
voltage open circuit (LVOC), and high-voltage
the bushing terminals, extra impedances
short circuit (HVSC) traces. The traces may
are introduced into the measurement lead
appear jagged, noisy, shifted to a higher (-)dB,
circuit. These additional impedances cause
and may not follow an expected shape.
the characteristic impedance of measurement
cables to change, which will impact the
Poor connections on the test lead ground clamps
response of the transformer. These impedance
can also produce wide-ranging changes in the
changes impact a wide range of frequencies and
response and will most likely be apparent when
comparing phases in a given test session. If will yield poor comparison to prior traces with
the test lead ground clamp is not adequately good lead connections.
grounded, the impedance of the test lead
changes, impacting the higher frequencies of the In the traces shown in Figure 2, the red trace
swept range. The impact can move further down was captured initially. Noting the jagged
the frequency range with worsening ground lead nature of the trace, the tester determined
connections. These seemingly minor changes that troubleshooting was required. Bushing
to the grounding circuit can make dramatic terminal connections were cleaned thoroughly
changes similar to that shown in Figure 1. In less with a wire brush and solvent. After ensuring a
significant cases, the changes may begin much robust metal-to-metal connection between the
higher in the frequency range. test lead clamps and the bushing terminals, the
blue trace was captured. The resulting response
In Figure 1, the blue trace was captured during follows an expected shape with less jagged
routine testing. The tester identified something features.
was wrong and began to troubleshoot. The
connections at the test lead grounds were
cleaned up with a wire brush to ensure solid Varying Tap Changer Positions
metal-to-metal contact. This resolved the initial When load tap changers or deenergized tap
issue and resulted in the red trace. changers (DETC) change position, the way
the tapped winding interacts with the various they are in the same positions as previously
RLC networks of the transformer will change. recorded traces prior to testing to ensure no
This interaction will impact the response of additional uncertainties are introduced into the
the swept frequencies through the transformer, analysis. It should be noted that changing taps
and different tap positions will cause different on one specific winding will not only impact
responses. The extent of the differences will that winding’s response, but may also impact the
depend on the specific design of the transformer responses of other windings; for example, low-
and the tap positions being compared. Tap voltage open circuit traces may also change upon
changers should always be checked to ensure DETC position change on the high-voltage
winding. This is due to the changing interaction can cause the transformer’s response to change.
between the RLC components of the high- Some stabilizing tertiary windings may come out
voltage and low- voltage windings. to a single bushing at one corner of the delta,
which could be either grounded or ungrounded
In the example in Figure 3, the prior (red) trace while the SFRA tests are performed on the
and the present (blue) trace were tested before primary and secondary windings. Some stabilizing
and after a planned DETC position change. The tertiary windings have one corner of the delta
transformer was fully tested before the DETC brought out to two bushings, which can either be
was moved to ensure it was in good condition shorted and left floating, shorted and grounded,
and aligned with prior results. The unit was then open and floating, or open and grounded. These
tested after the DETC was moved to attain new changes will impact the interaction of the circuit
baseline results. After changing DETC positions, elements that make up the RLC network inside
new SFRA baseline traces should always be the transformer and will result in variations
captured to enable future analysis. to the response while performing SFRA tests.
The changing response will most likely be seen
In Figure 4, the red trace was captured just before in traces captured on all windings within the
a DETC change; the blue trace was captured transformer, to varying degrees on each winding.
immediately after a change. Notice how the
changes are far less drastic than in Figure 3, which In the example shown in Figure 5, the prior (red)
emphasizes how important the specific design of HVOC trace and the present (blue) HVOC traces
the transformer is to the degree responses may were found to have different characteristics upon
change when changing tap positions. review in the field. After troubleshooting, it was
determined that the stabilizing tertiary winding
was in a different configuration when tested in
Stabilizing Tertiary Winding the factory compared to the configuration when
Configuration first assembled in the field. The tertiary was
Much like the impact varying tap positions may manipulated to be open, open and grounded,
have on a transformer’s response, manipulating closed, and finally closed and grounded to ensure
the configuration of a stabilizing tertiary winding that a matching configuration was found. After
TRANsFoRmER AIR-CELL
CoNsERVAToR BLADDERs
MADE IN
THE U.S.A.
FOR OVER
45 YEARS!
THE ® DIFFERENCE...
ExPEDITED DELIVERY
ULTRA-FAsT TURNARoUND - 2 To 3 DAY AVERAGE!
sTANDARD TEmPLATEs
DIGITAL LIBRARY oF PoPULAR sIzEs/sTYLEs!
REVERsE ENGINEERING
ATL CAN PRECIsELY DUPLICATE ANY BLADDER!
sTANDARD & CUsTom HARDwARE
mETALLIC FLANGEs, HANGER LooPs & moRE!
® CUsTomERs INCLUDE:
ABB Inc. - G.E. / Alstom Grid - Atlantic Transformer
CG Power USA - Calpine - Duke Energy - First Energy ULTRA-sTRoNG
Gexpro - Jacksonville Electric Authority - NASS - PSE&G “oVER-LAP”
Siemens - SPX Transformer Solutions & Many More! sTYLE sEAms ®
BLADDER DEsIGN GUIDE AVAILABLE oN oUR wEBsITE
800-526-5330 +1-201-825-1400 www.atlinc.com
INDUSTRY TOPICS
UNDERSTANDING
AND AVOIDING
BATTERY
FAILURE
B Y R ODRICK J . VAN WART, AVO Training Institute
PHOTO: © ISTOCKPHOTO.COM/PORTFOLIO/ETAJOE
that reduced — or no — back-up will be Maintenance costs are higher, but this is
available when needed. Using batteries to the cost for a reliable back-up system. The
back up important installations without any best testing scheme is a balance between
idea of their current health invalidates the maintenance costs and the risks of losing
whole concept of a reliable system. the battery and supported equipment.
Each company is different, and each must
2. Replace after a certain time with
individually weigh the cost versus risk of
minimum or no maintenance and testing. battery maintenance
This can also be a risky approach. It is also a
waste of capital if the batteries are replaced The batteries in any UPS require routine
earlier than needed. Properly maintained inspection and maintenance regardless of their
batteries can and do live longer than the age or warranty status — even maintenance-
predetermined replacement time. free batteries are only deemed maintenance-free
because they do not require adding water on an
3. Implement a serious maintenance and as-needed basis. Industry studies have shown
testing program to ensure the batteries that up to 20 percent of UPS failures can be
are in good condition, prolong their attributed to bad batteries; temperature and
life, and determine the optimal time for cumulative discharges including micro-cycling
replacement. A maintenance program are the primary culprits. When performing
including inspection and impedance preventive maintenance, data is obtained
and capacity testing is the way to track a from ohmic testing procedures during which
battery’s state of health. Degradation and impedance or conductance measurements trace
faults will be found before they become battery performance and identify any batteries
serious, and surprises can be avoided. with potential internal failures.
Everything looks good (left) until closer inspection reveals that sulfation has caused the plate to expand
and breach the container (right).
• Plate sulphation is an electrical path specific gravity of the acid gets too low, the
problem. A thorough visual inspection lead dissolves into it. Since the liquid (and
in vented lead acid (VLA) batteries can the dissolved lead) are immobilized by the
sometimes find traces of plate sulphation. glass matte, when the battery is recharged,
Sulphation is due to low charger voltage the lead comes out of solution and forms
settings or incomplete recharge after an threads of thin lead metal, known as
outage. Sulphates form when the volts per dendrites, inside the matte. In some cases,
cell (VPC) are not set high enough during the lead dendrites short through the matte
recharge. Sulphation will lead to higher to the other plate. The float voltage may
impedance and a lower capacity. drop slightly but impedance can detect this
failure mode easily.
• Dry-out is a phenomenon that occurs
primarily in valve regulated lead acid • Thermal run-away occurs when a battery’s
(VRLA) batteries due to excessive heat internal components melt down in a self-
(lack of proper ventilation), high ambient sustaining reaction. The impedance and
temperatures, and overcharging, which can float current increase in advance of thermal
cause elevated internal temperatures. At run-away. Thermal run-away is relatively
elevated internal temperatures, the sealed easy to avoid simply by using temperature-
cells will vent through the pressure relief compensated chargers and properly
valve (PRV). When sufficient electrolyte ventilating the battery room or cabinet.
is vented, the glass matte is no longer in Temperature-compensated chargers reduce
contact with the plates, thus increasing the charge current as the temperature
internal impedance and reducing battery increases. Remember that heating is a
capacity. This failure mode is one of function of the square of the current. Even
the more common failure modes of though thermal run-away may be avoided
VRLA batteries and is easily detected by by temperature-compensated chargers, the
underlying cause is still present.
impedance testing.
• Soft (aka dendritic) shorts and hard
shorts occur for a number of reasons. Hard CONCLUSI ON
shorts are typically caused by paste lumps Systematic inspections and an effective
pushing through the matte and shorting preventive maintenance plan can ensure
out to the adjacent (opposite polarity) standby battery systems are capable of
plate. Soft shorts, on the other hand, are supporting the critical role UPS systems play
caused by deep discharges. When the in maintaining power to critical loads.
We are Your
Protective
Relay Solution
Largest inventory of protective
relays in the country
Dedicated group of 8 relay
specialists
Upgrade support
All relays are supplied in
like-new condition, tested, and
with a 1-year warranty
PRESENT
sertecrelays.net
INDUSTRIAL ELECTRONICS
ST W
TE O
N
Toll Free
877-TRIP-FIX
PF MEASUREMENTS
ON COMPLETE
PHOTO: © ISTOCKPHOTO.COM/PORTFOLIO/KOPITINPHOTO
Figure 2: Electric Field Distribution: (left) without EPG, (right) with EPG Various compounds are used for EPG, and
each of them has its own conductive behavior.
The chosen material will remarkably affect
I power factor values when voltage is increased
above voltage breakdown (VBD), which is
usually significantly lower than the rated line-
to-ground (L-G) voltage of the machine.
PD HYSTERESI S
G U A R D IN G F OR Modern power factor test instruments are now
I N D IVID U AL B A RS/C OILS able to record as many points as necessary
The power factor tip-up test is commonly used and take measurements during the decreasing
for quality control on newly manufactured voltage stage of the test. Instead of simply
coils and bars. Depending on the measuring the tip-up value between two points,
manufacturer and on customer requirements, instruments can now record many data points,
it can be performed on each coil/bar or on enabling visualization of the power factor
samples of a production lot. voltage sweep curves. These curves can be used
to extract additional information and enhance
To remove the influence of EPG, various diagnostic capability.
guarding techniques are used in the factory that
cause the test to become more sensitive to the
void content within the bulk insulation and less
sensitive to the conduction behavior of EPG.
Figure 5 shows a schematic of one guarding
technique; Figure 6 illustrates the difference
between measurements on a single coil with
and without guard electrodes. Guard electrodes
are not perfect, and a small contribution of
surface currents is usually still measurable even
with some guarding techniques.
4,00 4,00
Tan Delta [%] Tan Delta [%]
3,50 3,50
2,50 2,50
% 2,00 % 2,00
1,50 1,50
1,00 1,00
0,00 0,00
0
1000
2000
3000
4000
5000
6000
7000
1000
2000
3000
4000
5000
6000
7000
V V
Figure 6: PF Voltage Sweep Curves: (left) without Guard Rings, (right) with Guard Rings
3,50
Power factor (%)
3,00
PF MEASUREMENTS ON COMPLETE STATOR WINDINGS
2,50 NETAWORLD • 101
2,00
%
ADVANCEMENTS IN INDUSTRY
PD usually occurs above a certain voltage not all PD activity will exhibit this behavior.
level and results in small current impulses For example, corona-type PD is known to have
that create additional losses. Two parameters similar PDIV and PDEV values and therefore
are commonly measured during offline PD will
4,00
not exhibitTanthe hysteresis curve. Figure 7
Delta [%]
4,00
winding
3,00
with high inner PD activity; Figure 3,00
activity.
1,00 1,00
b) PD extinction voltage (PDEV): the voltage 0,50 Without guard rings 0,50
1000
2000
3000
4000
5000
6000
7000
0
decreased.
4,00 help
4,00 the test operator visualize whether the
Tan Delta [%] Tan Delta [%] V
3,50 increase
3,50 in power factor, with respect to the
In4,00many cases, PDIV is higher than PDEV. 4,00
With guard rings
3,00 Tan Delta [%] voltage,
3,00 is due to partial
Tan Delta [%] discharges or simply
This
3,50 means that, for a winding with high PD 3,50
2,50 the
2,50normal conduction behavior of EPG.
3,50
activity,
3,00 losses can be higher when the voltage 3,00 Power factor (%) With guard rings
% 2,00 % 3,00
2,00
is 1,50
decreased versus when voltage is increased.
2,50 2,50
1,50
2,50
It is believed this behavior creates so-called
% 2,00
1,00 MACHI NE CONSTRUCTIO N
% 2,00
1,00
2,00
PD 1,50 hysteresis in PF curves when performing
% 1,50
0,50 Without guard rings Machine construction can significantly
0,50
an0,00upward and a downward voltage ramp. In
1,00
1,50
1,00
influence the expected PF results for traditional
0,00
various measurements, thisWithout correlation
guard rings was 1,00
0
1000
2000
3000
4000
5000
6000
7000
1000
2000
3000
4000
5000
6000
7000
0,50 0,50
tip-up values and for PF voltage sweep curves.
confirmed
0,00 between PD activity V and a hysteresis 0,00
0,50 A-BCG V
0
1000
2000
3000
4000
5000
6000
7000
2000 1000
4000 2000
6000 3000
8000 4000
10000 5000
12000 6000
14000 7000
of PF curves. It is important to mention that 0,00
V When performing PF measurements
0 V on a clean
3,50 and healthy stator winding V that does not have
Power factor (%)
3,00
3,50
an EPG area, no significant increase of losses
2,50 Power factor (%) with respect to increased voltage is expected.
3,00 0,90
2,00 A0,85stator winding with rated
Power factor (%) voltage of 6 kV
2,50
%
1,50
and0,80 below is an example of a machine that
2,00
% 1,00
does
0,75 not have an EPG area. However, some
1,50
manufacturers
0,70
have started to install EPG on
0,50 A-BCG % 0,65
1,00 machines
0,60
operating at lower voltage, especially
0,00
0,50 A-BCG if 0,55
they are inverter fed. Figure 10 shows the
0
2000
4000
6000
8000
10000 10000
12000 12000
14000 14000
0,00
V
results
0,50
of a healthy and clean 4.16 kV machine
A-BCG
0,45
0
2000
4000
6000
8000
1000
2000
3000
4000
5000
6000
7000
8000
Inner
0,90
PD Activity
Power factor (%) V
0,85
0,90
0,80 2.00
Power factor (%) Power factor (%)
0,85
0,75 1,80
0,80
0,70 1,60
% 0,75
0,65 1,40
0,70
0,60 1,20
% 0,55
0,65 % 1,00
0,60
0,50 0,80
A-BCG
0,55
0,45 0,60
0,50
0,40 0,40
A-BCG A-BCG
0
1000
2000
3000
4000
5000
6000
7000
8000
0,45 0,20
0,40 0,00
V
0
1000
2000
3000
4000
5000
6000
7000
8000
1000
2000
3000
4000
5000
6000
7000
8000
2.00
V (%)
Power factor V
1,80
Figure
2.00
1,60 8: PF Voltage Sweep Curve with Some Figure 9: PF Voltage Sweep Curve with Low
Power factor (%)
Inner PD Activity
1,80
1,40 Inner PD Activity
1,60
1,20 2.50
% 1,40
1,00 Power factor (%)
1,20
0,80 2.00
0,00
% 0.50
1000
2000
3000
4000
5000
6000
7000
8000
1.00
V 0.00
ADVANCEMENTS IN INDUSTRY
500
1000
1500
2000
2500
3000
0.50
V
0.00
500
1000
1500
2000
2500
3000
2.50 4.50
Power factor (%)
Power factor (%) 4.00 V
2.00 3.50
4.50
3.00 Power factor (%)
4.00
1.50
2.50
% % 3.50
2.00
1.00 3.00
1.50
2.50
% 1.00
0.50 2.00
0.50
1.50
0.00 0.00
1.00
500
1000
1500
2000
2500
0
500
1000
1500
2000
2500
3000
0.50
V V
0.00
Figure 10: PF Voltage Sweep Curve of a Figure 11: PF Voltage Sweep Curve of a
500
1000
1500
2000
2500
4.50
Power factor (%)
Healthy 4 kV Machine
4.00 Retired
4,50 4 kV Machine with V High PD Activity
Power factor (%)
3.50 4,00
3.00 3,50
4,50
Power factor (%)
The
%
2.50 number and length of slots can also 3,00
4,00
significantly
2.00
impact expected values. Machines %
2,50
3,50
2,00
that
1.50
have many short slots will be subjected to 3,00
1,50
1.00
higher
0.50
influence from the surface current caused %
2,50
1,00
2,00 A-BCG
by0.00EPG. This is because the surface current 0,50
1,50
becomes dominant in comparison with the
0
500
1000
1500
2000
2500
0,00
1,00
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
current that goes throughV bulk insulation (refer 0,50
A-BCG
V
back to Figure 4). An example can be seen in 0,00
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
Figure
4,50 12, where PFPower
measurements
factor (%)
of a healthy
and
4,00
clean winding show a large increase of PF V
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
1.00
A S S E S S ME N T performed on similar machines can also be
0.00
V
Neither IEEE 286 nor IEC 60034-27-3 currently established. In any case, Vit is recommended to
0
1000
2000
3000
4000
5000
6000
7000
0.50
1000
2000
3000
4000
5000
6000
7000
2.50
V
coils and bars using Power
guard
factorelectrodes.
(%) However, display
7.00
an upward
A-BCG
trendB-ACG
over time.
C-ABG
it is important to mention that many have
2.00
Power factor (%)
6.00
questioned
1.50
those values; they are viewed as too If7.00
no historical data is available, the ability
5.00
restrictive
% by some and overly lenient by others. to perform an assessmentPower factor (%) from one single
6.00
In addition, these limits should not be applied
1.00 measurement
%
4.00
is limited. PD hysteresis can
for complete stator windings. The difficulty of 5.00
therefore
3.00
be used to verify the presence of PD
0.50
establishing global limits results from numerous within
%
4.00
2.00 the insulation. In addition, a comparison
variables
0.00 such as various insulating materials, between
3.00
1.00 phases of the machine could also be
0
1000
2000
3000
4000
5000
6000
7000
1000
2000
3000
4000
5000
6000
7000
1000
2000
3000
4000
5000
6000
7000
7.00
V
sweep
6.00
curves shouldPower
befactor
recorded
(%)
and trended Power
7.00 factor measurement
A-BCG Power B-ACG provides
C-ABG a general
factor (%)
over
5.00
time. When measurements are recorded assessment of insulation with limited capability
6.00
0,40
A-BCG 0.50
ADVANCEMENTS IN INDUSTRY
0,20
0,00
1000
2000
3000
4000
5000
6000
7000
8000
0.00
500
1000
1500
2000
2500
3000
V
values do not represent the most deteriorated In this specific case, it wasV necessary to increase
part of the winding, as a large power factor the
4.50test voltage up to U To display the PD
N. (%)
Power factor
value
2.50 can be due to voids distributed all over hysteresis
4.00
curves with enough resolution,
the winding or a fewPower
single, heavily aged bars or
factor (%) a 3.50
minimum of 10 data points is usually
3.00
coils. The impact of the latter case is potentially
2.00
recommended.
2.50
Therefore, the voltage was
much
1.50
more severe for the longevity of the increased
%
2.00
using increments of 0.1 x UN. The
winding. It is, however, good practice to perform
% results
1.50 are shown in Table 2 and Figure 14.
measurements
1.00
whenever possible and to trend 1.00
the
0.50
values throughout the asset’s lifetime. If an Comparing
0.50 the data from 2012 (Table 2 and
increase in power factor values or tip-up values is Figure
0.00
14) to the data of 1991 (Table 1 and
500
1000
1500
2000
2500
observed,
0.00 further investigation including visual Figure 13) shows significant increase of all
V
0
500
1000
1500
2000
2500
3000
inspection and additional electrical tests can be values for all three phases. Increased PF values
triggered to complete the Vassessment. could
4,50
be expected due to aging since the
4.50
Power factor (%) measurements
4,00
were Power
taken 20
factor (%) years apart. After
4.00
all,
3,50at the time of the 2012 measurements, the
C3.50
ASE S T UDY machine
3,00 had been operating for a little more
3.00
In2.50January 2012, power factor measurements than
%
2,50 30 years. However, the losses in phase A
%
were
2.00 performed on a 6.4 kV, 5.6 MVA hydro were
2,00
more than twice the losses measured in
1,50
generator
1.50 as part of a planned outage. The the other two phases. In addition, hysteresis
1,00
machine
1.00 was manufactured in 1981. The behavior
0,50
was noticeable in all three phases,
A-BCG but
neutral
0.50
point was disconnected to test each predominantly
0,00 on phase A. For these reasons,
0.00
individual phase separately, and the line additional electrical tests were recommended to
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
0
500
1000
1500
2000
2500
2,50 1.50
%
Table
2,00
1: PF Data from 1991 Table
% 2: PF Measurements before Repairs
1,50 1.00
1,00 PF at PF at
A-BCG 0.50
0,50 0.2 X UN PF at UN PF Tip-up 0.2 X UN PF at UN PF Tip-up
0,00
Phase A 0.75% 2.33% 1.58% Phase
0.00 A 3.74% 6.03% 2.29%
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
1000
2000
3000
4000
5000
6000
7000
Phase B 0.90% V2.35% 1.45% Phase B 1.51% V3.12% 1.61%
A-BCG B-ACG C-ABG
Phase C 0.74% 2.29% 1.55% Phase C 1.68% 3.08% 1.40%
2.50 7.00
Power factor (%) Power factor (%)
6.00
2.00
5.00
1.50
4.00
% %
1.00 3.00
2.00
0.50
1.00
0.00 0.00
0
1000
2000
3000
4000
5000
6000
7000
1000
2000
3000
4000
5000
6000
7000
V V
A-BCG B-ACG C-ABG A-BCG B-ACG C-ABG
5.00
5.00
• WINTER 2020
4.00
104 %
4.00 PF MEASUREMENTS
%
ON COMPLETE STATOR WINDINGS
3.00
3.00
2.00
A-BCG B-ACG C-ABG
7.00
ADVANCEMENTS IN INDUSTRY
Power factor (%)
6.00
5.00
1000
2000
3000
4000
5000
6000
7000
Phase B 1.81% 3.28% 1.47%
V IEEESTD.2001.92415.
Phase C 2.02%
A-BCG 3.23% C-ABG 1.21%
B-ACG
IEC/TS 60034-27-3, Rotating Electrical
7.00 Machines – Part 27: Dielectric Dissipation
Power factor (%)
6.00 Factor Measurements on Stator Winding
5.00
Insulation of Rotating Electrical Machines,
4.00
2015.
%
3.00 M. G. Krieg-Wezelenburg. “Dielectric
2.00 Dissipation Factor Measurements on
1.00
Stator Insulation — Results from a Global
0.00
Survey,” 2020 IEEE Electrical Insulation
Conference (EIC), Knoxville, TN, USA,
0
1000
2000
3000
4000
5000
6000
7000
V
A-BCG B-ACG C-ABG
2020, pp. 269-273, doi: 10.1109/
EIC47619.2020.9158740.
Figure 15: PF Voltage Sweep after Repairs
R. Omranipour and S. U. Haq. “How Critical
are IEC 60034-27-3 Maximum Values
for Dielectric Dissipation Factor and Tip-
the winding, an AC dielectric withstand test at
Up to Determine the Reliability of Motor
1.5 x UN was initiated. A breakdown occurred
Stator Insulation?” 2015 IEEE Electrical
in one coil located in the middle of the winding
Insulation Conference (EIC), Seattle, WA,
of phase A before reaching the final voltage
USA, 2015, pp. 364-368, doi: 10.1109/
level.
ICACACT.2014.7223474.
The failed coil was isolated from the winding,
and the electrical tests were repeated. The Mathieu Lachance joined OMICRON
results of the power factor measurements, after electronics Canada Corp. in 2019 and
repairs, are shown in Table 3 and Figure 15. presently holds the position of Regional
Application Specialist for rotating machines
Following the repairs, the losses of phase A and partial discharges. He previously
worked as a test engineer in the fields
were similar to losses from phase B and phase of partial discharges and high voltage.
C. Figure 15 also shows that hysteresis behavior Mathieu received a BS in electrical engineering from Université
has significantly diminished. Nevertheless, the Laval in 2014.
values are still significantly higher (100%) than
the data from 1991 and indicate insulation
deterioration on all three phases.
IP www.aemc.com
54
cover closed [email protected]
INSIGHTS & OBSERVATIONS — NETA CAP SPOTLIGHT
AEMC ®
INSTRUMENTS:
OVER 125 YEARS OF TECHNICAL HERITAGE
AND INNOVATION IN TEST INSTRUMENTATION
NETA Corporate Alliance Partners (CAPs) are a
group of industry-leading companies that have
joined forces with NETA to work together toward
a common aim: improving quality, safety, and
electrical system reliability.
NW: What is something NETA World Arnoux family. AEMC was originally known
readers don’t know about AEMC? as a premier supplier of current measurement
probes, and we still hold that position. Today,
Olobri: AEMC Instruments originally started we offer a wide range of test instruments for
in business in the United States in Boston, ground resistance testing, insulation resistance
Massachusetts, in 1976 as Instrumentation testing, power and energy monitoring, and
Corporation. It was a distribution arm of much more. Chauvin Arnoux in France was
Chauvin Arnoux based in Paris, France. one of the first developers of the multimeter.
As the business grew, a production facility
opened in Dover, New Hampshire, in the early NW: What recent company achievement or
1980s, and two additional business units were milestone are you particularly proud of?
added. A name-change to Advanced Electrical
Measurement and Control took place as it was Olobri: As a world-leading manufacturer
a better fit for the company’s business model, of ground resistance test instrumentation,
and in the early 1990s, the name was shortened we continually look for ways to advance the
to AEMC® Instruments as it is known today. technology to address the needs of the customer.
The company is incorporated as Chauvin Our latest offering to test the ground resistance
Arnoux® Inc., d.b.a. AEMC® Instruments. of towers such as electrical transmission and
It is still privately held and owned by the cellular communication has greatly improved
B
BULLOCK
B
BREAKERS
1-763-269-2832
ORDER NOW
Visit NETAWORLD.ORG or call 888.300.6382
SPECIFICATIONS AND STANDARDS ACTIVITY
2020
STANDARD
2020
S
STAND
ARD F
OR
R I C A L
LECT ECIFICATIONS
ANSI/
E
NETA
.O RG
WORLD
.NETA
STANDA
WWW
C O M M I S
R ELEC
R EQU
POWE
TR
RICAL
ICAL CO
LECT
FOR E
MM
ISSIO
NING
SPECIF
ICATIO
LATEST
NS
EDITION
TA N
S TA N D A RD
• In Stock
• New and Obsolete
• 800A—4000A
• Retrofit kits
• 24/7 Emergency Service
HPC New Generation HPC
We stock new General Electric HPCII drop in replacements for the THPC 3000 & 4000
amp GFI models for same day shipping. Call anytime for immediate service.
800-421-5082 www.qualityswitchgear.com
RETROFITTED BREAKER
6605 W. WT Harris Blvd. Suite F • Charlotte NC 28269 | 13 Jenkins Court • Mauldin, SC 29662 | 9481 Industrial Center Drive, Suite 5 • Ladson, SC 29456
704.573.0420 • 844-383-8617 • 704.573.3693 (fax) • www.powerproducts.biz
The Power of
Positive Results
No. 132
A N S W E R S
Thomas D. Sandri is A N SW E R S 3.
a. Figure 1 showed a common Mho (opposite
Training Development characteristic of an Ohm) relay characteristic
Manager at Shermco where:
1.
a. 25. Also known as a synch-check relay,
Industries. He has been
active in the field of it verifies that two voltages are within the
electrical power and specified quantity and phase angle. These are
X = reactance, r = resistance, z = impedance
telecommunications for over used mostly for synchronizing a generator
30 years. During his career, with an existing source to be connected to
It could also show the maximum torque angle
he has developed numerous it, not for synchronizing two generators. (Figure 4) and the values for the three. Any
training aids and training Auto-synchronizing relays are usually used to impedance value that falls inside the circle
guides and has conducted synchronize two generators. means a contact-closed condition.
domestic and international
seminars. Tom supports
a wide range of electrical 2.
d. Loss-of-excitation. Probably an easy X
Figure 2 in the question is a reverse power
relay. To operate, it must see both a voltage
(potential) and a current. It looks for power
Figure 3: Simple Generator System
flow going in the wrong direction.
COURTESY EMERSON AUTOMATION EXPERTS BLOG
b
Protective relays use their own symbol system.
It’s easy to get confused if you’re not used to
them. This one is a bit quirky. The current
d coil (b) is normally shown as the potential
coils are in Figure 2, but the potential coil (d)
S1 is shown split. Since the shorting bars (c) are
on terminals 5 and 6, the current coil must
be connected there. Terminals 7 and 8 are
a S1
the potential coil terminals and 1 and 2 are
the trip circuit with (a) being the seal-in coil.
This is an IJS Sync-Check relay.
ELECTRICAL
on the
TESTING
LEADING EDGE
ELEMCO SERVICES
offers a comprehensive array of state-of-the-art
electrical testing services and expertise.
HIGH, MEDIUM AND LOW VOLTAGE REPAIR
AND MAINTENANCE OF:
Switchgear / Circuit Breakers / Transformers / ATS Switches / Cables
TESTING, CALIBRATION AND REPAIR
OF METERS AND RELAYS
FIELD SERVICES:
Acceptance Testing and Commissioning / Infrared Surveys
Motor and Cable Testing
Load and Power Quality Recording and Analysis
Nu Heat Certified Repair Specialists
A&F Electrical Testing, Inc. ABM Electrical Power Solutions American Electrical Testing Co., LLC CE Power Engineered Services, LLC
80 Lake Ave S Ste 10 3700 Commerce Dr # 901-903 91 Fulton St., Unit 4 480 Cave Rd
Nesconset, NY 11767-1017 Baltimore, MD 21227-1642 Boonton, NJ 07005-1060 Nashville, TN 37210-2302
(631) 584-5625 (410) 247-3300 (973) 316-1180 (615) 882-9455
www.afelectricaltesting.com
ABM Electrical Power Solutions AMP Quality Energy Services, LLC CE Power Engineered Services, LLC
A&F Electrical Testing, Inc. 317 Commerce Park Drive 352 Turney Ridge Rd 40 Washington St
80 Broad St Fl 5 Cranberry Township, PA 16066-6407 Somerville, AL 35670 Westborough, MA 01581-1088
New York, NY 10004-2257 (724) 772-4638 (256) 513-8255 (508) 881-3911
(631) 584-5625
ABM Electrical Power Solutions AMP Quality Energy Services, LLC CE Power Engineered Services, LLC
ABM Electrical Power Services, LLC 814 Greenbrier Cir Ste E 41 Peabody Street 9200 75th Avenue N
720 S Rochester Ste A Chesapeake, VA 23320-2643 Nashville, TN 37210 Brooklyn Park, MN 55428
Ontario, CA 91761-8177 (757) 364-6145 (629) 213-4855 (877) 968-0281
(301) 397-3500
abm.com/Electrical ABM Electrical Power Solutions Apparatus Testing and Engineering CE Power Engineered Services, LLC
1817 O’Brien Road 11300 Sanders Dr Ste 29 72 Sanford Drive
ABM Electrical Power Services, LLC Columbus, OH 43228 Rancho Cordova, CA 95742-6822 Gorham, ME 04038
6541 Meridien Dr (724) 772-4638 (916) 853-6280 (800) 649-6314
Suite 113 www.abm.com www.apparatustesting.com
Raleigh, NC 27616 CE Power Engineered Services, LLC
(919) 877-1008 Absolute Testing Services, Inc. Apparatus Testing and Engineering 8490 Seward Rd.
8100 West Little York 7083 Commerce Cir Ste H Fairfield, OH 45011
ABM Electrical Power Services, LLC Houston, TX 77040 Pleasanton, CA 94588-8017 (800) 434-0415
2631 S. Roosevelt St (832) 467-4446 (916) 853-6280
Tempe, AZ 85282 www.absolutetesting.com CE Power Engineered Services, LLC
(602) 722-2423 Applied Engineering Concepts 1803 Taylor Ave.
Accessible Consulting Engineers, Inc. 894 N Fair Oaks Ave. Louisville, KY 40213
ABM Electrical Power Services, LLC 1269 Pomona Rd Ste 111 Pasadena, CA 91103 (800) 434-0415
3600 Woodpark Blvd Ste G Corona, CA 92882-7158 (626) 389-2108
Charlotte, NC 28206-4210 (951) 808-1040 www.aec-us.com CE Power Engineered Services, LLC
(704) 273-6257 www.acetesting.com 1200 W. West Maple Rd.
Applied Engineering Concepts Walled Lake, MI 48390
ABM Electrical Power Services, LLC Advanced Electrical Services 8160 Miramar Road (810) 229-6628
6940 Koll Center Pkwy Suite# 100 4999 - 43rd St. NE San Diego, CA 92126 www.cepower.net
Pleasanton, CA 94566 Unit 143 (619) 822-1106
(408) 466-6920 Calgary, AB T2B 3N4 CE Power Engineered Services, LLC
(403) 697-3747 BEC Testing 10840 Murdock Drive
ABM Electrical Power Services, LLC 50 Gazza Blvd Knoxville, TN 37932
9800 E Geddes Ave Unit A-150 Advanced Testing Systems Farmingdale, NY 11735-1402 (800) 434-0415
Englewood, CO 80112-9306 15 Trowbridge Dr (631) 393-6800
(303) 524-6560 Bethel, CT 06801-2858 www.bectesting.com CE Power Engineered Services, LLC
(203) 743-2001 3496 E. 83rd Place
ABM Electrical Power Services, LLC www.advtest.com Burlington Electrical Testing Co., LLC Merrillville, IN 46410
3585 Corporate Court 300 Cedar Ave (219) 942-2346
San Diego, CA 92123-1844 American Electrical Testing Co., LLC Croydon, PA 19021-6051
(858) 754-7963 25 Forbes Boulevard (215) 826-9400 CE Power Engineered Services, LLC
Suite 1 www.betest.com 1260 Industrial Park
ABM Electrical Power Services, LLC Foxboro, MA 02035 Eveleth, MN 55734
1005 Windward Ridge Pkwy (781) 821-0121 Burlington Electrical Testing Co., LLC (218) 744-4200
Alpharetta, GA 30005 www.aetco.us 846 Waterford Drive
(770) 521-7550 Delran, NJ 08075 CE Power Solutions of Florida, LLC
American Electrical Testing Co., LLC (609) 267-4126 3502 Riga Blvd., Suite C
ABM Electrical Power Services, LLC Green Hills Commerce Center Tampa, FL 33619
4221 Freidrich Lane Suite 170 5925 Tilghman St Ste 200 C.E. Testing, Inc. (866) 439-2992
Austin, TX 78744 Allentown, PA 18104-9158 6148 Tim Crews Rd www.cepowersol.com
(210) 347-9481 (484) 538-2272 Macclenny, FL 32063-4036
(904) 653-1900 CE Power Solutions of Florida, LLC
ABM Electrical Power Services, LLC American Electrical Testing Co., LLC www.cetestinginc.com/ 3801 SW 47th Avenue Suite 505
11719 NE 95th St. Ste H 34 Clover Dr Davie, FL 33314
Vancouver, WA 98682 South Windsor, CT 06074-2931 Capitol Area Testing, Inc. (866) 439-2992
(360) 713-9513 (860) 648-1013 P.O. Box 259
Suite 614 Control Power Concepts
ABM Electrical Power Solutions American Electrical Testing Co., LLC Crownsville, MD 21032 3750 Las Vegas Blvd S. Unit 3303
4390 Parliament Place 76 Cain Dr (757) 650-0740 Las Vegas, NV 89158
Suite S Brentwood, NY 11717-1265 www.capitolareatesting.com (702) 448-7833
Lanham, MD 20706 (631) 617-5330 www.controlpowerconcepts.com
(301) 967-3500 CE Power Engineered Services, LLC
4040 Rev Drive
Cincinnati, OH 45232
(800) 434-0415
Dude Electrical Testing, LLC Electric Power Systems, Inc. Electric Power Systems, Inc. Electrical Reliability Services
145 Tower Drive, Unit 9 684 Melrose Avenue 7308 Aspen Lane North 8500 Washington St NE Ste A6
Burr Ridge, IL 60527-7840 Nashville, TN 37211-3121 Suite 160 Albuquerque, NM 87113-1861
(815) 293-3388 (615) 834-0999 Brooklyn Park, MN 55428 (505) 822-0237
www.dudetesting.com (763) 315-3520
Electric Power Systems, Inc. Electrical Reliability Services
Eastern High Voltage, Inc. 2888 Nationwide Parkway Electric Power Systems, Inc. 2275 Northwest Pkwy SE Ste 180
11A S Gold Dr 2nd Floor 140 Lakefront Drive Marietta, GA 30067-9319
Robbinsville, NJ 08691-1685 Brunswick, OH 44212 Cockeysville, MD 21030 (770) 541-6600
(609) 890-8300 (330) 460-3706 (443) 689-2220
www.easternhighvoltage.com Electrical Reliability Services
Electric Power Systems, Inc. Electric Power Systems, Inc. 10606 Bloomfield Ave
ELECT, P.C. 54 Eisenhower Lane North 783 N. Grove Rd Suite 101 Santa Fe Springs, CA 90670-3912
375 E. Third Street Lombard, IL 60148 Richardson, TX 75081 (562) 236-9555
Wendell, NC 27591 (815) 577-9515 (214) 821-3311
(919) 365-9775 Electrical Reliability Services
www.elect-pc.com Electric Power Systems, Inc. Electric Power Systems, Inc. 400 NW Capital Dr
1330 Industrial Blvd. 11912 NE 95th St. Suite 306 Lees Summit, MO 64086-4723
Electek Power Services, Inc. Suite 300 Vancouver, WA 98682 (816) 525-7156
870 Confederation Street Sugar Land, TX 77478 (855) 459-4377
Sarnia, ON N7T2E5 (713) 644-5400 www.epsii.com Electrical Reliability Services
(519) 383-0333 7100 Broadway Ste 7E
Electric Power Systems, Inc. Electric Power Systems, Inc. Denver, CO 80221-2900
Electric Power Systems, Inc. 56 Bibber Pkwy # 1 Padre Mariano (303) 427-8809
21 Millpark Ct Brunswick, ME 04011-7357 272, Of. 602
Maryland Heights, MO 63043-3536 (207) 837-6527 Providencia, Santiago Electrical Reliability Services
(314) 890-9999 2222 W Valley Hwy N Ste 160
www.epsii.com Electric Power Systems, Inc. Electrical & Electronic Controls Auburn, WA 98001-1655
11861 Longsdorf St 6149 Hunter Rd (253) 736-6010
Electric Power Systems, Inc. Riverview, MI 48193-4250 Ooltewah, TN 37363-8762
11211 E. Arapahoe Rd (734) 282-3311 (423) 344-7666 Electrical Reliability Services
Ste 108 221 E. Willis Road, Suite 3
Centennial, CO 80112 Electric Power Systems, Inc. Electrical Energy Experts, LLC Chandler, AZ 85286
(720) 857-7273 8515 Calle Alameda NE W129N10818 Washington Dr (480) 966-4568
Ste A Germantown, WI 53022-4446
Electric Power Systems, Inc. Albuquerque, NM 87113 (262) 255-5222 Electrical Reliability Services
120 Turner Road (505) 792-7761 www.electricalenergyexperts.com 1380 Greg St. Ste. 216
Salem, VA 24153-5120 Sparks, NV 89431-6070
(540) 375-0084 Electric Power Systems, Inc. Electrical Engineering & Service Co., Inc. (775) 746-4466
3209 Gresham Lake Rd. 289 Centre St.
Electric Power Systems, Inc. Suite 155 Holbrook, MA 02343 Electrical Reliability Services
1090 Montour West Ind Park Raleigh, NC 27615 (781) 767-9988 11000 Metro Pkwy Ste 30
Coraopolis, PA 15108-9307 (919) 210-5405 www.eescousa.com Fort Myers, FL 33966-1244
(412) 276-4559 (239) 693-7100
Electric Power Systems, Inc. Electrical Equipment Upgrading, Inc.
Electric Power Systems, Inc. 5850 Polaris Ave., Suite 1600 21 Telfair Pl Electrical Reliability Services
6141 E Connecticut Ave Las Vegas, NV 89118 Savannah, GA 31415-9518 245 Hood Road
Kansas City, MO 64120-1346 (702) 815-1342 (912) 232-7402 Sulphur, LA 70665-8747
(816) 241-9990 www.eeu-inc.com (337) 583-2411
Electric Power Systems, Inc.
Electric Power Systems, Inc. 7925 Dunbrook Rd. Electrical Reliability Services Electrical Reliability Services
1230 N Hobson St. Suite G 610 Executive Campus Dr 9736 South Sandy Pkwy 500 West
Suite 101 San Diego, CA 92126 Westerville, OH 43082-8870 Sandy, UT 84070
Gilbert, AZ 85233 (858) 566-6317 (877) 468-6384 (801) 561-0987
(480) 633-1490 www.electricalreliability.com
Electric Power Systems, Inc. Electrical Reliability Services
Electric Power Systems, Inc. 6679 Peachtree Industrial Dr. Electrical Reliability Services 6351 Hinson Street, Suite A
915 Holt Ave Unit 9 Suite H 5909 Sea Lion Pl Ste C Las Vegas, NV 89118-6851
Manchester, NH 03109-5606 Norcross, GA 30092 Carlsbad, CA 92010-6634 (702) 597-0020
(603) 657-7371 (770) 416-0684 (858) 695-9551
Electrical Reliability Services
Electric Power Systems, Inc. Electric Power Systems, Inc. Electrical Reliability Services 36572 Luke Drive
3806 Caboose Place 306 Ashcake Road suite A 1057 Doniphan Park Cir Ste A Geismar, LA 70734
Sanford, FL 32771 Ashland, VA 23005 El Paso, TX 79922-1329 (225) 647-0732
(407) 578-6424 (804) 526-6794 (915) 587-9440 www.electricalreliability.com
Electric Power Systems, Inc. Electric Power Systems, Inc. Electrical Reliability Services Electrical Reliability Services
1129 E Highway 30 7169 East 87th St. 6900 Koll Center Pkwy Ste 415 9636 Saint Vincent Ave Unit A
Gonzales, LA 70737-4759 Indianapolis, IN 46256 Pleasanton, CA 94566-3119 Shreveport, LA 71106-7127
(225) 644-0150 (317) 941-7502 (925) 485-3400 (318) 869-4244
Electrical Reliability Services EnerG Test, LLC High Voltage Maintenance Corp. Hood Patterson & Dewar, Inc.
1426 Sens Rd. Ste. #5 206 Gale Lane 24 Walpole Park S 15924 Midway Road
La Porte, TX 77571-9656 Kennett Square, PA 19348 Walpole, MA 02081-2541 Addison, TX 75001
(281) 241-2800 (484) 731-0200 (508) 668-9205 (214) 461-0760
www.energtest.com
Electrical Reliability Services High Voltage Maintenance Corp. Hood Patterson & Dewar, Inc.
9753 S. 140th Street, Suite 109 Energis High Voltage Resources 1052 Greenwood Springs Rd. 4511 Daly Dr.
Omaha, NE 68138 1361 Glory Rd Suite E Suite 1
(402) 861-9168 Green Bay, WI 54304-5640 Greenwood, IN 46143 Chantilly, VA 20151
(920) 632-7929 (317) 322-2055 (571) 299-6773
Electrical Reliability Services www.energisinc.com www.hvmcorp.com
1402 Preston Road Hood Patterson & Dewar, Inc.
Ste 404. #706 EPS Technology High Voltage Maintenance Corp. 1531 Hunt Club Blvd
Dallas, TX 75254 37 Ozick Dr. 355 Vista Park Dr Ste 200
(972) 788-0979 Durham, CT 06422 Pittsburgh, PA 15205-1206 Gallatin, TN 37066
(203) 679-0145 (412) 747-0550 (615) 527-7084
Electrical Reliability Services www.eps-technology.com
4833 Berewick Town Ctr Drive High Voltage Maintenance Corp. Industrial Electric Testing, Inc.
Ste E-207 Giga Electrical & Technical Services, Inc. 8787 Tyler Blvd. 11321 Distribution Ave W
Charlotte, NC 28278 2743A N. San Fernando Road Mentor, OH 44061 Jacksonville, FL 32256-2746
(704) 583-4794 Los Angeles, CA 90065 (440) 951-2706 (904) 260-8378
(323) 255-5894 www.hvmcorp.com www.industrialelectrictesting.com
Electrical Reliability Services www.gigaelectrical-ca.com/
324 S. Wilmington St. High Voltage Maintenance Corp. Industrial Electric Testing, Inc.
Ste 299 Grubb Engineering, Inc. 24371 Catherine Industrial Dr Ste 207 201 NW 1st Ave
Raleigh, NC 27601 2727 North Saint Mary’s St. Novi, MI 48375-2422 Hallandale Beach, FL 33009-4029
(919) 807-0995 San Antonio, TX 78212 (248) 305-5596 (954) 456-7020
(210) 658-7250
Electrical Reliability Services www.grubbengineering.com High Voltage Maintenance Corp. Industrial Tests, Inc.
8983 University Blvd 3000 S Calhoun Rd 4021 Alvis Ct Ste 1
Ste. 104. #158 Halco Testing Services New Berlin, WI 53151-3549 Rocklin, CA 95677-4031
North Charleston, SC 29406 5773 Venice Boulevard (262) 784-3660 (916) 296-1200
(843) 797-0514 Los Angeles, CA 90019 www.industrialtests.com
(323) 933-9431 High Voltage Maintenance Corp.
Electrical Reliability Services www.halcotestingservices.com 1 Penn Plaza Infra-Red Building and Power Service, Inc.
13720 Old St. Augustine Rd. Suite 500 152 Centre St
Ste. 8 #310 Hampton Tedder Technical Services New York, NY 10119 Holbrook, MA 02343-1011
Jacksonville, FL 32258 4563 State St (718) 239-0359 (781) 767-0888
(904) 292-9779 Montclair, CA 91763-6129 www.hvmcorp.com www.infraredbps.com
(909) 628-1256
Electrical Reliability Services www.hamptontedder.com High Voltage Maintenance Corp. J.G. Electrical Testing Corporation
4099 SE International Way Ste 201 29 Diana Court 3092 Shafto Road
Milwaukie, OR 97222-8853 Hampton Tedder Technical Services Cheshire, CT 06410 Suite 13
(503) 653-6781 3747 W Roanoke Ave (203) 949-2650 Tinton Falls, NJ 07753
Phoenix, AZ 85009-1359 www.hvmcorp.com (732) 217-1908
Electrical Testing and Maintenance Corp. (480) 967-7765 www.jgelectricaltesting.com
3673 Cherry Rd Ste 101 High Voltage Maintenance Corp.
Memphis, TN 38118-6313 Hampton Tedder Technical Services 941 Busse Rd M&L Power Systems, Inc.
(901) 566-5557 4113 Wagon Trail Ave. Elk Grove Village, IL 60007-2400 109 White Oak Ln Ste 82
www.etmcorp.net Las Vegas, NV 89118 (847) 640-0005 Old Bridge, NJ 08857-1980
(702) 452-9200 (732) 679-1800
Electrical Testing Solutions High Voltage Maintenance Corp. www.mlpower.com
2909 Greenhill Ct Harford Electrical Testing Co., Inc. 14300 Cherry Lane Court
Oshkosh, WI 54904-9769 1108 Clayton Rd Suite 115 Magna IV Engineering
(920) 420-2986 Joppa, MD 21085-3409 Laurel, MD 20707 1103 Parsons Rd. SW
www.electricaltestingsolutions.com (410) 679-4477 (410) 279-0798 Edmonton, AB T6X 0X2
www.harfordtesting.com www.hvmcorp.com (780) 462-3111
Electrical Testing, Inc. www.magnaiv.com
2671 Cedartown Hwy SE High Energy Electrical Testing, Inc. High Voltage Maintenance Corp.
Rome, GA 30161-3894 5042 Industrial Road, Unit D 10704 Electron Drive Magna IV Engineering
(706) 234-7623 Farmingdale, NJ 07727 Louisville, KY 40299 141 Fox Cresent
www.electricaltestinginc.com (732) 938-2275 (859) 371-5355 Fort McMurray, AB T9K 0C1
www.highenergyelectric.com (780) 791-3122
Elemco Services, Inc. Hood Patterson & Dewar, Inc.
228 Merrick Rd High Voltage Maintenance Corp. 850 Center Way Magna IV Engineering
Lynbrook, NY 11563-2622 5100 Energy Dr Norcross, GA 30071 3124 Millar Ave.
(631) 589-6343 Dayton, OH 45414-3525 (770) 453-1415 Saskatoon, SK S7K 5Y2
www.elemco.com (937) 278-0811 https://hoodpd.com/ (306) 713-2167
www.hvmcorp.com
Magna IV Engineering Nationwide Electrical Testing, Inc. Potomac Testing Power Systems Testing Co.
96 Inverness Dr E Ste R 6515 Bentley Ridge Drive 12342 Hancock St 4688 W Jennifer Ave Ste 108
Englewood, CO 80112-5311 Cumming, GA 30040 Carmel, IN 46032-5807 Fresno, CA 93722-6418
(303) 799-1273 (770) 667-1875 (317) 853-6795 (559) 275-2171 ext 15
www.n-e-t-inc.com www.powersystemstesting.com
Magna IV Engineering Potomac Testing
Avenida del Condor sur #590 North Central Electric, Inc. 1130 MacArthur Rd. Power Systems Testing Co.
Oficina 601 69 Midway Ave Jeffersonville, OH 43128 600 S Grand Ave Ste 113
Huechuraba 8580676 Hulmeville, PA 19047-5827 Santa Ana, CA 92705-4152
+(56) -2-26552600 (215) 945-7632 Power Engineering Services, Inc. (714) 542-6089
www.ncetest.com 9179 Shadow Creek Ln
Magna IV Engineering Converse, TX 78109-2041 Power Systems Testing Co.
Unit 110, 19188 94th Avenue Northern Electrical Testing, Inc. (210) 590-4936 6736 Preston Ave Ste E
Surrey, BC V4N 4X8 1991 Woodslee Dr www.pe-svcs.com Livermore, CA 94551-8521
(604) 421-8020 Troy, MI 48083-2236 (510) 783-5096
(248) 689-8980 Power Engineering Services, Inc.
Magna IV Engineering www.northerntesting.com 1 Ellis Road, Suite 100 Power Test, Inc.
Suite 200, 688 Heritage Dr. SE Friendswood, TX 77546 2200 Highway 49 S
Calgary, AB T2H 1M6 Orbis Engineering Field Services Ltd. (210) 590-4936 Harrisburg, NC 28075-7506
(403) 723-0575 #300, 9404 - 41st Ave. (704) 200-8311
Edmonton, AB T6E 6G8 Power Engineering Services, Inc. www.powertestinc.com
Magna IV Engineering (780) 988-1455 124 S West St. Suite 200
4407 Halik Street Building E www.orbisengineering.net Alexandria, VA 22314 PowerSouth Testing, LLC
Suite 300 (703) 299-3430 240 Pine Pitch Road
Pearland, TX 77581 Orbis Engineering Field Services Ltd. Cedartown, GA 30125
(346) 221-2165 #228 - 18 Royal Vista Link NW Power Products & Solutions, LLC (678) 901-0205
Calgary, AB T3R 0K4 6605 W WT Harris Blvd www.powersouthtesting.com
Magna IV Engineering (403) 374-0051 Suite F
10947 92 Ave Charlotte, NC 28269 Powertech Services, Inc.
Grande Prairie, AB T8V 3J3 Orbis Engineering Field Services Ltd. (704) 573-0420 x12 4095 Dye Rd
1.800.462.3157 Badajoz #45, Piso 17 www.powerproducts.biz Swartz Creek, MI 48473-1570
Las Condes, Santiago (810) 720-2280
Midwest Engineering Consultants, Ltd. +56 2 29402343 Power Products & Solutions, LLC www.powertechservices.com
2500 36th Ave 13 Jenkins Ct
Moline, IL 61265-6954 Pace Technologies, Inc. Mauldin, SC 29662-2414 Precision Testing Group
(309) 764-1561 9604 - 41 Avenue NW (800) 328-7382 5475 Highway 86 Unit 1
www.Midwestengr.com Edmonton, AB T6E 6G9 Elizabeth, CO 80107-7451
(780) 450-0404 Power Products & Solutions, LLC (303) 621-2776
MTA Electrical Engineers www.pacetechnologies.com 9481 Industrial Center Dr. www.precisiontestinggroup.com
350 Pauma Place Unit 5
Escondido, CA 92029 Pace Technologies, Inc. Ladson, SC 29456 Premier Power Maintenance Corporation
(760) 658-6098 #10, 883 McCurdy Place (844) 383-8617 4035 Championship Drive
Kelowna, BC V1X 8C8 Indianapolis, IN 46268
National Field Services (250) 712-0091 Power Solutions Group, Ltd. (317) 879-0660
651 Franklin 425 W Kerr Rd
Lewisville, TX 75057-2301 Pacific Power Testing, Inc. Tipp City, OH 45371-2843 Premier Power Maintenance Corporation
(972) 420-0157 14280 Doolittle Dr (937) 506-8444 2725 Jason Rd
www.natlfield.com San Leandro, CA 94577-5542 www.powersolutionsgroup.com Ashland, KY 41102-7756
(510) 351-8811 (606) 929-5969
National Field Services www.pacificpowertesting.com Power Solutions Group, Ltd.
1890 A South Hwy 35 251 Outerbelt St. Premier Power Maintenance Corporation
Alvin, TX 77511 Pacific Powertech Inc. Columbus, OH 43213 3066 Finley Island Cir NW
(800) 420-0157 #110, 2071 Kingsway Ave. (614) 310-8018 Decatur, AL 35601-8800
Port Coquitlam, BC V3C 6N2 (256) 355-1444
National Field Services (604) 944-6697 Power Solutions Group, Ltd.
1405 United Drive www.pacificpowertech.ca 5115 Old Greenville Highway Premier Power Maintenance Corporation
Suite 113-115 Liberty, SC 29657 4301 Iverson Blvd Ste H
San Marcos, TX 78666 Phasor Engineering (864) 540-8434 Trinity, AL 35673-6641
(800) 420-0157 Sabaneta Industrial Park #216 (256) 355-3006
Mercedita, PR 00715 Power Solutions Group, Ltd.
National Field Services (787) 844-9366 172 B-Industrial Dr. Premier Power Maintenance Corporation
3711 Regulus Ave. www.phasorinc.com Clarksville, TN 37040 7301 E County Road 142
Las Vegas, NV 89102 (931) 572-8591 Blytheville, AR 72315-6917
(888) 296-0625 Potomac Testing (870) 762-2100
1610 Professional Blvd Ste A Power System Professionals, Inc.
National Field Services Crofton, MD 21114-2051 429 Clinton Ave Premier Power Maintenance Corporation
2900 Vassar St. #114 (301) 352-1930 Roseville, CA 95661 7262 Kensington Rd.
Reno, NV 89502 www.potomactesting.com (866) 642-3129 Brighton, MI 48116
(775) 410-0430 (517) 715-9997
Premier Power Maintenance Corporation RESA Power Service Shermco Industries Shermco Industries
4537 S Nucor Rd. #181-1999 Savage Road, 1711 Hawkeye Dr. 2901 Turtle Creek Dr.
Crawfordsville, IN 47933 Richmond, BC V6V OA5 Hiawatha, IA 52233 Port Arthur, TX 77642
(317) 879-0660 (604) 303-9770 (319) 377-3377 (409) 853-4316
Premier Power Maintenance Corporation Reuter & Hanney, Inc., a CE Power Shermco Industries Shermco Industries
1901 Oakcrest Ave., Suite 6 Company 1705 Hur Industrial Blvd 5145 NW Beaver Dr.
Saint Paul, MN 55113 Northampton Industrial Park Cedar Park, TX 78613-7229 Johnston, IA 50131
(612) 616-4236 149 Railroad Dr (512) 267-4800 (515) 265-3377
Ivyland, PA 18974-1448
Premier Power Maintenance Corporation (215) 364-5333 Shermco Industries Shermco Industries
119 Rochester Dr. www.reuterhanney.com 3434 25th Street NE 998 E. Berwood Ave.
Louisville, KY 40214 Calgary, AB T1Y 6C1 Saint Paul, MN 55110
(256) 200-6833 Reuter & Hanney, Inc., a CE Power (403) 769-9300 (651) 484-5533
Company
RESA Power Service 11620 Crossroads Cir Shermco Industries Shermco Industries
46918 Liberty Dr Middle River, MD 21220-2874 5145 Beaver Dr 12796 Currie Court
Wixom, MI 48393-3600 (410) 344-0300 Johnston, IA 50131 Livonia, MI 48150
(248) 313-6868 (515) 265-3377 (734) 469-4050
www.resapower.com REV Engineering Ltd.
3236 - 50 Avenue SE Shermco Industries Shermco Industries
RESA Power Service Calgary, AB T2B 3A3 4510 South 86th East Ave. 1720 S. Sonny Ave.
3890 Pheasant Ridge Dr. NE (403) 287-0156 Tulsa, OK 74145 Gonzales, LA 70737
Suite 170 www.reveng.ca (918) 234-2300 (225) 647-9301
Blaine, MN 55449
(763) 784-4040 Rondar Inc. Shermco Industries Shermco Industries
333 Centennial Parkway North 1375 Church Avenue 7136 Weddington Rd #128
RESA Power Service Hamilton, ON L8E2X6 Winnipeg, MB R2X 2T7 Concord, NC 28027
4540 Boyce Parkway (905) 561-2808 (204) 925-4022 (910) 568-1053
Cleveland, OH 44224 www.rondar.com
(800) 264-1549 Shermco Industries Shermco Industries
www.resapower.com Rondar Inc. 1033 Kearns Crescent 5805 Hwy 43
9-160 Konrad Crescent RM of Sherwood, SK S4K 0A2 Satsuma, AL 36507
RESA Power Service Markham, ON L3R9T9 (306) 949-8131 (251) 679-3224
47119 Cartier Court (905) 943-7640
Wixom, MI 48393-2872 Shermco Industries Shermco Industries
(248) 896-0200 Scott Testing, Inc. 33002 FM 2004 5211 Linbar Dr. Suite 507
245 Whitehead Rd Angleton, TX 77515-8157 Nashville, TN 37211
RESA Power Service Hamilton, NJ 08619 (979) 848-1406 (615) 928-1182
19621 Solar Circle, 101 (609) 689-3400
Parker, CO 80134 Shermco Industries Shermco Industries
www.scotttesting.com
(303) 781-2560 12000 Network Blvd #307-2999 Underhill Ave
Sentinel Field Services, LLC Building D, Suite 410 Burnaby, BC V5A 3C2
RESA Power Service 7517 E Pine St San Antonio, TX 78249-3354 (972) 793-5523
40 Oliver Terrace Tulsa, OK 74115-5729 (210) 877-9090
Shelton, CT 06484-5336 Shermco Industries
(918) 359-0350
(800) 272-7711 Shermco Industries 1411 Twin Oaks Street
www.sentinelpowerservices.com
3731 - 98 Street Wichita Falls, TX 76302
RESA Power Service Shermco Industries Edmonton, AB T6E 5N2 (972) 793-5523
13837 Bettencourt Street 2425 E Pioneer Dr (780) 436-8831
Cerritos, CA 90703 Shermco Industries
Irving, TX 75061-8919
(800) 996-9975 Shermco Industries 11800 Jordy Rd.
(972) 793-5523
www.resapower.com 417 Commerce Street Midland, TX 79707
www.shermco.com
Tallmadge, OH 44278 (972) 793-5523
RESA Power Service Shermco Industries (614) 836-8556
2390 Zanker Road Sigma Six Solutions, Inc.
112 Industrial Drive
San Jose, CA 95131 Shermco Industries 2200 W Valley Hwy N Ste 100
Minooka, IL 60447-9557
(800) 576-7372 3807 S Sam Houston Pkwy W Auburn, WA 98001-1654
(815) 467-5577
Houston, TX 77056 (253) 333-9730
RESA Power Service Shermco Industries (281) 835-3633 www.sigmasix.com
1401 Mercantile Court 233 Faithfull Cr.
Plant City, FL 33563 Shermco Industries Sigma Six Solutions, Inc.
Saskatoon, SK S7K 8H7
(813) 752-6550 7050 109th Ave www.sigmasix.com
(306) 955-8131
La Vista, NE 68117 Quincy, WA 98848
RESA Power Service Shermco Industries (402) 933-8988 (253) 333-9730
6268 Route 31 2231 E Jones Ave Ste A
Cicero, NY 13039 Shermco Industries Southern New England Electrical
Phoenix, AZ 85040-1475
(315) 699-5563 1301 Hailey St. Testing, LLC
(602) 438-7500
Sweetwater, TX 79556 3 Buel St Ste 4
(325) 236-9900 Wallingford, CT 06492-2395
(203) 269-8778
www.sneet.org
Star Electrical Services & General Tidal Power Services, LLC Utilities Instrumentation Western Electrical Services
Supplies, Inc. 1056 Mosswood Dr Service - Ohio, LLC 3676 W California Ave Ste C106
PO Box 814 Sulphur, LA 70665-9508 998 Dimco Way Salt Lake City, UT 84104-6533
Las Piedras, PR 00771 (337) 558-5457 Centerville, OH 45458 (888) 395-2021
(787) 716-0925 (937) 439-9660 www.westernelectricalservices.com
www.starelectricalpr.com Tidal Power Services, LLC www.uiscorp.com
1806 Delmar Drive Western Electrical Services
Taurus Power & Controls, Inc. Victoria, TX 77901 Utilities Instrumentation Service, Inc. 4510 NE 68th Dr Unit 122
9999 SW Avery St (281) 710-9150 2290 Bishop Cir E Vancouver, WA 98661-1261
Tualatin, OR 97062-9517 Dexter, MI 48130-1564 (888) 395-2021
(503) 692-9004 Titan Quality Power Services, LLC (734) 424-1200
www.tauruspower.com 1501 S Dobson Street www.uiscorp.com Western Electrical Services
Burleson, TX 76028 5505 Daniels St.
Taurus Power & Controls, Inc. (866) 918-4826 Utility Service Corporation Chino, CA 91710
19226 66th Ave S. #L102 www.titanqps.com PO Box 1471 (602) 426-1667
Kent, WA 98032-2197 Huntsville, AL 35807
(425) 656-4170 Titan Quality Power Services, LLC (256) 837-8400 Western Electrical Services
7630 Ikes Tree Drive www.utilserv.com 620 Meadow Ln.
Tidal Power Services, LLC Spring, TX 77389 Los Alamos, NM 87547
4211 Chance Ln (281) 826-3781 Western Electrical Services (505) 469-1661
Rosharon, TX 77583-4384 14311 29th St E
(281) 710-9150 Titan Quality Power Services, LLC Sumner, WA 98390-9690 Western Electrical Services
www.tidalpowerservices.com 7000 Meany Ave. (253) 891-1995 8985 Double Diamond Pkwy, #10B
Bakersfield, CA 93308 www.westernelectricalservices.com Reno, NV 98521
Tidal Power Services, LLC (661) 589-0400 (602) 426-1667
8184 Highway 44 Ste 105 Western Electrical Services
Gonzales, LA 70737-8183 Tony Demaria Electric, Inc. 5680 S 32nd St
(225) 644-8170 131 W F St Phoenix, AZ 85040-3832
Wilmington, CA 90744-5533 (602) 426-1667
(310) 816-3130 www.westernelectricalservices.com
www.tdeinc.com
Level up with
Certification.
ADVANCE YOUR KNOWLEDGE. BUILD FOR TODAY. BUILD FOR THE FUTURE.
Contact your NETA Accredited Company Representative to learn more.
Certification is available only to technicians currently employed by a NETA Accredited Company.
ADVERTISERS
This issue’s advertisers are identified below. MANUFACTURERS AND
Please thank these advertisers by telling them you OTHER SERVICE PROVIDERS
saw their advertisement in NETA World.
Advanced Test Equipment Rentals (ATE Corp). . . . . . . . . . . . . . . 37
AEMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Aero Tech Laboratories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
AVO Training Institute. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
BCS Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Belyea Company. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Bullock Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
ECP Solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Circuit Breaker Sales Co., Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
High Voltage Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
INDEPENDENT NETA High Voltage Electric Service, Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
ACCREDITED COMPANIES HV Diagnostics, Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Intellirent. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Absolute Testing Services, Inc. . . . . . . . . . . . . . . . . . . . . . . . . 9 Megger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inside Front Cover
American Electrical Testing Co., LLC . . . . . . . . . . . . . . 115 National Switchgear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Apparatus Testing and Engineering. . . . . . . . . . . . . . . . . . . . 6 NETA ANSI/NETA ECS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Eastern High Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 NETA Certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Electrical Energy Experts, Inc.. . . . . . . . . . . . . . . . . . . . . . . . 82 NETA Handbook Series III . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Electrical Reliability Services (Vertiv). . . . . . . . . . . . . . . . . . 8 NETA PowerTest 2021 Call for Exhibitors. . . . . . . . . . . . . . . . . . . . 69
Elemco Testing Co., Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . 117 NETA PowerTest 2021 Call for Sponsors. . . . . . . . . . . . . . . . . . . . . 51
EnerG Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 NETA Training. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Harford Electrical Testing Co. . . . . . . . . . . . . . . . . . . . . . . . 96 NETA World Journal Website. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
High Voltage Maintenance Corp. . . . . . . . . . . . . . . . . . . . . 60 OMICRON electronics Corp. USA. . . . . . . . . . . . . . . . . Back Cover
Industrial Electric Testing, Inc.. . . . . . . . . . . . . . . . . . . . . 110 Phenix Technologies, Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Infra-Red Building and Power Service, Inc.. . . . . . . . . . . . 28 Protec Equipment Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
North Central Electric, Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . 31 Quality Switchgear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Orbis Engineering Field Services LTD. . . . . . . . . . . . . . 117 Raytech. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inside Back Cover
Potomac Testing, Inc. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Sertec. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Power Products & Solutions, Inc.. . . . . . . . . . . . . . . . . . . 114 Solid State Exchange. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Power Systems Testing Co.. . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Southland Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Scott Testing Inc. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Technitrol, Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Shermco Industries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Thyritronics, Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Sigma Six Solutions, Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Utility Relay Company. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Taurus Power & Controls, Inc.. . . . . . . . . . . . . . . . . . . . . . . 38
Tony Demaria Electric, Inc.. . . . . . . . . . . . . . . . . . . . . . . . . . 59
Utilities Instrumentation Service. . . . . . . . . . . . . . . . . . . . . 38
Offering the following easy to set up, and easy to use product lines:
• Transformer Ratiometers
• Winding Resistance
• Contact Resistance
• Current Transformer Test Sets
• Power Factor Test Sets